Professional Documents
Culture Documents
PTS 11.32.01
January 2019
FOREWORD
PETRONAS Technical Standards (PTS) has been developed based on the accumulated knowledge,
experience and best practices of the PETRONAS group supplementing National and International
standards where appropriate. The key objective of PTS is to ensure standard technical practice across
the PETRONAS group.
Compliance to PTS is compulsory for PETRONAS-operated facilities and Joint Ventures (JVs) where
PETRONAS has more than fifty percent (50%) shareholding and/or operational control, and includes
all phases of work activities.
Contractors/manufacturers/suppliers who use PTS are solely responsible in ensuring the quality of
work, goods and services meet the required design and engineering standards. In the case where
specific requirements are not covered in the PTS, it is the responsibility of the
Contractors/manufacturers/suppliers to propose other proven or internationally established
standards or practices of the same level of quality and integrity as reflected in the PTS.
In issuing and making the PTS available, PETRONAS is not making any warranty on the accuracy or
completeness of the information contained in PTS. The Contractors/manufacturers/suppliers shall
ensure accuracy and completeness of the PTS used for the intended design and engineering
requirement and shall inform the Owner for any conflicting requirement with other international
codes and technical standards before start of any work.
PETRONAS is the sole copyright holder of PTS. No part of this document may be reproduced, stored
in a retrieval system or transmitted in any form or by any means (electronic, mechanical, recording or
otherwise) or be disclosed by users to any Owner or person whomsoever, without the prior written
consent of PETRONAS.
The PTS shall be used exclusively for the authorised purpose. The users shall arrange for PTS to be
kept in safe custody and shall ensure its secrecy is maintained and provide satisfactory information to
PETRONAS that this requirement is met.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 3 of 31
Table of Contents
1.0 INTRODUCTION ..................................................................................................... 5
1.1 SCOPE ............................................................................................................................ 5
1.2 GLOSSARY OF TERMS..................................................................................................... 5
1.3 SUMMARY OF CHANGES ............................................................................................... 7
2.0 DESIGN REQUIREMENTS ........................................................................................ 8
2.1 DESIGN INFORMATION .................................................................................................. 8
2.2 PROTECTION CRITERIA .................................................................................................. 8
3.0 SITE SURVEYS ...................................................................................................... 10
4.0 ELECTRICAL ISOLATION ........................................................................................ 11
4.1 isolating FLANGES ........................................................................................................ 11
4.2 EARTHING .................................................................................................................... 12
5.0 ELECTRICAL CONTINUITY ..................................................................................... 13
6.0 COATING, DESIGN LIFE AND CURRENT DENSITY REQUIREMENTS.......................... 14
6.1 PIPELINE COATING ....................................................................................................... 14
6.2 DESIGN LIFE ................................................................................................................. 14
6.3 CURRENT DENSITY REQUIREMENTS ............................................................................ 14
7.0 CHOICE OF CATHODIC PROTECTION SYSTEM ........................................................ 15
8.0 IMPRESSED CURRENT CATHODIC PROTECTION (ICCP) SYSTEM ............................. 16
8.1 SOURCE OF DC VOLTAGE ............................................................................................. 16
8.2 GROUNDBEDS .............................................................................................................. 17
8.3 CURRENT CONTROL AND DISTRIBUTION..................................................................... 19
9.0 SACRIFICIAL ANODE CATHODIC PROTECTION (SACP) SYSTEM............................... 20
9.1 ZINC ANODES ............................................................................................................... 21
9.2 MAGNESIUM ANODES ................................................................................................. 21
9.3 CHEMICAL BACKFILL .................................................................................................... 21
9.4 CABLES AND CABLE CONNECTIONS ............................................................................. 21
10.0 MONITORING FACILITIES ..................................................................................... 22
10.1 POTENTIAL MONITORING STATIONS ........................................................................... 22
10.2 FOREIGN PIPELINE BONDING FACILITIES ..................................................................... 22
10.3 TEST FACILITIES AT CASINGS........................................................................................ 22
10.4 TEST FACILITIES AT ISOLATION JOINTS / FLANGES ...................................................... 22
10.5 DRAIN POINT TEST FACILITIES ..................................................................................... 22
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 4 of 31
1.0 INTRODUCTION
This PTS specifies the minimum technical requirements for the design of cathodic protection
systems for onshore buried pipelines and based on PETRONAS lesson learnt and best
practices.
