You are on page 1of 5

SM.

F-01

BOX RLF 800 T4 11kW


GENERAL DATA

BACKWARD CURVED CENTRIFUGAL FAN IN SOUNDPROOF CABINET 400ºC/2H

MANUFACTURING FEATURES
• Box manufactured in galvanised steel sheet.
• Circular inlet flange.
• Backward impeller with self-cleaning system, direct coupling motor.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation
type 400ºC/2h .
• Manufactured with standard voltages: 230/400V 50Hz in three phase motors up to 3kW
and 400V 50Hz for higher powers and 2 speed motors.
• Exchangeable pannels
• Open drive.

APPLICATIONS
Designed for inline installation, they are suitable for:
• Air renewal in buildings and industries.
Project Specification
• Maximum working temperature: 60ºC.
• Removing smoke in case of fire. The motor inside the hazardous area (400 ° C / 2 h)
Air Flow Rate: 25,000 m3/h
Static Pressure: 500 Pa
Power Supply: 11 kW
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-0582

PERFORMANCE CURVE
20ºC 0m 1.2 Kg/m3
2000 80 Design point

Flow (m3/h) 25000


12
1750 70
Pressure (Pa) 500

1500 60 10
Service point

T.max (ºC) 80
1250 50
Efficiency (%25)

8
Q (m3/h) 31708.05
P (kW)
P (Pa)

1000 40 Ps (Pa) 804.32


6
Pd (Pa) 186.01
750 30
Pt (Pa) 990.33
4
500 20 Speed (m/s) 17.61

Security coefficient 1
2
250 10
Fan total efficiency 69.621

0 0 0 Efficiency (%) 76.25


0 5k 10k 15k 20k 25k 30k 35k 40k
Pabs (kW) 12.1
Q (m3/h)
Pwmec (kW) 11.05
Static pressure Dynamic pressure Total pressure
Absorbed power Fan total efficiency Resistive

TECHNICAL DATA

Fan

RPM 1455 Approx. weight 339 kg Max. Flow 39060 m3/h

1
This report data could change without any previous advise

v5.11.1 21/04/2020 09:41:45


Motor

Power 11 kW RPM 1470 I max. (400V) 21,2 A I max. (690V) 12,3 A

Size 160M Approx. weight 105 kg Efficiency (%) 90.2 % FP 0.83

ERP DATA

Fan data sheet 2000 80

Unit for non-residential ventilation (LOT 1750 70


Fan type
6)
1500 60
Typology Unidirectional

reports.other None 1250 50

Efficiency
Type of driver None

Ps (Pa)
1000 40

Motor power (kW) 11


750 30
ERP
Fan values Requirements 500 20

2018
250 10
Max. efficiency (%) 71.03 57.77

Effic. Heat recovery (%) - 0 0


0 5000 10000 15000 20000 25000 30000 35000 40000

Pabs (kW) 12.727 Q (m3/h)

reports.flow (m3/h) 23820.51

Static pressure (Pa) 1290.38

Speed (m/s) 13.23

SFP (W/m3/s) 1923.47

ACOUSTIC DATA

120 Sound power

63 Hz 77

125 Hz 91
100
100
250 Hz 89
94
91 92 92 500 Hz 92
89 89
86 1000 Hz 94

79 2000 Hz 92
80 77
72 73 4000 Hz 89
71 71
69 68 8000 Hz 86
65
TOTAL 100
dB(A)

60 56
Sound pressure 3m (in)

63 Hz 56

40
125 Hz 71

250 Hz 69

500 Hz 72

1000 Hz 73
20
2000 Hz 71

4000 Hz 68

8000 Hz 65
0
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz TOTAL
TOTAL 79

2
This report data could change without any previous advise

v5.11.1 21/04/2020 09:41:45


DIMENSIONS

Dimensions (mm)

