Professional Documents
Culture Documents
More than just a product, EPack Lite power controllers bring • Controls non variable resistive and primary
a tailored solution based on more than 50 years of Eurotherm
transformer loads
expertise.
• Wide range of firing modes: Logic, Phase
> See EPack™ compact SCR power controllers brochure HA031554 Angle, Adjustable Burst Firing, Fast Cycle
to discover how full EPack range can add value to your business
• Measurements: Current, voltage or
The EPack Lite-1PH controller provides control of single phase impedance and more
non variable resistive or primary transformer loads. It combines • Load fault detection up to 1 element of 6
simplicity of setup and operation in a compact format. • SCCR 100kA
The combination of advanced configurable firing modes allows
close matching to load characteristics to optimise process
efficiency.
EPack Lite-1PH Data Sheet eurotherm.co.uk/epack 2
Specifications
General Fuses
Directive EMC directive 2014/30/EU Current Rating Fuse Holder Size Dimensions H x W x D
Low Voltage Directive 2014/35/EU ≤25A without MS 10x38mm / 13/32x1-1/2in 88.5x17.5x64.5mm / 3.48x0.69x2.54in
≤25A with MS 14x51mm / 9/16x2in 110.8x26.5x76.5mm / 4.36x1.04x3.01in
Safety Specification EN60947-4-3:2014
32A with or without MS 14x51mm / 9/16x2in 110.8x26.5x76.5mm / 4.36x1.04x3.01in
EMC Emissions Specification EN60947-4-3:2014 - Class A product
40A with or without MS 14x51mm / 9/16x2in 110.8x26.5x76.5mm / 4.36x1.04x3.01in
EMC Immunity Specification EN60947-4-3:2014
50A with or without MS 22x58mm / 2-9/32in 127.5x35x76.5mm / 5.02x1.38x3.01in
Vibration Tests EN60947-1 annex Q category E
63A with or without MS 27x60mm / 1-1/16x2-3/8in 149.4x40x93.5mm / 5.88x1.57x3.68in
Shock Tests EN60947-1 annex Q category E
80A with or without MS 27x60mm / 1-1/16x2-3/8in 149.4x40x93.5mm / 5.88x1.57x3.68in
Approvals
100A with or without MS 27x60mm / 1-1/16x2-3/8in 149.4x40x93.5mm / 5.88x1.57x3.68in
European Community EN60947-4-3:2014: Low-voltage switchgear 125A with or without MS 27x60mm / 1-1/16x2-3/8in 149.4x40x93.5mm / 5.88x1.57x3.68in
and controlgear - Part 4-3:Contactors and
motor-starters - AC semiconductor controllers
and contactors for non-motor loads (identical
Power
to IEC60947-4-3:2014) Nominal Current 4 to 125 amps
Declaration of conformity available on request. Nominal Voltage 100 to 500Vac +10%/–15%
US & Canada UL60947-4-1 CAN/CSA C22.2 NO.60947-4-1-14 Accuracy ±2% of full scale - from 100 to 500V +10%/–15%
Low-Voltage Switchgear and Controlgear Frequency 47Hz to 63Hz
- Part 4-1: Contactors and Motor-Starters - Short Circuit Protection By external supplemental high speed fuses
Electromechanical Contactors and Motor- Rated Conditional Short-circuit
Starters - U.L. File N° E86160 100kA (Coordination Type 1)
Current
Australia Regulatory Compliance Mark (RCM) Type Of Loads
to Australian Communication and Media Authority
AC51 Resistive or slightly inductive load (cos phi>0.8)
Based on compliance to EN60947-4-3:2014
AC-56a Transformer Primary
China Product not listed in catalogue of products
subject to China Compulsory Certification (CCC)
Control
Protection CE: 16 to 63A > IP10 according to EN60529
Auxillary Power Supply 100V to 500V +10%/–15% or 24 ac/dc (±20%)
80 to 125A > IP20 according to EN60529
UL: open type Control Setpoint Analog or Logic input
Analogue Input Signal
Voltage Range: 0-5V, 1-5 V, 0-10V or 2-10V
Condition Of Use
Impedance: 140 k Ohms typical (0-10V signal)
Atmosphere Non-corrosive, non-explosive, non-conductive
Current Range: 0-20mA or 4-20mA
Degree Of Pollution Degree 2
Input resistance: 100 ohms to allow three
Storage Temperature –25°C to 70°C (maximum)
units wired in series to be driven from a single
Usage Temperature 0 to 45°C at 1000m controller’s analogue output
0 to 40°C at 2000m
Resolution 11 bits
Altitude 1000m maximum at 45°C
Linearity ±0.1% of Scale
2000m maximum at 40°C
Phase Angle, Intelligent Half cycle, Variable
Derating Curves Firing Mode
Altitude (meters) Modulation Burst firing (FC1, C16, C64), Fix
modulation period (2 seconds fixed), Logic
mode
2000
Control Mode V control, I control, Open loop
2 2
Display
Technology TFT
Size 1.5”
Messages Messages for configuration, monitoring and
diagnostics
