Professional Documents
Culture Documents
00-381-9312 | +1-401-781-8220
www.tyco-fire.com
Operation
The By-Pass Valve in the Model AMD-3
Automatic Nitrogen Maintenance De- INLET (HIGH
vice is opened to quickly fill the system PRESSURE)
during initial pressurization. After the GAUGE
required system pressure is reached, /2" )
9-14 mm
OUTLET (LOW
the By-Pass Valve is closed and the PRESSURE) ,
Cylinder Control Valve is left open to
GAUGE (241
place the Model AMD-3 Device in au-
tomatic operation.
Given a small leak in the system, the
Pressure Regulator will automatically CYLINDER
maintain system pressure at the pre- CONTROL
set level. The 3/32 inch (2,4 mm) orifice VALVE
in the Restrictor Check Valve limits the (NORMALLY
flow of nitrogen from the Pressure Reg- OPEN)
ulator into the system to a value signifi-
cantly less than that exhausted by the RESTRICTOR
C.G.A.
operation of a 5.6 K-factor sprinkler. CHECK VALVE
CONNECTION
P/N 92-326-1-003
NO. 580
Installation "
The TYCO Model AMD-3 Automatic Ni- 1/2 )
trogen Maintenance Device must be in- 12,-5 mm TWO-STAGE
7 PRESSURE
stalled in accordance with the following (31 REGULATOR CYLINDER OF
instructions. BY-PASS (ADJUSTABLE) 3000 PSI MAX.
1. Assemble the Model AMD-3 Device VALVE P/N 92-290-1-001 NITROGEN
(NORMALLY
components as shown in Figure 1.
CLOSED)
Apply pipe-thread sealant sparingly 1/4" TUBE,
P/N 46-047-1-002
to male pipe threads only. 5 FEET LONG
2. Make connections a minimum of 1/2 1/4" MALE NPT
(DN15) pipe size between the Model x 1/4" TUBE
AMD-3 Device and the system. CONNECTOR
3. Place a 1/2 inch (DN15), non-spring (156-1/4 1/2" NPT OUTLET
loaded, rubber-faced, swing-type 8,8 "
mm CONNECTION
check valve (such as P/N 46-049- ) (TO SYSTEM)
1-004) between the Model AMD-3
Device and the system to pressur-
ize. A check valve of this type is typ-
ically provided in the air supply trim
of TYCO dry pipe valves, preaction
valves, and dry pilot trim.
FIGURE 1
4. Install a minimum 1/4 inch size pres- MODEL AMD-3
sure relief valve (such as P/N 92-343- AUTOMATIC NITROGEN MAINTENANCE DEVICE
1020) between the Model AMD-3
Device and the system piping. A re-
lief valve of this type is typically pro- c. Inspect the Cylinder Control e. With the cylinder securely in
vided in the air supply trim of TYCO Valve outlet for dirt, dust, dam- place and while standing to
dry pipe valves, preaction valves, and aged threads, oil, or grease. Re- the side or rear of the Cylin-
dry pilot trim. move dirt and dust with a clean der Control Valve, momentarily
cloth. If damaged threads, oil, crack open the Cylinder Control
5. Following the steps outlined in the or grease are present, replace Valve. This procedure is intend-
caution below, install the nitrogen the cylinder. ed to blow out any foreign mat-
cylinder. ter that may be inside the valve
d. Inspect the Pressure Regula-
outlet.
CAUTION tor inlet for dirt, dust, damaged
threads, oil, or grease. Re- f. Attach the Model AMD-3 Device
a. The following instructions re- move dirt and dust with a clean to the Cylinder Control Valve
garding the nitrogen cylin- cloth. If damaged threads, oil, and securely wrench-tighten.
der must be strictly followed. or grease are present, have the
Failure to do so may result in Pressure Regulator serviced by
personal injury or property an authorized agent of the Vic-
damage. tor Equipment Company.
b. Secure the cylinder to a wall or
post, ensuring it will not tip or
fall if accidently bumped.
TFP1241
Page 3 of 4
Operating -30
Procedure
DEWPOINT OF SUPPLY
Place the TYCO Model AMD-3 Auto-
matic Nitrogen Maintenance Device in -40
NITROGEN, °F
operation in accordance with the fol-
lowing procedure.