A 1060 B 1060 C 1060 D 952 E 887

G 74 H 1262 J 1212 K 887 L 817

ØF 798

WIRING DIAGRAM

3
This report data could change without any previous advise

v5.11.1 21/04/2020 09:41:45


LGAI Technological Center, S.A. (APPLUS)
Campus UAB - Ronda de la Font del Carme s/n
08193 Bellaterra (Barcelona)
T +34 93 567 20 00
www.applus.com

CERTIFICATE
No. 0370-CPR-0582
No.
CERTIFICATE OF CONSTANCY OF PERFORMANCE
In compliance with Regulation 305/2011/EU of the European Parliament and of the Council of 9 March 2011 (the
Construction Products Regulation or CPR), this certificate applies to the construction product:

SMOKE AND HEAT CONTROL SYSTEMS. PART 3: SPECIFICATION FOR POWERED SMOKE AND HEAT CONTROL
VENTILATORS (FANS)
RANGE: BOX RLFX F400 - BOX RLF F400

Place on the market under the name of:

VENTILACIÓN INDUSTRIAL IND., S.L.


CRTA. CAMPRODON, S/N
17860 ST. JOAN DE LES ABADESSES (GIRONA)

And produced in the manufacturing plant:

CRTA. CAMPRODON, S/N


17860 ST. JOAN DE LES ABADESSES (GIRONA)

This certificate attests that all provisions concerning the assessment and verification of constancy of performance
described in Annex ZA of the standard

EN 12101-3:2015

under system 1 are applied and that the product fulfils all the prescribed requirements set out above.

This certificate was first issued on 28th December 2007 and will remain valid as long as the test methods and/or
factory production control requirements included in the harmonised standard, used to assess the performance of the
declared characteristics, do not change, and the product, and the manufacturing conditions in the plant are not
modified significantly. It is confirmed and modified on 9th December 2019.

The monitoring assessment will be done before December 2020

Bellaterra, 9th December 2019

Xavier Ruiz Peña


Managing Director, Product Conformity B.U.

This document is not valid without its technical annex, whose number coincides with the number of certificate.

Page 1 / 2

LGAI TECHNOLOGICAL CENTER, S.A. CIF: A-63207492


LGAI Technological Center, S.A. (APPLUS)
Campus UAB s/n – Ronda de la Font del Carme, s/n
E - 08193 Bellaterra (Barcelona)
T +34 93 567 20 00
www.appluslaboratories.com
Technical Annex Ed. 5
09/12/2019

0370-CPR-0582

CERTIFIED PERFORMANCES

Clauses in this
Essential characteristics Mandated level(s) or class(es)
European Standard

Response delay NA
- Opening under wind load within a given time; 4.1.1
- Opening under snow load within a given time. NA
• Thermally uninsulated
• Dual purpose use
Operational reliability • For use inside and outside a
4.2.2
- Application categories; smoke reservoir
- Motor rating. • Horizontal direction of motor
shaft.
4.2.3 NPD
Effectiveness of smoke/hot gas extraction:
- Gas flow and pressure maintenance during smoke and 4.3.2 +/-20% (PS)
heat extraction test.
Resistance to fire 4.4 F400 (120)

Ability to open under environmental conditions NA


- Opening under wind load within a given time; 4.5
- Opening under snow load within a given time. NA

Durability of operational reliability 4.6 NPD

PASS; NPD = No Performance Determined; NA = Not Applicable

PRODUCT

1.- Application: 2.- Characteristics:

• Extractor tested inside the furnace. • Motor: “CMT” F400 type by Tilman:
• Extractor F400 (120). - From sizes 80 to 132
• Dual use. - Up to 7.5 kW
• Horizontal direction of motor shaft. - 4, 6, 4/8 poles
• Motor: “FLSHT” F400 type by Nidec Leroy Somer
- From sizes 80 to 160
- Up to 15 kW
- 4, 6, 4/8 poles
• Fans tested at 50 Hz (Also valid for 60 Hz D.O.L
in models with 6p polarity or greater number of
poles)
3.- Accessories:

• Frequency converter model “Powerdrive F300” by


Nidec brand.

The complete technical data of the certified range BOX RLFX F400 & BOX RLF F400 are detailed in the technical