Professional Documents
Culture Documents
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
List of Figures
Figure 1: Mounting High Voltage Terminal Pads.......................................................................... 9
Figure 2: Checking for Continuity ................................................................................................10
IB-DT09-F1-COM
Page 2 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004249
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
Figure 3: Manifold Block with Isolation Valve and Pressure Relief Tool .................................. 11
Figure 4: Quick Connect Valve ..................................................................................................... 12
Figure 5: Motor Overload Switch (Example) – Press “START” .................................................... 16
Figure 6: Manual Operation ......................................................................................................... 17
Figure 7: Transducer - Seismic Frame ........................................................................................ 20
Figure 8: Transducer - Linkage Cover ......................................................................................... 20
Figure 9: Rem ove Pin from Linkage............................................................................................. 21
Figure 10: Mount Bracket and Pin ............................................................................................... 21
Figure 11: Vanguard Linear Transducer ..................................................................................... 21
Figure 12: Doble 3190 Linear Transducer .................................................................................. 22
Figure 13: Remove Center Bolt from Lever ................................................................................ 22
Figure 14: Vanguard Rotary Transducer .................................................................................... 22
Figure 15: Novotechnik Rotary – Bracket ................................................................................... 23
Figure 16: Doble TR3170 Transducer .......................................................................................... 23
Figure 17: Doble TR3190 Transducer .......................................................................................... 24
Figure 18: Timing: Closing (C) Operation..................................................................................... 25
Figure 19: Timing: Opening (O) Operation .................................................................................. 26
Figure 20: Timing: Trip-Free (CO) Operation ............................................................................... 27
IB-DT09-F1-COM
Page 3 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004250
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
Revision History
Revision Record Description Revised by Date
IB-DT09-F1-COM
Page 4 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004251
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
COMMISSIONING CHECKLIST
OWNER: SUBSTATION:
1.3 Field Assembled Elements Tightness / Torque 1.4 External Condition (Cleanliness, Damages, Rust)
5.7 M anual M echanical Close / Trip Operation 5.8 Mechanical Counter Check
5.9 Position / Spring Indicator Flags Check 5.10 Local Electrical Close
5.13 Local Electrical Backup Trip 5.14 Close / Trip Position Lights Operation Check
IB-DT09-F1-COM
Page 5 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004252
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
Print Name:
Signature:
Date:
Return a copy to: GE Grid Solutions Inc., Attn: QA, One Power Lane, Charleroi, PA 15022, USA
IB-DT09-F1-COM
Page 6 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004253
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
WARNING
Porcelain insulators under pressures greater than 3-5 psi pose a significant pressure/explosion hazard.
Failure to reduce the pressure to safe levels when commencing work on pressurized insulators could result
in significant injury or damage to adjacent property.
IMPORTANT
Read all safety instructions in the IB-SAFE and IB-SF6 documents prior to performing commissioning.
Closely follow all instructions and service advisories. Thoroughly study these instructions before beginning
any operation or adjustment.
Thoroughly instruct and supervise all personnel associated with the installation, operation or maintenance of
high voltage circuit breakers regarding high voltage equipment in general, and specifically on the particular
breaker model that is being serviced.
The commissioning checklist’s primary purpose is to ensure that in the course of commissioning, all of the
important work, which must be carried out to guarantee the reliability of the breaker, is performed.
IMPORTANT
In the event of any warranty claim, the absence of this checklist may result in reduction of the claim.
Please note:
1. General information such as name of the user, name of substation, type of breaker, serial number and
the year of manufacture must always be filled in.
2. Each commissioning checklist is only valid for one breaker. Treat the commissioning checklist in the
book as a master and photocopy it whenever commissioning or recommissioning the breaker.
3. Note the serial number of the breaker on each page.
4. Carry out all work described in previous sections.
WARNING
Never install or replace the high-voltage terminals when the breaker is pressurized.
High voltage terminals are optional accessories (supplied when requested by the customer) for circuit
breakers (Bag H1). If provided by GE Grid Solutions, attach the optional HV terminal clamps (or adapters)
using the provided hardware to the four-hole pad on the top of the bushings (Figure 1).
1. Verify alignment of the high voltage terminal pads prior to assembly.
2. Before making the connection, thoroughly clean the bare contact surfaces as described:
a. For bare aluminum, bronze, or copper contact surfaces, abrade the contact surface using a
wire brush or pad (for example, Scotchbrite®) to remove oxidation.
IMPORTANT
Aluminum oxidizes quickly; it is imperative that the preceding step (2.a) is completed even if the surface
looks clean.
b. For tin or silver plated contact surfaces, clean with care as described in 2.a. Ensure that the
surface of the plating is not broken. Alternatively, the plated surfaces may be cleaned with a
solvent that will not damage the plating.
3. Clean tin or silver plated contact surfaces with care to ensure that the surface of the plating is not
broken. Alternatively, the plated surfaces may be cleaned with a solvent that will not damage the
plating.
4. Immediately apply a thin layer of contact grease such as Penetrox A to all contact surfaces to
prevent further oxidation of the contact surfaces. Brush contact grease onto contact surfaces with a
wire brush or pad (for example, Scotchbrite ®).
5. Assemble hardware (Bag H2, if supplied) and torque according to GE Grid Solutions Specification TS-
00007 within 5 minutes of completing grease application (step 4).
6. Remove excess contact grease, leaving a small bead around the outside edge of the joint to prevent
water infiltration.
7. Clean any dirt or debris, which was created during preparation of the HV terminals, from the
bushings.
IB-DT09-F1-COM
Page 8 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004255
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
1) Remove Oxidation
2) Clean with Alcohol
3) Apply Contact Grease with
Scotchbrite®
1.7 Grounding
Verify that the breaker has been grounded per the IB-GROUND document.
IMPORTANT
Take these readings early in the morning, to avoid inaccuracies caused by solar heating of the circuit
breaker during the day.
The breaker specific rated pressure can be found in the control schematics in the IB-REP document. These
values may differ from the standard values listed in the IB-DT09-F1-BRKR-DESC document if a special density
monitor was ordered. Verify that the gas cylinder is the one provided with the equipment or that the gas
meets GE Grid Solutions requirements (IB-SF6). Read and note on the commissioning checklist the SF6 gas
pressure with a calibrated gauge.