1.1 SCOPE
1.1.1 This PTS applies for onshore pipeline system and shore approach section.
Refer to PTS 00.01.03 for PTS Requirements, General Definition Of Terms, Abbreviations &
Reading Guide.
No Term Definition
No Term Definition
application of cathodic protection, such as
impressed current stations, galvanic anodes,
bonds, and isolating joints.
No Term Definition
No Abbreviations Description
1 AC Alternating Current
4 DC Direct Current
Table 1.2: Specific Abbreviations
2.1.1 The Owner shall submit all the technical information required for cathodic protection design
to the Contractor which shall include but not limited to items below:
i. Pipeline details i.e. length, size, type of coating, intended protection scope.
iv. Pertinent drawings i.e. pipeline route, existing systems, crossings, casing and
foreign structures/pipelines.
v. Existing CP system design records including inspection and maintenance (if any)
"Instant-OFF" POTENTIALS, mV
REFERENCE ELECTRODE :
Cu/CuSO4 Ag/AgCl/ seawater
2.2.1 The "Instant-OFF" potential on all parts of the pipeline shall be equal to or more negative than
the protection potential value stated in Table 2.1 fo the pipeline to be considered fully
cathodically protected.
2.2.2 The "OFF" potentials for carbon steel shall not be more negative than the overprotection limit
value as stated in Table 2.1 to avoid detrimental effects on the applied coating or on the
pipeline due to overprotection.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 9 of 31
2.2.3 The protection criteria for corrosion resistant steel and some high strength steel pipelines
shall be determined by taking into account the material susceptibility to hydrogen induced
stress cracking. This shall include cathodic protection design for pipeline crossing or
approaching another pipeline made of such materials.
2.2.4 Presence of active sulphate reducing bacteria in anaerobic soil shall be confirmed via soil
investigation to determine the imminent protection for anaerobic environments.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 10 of 31
A site survey shall be carried out prior to execution of cathodic protection design. The site
survey shall collect the following data but not limited to;
v. Stray Currents
Seasonal changes shall be taken into consideration if the surveyed area is affected and
different seasonal condition surveys shall be performed if possible. The worst case out of the
surveys shall be taken as the basis for the design.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 11 of 31
Electrical isolation preferably using MIJ shall be provided to separate pipeline cathodic
protection system from other plant, foreign structures/pipeline and electrical and instrument
earthing systems.
Isolation joint/flange may also be used and shall be installed above ground or in inspection
pits; and shall not be buried. Each isolation joint/flange shall be provided with test facilities.
The isolation joint/flange shall be equipped with earthing or surge arrestors in areas with risk
of high voltages presence on the pipeline i.e. due to adjacent power systems or lightning.
iv. Between pipeline sections running in different types of electrolyte (e.g. river
crossings) and/or different method of installation (e.g. HDD for river crossings,
highway crossings, railway crossings etc.);
Unless running in the same trench and having the same coating system, parallel pipelines shall
be electrically isolated from each other.
Pipelines should avoid touching or near any metal; and should be electrically isolated from
pipe supports.
Safety or instrument earthing shall be compatible with the cathodic protection system.
For design of Isolation joint refer to PTS 11.31.05 - PIPELINE ISOLATING JOINTS
(AMENDMENTS/SUPPLEMENTS TO MSS SP-75)
For design of Isolation spool refer to PTS 11.31.05 - PIPELINE ISOLATING JOINTS
(AMENDMENTS/SUPPLEMENTS TO MSS SP-75)
4.1.1 Raised face or full face flanges should use insulating gasket of neoprene coated phenolic resin
type. Sleeve and washer shall be made from phenolic resin or equivalent.
