You are on page 1of 6

Essential Power Control

EPack Lite-1PH Compact SCR Power Controllers


TM

Simplicity Without Compromise On Performance

Product at a Glance Key Features:


The end user, the machine builder or the system integrator expects
• Nominal load current from 4 to 125 amps
the best solutions in term of performance, ease of use and
reliability in order to control the energy delivered to their process. • Voltage up to 500V
Whether replacing an existing product or building a new process, • Compact DIN Rail and bulkhead mounting
the EPack Lite power controller has been carefully designed to
TM

• Configurable via front panel


aid easy and fast integration in industrial systems.
• Fast start up with ‘Quick Start’ or ‘Clone
The EPack Lite range offers a simplified choice, fast commissioning
without any compromise on performance in order to provide a Code’ features
high level of quality, accuracy and reliability to the process. • V or I control or Open loop
2 2

More than just a product, EPack Lite power controllers bring • Controls non variable resistive and primary
a tailored solution based on more than 50 years of Eurotherm
transformer loads
expertise.
• Wide range of firing modes: Logic, Phase
> See EPack™ compact SCR power controllers brochure HA031554 Angle, Adjustable Burst Firing, Fast Cycle
to discover how full EPack range can add value to your business
• Measurements: Current, voltage or

The EPack Lite-1PH controller provides control of single phase impedance and more
non variable resistive or primary transformer loads. It combines • Load fault detection up to 1 element of 6
simplicity of setup and operation in a compact format. • SCCR 100kA
The combination of advanced configurable firing modes allows
close matching to load characteristics to optimise process
efficiency.
EPack Lite-1PH Data Sheet eurotherm.co.uk/epack 2

Specifications
General Fuses
Directive EMC directive 2014/30/EU Current Rating Fuse Holder Size Dimensions H x W x D
Low Voltage Directive 2014/35/EU ≤25A without MS 10x38mm / 13/32x1-1/2in 88.5x17.5x64.5mm / 3.48x0.69x2.54in
≤25A with MS 14x51mm / 9/16x2in 110.8x26.5x76.5mm / 4.36x1.04x3.01in
Safety Specification EN60947-4-3:2014
32A with or without MS 14x51mm / 9/16x2in 110.8x26.5x76.5mm / 4.36x1.04x3.01in
EMC Emissions Specification EN60947-4-3:2014 - Class A product
40A with or without MS 14x51mm / 9/16x2in 110.8x26.5x76.5mm / 4.36x1.04x3.01in
EMC Immunity Specification EN60947-4-3:2014
50A with or without MS 22x58mm / 2-9/32in 127.5x35x76.5mm / 5.02x1.38x3.01in
Vibration Tests EN60947-1 annex Q category E
63A with or without MS 27x60mm / 1-1/16x2-3/8in 149.4x40x93.5mm / 5.88x1.57x3.68in
Shock Tests EN60947-1 annex Q category E
80A with or without MS 27x60mm / 1-1/16x2-3/8in 149.4x40x93.5mm / 5.88x1.57x3.68in
Approvals
100A with or without MS 27x60mm / 1-1/16x2-3/8in 149.4x40x93.5mm / 5.88x1.57x3.68in
European Community EN60947-4-3:2014: Low-voltage switchgear 125A with or without MS 27x60mm / 1-1/16x2-3/8in 149.4x40x93.5mm / 5.88x1.57x3.68in
and controlgear - Part 4-3:Contactors and
motor-starters - AC semiconductor controllers
and contactors for non-motor loads (identical
Power
to IEC60947-4-3:2014) Nominal Current 4 to 125 amps
Declaration of conformity available on request. Nominal Voltage 100 to 500Vac +10%/–15%
US & Canada UL60947-4-1 CAN/CSA C22.2 NO.60947-4-1-14 Accuracy ±2% of full scale - from 100 to 500V +10%/–15%
Low-Voltage Switchgear and Controlgear Frequency 47Hz to 63Hz
- Part 4-1: Contactors and Motor-Starters - Short Circuit Protection By external supplemental high speed fuses
Electromechanical Contactors and Motor- Rated Conditional Short-circuit
Starters - U.L. File N° E86160 100kA (Coordination Type 1)
Current
Australia Regulatory Compliance Mark (RCM) Type Of Loads
to Australian Communication and Media Authority
AC51 Resistive or slightly inductive load (cos phi>0.8)
Based on compliance to EN60947-4-3:2014
AC-56a Transformer Primary
China Product not listed in catalogue of products
subject to China Compulsory Certification (CCC)
Control
Protection CE: 16 to 63A > IP10 according to EN60529
Auxillary Power Supply 100V to 500V +10%/–15% or 24 ac/dc (±20%)
80 to 125A > IP20 according to EN60529
UL: open type Control Setpoint Analog or Logic input
Analogue Input Signal
Voltage Range: 0-5V, 1-5 V, 0-10V or 2-10V
Condition Of Use
Impedance: 140 k Ohms typical (0-10V signal)
Atmosphere Non-corrosive, non-explosive, non-conductive
Current Range: 0-20mA or 4-20mA
Degree Of Pollution Degree 2
Input resistance: 100 ohms to allow three
Storage Temperature –25°C to 70°C (maximum)
units wired in series to be driven from a single
Usage Temperature 0 to 45°C at 1000m controller’s analogue output
0 to 40°C at 2000m
Resolution 11 bits
Altitude 1000m maximum at 45°C
Linearity ±0.1% of Scale
2000m maximum at 40°C
Phase Angle, Intelligent Half cycle, Variable
Derating Curves Firing Mode
Altitude (meters) Modulation Burst firing (FC1, C16, C64), Fix
modulation period (2 seconds fixed), Logic
mode
2000
Control Mode V control, I control, Open loop
2 2