IB-DT09-F1-COM
Page 9 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004256
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
IB-DT09-F1-COM
Page 10 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004257
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
4
6
Figure 3: Manifold Block with Isolation Valve and Pressure Relief Tool
1 Density Monitor 2 Manifold Block
3 Manifold Isolation Valve 4 Pressure Relief Tool
5 Fill Port 6 Needle Valve
a. Making sure the needle valve is closed; install the pressure relief tool into the fill port on the
manifold block
b. Turn the manifold isolation valve counterclockwise to isolate the manifold block from the
tank.
c. Slowly open the needle valve until the density monitor needle goes to the yellow/green
border that indicates “Low Pressure Alarm” and then close the needle valve to maintain the
indicator needle in that position. Check for continuity with a multimeter at the density
monitor contacts 1 and 2 found in the control cabinet (refer to Figure 2 above for a visual
representation). Report the pressure value on the commissioning checklist.
d. Repeat the previous step with the needle going down to the lockout pressure that is indicated
by the transition from yellow to red on the density monitor. Check for continuity between
density monitor contacts 3-4 and 5-6. Report the lockout pressure in the commissioning
checklist.
e. Remove the pressure relief tool and open the isolation valve.
IB-DT09-F1-COM
Page 11 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004258
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
3. For standard plumbing systems (without 3-way valves or a pressure relief tool):
3
1a
4 1b
4. Operate the tank isolating valves (Figure 4, Item 1) of all 3 poles by releasing the lower nut (Figure 4,
Item 1b) for 4 to 6 mm (3 turns) with a 1” or 26/27mm wrench. This will isolate the tank from the
density monitor.
CAUTION
Don’t disengage the nuts (Figure 4, Item 1b) fully to avoid uncontrolled blow off.
Don’t dismantle the valve bodies (Figure 4, Item 1a)
5. Remove the cap of the DILO® filling port (Figure 4, Item 4).
6. Operate the DILO® filling port (Figure 4, Item 3) by pushing the valve pin for a controlled SF 6 blow off.
7. Release the pressure at the value for SF 6 alarm, check the contacts 1-2 with a multimeter. Note the
pressure value on the commissioning checklist.
IB-DT09-F1-COM
Page 12 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004259
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
8. Release the pressure at the value for SF 6 lockout, check the contacts 3-4 and 5-6 with a multimeter.
Note the pressure on the commissioning checklist.
NOTE
Because of the small volume within the gauge and density monitor assembly, a pressure drop of 5 – 10 psig
(0.34 – 0.69 bar) may be witnessed as the fittings are unscrewed. If, at any time during this sequence, the
pressure of the WIKA® gauge drops too quickly, or too low, simply tighten the assembly back on to the
breaker and repeat he above procedure.
9. Retighten fittings with a torque of 147 ft-lb (200 Nm). Be sure to use an additional wrench to assure
the fitting do not become loose from the tank.
10. As necessary, fill the system with SF 6 gas to the rated density using the procedure in the IB-FILL-SF6
document.
IMPORTANT
The contacts of the WIKA® density monitor are not adjustable. If the density monitor is found to be out of
calibration, notify GE Grid Solutions Inc (contact information for GE Grid Solutions Customer Service is listed
in the IB-DT09-F1-SPR-PRTS document).
IB-DT09-F1-COM
Page 13 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004260
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
IMPORTANT
DO NOT manually charge the circuit breaker if the handle appears to be restricted during charging. Contact
GE Grid Solutions Inc. Customer Service if experiencing such a problem.
DANGER
Before installing the supply and control cables, make sure the circuit breaker is not energized.
CAUTION
Before applying voltage or turning on the motor protection switch, make sure there are no objects
or parts of the body in the charging system area.
When the supply voltage is applied, the anti-condensation heater will be hot. It may burn skin or clothing.
Do not touch the heater.
The control cabinet(s) is wired at the factory, with all lead wires from the mechanism components connected
to terminal blocks. Make all customer connections at the terminal blocks. Refer to the specific wiring and
connection diagrams in IB-REP.
Attach the customer’s power and auxiliary circuit leads to the circuit breaker in the central control cabinet.
Bring the leads through the bottom of the cabinet after removing the dropout panel provided in the cabinet
floor and punching the appropriate conduit entrance holes in it.
IB-DT09-F1-COM
Page 14 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004261
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
1. Measure the resistance of the anti-condensation heater(s) at the terminals in the mechanism. Note this
value(s) on the commissioning checklist.
2. Check the measured value(s) against the reference value on the routine test report (IB-REP).
IMPORTANT
Anti-condensation heaters must remain on at all times (even if breaker is not being used – see storage
chapter) to prevent moisture from developing inside of the co ntrol cabinet.
5.2 Polarity
Verify DC input polarity. Only then controls may be energized.
IB-DT09-F1-COM
Page 15 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004262
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
Press Start
CAUTION
This is the first operation of the breaker and as a safety precaution, all personnel should be at least 40
meters away from the circuit breaker or in a protected area.
WARNING
Never operate the mechanism when decoupled from the circuit breaker.
IB-DT09-F1-COM
Page 16 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004263
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
IMPORTANT
Refer to document IB-FK-MECH-DESC-STD for additional information on the operating mechanism.
CAUTION
When operating the breaker manually, make sure that:
Gas pressure is greater than the Lockout set point (refer to the control schematics in the IB -REP
document for actual value).
All tools are removed and personnel are clear of the operating mechanism.
Control and auxiliary power are removed.
Only use the hand crank when all local control power has been de-energized.
Do not operate the manual control switch unless all of the above are observed
Observe the warning tag below, which is attached to the mechanism
Prior to performing any manual operations, the Manual Release Disabling Device must be repositioned
downward and to the left.
1. This is accomplished by first loosening the M6 bolts indicated in Figure 6.
2. Next slide the disabling device plate along the slots provided. Be sure to retighten the M6 bolts once
the disabling device is repositioned. This device may remain in the off position (ability to rotate the
release levers) unless service or maintenance on the mechanism or circuit breaker warrant
otherwise.
Perform the local close and then trip operations manually by using the manual operation releases as
depicted in Figure 6.
IB-DT09-F1-COM
Page 18 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004265
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
NOTE
Sections 6.0 and 7.0 are for breakers that ship with the bushings not assembled to the tanks (dead tank
circuit breaker) / base frame (live tank circuit breaker).
6.2 Amperage
On the commissioning checklist, enter the amperage at which the measurement is performed. A minimum
current of 100 A DC is required.
CAUTION
Never operate the breaker with an SF 6 gas density at or below the lockout value.
