Professional Documents
Culture Documents
PTS 15.20.14
October 2018
FOREWORD
PETRONAS Technical Standards (PTS) has been developed based on the accumulated knowledge,
experience and best practices of the PETRONAS group supplementing National and International
standards where appropriate. The key objective of PTS is to ensure standard technical practice across
the PETRONAS group.
Compliance to PTS is compulsory for PETRONAS-operated facilities and Joint Ventures (JVs) where
PETRONAS has more than fifty percent (50%) shareholding and/or operational control, and includes
all phases of work activities.
Contractors/manufacturers/suppliers who use PTS are solely responsible in ensuring the quality of
work, goods and services meet the required design and engineering standards. In the case where
specific requirements are not covered in the PTS, it is the responsibility of the
Contractors/manufacturers/suppliers to propose other proven or internationally established
standards or practices of the same level of quality and integrity as reflected in the PTS.
In issuing and making the PTS available, PETRONAS is not making any warranty on the accuracy or
completeness of the information contained in PTS. The Contractors/manufacturers/suppliers shall
ensure accuracy and completeness of the PTS used for the intended design and engineering
requirement and shall inform the Owner for any conflicting requirement with other international
codes and technical standards before start of any work.
PETRONAS is the sole copyright holder of PTS. No part of this document may be reproduced, stored in
a retrieval system or transmitted in any form or by any means (electronic, mechanical, recording or
otherwise) or be disclosed by users to any company or person whomsoever, without the prior written
consent of PETRONAS.
The PTS shall be used exclusively for the authorised purpose. The users shall arrange for PTS to be
kept in safe custody and shall ensure its secrecy is maintained and provide satisfactory information to
PETRONAS that this requirement is met.
TABLE OF CONTENTS
1.0 INTRODUCTION
This PTS provides the minimum technical requirements for external cathodic protection (CP)
system design, installation, commissioning and monitoring of the underground and
submerged metallic piping system. This PTS was developed to ensure the safe and reliable
operations of the equipment at PETRONAS assets. This PTS adopts NACE SP0169 with
additional requirements as an amendment and supplement based on PETRONAS lessons
learnt and best practices.
1.1 SCOPE
This PTS is applicable for underground and submerged metallic piping system. This PTS does
not cover cathodic protection for pipeline systems, structure and equipment, for which
specific PTS already in place as following:
Refer to PTS 00.01.03 for PTS Requirements, General Definition Of Terms, Abbreviations &
Reading Guide.
None
No Abbreviations Description
3 CP Cathodic Protection
5 IF Insulating Flange
7 RP Recommended Practice
9 TA Technical Authority
This PTS 15.20.14 (April 2019) replaces PTS 15.12.01 (September 2018).
In this and the following sections the reference clauses of NACE SP0169 are amended or
supplemented. Existing clause is revised or new sections are added as mentioned. Clause that
are not mentioned in this PTS shall apply and remain valid.
“The provisions of this standard shall be applied under the responsible direction of competent
individuals. Such individuals must either be registered professional engineers, NACE
International certified Corrosion Specialists or Level 3 CP Technologist, or individuals qualified
by professional education and related practical experience. All of the above individuals shall
be able to demonstrate suitable experience in external corrosion control of underground or
submerged piping systems.”
2.2 NACE SP0169 - 2013; SECTION 3: DETERMINATION OF NEED FOR EXTERNAL CORROSION
CONTROL
“The need for CP for external corrosion protection of underground and submerged metallic
piping system shall be based on risk in term of safety, environmental and economic. Factors
recommended to be considered in the risk assessment is summarized in Table 1.
Where risk assessment indicates that CP system is not required for external corrosion
protection of a piping system, endorsement from relevant TA shall be obtained.”
“External coatings are commonly utilized in conjunction with CP. When specified, they should
be properly selected, and applied. Desirable characteristics of external coatings shall be
compatible to CP system are given in Paragraph 5.1”
“Joints, fittings, and tie-ins must be coated with materials compatible with the existing
coatings and service environments.”
2.5 NACE SP0169 - 2013; SECTION 6: CRITERIA AND OTHER CONSIDERATIONS FOR CATHODIC
PROTECTION
“On mill-scaled or uncoated existing steel piping, cathodic polarization greater than 100 mV
might be required. Use of mill-scaled or uncoated of piping with intention to be protected by
CP system only is strictly prohibited for new piping system.”
“When the potential is made too negative, detrimental effects can occur such as damage to
the piping’s coating, hydrogen embrittlement of susceptible steel or corrosion of amphoteric
materials. The most negative potential allowed with CP application, the overprotection
potential, should not exceed -1150 mV as measured with respect to a saturated
copper/copper sulphate (CSE) reference electrode.”
“Other maintenance and operating data including piping operating temperature range”
“CP system design shall consider all factors that potentially detrimental to CP performance
including presence of CP currents drain due to contact with foreign steel structure or missing
or failure of electrical isolation, current shielding by existing steel structure actual, poor
coating quality against theoretical coating quality, and presence of previously unidentified
electrical isolation.”
“Layout drawings shall be prepared for every sacrificial anode or impressed current CP
installation, showing the details and location of the components of the CP system with respect
to the protected structure(s) and to major physical landmarks. These drawings should include
right-of-way information.”
“All construction work on CP systems should be performed under the surveillance of trained
and qualified personnel to verify that the installation is in strict accordance with the drawings
and specifications. Persons who perform the measurement, testing, survey and inspection in
this standard for CP design data gathering and evaluation of CP system at least shall be
recognized by NACE as Level 1 CP Tester.”
2.8 NACE SP0169 - 2013; SECTION 10: OPERATION AND MAINTENANCE OF CP SYSTEMS
“When practicable and determined necessary by sound engineering practice, CIPS and Pipe
Coating Holiday Survey may be conducted at interval not exceeding five (5) years to:
a) assess the effectiveness of the CP system;
b) provide baseline operating data;
c) locate areas of inadequate protection levels;
d) locate areas of possible coating deterioration;
e) identify locations likely to be adversely affected by construction, stray currents, or
other environmental conditions; or
f) select areas to be monitored periodically.
Additional reasons for performing CIPS and Pipe Coating Holiday Survey are listed in NACE
SP0207. Guideline to evaluate and select suitable Pipe Coating Holiday Survey or alternative
method to CIPS is provided in NACE SP0502.”
“If effective CP criteria cannot be achieved after multiple adjustment to the CP system, more
extensive investigation and testing, such as CIPS or isolation checking, should be conducted
to determine the cause of the non-conformance”.
“All impressed current electrical systems including TRU, junction boxes and shunt, shall be
inspected and tested at intervals of two (2) months. Longer or shorter intervals for monitoring
might be appropriate based on previous performance record. Evidence of proper functioning
can be current output, normal power consumption, a signal indicating normal operation, or
satisfactory CP levels on the pipe. The maximum monitoring interval shall not exceed six (6)
months. Maintenance of impressed current electrical system shall be in accordance to PTS
13.02.01”.
“The effectiveness of isolating fittings, continuity bonds, and casing isolation should be
evaluated at intervals of two (2) months or during the external corrosion control surveys. This
can be accomplished by electrical measurements. Longer or shorter intervals for monitoring
might be appropriate based on previous performance record and component age. The
maximum monitoring interval shall not exceed one (1) year.”
“The test equipment used for obtaining each electrical value should be of an appropriate type.
Instruments and related equipment shall be maintained in good operating condition and
checked for accuracy.”
3.0 BIBLIOGRAPHY
INTERNATIONAL STANDARDS
Risk-based Inspection Methodology API RP 581 – 2016
Control of External Corrosion on Underground or Submerged NACE SP0169 – 2013
Metallic Piping Systems
Performing Close-Interval Potential Surveys and DC Surface Potential NACE SP0207 – 2007
Gradient Surveys on Buried or Submerged Metallic Pipelines
Pipeline External Corrosion Direct Assessment Methodology NACE SP0502 – 2010