Configurable Digital Inputs Input 1: enable by default


1750
Input 2: setpoint, alarm acknowledgment, 10V
supply, ...
1500
Voltage Inputs Active level (high): 11V<Vin<30V with
6mA<lin<30mA
1250
Non-active level (low): -3V<Vin<5V with
2mA<Iin<30mA or 5V<Vin<11V with Iin<2mA
1000
PLC compatible inputs, types 1 & 2 according
to IEC 61131-2
40 41 42 43 44 45 Contact Closure Inputs Source current: 10mA min; 15mA max
Operating temperature (°C)
Open contact (non active) resistance:
800 Ohms to ∞
Closed contact (active) resistance: 0 to 450 Ohms
Mechanical details
Absolute Maximum ±30V or ±25mA
Unit Height Width Depth Weight
One Alarm Relay Changeover relay 2A rms - 264V rms normally
16 to 32A 129.2mm / 5.09in 51mm / 2.01in 136.2mm / 9.04in 0.8kg / 1.76lb
energised. (250V rms max for UL)
40 to 63A 129.2mm / 5.09in 72mm / 2.83in 173.3mm / 9.04in 0.95kg / 2.09lb
This relay will be de-energised by default in
80 to 100A 197.6mm / 7.78in 80mm / 3.15in 202.1mm / 9.04in 1.8kg / 3.97lb
case of serious alarms: short circuit thyristor,
125A 197.6mm / 7.78in 120mm / 4.72in 202.1mm / 9.04in 2.5kg / 5.51lb open circuit, fuse blown, missing main, chop off

Display
Technology TFT
Size 1.5”
Messages Messages for configuration, monitoring and
diagnostics
EPack Lite-1PH Data Sheet eurotherm.co.uk/epack 3

Mechanical Details Connector Details (pinout)


16A to 32A I/O Details
Input Connectors
View on upper face Digital Inputs
1
EPack (auxiliary) supply power Contact inputs
(low voltage option shown)

51mm 800Ω to ∞ = Open


(2.01in) 0Ω to 450Ω = Closed
451Ω to 799Ω= Undefined
46.7mm
Phase reference Load power 11V<Vin<30V = High with 6mA<lin<30mA 1
(1.84in)
(neutral) input -3V<Vin<5V = Low with 2mA<Iin<30mA
or 5V<Vin<11V with Iin<2mA

View on right-hand face Voltage level inputs

Analogue Input
1
129.2mm (5.09in)

V/mA input
121mm (4.76in)
163.5mm (6.44in)

174mm (6.85in)
0 to 10V 0 to 20mA

117mm (4.61in)

147mm (5.79in)
1 to 5V 4 to 20mA
2 to 10V
0 to 5V

32A unit shown;


Other units have
same connections

Protective earth
ground (M5) Relay Output
136.2mm (5.36in)
Front view nc
View on lower face Com
no
I/O connector
Switching characteristics
(resistive loads)
Vmax: 264V RMS
Vmin: 5V
Weight: 0.8kg / 1.76lb Relay output Load power output Imax: 2A RMS
View on lower face Imin: 10 mA

40A to 63A Power Supply Details


16A to 63A
View on upper face
View on upper face
EPack (auxiliary) supply power
AC/DC

(low voltage option shown)


24V

Auxiliary voltage
72mm alternatives
(2.83in) (as specified at
time-of-order)
46.7mm
(1.84in) Phase reference Load power
(neutral)
Neutral
input
reference
View on right-hand face

From Supply
163.5mm (6.44in)

power for load


129.2mm (5.09in)

121mm (4.76in)

174mm (6.85in)
117mm (4.61in)

Lift-up flap
147mm (5.79in)

Center pin
not connected
32A unit shown;
Other units have
same connections
Access to supply
termination
screw head

Protective earth
ground (M5) Access to load
termination
Front view 173.3mm (6.81in) screw head

View on lower face Pull-down flap


1 2 3 4 5 Protective earth
I/O connector ground (M6 nut)
04 01 02
To load

Insulated handle 60mm / 2.36in min Flat blade


Weight: 0.95kg / 2.09lb Relay output Load power output recommended:
1 x 5.5mm
Screwdriver/Torque wrench screwdriver (0.039 x 0.21in)
bit details for line and load termination or 1.2 x 6.5mm
(0.047 x 0.25in)
EPack Lite-1PH Data Sheet eurotherm.co.uk/epack 4

Mechanical Details Connector Details (pinout)


80A to 100A I/O Details
Input Connectors
Digital Inputs
View on upper face 1
Contact inputs
Load power input

90.5mm
(3.56 in)
EPack (auxiliary) supply power
(low voltage option shown) 800Ω to ∞ = Open
0Ω to 450Ω = Closed

(3.15 in)
451Ω to 799Ω= Undefined

80mm
AC/DC
24V
Phase reference (neutral)

N/L2
11V<Vin<30V = High with 6mA<lin<30mA 1
-3V<Vin<5V = Low with 2mA<Iin<30mA
Front view or 5V<Vin<11V with Iin<2mA
202.1 mm (7.96 in)
46.7mm (1.84 in) Voltage level inputs
Wire guide (2 places) View on right hand side
Access to supply Analogue Input
termination 1
1/L1
screw head V/mA input
321.23mm (12.65 in)

218.25mm (8.59 in)

Door catch 0 to 10V 0 to 20mA


197.6mm (7.78 in)

175.46mm (6.91 in)


231.00mm (9.09 in)
182mm (7.17 in)

1 to 5V 4 to 20mA
2 to 10V
0 to 5V

32A unit shown;


Door catch Other units have
2/T1 same connections
Access to load
termination Protective
screw head earth ground
(M6 nut) Relay Output

nc
130.50mm Load power output
(5.14 in) Com
I/O connector no
(3.15 in)

1 2 3 4 5
80mm

Relay output 04 01 02

Switching characteristics
(resistive loads)
Vmax: 264V RMS
Vmin: 5V
Imax: 2A RMS
Weight: 1.8kg / 3.97lb View on lower face View on lower face Imin: 10 mA

125A Power Supply Connection Details


View on upper face
80A to 125A
Load power input View on upper face
90.5mm
(3.56 in)

EPack (auxiliary) supply power From supply


(low voltage option shown) Supply voltage power
alternatives for load
(4.72 in)
120mm
AC/DC
24V

Phase reference (neutral) (as specified at


time of order)
N/L2

24V
Front view AC/DC
46.7mm (1.84 in) 202.1 mm (7.96 in)

Wire guide (2 places) View on right hand side


24V
AC/DC Neutral
Access to supply
N/L2
reference
termination (either pin
1/L1
screw head Center
pin not
321.23mm (12.65 in)

218.25mm (8.59 in)

Door catch Access to supply


connected
197.6mm (7.78 in)

175.46mm (6.91 in)


231.00mm (9.09 in)
182mm (7.17 in)

termination
screw head
1/L1

Open the door


by pressing on
100A unit shown; the catches
Door catch 125A unit have
2/T1
same connections (two places)
Access to load
termination Protective
screw head earth ground
(M6 nut)
Protective
2/T1
earth ground
150.33mm Load power output (M6 nut) Access to load
(5.92 in) termination
I/O connector screw head
(3.15 in)

1 2 3 4 5
80mm

Relay output 04 01 02
To load

Insulated handle 60mm / 2.36in min Flat blade


recommended:
1 x 5.5mm
Weight: 2.5kg / 5.51lb View on lower face Screwdriver/Torque wrench screwdriver (0.039 x 0.21in)
bit details for line and load termination or 1.2 x 6.5mm
(0.047 x 0.25in)
EPack Lite-1PH Data Sheet eurotherm.co.uk/epack 5

Order Codes
The EPack Lite power controller is ordered using a short code for the chargeable options and an extended option
configuration code for commissioning.

If the extended code is not used, the software configuration is completed using a quick start procedure.

Current rating of EPack Lite controllers may be upgraded at any time using a software key order code.

Product Coding
1 2 3 4 5 6 7 8

EPACK-LITE-1PH XXX

9 10 11 12 13 14 15 16 17 18 19

XXX

Model 5 Warranty
Optional Configuration
Power XXX Standard Warranty
EPACK LITE-1PH
Controller WL005 5 Year Warranty
USWL3 US Extended Warranty 9 Nominal Load Current 14 Burst Min ON Time
1 Maximum Current nnnA 1 - Value field 1 None
XXX
6 Custom Labelling Single cycle 1 period
16A 16 amps FC1
min ON time
25A 25 amps XXX Standard (Eurotherm) 10 Nominal Line Voltage C16
Burst with 16 periods
32A 32 amps FXXXX Special Label 100V 100 volts min ON time
40A 40 amps C64
110V 110 volts Burst with 64 periods
50A 50 amps 115V 115 volts min ON time
7 Fuse
63A 63 amps 120V 120 volts
80A 80 amps XXX Without 127V 127 volts
100A 100 amps HSP High Speed fuse 200V 200 volts 15 Analog Input Function
125A 125 amps without microswitch 208V 208 volts XX None
HSM High Speed fuse 220V 220 volts SP Setpoint
with microswitch 230V 230 volts
2 Auxillary Power Supply
240V 240 volts
500V 500V max 277V 277 volts 16 Analog Input Type
8 Configuration
24V 24V ac/dc 380V 380 volts 0V 0-10 volts
XXXXX Default 400V 400 volts 1V 1-5 volts
LC Long code 415V 415 volts
3 Reserved 2V 2-10 volts
440V 440 volts 5V 0-5 volts
XXX Reserved 460V 460 volts 0A 0-20 mA
480V 480 volts 4A 4-20mA
500V 500 volts
4 Control Option
V2 2
V control (standard) 17 Digital Input 1 Function
I2 2
I control
11 Load type
XX None
OL Open loop control XX Resistive FI Firing
TR Transformer primary LG Setpoint for logic mode
AK Alarm
12 Heater Type acknowledgement
FB Fuse Blown
XX Resistive

18 Digital Input 2 Function


13 Firing Mode
XX None
PA Phase Angle FI Firing
IHC Intelligent Half Cycle LG Setpoint for logic mode
BF Variable Modulation AK Alarm
Burst Firing acknowledgement
FX Fix modulation period FB Fuse Blown
(default 2 seconds) SU 10V supply
LGC Logic mode

19 Reserved
XXX Reserved
EPack Lite-1PH Data Sheet eurotherm.co.uk/epack 6

Software Upgrade Options


1 2

1 Serial Number Instrument


nnnn Serial number

2 Current Ratings Upgrade


XXX No change
16A-25A 16A to 25A
16A-32A 16A to 32A
25A-32A 25A to 32A
40A-50A 40A to 50A
40A-63A 40A to 63A
50A-63A 50A to 63A
80A-100A 80A to 100A

Faraday Close, Durrington


Worthing, West Sussex, BN13 3PL
Phone: +44 1903 268500
www.eurotherm.co.uk

Document Number HA033174 Issue 1

®2018 Schneider Electric. All Rights Reserved. Life Is On Schneider Electric, Eurotherm, EurothermSuite, eCAT, EFit, EPack, EPower, Eycon, Eyris, Chessell, Mini8, nanodac, optivis,
piccolo and versadac are trademarks and property of Schneider Electric SE, its subsidiaries and affiliated companies. All other trademarks are the property of their respective