IB-DT09-F1-COM
Page 19 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004266
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
Remove
Linkage
IB-DT09-F1-COM
Page 20 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004267
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
Linkage Pin
Pin
Bracket
IB-DT09-F1-COM
Page 21 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004268
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
IB-DT09-F1-COM
Page 22 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004269
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
Standoff adapter
Bracket
Novotechnik Rotary
Transducer
Linkage
C-Clamp
Transducer
Bracket
IB-DT09-F1-COM
Page 23 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004270
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
IB-DT09-F1-COM
Page 24 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004271
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
NOTE
Before beginning test operations, make sure that the circuit breaker is filled to its rated d ensity, the closing
spring indicator shows "Charged” and the supply voltage is at its rated value.
Breaker is Closed
X7
Close Time
Travel
Curve
Contact just begings to
occur in the interrupter
Breaker is Opened
IB-DT09-F1-COM
Page 25 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004272
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
Breaker is Closed
X7
Breaker is Opened
IB-DT09-F1-COM
Page 26 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004273
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Commissioning Instructions
Breaker is Closed
Momentarily
Trip-Free Time
Travel
Curve
Contact has just
Contact just begins to separated in the
occur in the interrupter interrupter
Breaker is Opened
IB-DT09-F1-COM
Page 27 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004274
Commissioning Instructions
Fo r Type DT1-72.5 F1 Circuit Break ers
DANGER
Under no circumstance, perform any test that circulates primary current while the secondary is open.
Circulating primary current while the secondary is open will produce dangerously high voltages.
Take care to prevent unintentional core magnetism during field -testing. Do not use any source of DC
current on a current transformer since certain types of DC instruments will severely magnetize the core and
drastically increase its exciting current characteristics. When using a variable voltage source always run the
voltage down to zero volts before turning it off; failure to do so will result in core magnetism.
DANGER
DO NOT perform Hi-Pot dielectric tests on this circuit breaker with a DC voltage!
International standards, such as IEC 62271-203, recommend not to perform DC voltage tests on metal-
enclosed switchgear. This circuit breaker contains internal solid insulation made with fiber/cloth reinforced
vacuum-impregnated epoxy. This insulation is used in interrupter line-to-ground supports, operating rods
and gap insulators. Epoxy insulation is susceptible to strong polarization under a DC voltage. The
application of a DC voltage will generate charge separation which will enhance the voltage stress of these
components. This is very likely to cause a dielectric failure and permanent damage to the insulation du ring
the DC test or during final energization of the circuit breaker under AC voltage. Nevertheless, megger
testing in the range of 10-20 kV is acceptable. Tests above these values should not be performed under a
DC voltage. Performing any hi-pot tests above this value will void the circuit breaker warranty; GE Grid
Solutions is not responsible for any damage caused by such a test.
8.0 Comments
Briefly describe work performed and if customer expectations were met. Describe all other tests performed.
Note all remarks and nonconformance. Comment on desirable improvements. Comment on the general
appearance of the substation or plant and overall condition.
IB-DT09-F1-COM
Page 28 of 28
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004275
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
IB-DT09-F1-MAINT
Page 1 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004276
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
IB-DT09-F1-MAINT
Page 2 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004277
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
List of Figures
Figure 1: Permissible Number of C-O Operations .............................................................................. 10
Figure 2: RTV Weather/ Mastic Seal ....................................................................................................... 13
Figure 3: Tank Vacuum Cleaner .............................................................................................................. 15
Figure 4: Cleaning of Tank ........................................................................................................................ 15
Figure 5: Vacuuming Filter Acceptance Levels ................................................................................... 15
Figure 6: Pole Assembly – Lubrication .................................................................................................. 18
Figure 7: Lubrication of the Drive Shaft................................................................................................ 19
Figure 8: Linkage Assembly - Lubrication ............................................................................................ 20
Figure 9: Points of Lubrication on the Bushing High Voltage Terminals ..................................... 21
Figure 10: Desiccant and Retaining Screen......................................................................................... 22
Figure 11: PRD and Desiccant Assembly .............................................................................................. 23
Figure 12: PRD Flange ................................................................................................................................ 24
Figure 13: Installing the PRD Cover ....................................................................................................... 25
Figure 14: Cabinet Seals (Generic Cabinet) .......................................................................................... 25
Figure 15: Changing the Interrupter (Generic Picture) ..................................................................... 26
Figure 16: Front View of Mechanism ..................................................................................................... 27
Figure 17: Locating the Trip Coils ........................................................................................................... 28
Figure 18: Trip Coil Location .................................................................................................................... 28
Figure 19: Trip Coil Detail .......................................................................................................................... 29
Figure 20: Removing Magnetic Segment .............................................................................................. 29
Figure 21: Removing the Trip Coil .......................................................................................................... 30
Figure 22: Locating the Close Coil(s) ...................................................................................................... 30
Figure 23: Locating the Motor ................................................................................................................. 31
Figure 24: Motor Securing Bolts .............................................................................................................. 32
Figure 25: Clamping Mechanism on Center Conductor ................................................................... 33
Figure 26: Removing the Bushing ........................................................................................................... 33
Figure 27: Bushing and CT Assembly .................................................................................................... 34
Figure 28: Shim Placement (Representation Only) ............................................................................ 35
Figure 29: CT Orientation .......................................................................................................................... 35
Figure 30: CT Wiring ................................................................................................................................... 36
Figure 31: Anti-condensation Heater Cover ........................................................................................ 37
IB-DT09-F1-MAINT
Page 3 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004278
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
List of Tables
Table 1: Recommended Maintenance Schedule .................................................................................. 7
Table 2: Tank Cleaning Acceptance Criteria ....................................................................................... 16
Table 3: List of Replacement Seals ........................................................................................................ 17
Table 4: List of Lubricants and Greases ............................................................................................... 17
IB-DT09-F1-MAINT
Page 4 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004279
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
Revision History
Revision Record Description Revised by Date
IB-DT09-F1-MAINT
Page 5 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004280
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
1.0 General
These maintenance directives incorporate measures for avoiding the hazards involved in the application of
SF6 gas to switchgear. Such directives are protective measures and recommendations for the user of SF6
switchgear.
NOTE
The maintenance schedule described in this document is only a recommendation and local rules or
substation plans or regulations may take precedence over the guidelines provided herein.
Any personnel performing maintenance or inspection on SF6 switchgear should read this section and comply
with these instructions as well as the safety precautions prescribed by their employer. Failure to observe the
safety precautions described herein, and those defined by the employer, may result in injury or death.
IMPORTANT
Maintenance is to be carried out by GE Grid Solutions service technicians or by trained personnel.