4.1.2 Both sides of the bolts shall be insulated with full length phenolic or composite sleeves and
phenolic resin insulating washers and steel washers.
4.1.3 Prior to welding onto the pipeline, isolating flanges should be assembled and tested. The
isolating flange shall withstand a voltage of 1500 volt DC across the flange assembly for one
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 12 of 31
minute without causing breakdown of the insulation or flash over. The resistance across the
assembled flange shall be taken successively and shall read higher than 1 MΩ.
4.1.4 With the exceptional of sour service condition, flange protectors or protective tape shall be
applied to protect isolating flange from dirt and moisture ingress.
4.2 EARTHING
4.2.1 Cathodic protection system for pipeline shall be electrically isolated from common or plant
earthing system to prevent current leakage.
4.2.2 Electrical safety earthing application shall be made compatible with the cathodic protection
systems as per following requirements:
iii. Install in the earthing circuit or by the installation of separate earthing electrodes.
4.2.3 For the purpose of mitigating the AC induced voltages such as pipeline in parallel with
transmission line, earthing should be installed at the following locations:
Isolation joints installed at coating/electrolyte changes shall always be bonded at test posts;
to keep the pipeline electrically continuous when the cathodic protection is operational.
For non-welded pipeline applications, the continuity of the cathodic protection shall be
maintained and shall be tested i.e. by carrying out overlapping potential measurements. This
can be ensured by erection of permanent bonds over high resistance flanges/couplings, using
cables and approved attachment methods.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 14 of 31
6.1.1 The appropriate design parameters for each coating type shall be used in the design in case
of adjacent structures having different type of coatings or significant difference in coating
condition. Pipeline isolation shall be provided should the interference is expected.
6.2.1 Unless stated otherwise by the Owner, the cathodic protection system shall be designed for
the pipeline design life.
6.3.1 The minimum current density design values shall be based on Table 3 from ISO 15589-1.
6.3.2 A current drainage test shall be carried out to determine the current requirement for existing
pipelines, where the actual condition of the applied coating is unknown.
6.3.3 The higher of the two values computed by above methods; pipeline current demand and
current drainage test, shall be used as the cathodic protection system capacity.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 15 of 31
By means of requisition, the type of cathodic protection system shall be indicated. In case not
specified, the type of cathodic protection system shall be proposed by the Contractor with his
justification included in the basic design.
i. Soil resistivity
viii. Maintenance
Impressed current shall be used if the above criteria do not clearly justify one particular
system.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 16 of 31
8.1.1 Transformer/rectifiers
iii. Transformer/rectifiers shall be fit to operate under the normal service conditions.
The output voltage shall be adjustable from zero to the maximum rated output
when on load. Tapping switches shall be front-mounted; if required, with a step-
size of maximum 3% of maximum output. Transformer tapping using relocation
of jumpers shall not be used.
v. The rectifier shall be fabricated to provide full wave rectification using high
current density selenium cells or silicon diodes. The current rating of the diodes
shall be higher than 1.25 times the maximum current rating of the rectifier and
have a minimum peak inverse voltage of 1200 V.
vi. The output rms ripple current shall not exceed 5% of the DC output current
between 5% and 100% of the rated current output.
ix. Meters of approximately 70mm diameter or similarly sized square pattern meters
with measuring accuracy better than 2% of full scale shall be provided to the
transformer/rectifier to read the output voltage and current.
x. The polarity of the DC terminals and AC supply terminals shall be clearly marked.
AC and DC cables shall be separated by an insulating panel.
xi. Unless otherwise stated, a built-in timer unit shall be required. The timer unit shall
be capable of switching the full output current in a sequence of 50 seconds on
and 10 seconds off and may be mechanical or electronic. All transformer/rectifier
timer units should be provided with a facility for synchronous switching in the
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 17 of 31
xii. The incoming cables shall terminate in separate non oil filled cable boxes and
penetration into the tank shall be via bushings above oil level for an oil cooled
transformer/rectifier. A sight glass and thermometer shall be provided.
xiv. The enclosure shall have a minimum degree of protection IP 54 in accordance with
IEC 529, if installed outdoors.