EPack Lite-1PH Data Sheet eurotherm.co.uk/epack 3
Analogue Input
1
129.2mm (5.09in)
V/mA input
121mm (4.76in)
163.5mm (6.44in)
174mm (6.85in)
0 to 10V 0 to 20mA
117mm (4.61in)
147mm (5.79in)
1 to 5V 4 to 20mA
2 to 10V
0 to 5V
Protective earth
ground (M5) Relay Output
136.2mm (5.36in)
Front view nc
View on lower face Com
no
I/O connector
Switching characteristics
(resistive loads)
Vmax: 264V RMS
Vmin: 5V
Weight: 0.8kg / 1.76lb Relay output Load power output Imax: 2A RMS
View on lower face Imin: 10 mA
Auxiliary voltage
72mm alternatives
(2.83in) (as specified at
time-of-order)
46.7mm
(1.84in) Phase reference Load power
(neutral)
Neutral
input
reference
View on right-hand face
From Supply
163.5mm (6.44in)
121mm (4.76in)
174mm (6.85in)
117mm (4.61in)
Lift-up flap
147mm (5.79in)
Center pin
not connected
32A unit shown;
Other units have
same connections
Access to supply
termination
screw head
Protective earth
ground (M5) Access to load
termination
Front view 173.3mm (6.81in) screw head
90.5mm
(3.56 in)
EPack (auxiliary) supply power
(low voltage option shown) 800Ω to ∞ = Open
0Ω to 450Ω = Closed
(3.15 in)
451Ω to 799Ω= Undefined
80mm
AC/DC
24V
Phase reference (neutral)
N/L2
11V<Vin<30V = High with 6mA<lin<30mA 1
-3V<Vin<5V = Low with 2mA<Iin<30mA
Front view or 5V<Vin<11V with Iin<2mA
202.1 mm (7.96 in)
46.7mm (1.84 in) Voltage level inputs
Wire guide (2 places) View on right hand side
Access to supply Analogue Input
termination 1
1/L1
screw head V/mA input
321.23mm (12.65 in)
1 to 5V 4 to 20mA
2 to 10V
0 to 5V
nc
130.50mm Load power output
(5.14 in) Com
I/O connector no
(3.15 in)
1 2 3 4 5
80mm
Relay output 04 01 02
Switching characteristics
(resistive loads)
Vmax: 264V RMS
Vmin: 5V
Imax: 2A RMS
Weight: 1.8kg / 3.97lb View on lower face View on lower face Imin: 10 mA
24V
Front view AC/DC
46.7mm (1.84 in) 202.1 mm (7.96 in)
termination
screw head
1/L1
1 2 3 4 5
80mm
Relay output 04 01 02
To load
Order Codes
The EPack Lite power controller is ordered using a short code for the chargeable options and an extended option
configuration code for commissioning.
If the extended code is not used, the software configuration is completed using a quick start procedure.
Current rating of EPack Lite controllers may be upgraded at any time using a software key order code.
Product Coding
1 2 3 4 5 6 7 8
EPACK-LITE-1PH XXX
9 10 11 12 13 14 15 16 17 18 19
XXX
Model 5 Warranty
Optional Configuration
Power XXX Standard Warranty
EPACK LITE-1PH
Controller WL005 5 Year Warranty
USWL3 US Extended Warranty 9 Nominal Load Current 14 Burst Min ON Time
1 Maximum Current nnnA 1 - Value field 1 None
XXX
6 Custom Labelling Single cycle 1 period
16A 16 amps FC1
min ON time
25A 25 amps XXX Standard (Eurotherm) 10 Nominal Line Voltage C16
Burst with 16 periods
32A 32 amps FXXXX Special Label 100V 100 volts min ON time
40A 40 amps C64
110V 110 volts Burst with 64 periods
50A 50 amps 115V 115 volts min ON time
7 Fuse
63A 63 amps 120V 120 volts
80A 80 amps XXX Without 127V 127 volts
100A 100 amps HSP High Speed fuse 200V 200 volts 15 Analog Input Function
125A 125 amps without microswitch 208V 208 volts XX None
HSM High Speed fuse 220V 220 volts SP Setpoint
with microswitch 230V 230 volts
2 Auxillary Power Supply
240V 240 volts
500V 500V max 277V 277 volts 16 Analog Input Type
8 Configuration
24V 24V ac/dc 380V 380 volts 0V 0-10 volts
XXXXX Default 400V 400 volts 1V 1-5 volts
LC Long code 415V 415 volts
3 Reserved 2V 2-10 volts
440V 440 volts 5V 0-5 volts
XXX Reserved 460V 460 volts 0A 0-20 mA
480V 480 volts 4A 4-20mA
500V 500 volts
4 Control Option
V2 2
V control (standard) 17 Digital Input 1 Function
I2 2
I control
11 Load type
XX None
OL Open loop control XX Resistive FI Firing
TR Transformer primary LG Setpoint for logic mode
AK Alarm
12 Heater Type acknowledgement
FB Fuse Blown
XX Resistive
19 Reserved
XXX Reserved
EPack Lite-1PH Data Sheet eurotherm.co.uk/epack 6
®2018 Schneider Electric. All Rights Reserved. Life Is On Schneider Electric, Eurotherm, EurothermSuite, eCAT, EFit, EPack, EPower, Eycon, Eyris, Chessell, Mini8, nanodac, optivis,
piccolo and versadac are trademarks and property of Schneider Electric SE, its subsidiaries and affiliated companies. All other trademarks are the property of their respective
owners.