CAUTION
During maintenance operations, take all safety precautions to protect personnel working on the equipment;
particularly read IB-SAFE and IB-SF6.
IMPORTANT
Any time that one of the phases is opened (e.g. when mounting bushings on the tanks, or when performing
maintenance that requires opening the vessel) the desiccant must be replaced. This must always be the last
procedure before closing up the chamber and pulling a vacuum, refilling with gas and then putting the
circuit breaker into service.
IB-DT09-F1-MAINT
Page 6 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004281
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
IMPORTANT
Shorten the inspection and maintenance intervals in the case of service under extreme conditions, i.e.,
continuously high ambient temperatures,
presence of abrasive dust or grit,
heavy dust accumulation,
continuously high humidity,
salty climate
presence of aggressive gases or vapors,
DANGER
For MA1:
It is not necessary to de-energize the circuit breaker as long as the walk-by is visual only. If any
maintenance action is to be taken other than visual (for example fixing paint or toping of with gas) GE Grid
Solutions recommends de-energizing the circuit breaker and does not take any responsibility in the case of
damage or injury.
IB-DT09-F1-MAINT
Page 7 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004282
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
DANGER
For MA2 through MA5:
Follow all regional and operator-specified safety precautions. In addition, observe the following instructions:
Isolate the breaker (De-energize the circuit breaker)
Ground the breaker.
Disconnect the supply and motor voltages.
CAUTION
Porcelain insulators under pressures greater than 3-5 psi pose a significant pressure/explosion hazard.
Failure to reduce the pressure to safe levels when commencing work on pressurized insulators could result
in significant injury or damage to adjacent property.
IMPORTANT
For MA3 through MA5:Upon completion of the maintenance program, re-commission the breaker
according to IB-DT09-F1-COM.
DANGER
GE Grid Solutions recommends discharging the closing and tripping springs when carrying out
maintenance work on the circuit breaker for reasons of personal safety. Verify the following conditions:
Circuit breaker in closed position
Closing spring charged
Then proceed as follows:
FINISH
1. Interrupt the motor supply voltage; START & SAFE
2. Carry out one opening operation;
3. Carry out one closing operation;
4. Carry out one opening operation.
The closing and tripping springs are then discharged such that no further operations are possible.
For more information, refer to IB-DISP-MECH-STD 4.1 Figure 1.
IB-DT09-F1-MAINT
Page 8 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004283
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
Arm2 s t arc
IB-DT09-F1-MAINT
Page 9 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004284
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
10000
2000
1000
No. of Operations
100
15
10
1
1 10 40 100
Current (kA)
Figure 1: Permissible Number of C-O Operations
Versus Breaking Current in kA without Maintenance of the Arcing Contacts
IB-DT09-F1-MAINT
Page 10 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004285
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
3.3 Check the Density Monitor and Topping off with Gas if Necessary
Check the SF6 pressure on the density monitor (the SF6 density monitor must indicate in the green zone on
the WIKA® gauge, ideally on the black dot). For a more accurate reading of the gas density, measure the
pressure with a digital pressure gauge and compare with the SF6 density curve at the with respect to the
ambient temperature. Top off with gas if necessary according to the procedure in IB-FILL-SF6.
CAUTION
Never top off with gas while the circuit breaker is energized.
CAUTION
Do not check the density set points unless the circuit breaker is de-energized.
IB-DT09-F1-MAINT
Page 11 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004286
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
Check the function of the anti-condensation heaters: turn the heaters on and allow time for them to
heat up. Verify the heaters have gotten warm and then shut them off. Make sure that there are no
overheating marks.
o For thermally controlled heaters (if applicable), verify that the heaters turn on and off at the
preset temperatures. If necessary, change any heaters found to be defective.
CAUTION
For porcelain bushings, be extremely careful to no damage the porcelain with tools or abrupt movement
when checking for hardware tightness.
Terminal Pad Hardware
Mechanism to Structure Hardware
IMPORTANT
Under no circumstances should any hardware be checked inside the operating mechanism, even if it is
discharged. It is maintenance free until the mechanical operation limit has been reached in which case the
entire mechanism should be replaced.
3.6 Check SF6 Density Monitor Set Points and Gas Quality
De-energize the breaker.
Check the SF6 density monitor set points by following the procedure in the commissioning
instructions. If you find the values are outside required tolerances replace the density monitor as an
entire unit.
CAUTION
The breaker will operate when testing for lockout pressure.
Check the moisture content of the breaker; it should not exceed 500 ppmv. Typical values are less
than 100 ppmv.
Check the acidity content of the SF6 gas and compare against acceptance criteria in IB-SF6.
IB-DT09-F1-MAINT
Page 12 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004287
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
NOTE
If the moisture or acidity content exceeds the maximum rating then:
Reclaim the gas.
Replace the desiccant bags.
o For high acidity content, clean the inside of the tank for particles and SF6 by-products.
Pull Vacuum.
Refill with SF6 gas that meets GE Grid Solution’s purity criteria according to IB-ST6.
IB-DT09-F1-MAINT
Page 13 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004288
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
CAUTION
Never operate the breaker with a gas density at or below the lockout value.
Ensure the values correspond to those given in the routine test reports within the tolerances specified in the
specifications document. If the values measured are outside the specified values, contact GE Grid Solutions
Customer Service.
NOTE
The opening time is the time from energizing the trip coil to separation of the main contacts.
The closing time is the time from energizing the close coil to contact touch.
NOTE
This procedure must be performed by an GE Grid Solutions service technician.
NOTE
The bushings and interrupter must be removed to allow room for cleaning inside the tank.
NOTE
For each flange connection that is opened:
Clean and lubricate each flange surface before sealing back up.
Replace, clean and lubricate the new seal.
1. Clean the inside of the tank with a designated vacuum cleaner filtered with an inline filter for inspection
of collected material. Coffee filter placed at hose connection on vacuum provides adequate filtration.
IB-DT09-F1-MAINT
Page 14 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004289
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
IB-DT09-F1-MAINT
Page 15 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004290
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
IMPORTANT
After cleaning, do not touch the solid insulation with fingers or a flashover may result.
5. Reinstall the bushings according to the procedures given in the assembly chapter.
IMPORTANT
As a general rule when performing seal replacement and grease/lubricant reapplication:
NEVER use Molykote lubricants on any internal areas in contact with SF6.