8.2 GROUNDBEDS
8.2.1 The groundbed of an impressed current cathodic protection system shall be designed such
that:
i. Its mass and quality is sufficient to last for the design life of the system.
ii. Its resistance to earth allows the maximum predicted current demand to be met
at 80% or less of the voltage capacity of the DC source during the design life of
the system.
iii. Its location is remote from the pipeline and any other buried structure, to provide
a regular distribution of current along the pipeline.
iv. The risk of causing harmful interference on other buried structures is minimized.
8.2.2 The selection of the location and the type of groundbed shall depend on local conditions such
as:
i. If the soil conditions at the required depth are suitable to meet the requirements
in subsection 8.2.
8.2.4 The Contractor shall include and specify information below in his basic design:
vi. Backfilling.
Metallic casing (such as steel, iron or aluminium) may be used if the casing does not result in
undesirable current discharge at or near ground level. However, metallic casing should not be
used opposite anodes in open hole deep anode beds. Casing at depth shall be electrically
isolated from metal casing and structures at the surface. Non-metallic casing (such as cement,
thermoplastics or reinforced thermosetting materials) may be used to prevent current
discharge at or near ground level.
To prevent gas blocking of the well, adequate venting pipes shall be provided to the deepwell
groundbeds. The vent pipe shall be of chlorine resistant material. Vent pipe blockage by coke
backfill shall be avoided using filter gravel. The vent pipe should be carried to a sufficient
height to prevent damage to surrounding equipment and intrusion of surface water.
i. If the soil conditions at the proposed groundbed depth, are suitable to meet the
requirements in subsection 8.2.
ii. If sufficient distance from the pipeline can be achieved and there is no risk of
shielding.
The anodes or the highest point of the carbonaceous backfill shall be not less than 1 metre
below ground level.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 19 of 31
i. Graphite.
iii. Magnetite.
v. Platinised titanium/niobium.
Unless the ground conditions dictate otherwise, a carbonaceous backfill or other low
resistivity backfill material shall be used.
For the purpose of measuring anode current outputs, individual anode circuits shall be
provided with shunts.
ii. If required, variable resistors shall be installed in the negative drain circuit to
balance the current to each of the adjacent pipelines. An appropriately sized
shunt and diode shall be provided at the DC source for each of the negative circuit.
iii. A distribution box for all cables, diodes and current measurement facilities shall
be installed.
By the means of requisition, the DC voltage source shall be provided with automatic potential
control. The suitable permanent reference electrode shall be buried close to the pipeline to
achieve this.
The potential measuring circuit shall have a minimum input resistance of 100 MΩ. The control
system shall have an accuracy of 10 millivolts and shall be provided with adjustable voltage
and current limiting circuits and/or alarms to protect the pipeline against overprotection in
case of failure of a reference cell. A panel mounted meter to read the pipe-to-soil potential
shall be provided.
8.3.3 Cables
All cables, cable connections and cable accessories shall be in accordance with section 12.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 20 of 31
i. If the pipeline (section) runs in low resistivity soil, water, swamps or marshes.
ii. The selected type of anode is capable of continuously supplying the maximum
current demand.
iii. The total mass of anode material is sufficient to supply the required current during
the design life of the system.
The anodes should be buried in low resistivity chemical backfill to obtain the required output.
The Manufacturer/Supplier of sacrificial anodes shall supply anodes which are clearly marked
with the type of material (trade name), anode weight (without backfill), and charge number.
The supplier shall provide full documentation of number, types, weight, dimensions, chemical
analysis and performance data of the anodes.
The anodes shall be inspected for mechanical damage, casting quality and the bonding of the
anode core/cable.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 21 of 31
9.1.1 Zinc anodes can be considered if the resistivity of the electrolyte is 5000 ohm.cm.
9.1.2 For non-standard applications (e.g. high temperature) special alloys may be used which shall
be approved by the Owner.
