Wall System KS1000 FH – Horizontal


Load Span Table – (kN/m²) max. sag L/100

Notes:
The calculations have been made in accordance with the European standards and recommendations contained in ECCS 66 1991.
The table contains allowed standard values for the variable loading of the given span.
Consult with Kingspan for the table values of other profiles, as well as dark colors.
Allowed deflection considered in the table values is L/100. If required otherwise, special calculations must be made.
The table is to be applied for common, short, variable loads (for instance wind) and considers the influence of common winter and summer
temperatures. If other ways of loading (long-term loads, special thermal load in for instance cold stores) are applicable, special calculations must be made.
The minimum intermediate support width bmin has been determined assuming one screw of 6.3 mm diameter is used for the support width. If arranged
otherwise, this width is to be adjusted accordingly.
The above-mentioned calculations apply to panels with standard steel skin strength specification of the fv = 220 MPa.
The minimum end support with amin is 40 mm.