Coat all flanges with Dow 111 silicone grease to prevent moisture penetration and to lubricate the
seals and seal grooves. Apply lubricants or grease by hand. Refer to the IB-FLANGE document for
information regarding the proper technique for greasing flange surfaces and seals.
Do not use brushes or any device for applying lubricants because they may introduce particles
during lubrication. Thoroughly clean the areas and reapply the proper lubricants or grease
(instructions for cleaning and greasing can be found in the IB-FLANGE document). Take care
lubricating gaskets, seals, etc.; verify that there is no damage and that no particles are present that
would prevent a gas tight seal.
Clean all functional elements with a lint free wipe that has been soaked in denatured alcohol.
IB-DT09-F1-MAINT
Page 16 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004291
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
No. Seals
S1 □ Bushing top flange seal
S2 □ Bushing bottom flange seal
S3 □ Tank nozzle seal (if adapter plate is used)
S4 □ End-cover seal
S5 □ N/A
S6 □ PRD End Cover seal
S7 □ PRD seal
S8 □ Desiccant Cover Seal
IB-DT09-F1-MAINT
Page 17 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004292
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
L1 L5
L1
L5 L1
L2
L5 L1 L5 L1
IB-DT09-F1-MAINT
Page 18 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004293
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
L2
L2
Upper Bearing
L8
Lower Bearing
IB-DT09-F1-MAINT
Page 19 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004294
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
L4
L4
L7
L4
L4
Loctite 271 on L7
threaded locknut
IB-DT09-F1-MAINT
Page 20 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004295
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
L5
L3
NOTE
This step requires purchasing:
New Desiccant
PRD Tank Cover Gasket
NOTE
The molecular sieve used in this circuit breaker is synthetic Zeolite type A which is highly porous and
belongs to the class of aluminosilicates. These crystals are characterised by a three-dimensional pore
system, with pores of precisely defined diameter. The corresponding crystallographic structure is formed by
tetrahedras of AlO4 and SiO4.
IB-DT09-F1-MAINT
Page 21 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004296
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
1. Clean the flange surface and O-ring with denatured alcohol and lint-free wipes, and then clean the
desiccant retainer screen.
IMPORTANT
The molecular sieve absorbs moisture and decomposition products of SF6 gas and will begin absorbing as
soon as the airtight aluminum package is opened. Install the absorption filter, seal the breaker and the
vacuum process within 5 minutes of opening the package to avoid premature moisture saturation.
2. Apply a thin layer of Loctite® 242 to the threads of the desiccant screen-retaining bolt, and then
install the desiccant screen.
3. Apply a thin layer of Dow 111 grease to the flange surface and O-ring.
4. Insert the O-ring into the flange groove.
5. Apply a thin layer of never-seize on the bolts used to fasten the PRD cover casting to the tank.
6. Ensure that the desiccant package is intact then open it and insert the bag behind the screen as
shown below.
Loctite® 242 on
retaining bolt
5 MIN Left!
IB-DT09-F1-MAINT
Page 22 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004297
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
NOTE
The PRD of the DT1-38/72.5 F1 is designed to relieve the breaker pressure at 185 psig (12.7 bar rel.).
IMPORTANT
Any time that one of the phases is opened (e.g. when mounting bushings on the tanks, or when performing
maintenance that requires opening the vessel) the desiccant must be replaced. This must always be the last
procedure before closing up the chamber and pulling a vacuum, refilling with gas and then putting the
circuit breaker into service.
The breaker requires 0.44 lbs. (0.2 kg) of desiccant per pole. The filters (also called a “molecular sieve”) are
vacuum packed in aluminum packages. Before using it, verify that the aluminum packages were not
damaged. Do not use the filter materials if the packages are damaged.
IB-DT09-F1-MAINT
Page 23 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004298
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
1. Clean the PRD end cover with denatured alcohol and low lint wipes.
2. Apply a light film of Dow Corning 111 grease to the flange of the PRD tank cover.
IMPORTANT
Do NOT touch the PRD burst disk on or near the convex portion. Do not allow the convex portion (bulge) to
touch the bell-crank during assembly or to be touched by the installer. The convex side (bulge) points
towards the pressure. This region is extremely sensitive and it will not operate properly in service if touched.
The only portion of the burst disk which may be handled is the tag.
Handle Here
Do Not Touch!
4. Install the burst disc cover onto the assembly with the opening located in the upward position. Align
the mounting holes for the shield with the boss.
5. Apply a thin layer of anti seize on the hardware and secure the cover in place.
6. Torque the hardware in a star pattern to GE Grid Solutions spec TS-00007.
IB-DT09-F1-MAINT
Page 24 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004299
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
Loctite® 242
Cabinet Seal
NOTE
This procedure must be performed by an GE Grid Solutions service technician.
IB-DT09-F1-MAINT
Page 25 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004300
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
3.16 Replacing the Interrupter after the Electrical Wear Limit has been Reached
NOTE
This procedure must be performed by an GE Grid Solutions service technician.
IB-DT09-F1-MAINT
Page 26 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004301
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
CAUTION
Ensure that the breaker mechanism is completely discharged and all supply voltage has been removed
before performing this work.
NOTE
The mechanism supplied may vary in layout from Figure 16: Front View of Mechanism
IB-DT09-F1-MAINT
Page 27 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004302
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
3. To identify / locate the trip coil(s), look into the rear of the mechanism from the right side as shown in
the figure below:
IB-DT09-F1-MAINT
Page 28 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004303
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
4. Each coil has one (1) retainer clip. Remove the coil’s retainer clip by pressing in at the bottom and
sliding the clip upward. The retainer is made out of spring steel and will not function properly if it is
bent; use care when handling.
Press here
Magnet
Segment
IB-DT09-F1-MAINT
Page 29 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004304
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
Coil
IB-DT09-F1-MAINT
Page 30 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004305
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
CAUTION
Ensure that the breaker mechanism is completely discharged and all supply voltage has been removed
before performing this work.
It may be necessary to replace the motor as part of maintenance. Follow the instructions below:
1. Remove the breaker from service.
2. Open the mechanism cabinet door and remove the left side panel. The motor is located on the left
side of the mechanism (Figure 23). The motor is secured in place by 2 bolts on the backside of the
mechanism structure panel. The standard motor may be removed without removing the mechanism
panel. If the motor is unable to be removed due to interference with the mechanism panel, contact
GE Grid Solutions Service (contact information is listed in the IB-DT09-F1-SPR-PRTS document) for
assistance with removing the mechanism panel.
Mechanism
Structure Panel Mechanism
Panel
Motor
IB-DT09-F1-MAINT
Page 31 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004306
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
4. Remove the bolts that secure the motor in place while holding the motor to ensure that it does not
fall after the bolts are removed.
NOTE
Contact GE Grid Solutions Customer Service for suitable replacement parts:
Current Transformer(s)
Current Transformer Shim Materials
Nozzle Flange Seal
Bushing Flange Seal
Desiccant
1. Remove the circuit breaker from service and evacuate SF6 according to IB-FILL-SF6.
2. Disconnect the CT wiring from the terminal blocks for all the current transformers on the bushing.
3. Remove the wiring from the conduit. Some disassembly of the conduit may be necessary.
4. Remove the CT cover.
5. Remove the bushing or the center conductor. In both cases, be sure to remove the center conductor
clamp bolt from the interrupter (both sides) or else damage to the interrupter and center conductor
will occur.
IB-DT09-F1-MAINT
Page 32 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004307
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
Clamping bolt
Clamping
mechanism
IMPORTANT
Cover all vessel and bushing insulator openings after disassembly to assure no materials, debris, or
contaminants are introduced. Take extreme care to avoid dropping bolts, washers, and tools into the
interrupter enclosure.
IB-DT09-F1-MAINT
Page 33 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004308
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
6. Lift the current transformer from the tank nozzle of the breaker.
3
2
9
4
8 10
IB-DT09-F1-MAINT
Page 34 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004309
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
7. Once the old CT’s are removed, apply RTV silicone to the “L” shaped shims. Install rubber shims
between the CT and the tank casting rib to fill in any gap and prevent the CT’s from moving around.
When there are multiple stacked CT’s, install rubber shims between each CT. Secure the support
block into position by applying RTV Silicone between the support block and the CT. Make sure not to
damage the CT.
Shims
L-Shaped Shims
Black marking
is on top
IB-DT09-F1-MAINT
Page 35 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004310
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
10. Pull the CT wiring through the conduit (make sure the plastic bushing material is in place to protect
the wire insulation) and reconnect at the CT terminal blocks according to the CT wiring diagram on
the nameplate or according to new customer’s requirements.
Terminal Block
CT Wiring Grounding Bar
Plastic
bushing
material
Conduit
DANGER
Under no circumstance, perform any test that circulates primary current (current through the circuit
breaker) while the secondary (current through the current transformer) is open. Circulating primary current
while the secondary is open will produce dangerously high voltages in the CT. To close the CT current path
and allow for safe testing make sure that the CT terminals are grounded with the terminal grounding bar
and that it must be screwed on over the CT terminal wires as shown in Figure 30. In normal service, the
grounding bar can be removed if it is replaced by a burden for monitoring purposes, assembled by the
customer.
DANGER
Take care to prevent unintentional core magnetism during field-testing. Do not use any source of DC
current on a current transformer since certain types of DC instruments will severely magnetize the core and
drastically increase its exciting current characteristics. When using a variable voltage source always run the
voltage down to zero volts before turning it off, failure to do so will result in core magnetism.
IB-DT09-F1-MAINT
Page 36 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004311
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
CAUTION
Ensure that the breaker mechanism is completely discharged, all supply voltage has been removed, and the
heater(s) and cover(s) have cooled, before performing this work.
Anti-condensation
Heater Wires
IB-DT09-F1-MAINT
Page 37 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004312
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
4. Remove the bolts that secure the cover in place and then remove the cover.
Securing Bolts
Clamp
Hardware
Anti-Condensation
Heaters
IB-DT09-F1-MAINT
Page 38 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004313
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
NOTE
Tank heaters are required only when the circuit breaker is rated for below -40°C temperature.
Refer to contact drawing schematics for respective wattages.
The heater circuit is designed to turn on the tank heaters depending on the ambient temperature. The
thermostat measuring the ambient temperature is adjustable, but has been set for proper operation by the
factory. Do not adjust!
Preliminary troubleshooting of this circuit may be performed by checking the circuit protection and the
circuit wiring.
WARNING
Refer to the IB-SAFE document for general safety precautions.
IB-DT09-F1-MAINT
Page 39 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004314
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
IB-DT09-F1-MAINT
Page 40 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004315
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Maintenance and Troubleshooting
l. Place the heater onto the tank. Ensure the leads of the heater are on the opposite side of the
mechanism cabinet.
m. Rub the heater surface by hand in order to remove any air pockets. Ensure the entire surface
of the heater is in contact with the tank.
Figure 38: Applying RTV Adhesive to Heater Pad Perimeter (Example Only)
IB-DT09-F1-MAINT
Page 41 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004316
Maintenance and Troubleshooting
For Type DT1-72.5 F1 Circuit Breakers
o. Use duct tape to hold the heater pad tightly against the tank while the adhesive sets. It is
acceptable, as necessary, to place duct tape onto other heaters that are already adhered to
the tank.
Figure 39: Supporting the Heater Pad with Duct Tape (Example Only)
p. Remove the duct tape after the adhesive has had time to set (approximately 24 hours).
q. Place the heater shield over the heaters such that the seam is at the bottom of the tank and
will line up with the conduit.
r. Route the new heater’s wires through the conduit attachment point on the heater shield,
through the conduit, and into the mechanism cabinet.
s. Assemble the heater shield hardware. Apply Loctite® 242 to the hardware prior to installation.
IMPORTANT
The cover fastener flanges should be parallel after assembly. Be sure that the cover is secure and that
there are no visible gaps.
IB-DT09-F1-MAINT
Page 42 of 42
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004317
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Recommended Spare Parts
IB-DT09-F1-SPR-PRTS
Page 1 of 4
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004318
Recommended Spare Parts
Fo r Type DT1-72.5 F1 Circuit Break ers
Revision History
Revision Record Description Revised by Date
IB-DT09-F1-SPR-PRTS
Page 2 of 4
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004319
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Recommended Spare Parts
IB-DT09-F1-SPR-PRTS
Page 3 of 4
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004320
Recommended Spare Parts
Fo r Type DT1-72.5 F1 Circuit Break ers
IB-DT09-F1-SPR-PRTS
Page 4 of 4
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004321
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Circuit Breaker Decommissioning and Disposal
List of Tables
Table 1: End-of-life Treatment for Metals .................................................................................... 5
Table 2: End-of-life Treatment for Organic Materials ................................................................. 6
Table 3: End-of-life Treatment for Ceramic-Based Materials .................................................... 6
Table 4: End-of-life Treatment for Oils and Greases ................................................................... 7
Table 5: End-of-life Treatment for Cements and Mastics ........................................................... 7
Table 6: PEP ..................................................................................................................................... 7
IB-DT09-F1-DISP
Page 1 of 8
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004322
Circuit Breaker Decommissioning and Disposal
Fo r Type DT1-72.5 F1 Circuit Break ers
Revision History
Revision Record Description Revised by Date
0 Original issued document WH 03/30/2011
1 Changed format from Alstom to GE L.W. 02/08/2016
IB-DT09-F1-DISP
Page 2 of 8
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004323
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Circuit Breaker Decommissioning and Disposal
Take every measure possible to not dissipate SF 6 in the air. Did you know that 1g of SF 6 has
the same global warming impact as 24000 g of CO 2, and it dwells in the atmosphere 2000
times longer!
IB-DT09-F1-DISP
Page 3 of 8
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004324
Circuit Breaker Decommissioning and Disposal
Fo r Type DT1-72.5 F1 Circuit Break ers
IB-DT09-F1-DISP
Page 4 of 8
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004325
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Circuit Breaker Decommissioning and Disposal
Aluminum alloy is the predominant material used in the circuit breaker. The a luminum
alloys used in our circuit breakers are readily separated and recycled to a very high degree
of purity.
Galvanized steel, used in the circuit breaker’s supportive structure is easy and cheap to
recycle. It does not pose a problem in terms of the quality of the recycled steel; however it
has to be dealt with as dust emission.
IB-DT09-F1-DISP
Page 5 of 8
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004326
Circuit Breaker Decommissioning and Disposal
Fo r Type DT1-72.5 F1 Circuit Break ers
Thermosetting resins
Epoxy Resin EP Insulating parts Thermal recovery
Glass-fiber Reinforced Epoxy EP - GF Insulating tubes "
Resin
Organic-fiber Reinforced EP - PET " "
Epoxy Resin EP - PA " "
Phenolic Resin PF Insulating parts "
Polyester Resin UP " "
Thermoplastics
Polyamide PA (-GF) Insulation material Plastic recycling
Polyethylene PE Packaging "
Polypropylene PP (-GF) "
Polyvinyldene Fluoride PVDF Polar parts "
Polyvinyl Chloride PVC Cable insulation "
Polycarbonate PC (-GF) Insulating material "
Polyethylene-terephtalate PET Ins. adsorb. bags "
Polybutylene-terephthalate PBT “
Polytetrafluoroethylene PTFE Insulating nozzle Discharge as dangerous wastes (2)
Elastomers
Propylene ethylene EPDM, EPR Seals Thermal recovery
Nitrile rubber NBR " "
Silicone VMQ, Q " "
Fluorinated rubber FEP " Discharge for dangerous wastes (2)
(1) As per standards ISO 1043-1 (2001) and 1043-2 (2000)
(2) Description as per the Official Gazette of the European Communities (93, 8 No. C212)
IB-DT09-F1-DISP
Page 6 of 8
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004327
General Electric Grid Solutions Circuit Breakers
Type DT1-72.5 F1 Circuit Breaker Decommissioning and Disposal
IB-DT09-F1-DISP
Page 7 of 8
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004328
Circuit Breaker Decommissioning and Disposal
Fo r Type DT1-72.5 F1 Circuit Break ers
IB-DT09-F1-DISP
Page 8 of 8
© General Electric 2016. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004329
Decommissioning and Disposal of FK3-X
General Electric Grid Solutions Circuit Breakers Mechanisms
List of Figures
Figure 1: Position Indicators .......................................................................................................... 5
Figure 2: Removing Side Panel ...................................................................................................... 6
Figure 3: Immobilizing the Mechanism ......................................................................................... 7
Figure 4: Dashpot Locking Ring ..................................................................................................... 8
IB-DISP-MECH-STD
Page 1 of 10
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004330
Decommissioning and Disposal of FK3-X Mechanisms
Revision History
Revision Record Description Revised by Date
0 Original issued document MM 03/07
1 Updated contact information WH 09/08
2 Changed from ALSTOM to GE Grid Solutions L.W. 12/02/2015
IB-DISP-MECH-STD
Page 2 of 10
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004331
Decommissioning and Disposal of FK3-X
General Electric Grid Solutions Circuit Breakers Mechanisms
1.0 Introduction
This document describes preparatory steps and presents materials lists for the disposal of individual parts at
the end of the life cycle of the motor-wound spring operating mechanism, models: FK3-06, FK3-1/131, FK3-1,
FK3-2, FK3-3, FK3-4, and FK3-5.
2.0 Safety
Refer to IB-SAFE and IB-SF6 for general safety procedures.
These spring operating mechanisms feature state-of-the-art design and high operational reliability. They can
nevertheless pose a hazard if used improperly.
The switchgear operator must therefore ensure that assigned personnel:
Are familiar with locally and nationally-applicable safety and accident prevention regulations,
particularly to high voltage switchgear and other high voltage equipment,
Are aware of and comply with the contents of these instructions,
Have received technical training on switchgears, including operating mechanisms.
Manipulations not in compliance with these instructions pose hazards for the personnel involved as well as
for the motor-wound spring operating mechanism.
Manipulations on the motor-wound spring operating mechanism that do not comply with the FK 3-X
instructions create a danger of death or injury to the person performing them. Damage to the motor -wound
spring operating mechanism may also result.
DANGER
Perform only manipulations that comply with the instructions for FK 3-X motor-wound spring operating
mechanisms.
If the gas pressure of the switchgear is lower than the minimum value for mechanical switching operation
(listed on the warning plate in the spring operating mechanism), an excessively high energy is released inside
the spring operating mechanism.
Damage to the switchgear and the spring operating mechanism may result.
CAUTION
Operate the spring operating mechanism only with a switchgear having a gas pressure higher than the
minimum value for mechanical switching operatio n.
2.1 Necessary Conditions for Removal of the Operating Mechanism from Switchgear
The switchgear is in the open position.
The switchgear is grounded on both sides.
The control voltage is disconnected.
IB-DISP-MECH-STD
Page 3 of 10
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004332
Decommissioning and Disposal of FK3-X Mechanisms
a) Mechanism in closed position with the closing b) Breaker opens upon activation of the trip release
spring charged (motor must be disconnected) latch. Closing spring remains charged.
c) Breaker closes and the closing spring discharges d) Breaker opens upon activation of the trip release
upon activation of the closing release latch. latch.
IMPORTANT
If this sequence is not observed or if the closing spring is recharged, the motor is not disconnected.
Disconnect the supply power to the motor and revisit these steps in full.
CAUTION
A pre-load remains on both springs as, even in the discharged state, they are not in their respective free
length conditions.
NOTE
The previous sequence depicted (Figure 1) details the extent of manual operations required to discharge the
trip and close springs. The number of required steps may vary depending on the initial state (status of the
closing spring and position of the breaker) of the respective equipment. However, the correct final state for
assurance of both springs being discahrged is displayed in Figure 1, View d.
IB-DISP-MECH-STD
Page 5 of 10
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004334
Decommissioning and Disposal of FK3-X Mechanisms
78.18
78.02
78.01 (2(2 sides)
sides)
(2 sides)
78.20 (2 sides)
IB-DISP-MECH-STD
Page 6 of 10
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004335
Decommissioning and Disposal of FK3-X
General Electric Grid Solutions Circuit Breakers Mechanisms
CAUTION
Use cloth slings when lifting the operating mechanism. Wire or chain may cause damage to the cabinet.
Immobilization with
slings:
Hmin = 1.64 ft. (0.5m)
Ø = 0.787 in. (20 mm)
IB-DISP-MECH-STD
Page 7 of 10
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004336
Decommissioning and Disposal of FK3-X Mechanisms
DANGER
Improperly attempting to remove a spring pre-load could result in severe injury or death.
DO NOT attempt to remove the pre-load for the springs. A GE Grid Solutions Service technician must be
present to perform this procedure. Contact GE Grid Solutions Service at:
IB-DISP-MECH-STD
Page 8 of 10
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004337
Decommissioning and Disposal of FK3-X
General Electric Grid Solutions Circuit Breakers Mechanisms
IB-DISP-MECH-STD
Page 9 of 10
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004338
Decommissioning and Disposal of FK3-X Mechanisms
Various
thermoplastics 1.4 kg Various small parts Incineration
IB-DISP-MECH-STD
Page 10 of 10
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004339
General Electric Grid Solutions Circuit Breakers Failure Reporting
Failure Reporting
Contents
1.0 Utilization of Failure Reports .............................................................................................. 3
1.1 Failure Reporting Form ....................................................................................................... 3
IB-FAIL
Page 1 of 4
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004340
Failure Reporting
Revision History
Revision Record Description Revised by Date
0 Original issued document MM 03/07
1 Changed from AREVA to ALSTOM WH 07/20/2010
2 Updated IEEE standard from IEEE 1325 to IEEE C37.10 AB 08/08/2012
3 Changed from ALSTOM to GE Grid Solutions L.W. 11/10/2015
IB-FAIL
Page 2 of 4
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004341
General Electric Grid Solutions Circuit Breakers Failure Reporting
IB-FAIL
Page 3 of 4
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004342
Failure Reporting
IB-FAIL
Page 4 of 4
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004343
General Electric Grid Solutions Circuit Breakers Failure Reporting Form
IB-FAIL-FRM
Page 1 of 4
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004344
Failure Reporting Form
Revision History
Revision Record Description Revised by Date
IB-FAIL-FRM
Page 2 of 4
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004345
General Electric Grid Solutions Circuit Breakers Failure Reporting Form
FAILURE REPORTING FORM FOR GENERAL ELECTRIC GRID SOLUTIONS CIRCUIT BREAKERS
Check all appropriate blocks and provide information indicated. For major trouble, provide additional information requested on the back of this
page, supplementing with additional pages if necessary.
EQUIPMENT:
Station User Ident. Of Breaker
Equipment Mfgr. GENERAL ELECTRIC Type Serial #
Nameplate
kV Short-circuit Current Continuous Current BIL
Brkr Background Shipped Installed Maintained Modernized Trouble Date
(Mo/Yr) (Mo/Yr) (Mo/Yr) (Mo/Yr) (Mo/Day/Yr)
Operational Counter Reading
Location: Indoor Outdoor Enclosure: Non-metal Clad Metal Clad GIS
Interrupter: Air Blast Air Magnetic Oil SF Vacuum Other _____________________________________
ENVIRONMENT:
General: Industrial Urban Suburban Rural Sea Coast Above 3000 ft High Contamination
Other
Weather Conditions: Dry Rain Lightning in the Area Snow Fog Freezing Rain Frost Condensation
Temp. Trend – Rising Falling Steady Extreme Cold Temperature °C
Wind – Calm Light Strong-Steady Strong-Gusty
External Mechanical Stress Involved: Normal Earthquake Wind Abnormal terminal loading
Other _________________________________ Nominal System Voltage _____________________________________
TROUBLE:
When discovered: Installation In Service Maintenance Test Other
Breaker mode at time of trouble: De-energized Closed Open Tripping Closing Reclosing
Fault Interruption Load Switching Line Switching
Breaker response at time of trouble: Not called upon to operate Performed as intended
Unsatisfactory operation Failed to operate
Subsystem in trouble: External insulation to ground Internal insulation to ground Insulating medium
Isolating Contact Bushing Interrupter Seal-Gaskets Air System SF6 system C.T.
Resistor sw or aux. int. Voltage grading dev. Line terminals Compressor Heater Electrical Controls
Wiring Operating mechanism Mechanical linkage Other
State specifically what failed (with instr. Book ref.):
Has it occurred before on this breaker? No Yes How many times
State how problem was corrected:
_______________________________________________________________________________________________________________
POSSIBLE CAUSE: Design/Manufacture Shipping Storage Installation Maintenance
Wear/Aging Animal/Birds Other Not Obvious
Comments and Suggestions:
_______________________________________________________________________________________________________________
EFFECT:
Breaker Down Time: No interruption 30 min or less 1 hr 2 hr 6 hr 12 hr 24 hr Other
Repair Time: Less then 30 min
1 hr 2 hr 6 hr 1 day 2 days 3 days 1 week Other
Breaker Outage Status: Immediate forced outage Outage within 20 min Required subsequent outage
Repair deferred until regular maintenance No outage for repair
User person completing report Date
User approval name Date
User contact name Telephone Number
User company ___________________________________________________________
(This form may be copied)
IB-FAIL-FRM
Page 3 of 4
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and
is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for
any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.
004346
Failure Reporting Form
(2) Operation and timing sequence (including all alarms) of this and related breakers from the last
time that conditions were definitely normal.
IB-FAIL-FRM
Page 4 of 4
© General Electric 2015. All rights reserved. Information contained in this document is provided without liability for information purposes only and is
subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any
particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.