9.2.1 Magnesium should not be used if the resistivity of the electrolyte is higher than 10000
ohm.cm.
9.2.2 The use of chemical backfill around buried anodes shall be used to increase current output
and to avoid passivity.
9.2.3 For special applications (e.g. high output in high resistivity soil) special alloys may be used,
which shall be approved by the Owner.
9.3.1 Backfill for sacrificial anodes shall consist of a mixture of gypsum, bentonite clay and sodium
sulphate. The ratio of the components shall be such to obtain optimum results in the
prevailing resistivity and soil wetness.
9.3.2 The supplier shall include the composition of the backfill material in the anode
documentation.
9.4.1 All cables, cable connections and cable accessories shall be in accordance with section 12.
Sacrificial anode cables shall be connected to the pipeline via a bondbox and shunts to allow
anode current monitoring.
9.4.2 For magnesium anodes it should be allowed to install a resistor in the anode circuit to limit
the protection levels to within the protection criteria.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 22 of 31
The contractor shall include in his design sufficient monitoring facilities to ensure effective
survey of the level of the cathodic protection along the pipeline. The minimum requirements
for monitoring facilities are given below.
10.1.1 To monitor pipe to soil potentials, test posts shall be installed at distances of maximum 1000m
along the pipeline. In urban or industrial areas, a closer distance (maximum 200m) should be
taken. At least one test post shall be installed between major obstacles such as waterways,
main roads and railways to allow unobstructed close interval potential surveys.
10.1.2 Two separate cables shall be attached to the pipeline and terminated in the test post.
10.1.3 If pipelines are running in parallel regardless in the same trench or not, each pipeline shall be
provided with separate potential monitoring facilities. Test posts should be installed not more
than 2.5m away from the pipeline.
At crossings with foreign pipelines, a bonding facility shall be provided, consisting of two
separate cables attached to each individual pipeline, terminating in a test post with suitable
facilities to install direct or resistive bonds. The cables to each pipeline shall be identified by
colour coding or tags.
10.3.1 If the casing is longer than 10 metres, a test facility shall be installed at both ends of the casing.
Shorter casings shall be provided with a test facility at one end only.
10.3.2 In each test facility, one test cable shall be connected to the pipeline and, if a steel casing is
used, one test cable shall be connected to the casing. Both cables shall be terminated in one
test post.
10.4.1 At all isolation joints/flanges, two cables shall be connected to each side of the joint or flange.
All cables shall be separately terminated in one test post with suitable facilities to install direct
or resistive bonds.
10.4.2 The cables to each side of the isolation joint shall be identified by colour coding or tags.
10.5.1 At the drain points each negative connection to the pipeline shall be provided with current
measurement facilities. Where multiple negative connections are installed separate shunts
and blocking diodes shall be provided, installed in a distribution box.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 23 of 31
10.5.2 At the drain point a potential monitoring station shall be installed; except on an above ground
section of the pipeline, using a separate test cable connected to the pipeline for the
measurement of the drain point potential.
The Contractor should propose other test facilities which he considers necessary for cathodic
protection monitoring. Such test facilities may include in-line current measurement facilities,
buried polarization coupons, etc.
All cables, test posts and distribution boxes shall be designed and installed in accordance with
section 12.
Surge arrestors shall be installed across isolation joints/flanges and across the output
terminals of DC voltage sources.
10.10.1 Surge arrestors required to prevent elevated voltages due to faults in adjacent electrical
power systems or lightning shall be of the spark gap type and shall be designed such that:
i. The impulse breakdown voltage of the electrodes is lower than that of the
isolation joint across which they are mounted.
ii. The spark gap is capable of discharging the expected lightning currents without
sustaining damage.
iii. The spark gaps are fully encapsulated to prevent sparks in open atmosphere and
to protect the spark gaps from moisture.
