SKETCH STAKING 

SHEET SHEET NO.: 1 Proj. No.: ____________ Page No.: ___________


OF 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
POLE PRI POLE  TRANS   MISC.    
POLE  BACK  GUY        E ANC.        SEC    N N N R/W          O MEMBERS NAME        
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS       
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N AND NO. OR      REMARKS
(ABC ) "G" MTRS. SIZE MTRS. "M"
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

1 60 1 1 C1

2 60 1 1 C1

3 60 1 1 C2 1 1‐1 1 2‐1

4 60 1 1 C2 1 1‐1 1 2‐1

5 60 1 1 C1

6 60 1 1 C2 1 1‐1 1 2‐1

7 60 1 1 C2 1 1‐1 1 2‐1

8 60 1 1 C2 1 1‐1 1 2‐1

9 60 1 1 C2 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
540 3 C1 6 1‐1 6 2‐1
6 C2

SEE SHEET NO. "1 OF 13"
SKETCH STAKING SHEET SHEET NO.:          2 Proj. No.: ____________ Page No.: ___________
OF 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

10 660 1 1 C2 1 1‐1 1 2‐1

11 60 1 1 C3 1 1‐1 1 2‐1

12 60 1 1 C2 1 1‐1 1 2‐1

13 60 1 1 C1

14 60 1 1 C1

15 60 1 1 C2 1 1‐1 1 2‐1

16 60 1 1 C2 1 1‐1 1 2‐1

17 60 1 1 C2 1 1‐1 1 2‐1

18 60 1 1 C1

19 60 1 1 C1

20 60 1 1 C2 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
660 4 C1 7 1‐1 7 2‐1
6 C2
1 C3

SEE SHEET NO. "2 OF 13"
SKETCH STAKING SHEET SHEET NO.:           3 Proj. No.: ____________ Page No.: ___________
OF 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

21 60 1 1 C1

22 60 1 1 C1

23 60 1 1 C2 1 1‐1 1 2‐1

24 60 1 1 C1

25 60 1 1 C2 1 1‐1 1 2‐1

26 60 1 1 C1

27 60 1 1 C2 1 1‐1 1 2‐1

28 60 1 1 C2 1 1‐1 1 2‐1

29 60 1 1 C1

30 60 1 1 C1

31 60 1 1 C2 1 1‐1 1 2‐1

32 60 1 1 C1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
720 7 C1 5 1‐1 4 2‐1
5 C2

SEE SHEET NO. "3 OF 13"
SKETCH STAKING SHEET SHEET NO.:        4 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

33 60 1 1 C2 1 1‐1 1 2‐1

34 60 1 1 C2 1 1‐1 1 2‐1

35 60 1 1 C2 1 1‐1 1 2‐1

36 60 1 1 C3 1 1‐1 1 2‐1

37 60 1 1 C2 1 1‐1 1 2‐1

38 60 1 1 C1

39 60 1 1 C2 1 1‐1 1 2‐1

40 60 1 1 C2 1 1‐1 1 2‐1

41 60 1 1 C1

42 60 1 1 C2 1 1‐1 1 2‐1

43 60 1 1 C2 1 1‐1 1 2‐1

44 60 1 1 C3 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
720 2 C1 10 1‐1 10 2‐1
8 C2
2 C3

SEE SHEET NO. "4 OF 13"
SKETCH STAKING SHEET SHEET NO.:        5 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

45 60 1 1 C2 1 1‐1 1 2‐1

46 60 1 1 C2 1 1‐1 1 2‐1

47 60 1 1 C1

48 60 1 1 C2 1 1‐1 1 2‐1

49 60 1 1 C2 1 1‐1 1 2‐1

50 60 1 1 C3 1 1‐1 1 2‐1

51 60 1 1 C2 1 1‐1 1 2‐1

52 60 1 1 C2 1 1‐1 1 2‐1

53 60 1 1 C3 1 1‐1 1 2‐1

54 60 1 1 C2 1 1‐1 1 2‐1

55 60 1 1 C1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
660 2 C1 9 1‐1 9 2‐1
7 C2
2 C3

SEE SHEET NO. "5 OF 13"
SKETCH STAKING SHEET SHEET NO.:        5 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

56 60 1 1 C2 1 1‐1 1 2‐1

57 60 1 1 C2 1 1‐1 1 2‐1

58 60 1 1 C2 1 1‐1 1 2‐1

59 60 1 1 C2 1 1‐1 1 2‐1

60 60 1 1 C2 1 1‐1 1 2‐1

61 60 1 1 C2 1 1‐1 1 2‐1

62 60 1 1 C3 1 1‐1 1 2‐1

63 60 1 1 C2 1 1‐1 1 2‐1

64 60 1 1 C2 1 1‐1 1 2‐1

65 60 1 1 C3 1 1‐1 1 2‐1

66 60 1 1 C3 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
660 8 C2 11 1‐1 11 2‐1
3 C3

SEE SHEET NO. "6 OF 13"
SKETCH STAKING SHEET SHEET NO.:        7 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

67 60 1 1 C2 1 1‐1 1 2‐1

68 60 1 1 C2 1 1‐1 1 2‐1

69 60 1 1 C2 1 1‐1 1 2‐1

70 60 1 1 C2 1 1‐1 1 2‐1

71 60 1 1 C2 1 1‐1 1 2‐1

72 60 1 1 C3 1 1‐1 1 2‐1

73 60 1 1 C2 1 1‐1 1 2‐1

74 60 1 1 C1

75 60 1 1 C2 1 1‐1 1 2‐1

76 60 1 1 C1

77 60 1 1 C2 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
660 2 C1 9 1‐1 9 2‐1
8 C2
1 C3