1. Determine the pressure that meets
the minimum requirements of the -50
system to pressurize.
2. Close the control valve in the air
supply trim to the system.
3. Turn the Two-Stage Pressure Reg- -60
ulator adjusting handle counter- 0 10 20 30 40 50 60
clockwise until the adjusting spring SYSTEM PRESSURE, PSIG
pressure is fully released.
* BASED ON A DEWPOINT OF -60°F AT ATMOSPHERIC PRESSURE.
4. Standing to the side of the nitrogen
cylinder opposite from the Pressure FIGURE 2
Regulator, slowly crack open the MAXIMUM DEWPOINT OF SUPPLY NITROGEN AS A
Cylinder Control Valve until the cyl- FUNCTION OF SYSTEM PRESSURE*
inder pressure is indicated on the
High Pressure Gauge and then fully
open the Cylinder Control Valve to
seal its packing. Care and Responsibility lies with sprinkler own-
ers for the inspection, testing, and
5. Slowly turn the Two-Stage Pres-
sure Regulator handle clockwise
Maintenance maintenance of their fire protection
system and devices in compliance with
until the Outlet Pressure Gauge in- The TYCO Model AMD-3 Automatic this document, as well as with the ap-
dicates the required pressure es- Nitrogen Maintenance Device must be plicable standards of the National Fire
tablished in Step 1. maintained and serviced in accordance Protection Association (for example,
with the following instructions, in addi- NFPA 25), in addition to the standards
6. Open the By-Pass Valve in the tion to any specific requirements of the of any authorities having jurisdiction.
Model AMD-3 Device. NFPA. Any impairment must be imme- Contact the installing contractor or
7. Open the control valve in the air diately corrected. sprinkler manufacturer regarding any
supply trim to the system. questions.
8. After the system pressure sta- NOTICE Automatic sprinkler systems should be
bilizes, note the value on the Before closing a fire protection system inspected, tested, and maintained by a
system pressure gauge and main control valve for maintenance qualified Inspection Service in accor-
compare it with the require- work on the fire protection system that dance with local requirements and/or
ment. Adjust the Pressure it controls, obtain permission to shut national code.
Regulator, as required (counter- down the affected fire protection sys- INSPECTION PROCEDURE
clockwise to decrease and clock- tem from the proper authorities and no- The Model AMD-3 Automatic Nitrogen
wise to increase). One-half turn tify all personnel who may be affected Maintenance Device must be inspect-
of the stem changes the outlet by this action. ed quarterly in accordance with the
pressure by approximately 8 psi. following instructions.
It is recommended that a spare supply
9. If the system pressure must be of nitrogen be kept on hand. 1. Verify that the control valve in the air
decreased, first re-adjust the supply trim to the system is open.
Make no attempt to field-repair or
Pressure Regulator, then momen-
replace any component of the Pressure 2. Verify that the nitrogen Cylinder Con-
tarily open a connection to the
Regulator. trol Valve is open.
system to reduce the pressure to
below the required value. Allow the Inspections should be made more 3. Verify that the By-Pass Valve is
system pressure to automatically frequently, after the system is initially closed.
stabilize. placed in service, to develop a guide-
line as to the required schedule for
10. Close the By-Pass Valve in the NOTICE
nitrogen cylinder replacement. Graph-
Model AMD-3 Device. Following a sprinkler operation, in
ing the Inlet Gauge pressure noted
during each inspection will assist in order to prevent a delay in the re-
NOTICE this evaluation. lease of the automatic control
Following a sprinkler operation, in valve, the By-Pass Valve must be
After placing a fire protection system closed when the fire protection sys-
order to prevent a delay in the re- in service, notify the proper authorities
lease of the automatic control tem is in service.
and advise those responsible for moni-
valve, the By-Pass Valve must be toring proprietary and/or central station 4. Verify that the system pressure
closed when the fire protection sys- alarms. gauge indicates the same value as
tem is in service. the previously established require-
11. Check all supply pressure connec- ment. If not, re-adjust per Step 8 of
tions for leaks. the Operating Procedure section.
TFP1241
Page 4 of 4
Copyright © 2005-2010 Tyco Fire Suppression & Building Products. All rights reserved.