10.11.1 For regular monitoring of cathodic protection systems the equipment to be used shall meet
the following requirements:
ii. In-line current meters shall not be used except for trouble shooting. Cathodic
protection currents shall be measured using fixed shunts or resistors or clamp-on
current probes.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 24 of 31
iii. Voltmeters and other monitoring equipment used to measure pipe to soil
potentials shall have an accuracy of better than 5 millivolts and shall have an input
resistance of at least 100 MΩ.
iv. Data loggers used to monitor pipe to soil potentials over prolonged periods shall
have an input resistance of at least 100 MΩ (also in a "dormant" mode, otherwise
shall be disconnected from the pipeline or reference electrode while the data
logger is in the "dormant" mode, e.g. by an automatic relay switch).
v. Cu/CuSO4 reference electrodes shall be used in combination with soil and fresh
water.
vii. Zinc reference electrodes shall only be used as permanent reference electrodes
in combination with soil and seawater.
11.1 CABLES
11.1.1 All cables shall be single core stranded copper cables, suitable for DC use and shall be double
insulated and sheathed to withstand the prevailing chemical and mechanical (soil) conditions.
The minimum cable size shall be 6 mm2.
11.1.2 All cables shall be sized such that no excessive voltage drops occur which reduce the capacity
of the system.
11.1.3 Resistance of anode cables may be used to balance the output of different anodes or
groundbeds. The detailed design shall give calculations to support this design detail.
11.1.5 All cables shall be laid without coils or kinks, buried in soft sand at a depth of at least 0.5m,
provided with cable protection tiles or warning tape as considered suitable for the area.
11.1.6 All buried cables shall be of one continuous length without splices. Cable to cable connections
should be made above ground inside distribution boxes to reduce the risk of damage and to
allow monitoring.
11.1.7 Cable routes shall be clearly marked using cable markers. These should be installed at
approximately 100 metre intervals and at every change of direction of the cable route.
11.2.1 Minimum anode cable size shall be 10 mm2. Cable connections shall be insulated using epoxy
resin and/or heat shrinkable insulation sleeves.
11.2.2 The cables of impressed current anodes shall be connected to the positive feeder cable inside
an above ground distribution box to enable current monitoring. The cables of sacrificial
anodes shall be connected to the pipeline via an above ground distribution box to allow
current monitoring and disconnection.
11.3.1 General
ii. The Contractor shall include in the design detail procedures of processes to be
used for cable connections. The detail procedures shall be approved by Owner.
Welders shall be fully qualified for the applicable welding process.
iii. Welding of cable connections shall not be carried out on bends or within 200mm
from welds.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 26 of 31
iv. All below ground electrical connections shall be fully encapsulated to comply with
the original coating standards before backfilling.
v. The following guideline for the selection of cable connections shall be followed:
a) Drain cables shall be connected using welding or studwelding.
b) Bond cables shall be connected using welding, studwelding or pinbrazing.
c) Potential measuring cables shall be connected using any of the referred
methods.
11.3.2 Welding
i. A metal plate, 50x50mm minimum, provided with a welded M10 threaded stud
bolt, shall be welded to the pipeline by two continuous welds in the
circumferential direction of the pipe only. The plate shall be made of the same
material as the pipeline.
ii. The cables shall be connected to the threaded studbolt using crimped or brazed
cable lugs, nuts and serrated washers.
ii. The stud material and consumables shall be compatible with the pipeline
material. The process shall not influence the pipeline material properties to fall
outside the original specifications.
iii. The size of threaded studs shall be 8mm or more to suit the cable size. The cables
shall be connected to the stud using crimped or brazed cable lugs, nuts and
serrated washers.