SEE SHEET NO. "7 OF 13"
SKETCH STAKING SHEET SHEET NO.:        8 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

78 60 1 1 C2 1 1‐1 1 2‐1

79 60 1 1 C1

80 60 1 1 C1

81 60 1 1 C2 1 1‐1 1 2‐1

82 60 1 1 C1

83 60 1 1 C2 1 1‐1 1 2‐1

84 60 1 1 C1

85 60 1 1 C2 1 1‐1 1 2‐1

86 60 1 1 C1

87 60 1 1 C2 1 1‐1 1 2‐1

88 60 1 1 C1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
660 6 C1 5 1‐1 4 2‐1
5 C2

SEE SHEET NO. "8 OF 13"
SKETCH STAKING SHEET SHEET NO.:        9 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

89 60 1 1 C2 1 1‐1 1 2‐1

90 60 1 1 C2 1 1‐1 1 2‐1

91 60 1 1 C2 1 1‐1 1 2‐1

92 60 1 1 C2 1 1‐1 1 2‐1

93 60 1 1 C1

94 60 1 1 C2 1 1‐1 1 2‐1

95 60 1 1 C1

96 60 1 1 C2 1 1‐1 1 2‐1

97 60 1 1 C3 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
540 2 C1 7 1‐1 7 2‐1
6 C2
1 C3

SEE SHEET NO. "9 OF 13"
SKETCH STAKING SHEET SHEET NO.:       10 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

98 60 1 1 C2 1 1‐1 1 2‐1

99 60 1 1 C2 1 1‐1 1 2‐1

100 60 1 1 C2 1 1‐1 1 2‐1

101 60 1 1 C2 1 1‐1 1 2‐1

102 60 1 1 C2 1 1‐1 1 2‐1

103 60 1 1 C2 1 1‐1 1 2‐1

104 60 1 1 C1

105 60 1 1 C2 1 1‐1 1 2‐1

106 60 1 1 C3 1 1‐1 1 2‐1

107 60 1 1 C2 1 1‐1 1 2‐1

108 60 1 1 C2 1 1‐1 1 2‐1

109 60 1 1 C2 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
660 1 C1 11 1‐1 11 2‐1
10 C2
1 C3

SEE SHEET NO. "10 OF 13"
SKETCH STAKING SHEET SHEET NO.:        11 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

110 60 1 1 C1

111 60 1 1 C1

112 60 1 1 C2 1 1‐1 1 2‐1

113 60 1 1 C1

114 60 1 1 C1

115 60 1 1 C2 1 1‐1 1 2‐1

116 60 1 1 C2 1 1‐1 1 2‐1

117 60 1 1 C2 1 1‐1 1 2‐1

118 60 1 1 C1

119 60 1 1 C1

120 60 1 1 C2 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
660 6 C1 5 1‐1 5 2‐1
5 C2

SEE SHEET NO. "11 OF 13"
SKETCH STAKING SHEET SHEET NO.:        11 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

121 60 1 1 C2 1 1‐1 1 2‐1

122 60 1 1 C1

123 60 1 1 C1

124 60 1 1 C2 1 1‐1 1 2‐1

125 60 1 1 C2 1 1‐1 1 2‐1

126 60 1 1 C2 1 1‐1 1 2‐1

127 60 1 1 C2 1 1‐1 1 2‐1

128 60 1 1 C2 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
480 2 C1 6 1‐1 5 2‐1
6 C2

SEE SHEET NO. "12 OF 13"
SKETCH STAKING SHEET SHEET NO.:        11 Proj. No.: ____________ Page No.: ___________
OF                 13 Checked by:___________ Staked by: ___________
SEE SHEET NO.             Project Name:             CONSTRUCTION OF POWER TWO PHASE DISTRIBUTION LINE MAP REF. Date: ________________ Date: ______________
Primary Cond: 1/0 ASCR            Project Location:                    MAGSIDEL, CALAYAN, CAGAYAN GOOGLE EARTH Released by:_____ Final Inv. By: ____________
Neutral Cond: 1/0 ASCR Date: ________________ Date: ______________
Ruling Span: 60 meters
PRI  L SECONDARY SERVICE C
PRI POLE  TRANS   MISC.     MEMBERS NAME        
POLE  BACK  POLE GUY        E ANC.        SEC    N N N R/W          O
TOP UNIT  FORMER     "M2" SPAN  WIRE  DROP  UNITS        AND NO. OR      
NO. SPAN  "E" A 'F" OR  O "J" O  SIZE O "K" RI. N
(ABC ) "G" MTRS. SIZE MTRS. "M" REMARKS
MTRS H C D UB . . . S
SPAN Q Q CODE Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE QUAN Q Q CODE Q CODE Q CODE Q CODE COMPUTER CODED

129 60 1 1 C2 1 1‐1 1 2‐1

130 60 1 1 C1

131 60 1 1 C1

132 60 1 1 C2 1 1‐1 1 2‐1

133 60 1 1 C2 1 1‐1 1 2‐1

134 60 1 1 C2 1 1‐1 1 2‐1

QUANTITY Q CODE Q CODE Q CODE Q CODE Q CODE QUAN CODE Q CODE Q Q CODE Q CODE Q CODE Q CODE
360 2 C1 5 1‐1 5 2‐1
4 C2

SEE SHEET NO. "13 OF 13"