11.3.4 Pinbrazing
i. The pinbrazing process shall use specially designed cable lugs and brazing pins to
braze the cables to the pipeline and shall be approved by the Owner.
ii. The brazing materials shall be compatible with the pipeline material. Penetration
of copper and/or other brazing metals into the pipeline shall not be deeper than
1mm and the hardness shall remain inside the original pipeline requirements.
iii. Pinbrazing shall not be used on austenitic stainless steel and duplex stainless steel
pipelines.
i. Thermit welding process shall be such that copper penetration into the pipeline
material shall not be deeper than 1mm and that the hardness shall remain inside
the original pipeline requirements.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 27 of 31
ii. Thermit weld charges shall not be greater than 15 grams and cable cores shall not
be heavier than 16mm2. If heavier cables need to be attached, the core shall be
separated into smaller strands of less than 16mm2 each and welded separately.
iii. Thermit welding shall not be used for austenitic stainless steel and duplex steel
pipelines.
Where welding, brazing or thermit welding is not possible, e.g. for safety reasons, the
Contractor may design glued electrical connections using metal plates bonded with electrically
conductive epoxy resin. This method shall not be used for current carrying cables (drain
cables, bond cables). The materials to be used and the installation procedure shall be
approved by the Owner.
11.4.1 If installed above ground they shall be provided with lockable access doors or caps, or have
external insulated contacts fitted, to allow easy connection of test clips for regular monitoring.
Cable entry shall be at the bottom through protective tubes.
11.4.2 If test stations are required to be installed underground, they shall have adequate water
drainage facilities and they shall be provided with a closure to avoid ingress of dirt.
11.4.3 Distribution boxes shall always be installed above ground and shall be provided with hinged
doors giving access to all internal components.
11.4.4 Distribution boxes shall be weatherproofed in accordance with the minimum degree of
protection IP 54 in accordance with IEC 529.
11.4.5 Test posts and distribution boxes shall be accessible during all seasons and shall be designed
such that they are not prone to vandalism or damage.
11.4.6 Distribution boxes and test posts used for bonding of current carrying cables (including bonds
between pipelines/structures or across isolation joints) shall be located outside hazardous
areas. If this is not possible, a box approved for the relevant area classification shall be used.
11.4.7 The Contractor shall propose the type of test post and distribution box for each application in
the detail design.
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 28 of 31
12.0 DOCUMENTATION
12.1.1 The basic design documents shall be submitted for approval by the Owner, covering the
following requirements:
i. Results of any site surveys and soil investigations that have been carried out.
ii. Results of any current drainage tests that have been carried out for retrofitting on
existing pipelines.
iii. Any requirements for modifications to existing pipeline systems such as electrical
separation or coating repair.
iv. Justification of the selected cathodic protection system and anode materials if the
choice is made by the Contractor.
viii. A list of the estimated number and types of cathodic protection monitoring
facilities.
ix. Any sensitivities in the proposed cathodic protection system that requires special
attention.
x. Any other information that is regarded by the Contractor as essential for this stage
of the cathodic protection design.
12.1.2 The detailed design documents shall be submitted to the Owner for approval before
construction starts and shall cover the following requirements:
i. A schedule of materials.
13.0 BIBLIOGRAPHY
INTERNATIONAL STANDARDS
Semiconductor convertors IEC 146
Degrees of protection provided by enclosures (IP code) IEC 529
Petroleum, petrochemical and natural gas industries — Cathodic ISO 15589-1-2015
protection of pipeline systems — Part 1: On-land pipelines
PTS 11.32.01
CATHODIC PROTECTION SYSTEMS FOR ONSHORE AND SHORE
January 2019
APPROACH PIPELINES
Page 30 of 31
PROJECT NAME:
DATASHEET FOR DESIGN OF CATHODIC PROTECTION SYSTEM FOR
ONSHORE BURIED AND SHORE APPROACH PIPELINES PROJECT NO:
ORDER/ENQUIRY NO:
A PIPELINE DATA
1 Pipeline Name/Code:
2 Pipeline Route:
3 Product(s) Transported: Sour Service
4 Years of Construction:
5 Design Life: years
6 Pipeline Length: m
7 Nominal Diameter: inches
8 Pipeline Material
9 External Coating:
10 Backfill Type:
11 Route Characteristic:
12 Branch Lines (use separate datasheet for each branch lines):
13 Attached Drawings: