Professional Documents
Culture Documents
TII
ED
4 th
Technical
Selection
Guide
www.koolair.com
Technical
selection
guide
1
summary 5 Grilles
41 Circular diffusers
61 Swirl diffusers
207 VAV/VAC
227 Acoustic
235 Air/Water
275 More…
2 3
Grilles
20-SH/21-SH (6) 31-1-F (32)
22-5 (16) 26-1(24)
21-SVC (10)
31-1-BANKSIDE (36)
21-SVR (10) 24-S1 (26)
27-R-FF (20)
21-DVC (12)
24-S2 (26)
20-45-H (14)
20-45-H-RFF (22)
KSG-3 (38)
20-45-HE (14)
1
swirl diffusers DF-RO-C and DFRE-GR-TR,
overpressure dampers 230-SP,
long-throw diffuser DF-47,
intumescent grilles LVV-40
and fire dampers SFR and SFC.
20-SH/21-SH Catalogue Series 20.1
General dimensions
H + 28 L + 28
H – 20 24 L – 20 24
6
33
H L
L= Opening Length
Screw Fixing, opening = (L – 5) x (H – 5)
H= Opening Height
Selection table
Single Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) Vk (m/s)
deflection 170 24 7 2.5 3.9
grilles
200 x 100 245 32 15 3.6 5.6
350 40 31 5.2 7.9
300 x 100 240 24 7 2.9 3.6
200 x 150 340 32 13 4.1 5.1
500 40 29 6.1 7.6
330 24 6 3.3 3.3
300 x 150 470 32 11 4.7 4.7
Product description Mounting 670 40 23 6.7 6.8
Single deflection grille, KOOLAIR, model 20-SH, With pressure clips. Mounting frame needed (-MM). 600 x 100 420 24 5 3.6 3.2
of dimensions LxH, for supplying air with horizontal Conceled fixing (-SFO). Mounting frame 400 x 150 600 32 10 5.2 4.5
blades, individually adjustable. needed (-MM). 300 x 200 870 40 22 7.5 6.6
It can incorporate volume control damper (-O) and With screws (-T). Without indication, the grille is 500 24 5 3.8 3.0
fixation accessory to be determined. provided with holes for screwing the mounting frame. 500 x 150 710 32 9 5.5 4.3
Finished in anodised aluminium or any RAL colour With plenum box made of galvanised steel sheet, 1030 40 19 7.9 6.2
upon request. side or top entry connection (-PE21/20). 600 x 150 580 24 4 4.1 2.9
300 x 300 840 32 9 5.9 4.2
1215 40 19 8.5 6.1
Other models 600 x 200 770 24 4 4.5 2.7
500 x 250 1110 32 8 6.5 4.0
20-SV. Single deflection aluminium grille with vertical
400 x 300 1600 40 16 9.4 5.7
blades.
1000 x 150 900 25 4 4.9 2.7
21-SH. Single deflection steel sheet grille LEGEND
600 x 250 1250 32 7 6.8 3.8
with horizontal blades. Q (m3/h): Air flow.
500 x 300 1830 40 15 9.9 5.5
21-SV. Single deflection steel sheet grille with vertical LwA [dB(A)]: Sound power level.
1260 24 3 5.5 2.4
blades. ∆Pt (Pa): Total pressure loss.
1100 x 200 1810 32 6 7.9 3.5
2610 40 13 11.4 5.1 X (m): Throw for a maximum velocity
of 0.25 m/s at the occupied zone
1200 x 250 1615 24 3 6.0 2.3
∆T = –10 ºC (cold), installed at 2.7 m
1000 x 300 2325 32 5 8.7 3.3
of height, with ceiling effect.
3360 40 11 12.5 4.8
Vk (m/s): Effective velocity.
The Selection Table shows a summary of dimensions. Other sizes available.
Consult the Sales Department.
6 7
20-DH/21-DH Catalogue Series 20.1
General dimensions
H + 28 L + 28
H – 20 24 L – 20 24
47
H L
L= Opening Length
Screw Fixing, opening = (L – 5) x (H – 5)
H= Opening Height
Selection table
Double Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) Vk (m/s)
deflection
200 x 100
160
220
24
32
8
16
2.7
3.7
4.5
6.2
grilles
300 x 100
310
220
40
24
31
7
5.2
3.0
8.8
4.2
200 x 150 310 32 14 4.3 5.9
430 40 26 5.9 8.1
310 24 6 3.5 3.9
300 x 150 435 32 12 4.9 5.5
Product description Mounting 600 40 23 6.8 7.6
Double deflection grille, KOOLAIR, model With pressure clips. Mounting frame needed (-MM). 600 x 100 390 24 5 3.8 3.7
20-DH, of dimensions LxH, for supplying air with Conceled fixing (-SFO). Mounting frame 400 x 150 540 32 10 5.3 5.1
horizontal and vertical blades, individually adjustable. needed (-MM). 300 x 200 760 40 21 7.4 7.2
It can incorporate volume control damper (-O) and With screws (-T). Without indication, the grille is 460 24 5 4.0 3.5
fixation accessory to be determined. provided with holes for screwing the mounting frame. 500 x 150 650 32 10 5.7 4.9
910 40 19 7.9 6.9
Finished in anodised aluminium or any RAL With plenum box made of galvanised steel sheet,
colour upon request. side or top entry connection (-PE21/20). 600 x 150 540 24 5 4.3 3.4
300 x 300 760 32 9 6.1 4.8
1050 40 17 8.4 6.6
Other models 600 x 200 720 24 4 4.8 3.2
500 x 250 1000 32 8 6.7 4.5
20-DV. Double deflection grille, first blades in vertical
400 x 300 1350 40 14 9.0 6.0
position, made in aluminium.
1000 x 150 800 24 4 4.9 3.0
21-DH. Double deflection grille, first blades in LEGEND
600 x 250 1120 32 7 6.9 4.2
horizontal position, made in steel sheet. Q (m3/h): Air flow.
500 x 300 1550 40 14 9.6 5.9
21-DV. Double deflection grille, first blades in vertical LwA [dB(A)]: Sound power level.
1150 24 3 5.7 2.8
position, made in steel sheet. ∆Pt (Pa): Total pressure loss.
1100 x 200 1625 32 6 8.0 3.9
2260 40 12 11.2 5.5 X (m): Throw for a maximum velocity
of 0.25 m/s at the occupied zone
1200 x 250 1510 24 3 6.4 2.7
∆T = –10 ºC (cold), installed at 2.7 m
1000 x 300 2080 32 5 8.8 3.7
of height, with ceiling effect.
2910 40 11 12.3 5.2
Vk (m/s): Effective velocity.
The Selection Table shows a summary of dimensions. Other sizes available.
Consult the Sales Department.
8 9
21-SVC/21-SVR Catalogue Series 20.1
Ø OF CIRCULAR DUCT
H mm
75 125 175 225
Selection table
Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) Vk (m/s)
deflection grille
525 x 75
260
370
24
32
11
21
4.5
6.3
3.6
5.0
for ducts
500
300
40
24
40
10
8.8
4.8
7.0
3.5
625 x 75 420 32 20 6.7 4.9
580 40 38 9.3 6.8
370 24 9 5.2 3.3
LEGEND
Du
10 11
21-DVC/21-DVR Catalogue Series 20.1
Ø OF CIRCULAR DUCT
H mm
75 125 175 225
Selection table
Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) Vk (m/s)
25 L – 20 25
1130 40 17 9.9 5.1
LwA [dB(A)]: Sound power level.
L + 30 L= Opening Length 870 24 4 5.6 2.5
∆Pt (Pa): Total pressure loss.
21-DVR H= Opening Height 825 x 225 1210 32 8 7.8 3.5
L–5 H–5 X (m): Throw for a maximum velocity
1680 40 15 10.8 4.8
of 0.25 m/s at the occupied zone
1040 24 4 6.0 2.4
∆T = –10 ºC (cold), installed at 2.7 m
1025 x 225 1450 32 7 8.3 3.3
43
12 13
20-45-H/21-45-H Cat. Series 20.2
General dimensions
H + 28 L + 28
H – 20 24 L – 20 24
6
33
20-45-H
H L
L= Opening Length
Screw Fixing, opening = (L – 5) x (H – 5)
H= Opening Height
20-45-HE
Selection table
Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Vk (m/s) Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Vk (m/s)
Return grille
120
80
40
24
22
6
4.6
2.4
1140
330
40
24
9
3
3.5
2.2
250 x 100 110 32 11 3.2 300 x 300 450 32 6 3.0
150 40 20 4.3 660 40 13 4.4
100 24 5 2.2 800 x 300 780 24 2 1.8
14 15
22-5 Catalogue Series 20.2
General dimensions
H + 28 L + 28
H – 20 24 L – 20 24
6
33
H L
L= Opening Length
Screw Fixing, opening = (L – 5) x (H – 5)
H= Opening Height
Egg crate
Selection table
grilles for
Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Vk (m/s)
return 200 x 200 320 24 13 2.9
400 x 100 430 32 24 3.8
580 40 42 5.1
250 x 250 450 24 11 2.6
300 x 200 610 32 19 3.5
Product description Mounting 400 x 150 820 40 35 4.6
Egg crate grille, KOOLAIR, model 22-5, With pressure clips. Mounting frame needed (-MM). 350 x 350 810 24 8 2.2
400 x 300 1090 32 14 2.9
of dimensions LxH, for returning air. Conceled fixing (-SFO). Mounting frame needed
600 x 200 1460 40 25 3.9
It can incorporate volume control damper (-O), (-MM).
450 x 450 1230 24 6 1.9
fixation accessory to be determined. With screws (-T). Without indication, the grille is
500 x 400 1650 32 11 2.6
Finished in anodised aluminium or any RAL colour provided with holes for screwing the mounting frame.
700 x 300 2210 40 19 3.5
upon request. With plenum box made of galvanised steel sheet,
600 x 600 1980 24 5 1.7
side or top entry connection (-PE21/20).
900 x 400 2650 32 8 2.3
Other models 1000 x 350 3550 40 15 3.0
700 x 700 2530 24 4 1.6
22-5-I. Egg crate grille, blades at 45º.
800 x 600 3390 32 7 2.1
22-5-SB. Dimensions 595x295 - 595x595,for 1000 x 500 4540 40 13 2.8
modular false ceiling. 1300 x 500 3130 24 3 1.5
1200 x 600 4190 32 6 2.0
800 x 800 5620 40 11 2.6
1600 x 500 3770 24 3 1.4
1350 x 600 5050 32 6 1.9 LEGEND
900 x 900 6770 40 10 2.5
Q (m3/h): Air flow.
1650 x 600 4450 24 3 1.3
LwA [dB(A)]: Sound power level.
1250 x 800 5970 32 5 1.8
∆Pt (Pa): Total pressure loss.
1000 x 1000 8000 40 9 2.4
Vk (m/s): Effective velocity.
16 17
25-H Catalogue Series 20.2
Selection table
Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Vk (m/s)
External grilles
400 x 100 77 24 6 2,0
200 x 200 107 32 12 2,8
or return air
148 40 23
500 x 100 94 24 6 1,9
3,8
can be installed indoors, smaller models can also be 600 x 150 200 24 5 1,7
With pressure clips. Mounting frame needed (-MM).
installed outdoors. It can incorporate volume control With screws (-T). Without indication, the grille is 450 x 200 270 32 9 2,3
damper (-O) and provided with holes for screwing the mounting frame. 370 40 16 3,2
anti-insect mesh (-MI). With plenum box made of galvanised steel sheet,
Finished in anodised aluminium or any RAL colour 600 x 200 275 24 4 1,6
side or top entry connection (-PE21/20).
upon request. 400 x 300 380 32 8 2,2
520 40 15 3,0
General dimensions
800 x 200 360 24 4 1,6
400 x 400 495 32 7 2,1
6 L + 28
685 40 14 3,0
1000 x 300 680 24 3 1,4
750 x 400 930 32 6 1,9
24
1290 40 11 2,6
L= Opening Length
900 x 400 850 24 3 1,3
600 x 600 1160 32 5 1,8
H + 28
1650 40 11 2,5
Q (m3/h): Air flow.
Screw Fixing, opening = (L – 5) x (H – 5) 1000 x 600 1340 24 2 1,2
LwA [dB(A)]: Sound power level.
1840 32 5 1,7
∆Pt (Pa): Total pressure loss.
2540 40 9 2,4
Vk (m/s): Effective velocity.
47
The Selection Table shows a summary of dimensions. Other sizes available.
Consult the Sales Department.
18 19
27-R-FF/22-R-FF General dimensions
CxD
Ø249
Ø249
420
27-R-FF
90o
A
Possibility of manufacturing plenum with a lateral or top connection to suit available height in false ceiling and
flow rate per grille.
Dimensions
22-R-FF
application
600 x 600
675 x 675
595
670
595
670
554
629
554
629
Unit mm
LEGEND
Q (m3/h): Air flow.
Lw-dB(A): Sound power level (grille without plenum).
Pst (Pa): Pressure drop (grille without plenum and with G2 efficiency filter).
20 21
20-45-H-RFF/25-H-RFF General dimensions
L H
57
24
L + 28 24
20-45-H-RFF
H + 28
Filterholder
H
25-H-RFF
grilles
57
24
L + 28 24
650 25 3 450 25 5
600 x 300 950 35 7 600 x 300 700 35 11
1400 45 15 1000 45 22
1250 25 2 880 25 4
600 x 600 1800 35 6 600 x 600 1300 35 8
2600 45 12 2000 45 19
Data does not include filter. Data does not include filter.
LEGEND
Q (m3/h): Air flow.
Lw-dB(A): Sound power level.
Pst (Pa): Pressure drop. Values with plenum.
22 23
S26 Catalogue Series 20.1
General dimensions
6
L + 28
24
26-1
L–20 x H–20
H + 28
LxH
33
L= Opening Length
H= Opening Height
Screw Fixing, opening = (L – 5) x (H – 5) S-26-1
26-4
Selection table
Curved-blade supply grilles Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
100 24 10 2.5
150 x 150 120 32 14 3.6
155 40 23 5.2
160 24 8 2.8
200 x 200 180 32 10 4.0
Product description Mounting 240 40 18 5.8
220 24 6 3.5
The curved-blade grilles, KOOLAIR 26 model, of LxH With pressure clips. Mounting frame needed (-MM).
250 x 250 280 32 10 5.0
dimensions specially designed to provide any type of Conceled fixing (-SFO). Mounting frame
350 40 16 7.3
discharge: from absolute horizontal to total verticality, needed (-MM).
295 24 5 3.2
whether ceiling- or wall-mounted. Supplied in 1, 2, 3 With screws (-T). Without indication, the grille is
300 x 300 350 32 8 4.6
and 4 airflow directions. Can include volume control provided with holes for screwing the mounting frame. 470 40 14 6.6
damper (-O). Natural anodized aluminum finish With plenum box made of galvanised steel sheet,
470 24 4 3.8
(uncoated). side or top entry connection (-PE21/20). 400 x 400 550 32 6 5.4
740 40 11 7.8
Other models 525 24 4 4.0
600 x 300 700 32 7 5.8
26-1. Curved-blade grille, 1-way air discharge. LEGEND
830 40 10 8.3
26-2. Curved-blade grille, 2-way air discharge. Q (m3/h): Air flow.
680 24 4 4.7
26-3. Curved-blade grille, 3-way air discharge. LwA [dB(A)]: Sound power level.
500 x 500 800 32 5 6.8
26-4. Curved-blade grille, 4-way air discharge. ∆Pt (Pa): Total pressure loss.
1.050 40 9 9.7
Y (m): Throw for a maximum velocity of
890 24 3 4.4
0.25 m/s at the occupied zone DT=-10ºC
600 x 600 1.050 32 4 6.4
(cold), installed at 3 m of height, with
1.400 40 8 9.2
ceiling effect.
The Selection Table shows a summary of dimensions. Other sizes available.
Consult the Sales Department.
24-S1/24-S2 Catalogue Series 20.2
General dimensions
6 50 Max.
L + 28
30 Min.
24
24
H + 36 x L + 36
H - 12 x L - 12
H + 28
24-S1
24
L= Nominal Length (Opening) Screw Fixing, opening = (L – 5) x (H – 5)
H= Nominal Heigth (Opening) 24-S1 (with counterframe)
24-S2 6 50 Max.
30 Min. L + 28
24
Door grilles
H-5xL-5
H + 28
Product description Recommended transfer velocity for selection is from
0,75 to 1,25 m/s L= Nominal Length (Opening) Screw Fixing, opening = (L – 5) x (H – 5)
Grille mounted in door for air transfer with For grille type 24-S1 (with counterframe) installation H= Nominal Heigth (Opening) 24-S2 (without counterframe)
fixed blades in V, KOOLAIR, model 24-S1 with is recommended in walls with upto 50 mm thickness.
counterframe, of dimensions LxH. Finished in anodised aluminium in its natural colour.
This type of grille is always delivered with a mounting Selection table 24-S1/24-S2
frame, provided with holes for screwing (-T).
The arrangement of the S-24 blades in inverted “V”, Other models Dimension Q (m3/h) LwA [dB(A)] ΔPt (Pa) Vk (m/s) Dimension Q (m3/h) LwA [dB(A)] ΔPt (Pa) Vk (m/s)
impedes vision through it when applied in doors, 300 x 100 45 20 3 0,8 600 x 200 220 20 3 0,8
24-S2. Grille mounted in door for air transfer with
partition,walls. 200 x 150 60 26 6 1,1 400 x 300 255 26 5 1,0
fixed blades in V without counterframe.
75 32 9 1,3 325 32 9 1,3
400 x 100 60 20 3 0,8 600 x 250 250 20 3 0,8
200 x 200 75 26 5 1,0 500 x 300 315 26 5 1,0
100 32 9 1,3 400 32 8 1,3
500 x 150 115 20 3 0,8 600 x 350 350 20 3 0,8
300 x 250 145 26 5 1,0 500 x 400 450 26 5 1,0
185 32 9 1,3 570 32 8 1,3
400 x 200 130 20 3 0,8 700 x 400 475 20 3 0,8
165 26 5 1,0 610 26 5 1,0
210 32 8 1,3 775 32 8 1,3
500 x 200 165 20 3 0,8 LEGEND
400 x 250 210 26 5 1,0 Q (m3/h): Air flow.
265 32 8 1,3
Lw-dB(A): Sound power level.
The Selection Table shows a summary of dimensions. Pst (Pa): Pressure drop.
Other sizes available. Consult the Sales Department. Vk (m/s): Effective velocity.
26 27
31-1 Catalogue Series 30
General dimensions
H + 28 L + 28
H – 20 24 L – 20 24
6
33
H L
L= Opening Length
H= Opening Height
Screw Fixing, opening = (L – 5) x (H – 5) 31-1
H+8 L+8
H – 14 11 L – 14 11
6
33
H L
L= Opening Length
Linear bar
H= Opening Height
31-15-11
Linear grille for supplying or returning air, KOOLAIR, 31-15. Linear bar grille with fixed blades (deflection 605 24 8 4,3 3,4
15º). 1000 x 100 825 32 14 5,9 4,6
model 31-1 of dimensions LxH, with horizontal
31-1/15-G. Linear bar grille with fixed blades 1130 40 27 8,1 6,6
fixed blades at 0º. It can incorporate volume
(deflection 0º or 15º), secondary deflection with 775 24 7 4,8 3,2
control damper (-O) and fixation accessory to be vertical blades. 1000 x 125 1060 32 13 6,5 4,4
determined. Finished in anodised aluminium or any 31-1/15-20. Linear bar grille with fixed blades 1445 40 24 8,9 5,9
RAL colour upon request. (deflection 0º or 15º), with fine frame of 20x1,5 mm.
900 24 7 5,0 3,1
31-1/15-G-20. Linear bar grille with fixed blades
1000 x 150 1230 32 12 6,9 4,2
Note: Possible to form continuous lines (Maximum (deflection 0º or 15º), secondary deflection with
vertical blades and fine frame of 20x1,5 mm. 1685 40 23 9,4 5,8
length per section 2000 mm).
31-1/15-E-PM. Linear bar grille with fixed blades 1145 24 6 5,6 2,9
LEGEND
(deflection 0º or 15º), with narrow frame of 8,7 mm 1000 x 200 1565 32 11 7,6 4,0
Q (m3/h): Air flow.
Mounting and mounting bridge. 2135 40 21 10,0 5,5
LwA [dB(A)]: Sound power level.
31-1/15-SB. Linear bar grill with fixed blades 1440 24 5 6,1 2,8
With pressure clips. Mounting frame needed (-MM). (deflection 0º or 15º), without frame. ∆Pt (Pa): Total pressure loss.
1000 x 250 1970 32 10 8,3 3,8
With fixing straps for filter (-FL). 31-1/15-11. Linear bar grille with fixed blades X (m): Throw for a maximum velocity
2690 40 19 11,4 5,2
With screws (-T). The grille is provided with holes for (deflection 0º or 15º), with frame of 11x6 mm. of 0.25 m/s at the occupied zone
31-1/15-6. Linear bar grille with fixed blades 1675 24 5 6,5 2,7
screwing the mounting frame. ∆T = –10 ºC (cold), installed at 2.7 m
(deflection 0º or 15º), with frame of 6,6 mm. 1000 x 300 2290 32 9 8,8 3,7
of height, with ceiling effect.
With plenum box made of galvanised steel sheet, with 3130 40 18 12,1 5,1
31-1/15 SPORT. The ball protection linear bar Vk (m/s): Effective velocity.
side or top spigot connection (-PE21/20). grilles are used for supply and extract, in gym, sport The Selection Table shows a summary of dimensions. Other sizes available.
Conceled fixing (-SFO). Mounting frame needed centres and multi-purpose halls. Consult the Sales Department.
(-MM).
28 29
31-HI Catalogue Series 30
General dimensions
H + 12 L + 12
16 H – 20 L – 20 16
5
46
H L
H-16 L-16
L= Opening Length
H= Opening Height
Screw Fixing, opening = (L – 16) x (H – 16)
Selection table
High-induction Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) Vk (m/s)
linear bar
325 x 125
300
400
24
32
9
15
3.7
4.9
3.6
4.8
grille
530
360
40
24
27
7
6.5
3.9
6.4
3.3
425 x 125 490 32 13 5.3 4.5
650 40 24 7.0 6
430 24 7 4.2 3.2
525 x 125 600 32 13 5.8 4.5
Product description Other models 750 40 21 7.2 5.6
High induction linear grille for supplying or returning 31-HI-G. Linear bar grille with fixed blades 490 24 6 4.3 3.1
air, KOOLAIR, model 31-HI of dimensions LxH, (deflection 5º or 15º), with secondary deflection. 625 x 125 710 32 13 6.3 4.4
with horizontal fixed blades at 5º or 15º deflection 850 40 19 7.5 5.3
(reversible core). It can incorporate volume 640 24 6 4.9 3.3
control damper (-O) and fixation accessory to be
Mounting 425 x 225 850 32 10 6.5 4.3
determined. With pressure clips. Mounting frame needed (-MM). 1100 40 17 8.4 5.6
Finished in anodised aluminium or any RAL With screws (-T). The grille is provided with holes for 750 24 5 5.2 3.1
colour upon request. screwing the mounting frame. 525 x 225 1000 32 9 6.9 4.1
1300 40 15 8.9 5.4
With plenum box made of galvanised steel sheet,
with side or top spigot connection (-PE21/20). 850 24 5 5.4 2.9
625 x 225 1150 32 8 7.3 4.0
PM. With mounting bridge.
1500 40 14 9.5 5.2
1150 24 5 6.3 3.0 LEGEND
825 x 225 1500 32 8 8.2 3.9
Q (m3/h): Air flow.
2000 40 15 11.0 5.3
LwA [dB(A)]: Sound power level.
1200 24 4 6.3 2.9
∆Pt (Pa): Total pressure loss.
625 x 325 1600 32 8 8.4 3.8
X (m): Throw for a maximum velocity
2150 40 14 11.3 5.2
of 0.25 m/s at the occupied zone
1500 24 4 6.9 2.7 ∆T = 0 ºC, installed at 3 m of height,
825 x 325 2000 32 7 9.1 3.6
with ceiling effect.
2650 40 12 12.1 4.8
Vk (m/s): Effective velocity.
The Selection Table shows a summary of dimensions. Other sizes available.
Consult the Sales Department.
30 31
31-1-F Catalogue Series 30
General dimensions
H + 27 L + 27
H + 25 L + 25
21
53
H – 20 L – 20
H L
L= Opening Length
H= Opening Height
Linear floor
grilles Selection table (Flow rate per linear metre of grille)
Linear floor grille, KOOLAIR, model 31-1-F, of 31-15-F. Linear floor grille (deflection 15º). 540 24 5 4.4 3
1000 x 100 730 32 10 6.1 4.1
dimensions LxH, for supplying or returning air with 31-1/15-F-G. Linear floor grille (deflection 0º or 15º),
1000 40 18 8.3 5.6
fixed blades (deflection 0º). with secondary blades in vertical position.
650 24 5 4.8 2.9
It can incorporate volume control damper (-O). 31-1/15-SB. Linear floor grille (deflection 0º or 15º),
1000 x 125 890 32 9 6.5 3.9
Finished in anodised aluminium or any RAL colour without frame.
1210 40 17 9.0 5.4
upon request. 31-1/15-NM. Linear floor grille (deflection 0º or 15º),
790 24 4 5.2 2.8
with flat frame 28 x 1,5.
1000 x 150 1080 32 8 7.1 3.8
Mounting 1480 40 15 9.7 5.1
1040 24 4 5.8 2.6
Side or Top entry plenum box (-PFL/PFS) in Note: Possible to form continuous lines (Maximum 1000 x 200 1420 32 7 7.9 3.6 LEGEND
galvanised steel sheet. length per section 2000 mm). 1940 40 14 10.8 4.9
Q (m3/h): Air flow.
1260 24 4 6.2 2.5
LwA [dB(A)]: Sound power level.
1000 x 250 1720 32 7 8.5 3.4
∆Pt (Pa): Total pressure loss.
2360 40 13 11.7 4.8
Y (m): Throw for a maximum velocity
1500 24 3 6.7 2.4 of 0.25 m/s at the occupied zone
1000 x 300 2050 32 6 9.1 3.3
∆T = –10ºC (cold).
2800 40 12 12.5 4.5
Vk (m/s): Effective velocity.
The Selection Table shows a summary of dimensions. Other sizes available.
Consult the Sales Department.
32 33
31-1-FS Catalogue Series 30
General dimensions
B A
H
53
Hmin = 21 mm
Selection table
Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Y (m) Vk (m/s) LEGEND
Q (m3/h): Air flow.
810 20 3 2.8 2.3
Grilles for
600 x 300 1000
1300
26
32
5
8
3.5
4.6
2.8
3.6
LwA [dB(A)]: Sound power level.
∆Pt (Pa): Total pressure loss.
raised access
Y (m): Throw for a maximum velocity of
1450 20 2 3.6 2.1
0.25 m/s at the occupied zone
600 x 600 1800 26 4 4.5 2.6
floor
∆T=-10ºC (cold).
2250 32 6 5.6 3.2
Vk (m/s): Effective velocity.
Product description
The KOOLAIR 31-1-FS linear grilles for raised
access floors of LxH dimensions are especially
designed for floor air supply or return. Fixed
horizontal vanes of sturdy profile (0º deflection).
Natural unanodized aluminum finish or RAL colour
upon request. Can include volume control dampers
(-O).
The units have been tested and meet EN13264:2001
requirements for heavy and extra-heavy structural
classes.
The supported load is 85 kg/cm2, and the evenly
distributed load is 2500 kg/m2.
Other models
31-15-FS. Linear grille for raised access floor
with fixed horizontal vanes (15º deflection)
of dimensions 599x599 or 599x299.
31-1/15-FS-G. Linear grille for raised access floor
(deflection 0º or 15º) with secondary blades in
vertical position.
34 35
31-1-BANKSIDE General dimensions
H - 35
15
20 HxL 20
ØD
31-1 BANKSIDE-SC
ØD + 150
20
25
15
20 HxL 20
31-1 BANKSIDE H
L x H (NOMINAL - 1)
Linear supply
or return grille
Selection table (Flow rate per linear metre of grille)
KSG-1 KSG-3
ØD ØD
B
E
A
A
E
B
KSG-1
C C
C C
Model A B ØD E
(SIDE SPIGOT) (TOP SPIGOT)
Safety grilles
350
400
357
487
430
480
517
567
298
348
390
440
Unit mm (KSG-1 model dimensions)
38 39
Circular
diffusers
NEW
NEW
2
67 Lombard Street
(London – United Kingdom)
Diffusers KCD-Q with plenum
and Linear Diffuser LK-70 with plenum.
43-SF Catalogue Series 40.1
General dimensions
ØA
82
52
6
ØB
ØC 43-SF-PM
Circular Diffuser Ø A Ø B ØC
diffuser with
160
200
159
199
213
264
247
287
multiple fixed
250
315
249
314
315
366
337
402
cones
355
400
354
399
417
468
442
487
Unit mm
42 43
44/45-SF Catalogue Series 40.1
General dimensions
Diffuser Ø A Ø B Ø C R K
R
315 314 566 606 176 142
355 354 664 714 200 167
K
400 399 754 814 200 168
450 449 850 920 215 186
B 500 499 985 1055 230 208
C
630 629 1108 1188 245 224
Circular 44-SF-PM
Unit mm
diffuser with
Selection table
adjustable
cones Dimension
Ø nominal
Q (m3/h)
90
LwA [dB(A)]
24
∆Pt (Pa)
14
X (m)
0.8
Vk (m/s)
4.9
4 100 110 32 24 1.0 6.3
150 40 38 1.3 8.0
220 24 15 1.5 3.4
6 160 280 32 25 1.8 4.3
Product description Other models 350 40 39 2.3 5.4
45-SF. Circular diffuser with removable core, 330 24 8 2.0 2.8
Circular diffuser with core adjustable by rotation
adjustable in two fixed positions. 8 200 440 32 14 2.6 3.7
KOOLAIR, model 44-SF,
44-SF-Q. Circular diffuser with adjustable core by 570 40 24 3.4 4.8
size _ mm (neck’s connection diameter). It can rotation integrated in a plate of 595x595, to be 510 24 11 1.8 3.4
incorporate volume control damper installed in a modular false ceiling (till Ø315). 10 250 660 32 19 2.4 4.4
(-49ML / -49-MO) and mounting accessories upon 45-SF-Q. Circular diffuser with removable core 870 40 32 3.1 5.7
request. Finished in anodised aluminium or any RAL integrated in a plate of 595x595, to be installed in a 820 24 11 2.3 3.7
colour upon request. modular false ceiling (till Ø315). 12 315 1050 32 19 3.0 4.8
Recommended installation height between 1350 40 31 3.9 6.1
2.5 and 5 m. 930 24 10 2.5 3.3
14 355 1230 32 17 3.4 4.4
1630 40 29 4.4 5.8
Mounting PM SM PMC 1120 24 7 2.3 3.5
PM. With mounting bridge for sheet ducts. 16 400 1430 32 12 3.0 4.4
1830 40 19 3.8 5.7
PMC. With mounting bridge for circular sheet ducts.
49CML. Mounting neck with flap damper for diffuser 1260 24 7 2.5 3.4 LEGEND
18 450 1610 32 11 3.2 4.3 Q (m3/h): Air flow.
44-SF. 49-MO 44-SF 49-ML / 45-SF 49-MM
2060 40 19 4.0 5.6
49CMK. Mounting neck with flap damper for diffuser LwA [dB(A)]: Sound power level.
1530 24 7 2.7 3.3 ∆Pt (Pa): Total pressure loss.
45-SF. 21 500 1960 32 11 3.4 4.2 X (m): Throw for a maximum velocity
PCFS. Top connection circular plenum in galvanized 2500 40 18 4.4 5.4
of 0.25 m/s at the occupied zone
steel sheet. (-A. internally insulated). 2340 24 6 3.2 3.1 ∆T = –10 ºC (cold), installed at a height
PCFL. Lateral connection circular plenum in 24 630 2990 32 10 4.1 4.0
of 3 m, with ceiling effect.
galvanized steel sheet. (-A. internally insulated). 44-SF 49-CML / 45-SF 49-CMK CML 3820 40 16 5.3 5.1
Vk (m/s): Effective velocity.
44 45
44-SF-TR Catalogue Diffuser 44-SF-TR
General dimensions
ØA
Diffuser Ø A Ø B Ø C E F R
R
200 199 385 415 55 66,5 216
E
250 249 468 498 55 68 222
315 314 566 606 60 82 238
F
355 354 664 714 60 106 272
ØB
ØC Unit mm
44-SF-TR-PM
circular
160
280
350
450
32
40
48
25
39
63
1.8
2.3
2.9
4.3
5.4
6.9
diffuser
200
440
570
32
40
14
24
2.6
3.4
3.7
4.8
740 48 48 4.2 4.4
660 32 19 2.4 4.4
250 870 40 32 3.1 5.7
1130 48 55 4.1 7.5
Product description Mounting 1060 32 19 3.0 4.8
Thermo-adjustable circular diffuser,height of central PM. Mounting bridge for sheet ducts. 315 1360 40 31 3.9 6.1
1740 48 50 4.9 7.8
core regulated by a thermal element KOOLAIR, PMC. Mounting bridge for circular sheet ducts.
1230 32 17 3.4 4.4
model 44-SF-TR, size _ (neck’s connection 49CML. Mounting neck with flap damper.
355 1630 40 29 4.4 5.8
diameter). PCFS. Top connection circular plenum in galvanized 2150 48 51 5.9 7.7
Recommended installation height between steel sheet. (-A. internally insulated)
3.5 and 7m. PCFL. Lateral connection circular plenum in
It can incorporate volume control damper (-49MM) galvanized steel sheet. (-A. internally insulated)
Selection table (Vertical discharge)
and mounting accessories upon request.
Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Ymax (m) Vk (m/s)
Finished in anodised aluminium or any RAL colour
240 32 22 3.24 5.2
upon request.
160 320 40 39 4.32 7.0
420 48 66 5.66 9.1
PM SM
Other models 301 32 15 2.33 3.4
LEGEND
200 420 40 28 3.19 4.7
44-SF-TR-Q. Circular diffuser thermo-adjustable, 580 48 52 4.41 6.5 Q (m3/h): Air flow.
integrated in a plate of 595x595, to be installed in a 540 32 18 3.14 4.3 LwA [dB(A)]: Sound power level.
modular false ceiling (up to size Ø315). 49-ML + NECK 250 720 40 31 4.21 5.7 ∆Pt (Pa): Total pressure loss.
670 48 56 5.64 7.6 X (m): Throw for a maximum velocity
870 32 18 3.64 4.8 of 0.25 m/s at the occupied zone
315 1140 40 30 4.78 6.3 ∆T = –10 ºC (cold), installed at a height
1500 48 52 6.28 8.3 of 3 m, with ceiling effect.
900 32 16 3.26 4.1 Vk (m/s): Effective velocity.
355 1300 40 27 4.28 5.4 Ymax (m): Maximum vertical penetration
49-CML CML 1700 48 47 5.60 7.0 at ∆T = +10 ºC (heating).
46 47
40.4/40.5-SF Catalogue Series 40.1
General dimensions
Diffuser Ø A Ø B Ø C R K
R
355 354 545 624 158 133,5
K
400 399 614 704 198 171,5
450 449 689 788 - 187,5
500 499 764 872 - 200
B
630 629 955 1063 - 222
40-4-SF-PM 710 709 1070 1180 - 217
800 799 1200 1323 - 248
900 899 1350 1470 - 281
Circular Unit mm
cones
4 100
90
120
24
32
13
24
1.3
1.7
3.5
4.8
170 40 44 2.4 6.6
150 24 7 1.7 4.0
6 160 200 32 13 2.3 5.4
270 40 24 3.2 7.3
Product description 49CML. Mounting neck with flap damper for
diff. 40.4-SF (up to size Ø400). 350 24 14 3.0 5.2
Circular cones diffuser (2 rings) adjustable by 49CMK. Mounting neck with flap damper for 8 200 460 32 25 4.0 6.9
rotation, KOOLAIR, model 40.4-SF, size _ mm diff. 40.5-SF (up to size Ø400). 620 40 44 5.4 9.2
(neck’s connection diameter). PCFS. Top connection circular plenum in galvanized
560 24 15 3.9 5.4
It can incorporate volume control damper (-49ML steel sheet. (-A. internally insulated)
/ -49MO) and mounting ac- cessories upon PCFL. Lateral connection circular plenum in 10 250 740 32 25 5.1 7.1
request. galvanized steel sheet. (-A. internally insulated) 970 40 44 6.8 9.3
Finished in anodised aluminium or any RAL colour 810 24 12 4.5 4.9
upon request. Recommended installation height 12 315 1050 32 20 5.8 6.4
between 2.5 and 5 m.
1370 40 35 7.6 8.3
1070 24 12 5.1 4.8
Other models 14 355 1380 32 21 6.6 6.2
40.5-SF. Circular diffuser with removable core, 1780 40 34 8.5 8.0
adjustable in two fixed positions (up to
1300 24 12 5.7 4.9
size Ø630). PM SM PMC
40.4-SF-Q. Circular diffuser with adjustable core 16 400 1660 32 20 7.2 6.3
by rotation integrated in a plate of 595x595, 2120 40 33 9.2 8.0
to be installed in a modular false ceiling (up to 1540 24 12 6.2 5.0 LEGEND
size Ø355). 18 450 1940 32 19 7.9 6.4
40.5-SF-Q. Circular diffuser with removable core 49-MO 40.4-SF 49-ML / 40.5-SF 49-MM
2460 40 31 10.0 8.1
Q (m3/h): Air flow.
integrated in a plate of 595x595, to be installed in LwA [dB(A)]: Sound power level.
a modular false ceiling (up to size Ø355). 1780 24 12 6.8 5.2
∆Pt (Pa): Total pressure loss.
21 500 2230 32 19 8.6 6.5
X (m): Throw for a maximum velocity
Mounting 2800 40 30 10.7 8.2
of 0.25 m/s at the occupied zone
2570 24 12 8.4 5.5
PM. Mounting bridge for sheet ducts. ∆T = –10 ºC (cold), installed at a height
24 630 3150 32 18 10.4 6.8
PMC. Mounting bridge for circular sheet ducts. of 3 m, with ceiling effect.
40.4-SF 49-CML / 40.5-SF 49-CMM CML 3890 40 28 12.8 8.3
Vk (m/s): Effective velocity.
48 49
DAI Catalogue DAI
General dimensions
ØB
ØA
50 - 65
D
6
20
ØC
DAI+SMAI
High-induction
circular Diffuser A B C D
diffuser
160 159 358 418 133
200 199 428 486 141
250 249 520 579 158
315 314 567 625 153
355 354 637 696 164
Unit mm
Product description Mounting
High-induction circular diffuser, for mixing primary SMAI. High-induction mounting system, with volume
air and inducted ambient air. KOOLAIR, model DAI, control damper.
size _ mm (neck’s connection diameter). Made in 49SMAI. Mounting neck with volume control
aluminium. Finished in any RAL colour upon request. damper.
Recommended installation height between 2.5 PCFS. Top connection circular plenum in galvanized
and 3 m. steel sheet. (-A. internally insulated).
PCFL. Lateral connection circular plenum in
Selection table
galvanized steel sheet. (-A. internally insulated).
Other models Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
DAI-Q. Circular high induction diffuser integrated in 140 24 10 0.9
a plate of 595x595, to be installed in a modular false 160 190 32 18 1.2
ceiling (up to size 315). 240 40 28 1.6
250 24 12 1.4
200 330 32 21 1.8
Primary air temperature 12ºC 420 40 34 2.3
Induction rate: 71% 400 24 13 1.9
SM 49-MM 250 510 32 21 2.5
LEGEND
660 40 35 3.2
Q (m3/h): Air flow.
590 24 12 2.5
LwA [dB(A)]: Sound power level.
315 760 32 20 3.3
∆Pt (Pa): Total pressure loss.
970 40 22 4.0
X (m): Throw for a maximum velocity
Air supplied into 700 24 11 2.9
of 0.25 m/s at the occupied zone
the room 17ºC 355 900 32 19 3.7
Air inducted 24ºC 49-SMAI SMAI ∆T = –10 ºC (cold), installed at a height
1150 40 30 4.7
of 3 m.
50 51
DCL Catalogue Diffuser DCL
General dimensions
A Opening Ø A Ø B Ø C K
125 124 252 272 90
50 - 65
160 159 286 316 90
200 199 385 415 121
250 249 468 498 123
315 314 566 606 142
K
Unit mm
B
C
DCL+CML
135 24 11 0,5
125 180 32 18 0,7
Circular
230 40 30 0,9
160 24 11 0,6
diffuser
160 230
300
32
40
20
36
0,9
1,2
300 24 15 1,0
200 390 32 23 1,3
515 40 41 1,7
480 24 14 1,4
Product description Other models 250 600 32 24 1,7
800 40 42 2,3
Circular diffuser, KOOLAIR, model DCL, size _ mm DCL-Q. Circular diffuser integrated in a plate of
720 24 15 1,8
(neck’s connection diameter). It can incorporate 595x595, to be installed in a modular false ceiling
315 860 32 23 2,2
volume control damper and mounting neck. (till size Ø 315).
1150 40 40 2,9
Finished in any RAL colour upon request. DCL-TR. Thermo-adjustable circular diffuser.
Recommended installation height between DCL-TR-Q. Thermo-adjustable circular diffuser
2.5 and 5 m. integrated in a plate of 595x595, to be installed in a Selection table (Vertical discharge *)
modular false ceiling (till size Ø 315).
Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Ymax (m)
Mounting 140 32 24 3,3
SM. Mounting system. 125 185 40 41 4,3
240 48 70 5,6
49CML. Mounting neck with volume control damper.
PCFS. Top connection circular plenum in galvanized DCL-TR 49-ML + NECK 215 32 28 3,5
160 280 40 48 4,5 LEGEND
steel sheet. (-A. internally insulated).
365 48 82 5,9
PCFL. Lateral connection circular plenum in Q (m3/h): Air flow.
265 32 17 2,4 LwA [dB(A)]: Sound power level.
galvanized steel sheet. (-A. internally insulated).
200 360 40 31 3,2 ∆Pt (Pa): Total pressure loss.
DCL 49-ML SM
495 48 58 4,4
X (m): Throw for a maximum velocity
470 32 21 3,3 of 0.25 m/s at the occupied zone
250 625 40 37 4,3 ∆T = –10 ºC (cold), installed at a height
840 48 67 5,8 of 3 m.
760 32 21 3,8 Ymax (m): Maximum vertical penetration
315 1000 40 37 5,0 at ∆T = +10 ºC (heating).
49-CML CML
1300 48 62 6,5
* Apply vertical discharge outlets for ceiling heights > 3 m or with exposed installations.
52 53
DCLT General dimensions
DCLT
ØA
SUPPLEMENTARY
PROFILE FOR
12.5 mm CEILING
12,5
15
ØC
40 ØB 40
15
720 24 15 1,8
_ mm (connection Ø), for installation in suspended
315 860 32 23 2,2
drywall ceilings.
1150 40 40 2,9
40
Characterised by the lack of profile on show.
Complete with movable central core to discharge air
Selection table (Vertical discharge *) 40
12,5
horizontally and vertically.
Option to include a regulating damper and/or plenum
Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Ymax (m)
with lateral/top connection.
Painted finish in RAL colour of choice. 140 32 24 3,3
125 185 40 41 4,3
Recommended installation height between 2.5 and SUPPLEMENTARY PROFILE FOR
240 48 70 5,6 12.5 mm CEILING
5 m.
215 32 28 3,5
160 280 40 48 4,5
Mounting DCLT-TR 49-ML + NECK 365 48 82 5,9
LEGEND
265 32 17 2,4
49ML. Regulating damper. Q (m3/h): Air flow.
200 360 40 31 3,2
PCFS. Top connection circular plenum in galvanized 495 48 58 4,4 LwA [dB(A)]: Sound power level.
steel sheet. (-A. internally insulated). ∆Pt (Pa): Total pressure loss.
470 32 21 3,3
PCFL. Lateral connection circular plenum in 250 625 40 37 4,3 X (m): Throw for a maximum velocity
galvanized steel sheet. (-A. internally insulated). 840 48 67 5,8 of 0.25 m/s at the occupied zone
∆T = –10 ºC (cold), installed at a height
DCLT 49-ML 760 32 21 3,8
of 3 m.
315 1000 40 37 5,0
Ymax (m): Maximum vertical penetration
1300 48 62 6,5
at ∆T = +10 ºC (heating).
* Apply vertical discharge for ceiling heights > 3 m or with exposed installations.
GPD Catalogue Extraction Valves
General dimensions GPD Selection table
48 Dimension Q (m3/h) LwA [dB(A)] ΔPt (Pa)
45 20 18
80 60 25 28
70 30 43
65 20 36
Ø HOLE
100 75 25 49
ØB
ØA
90 30 68
110 20 27
125 135 25 38
160 30 55
120 20 25
150 145 25 37
GPD 160 30 50
Model Ø A Ø B Ø Hole
125 20 26
GPD-80 115 62 85 160 150 25 37
GPD-100 138 75 105 170 30 52
GPD-125 164 100 130
GPD-150 202 120 155 215 20 31
GPD-160 211 130 165 200 250 25 45
GPD-200 248 158 205 290 30 58
Unit mm
Data for 5 mm core adjustment.
Ø HOLE
45 20 18
Exhaust/supply outlets
ØB
ØA
100 55 25 28
65 30 38
80 20 21
125 100 25 29
115 30 42
105 20 28
Product description Model Ø A Ø B Ø Hole
150 135
160
25
30
48
75
GPDI-80 115 76 85 110 20 27
Exhaust/supply outlets, KOOLAIR, GPD model - 160 140 25 37
GPDI-100 138 92 105
for use in confined spaces (bathrooms, lavatories, GPDI-125 164 111 130 170 30 50
GPDI-150 202 135 155 200 20 29
kitchens, etc). GPDI-160 211 147 165 200 270 25 38
Standard finish in RAL 9010. GPDI-200 248 194 205 320 30 55
Unit mm Data for 6 mm core adjustment.
8
50 25 19
GPD-Auto. Circular self-adjusting plastic extract 80 68 30 36
valve. 82 35 52
Ø A (EXT.)
Ø B (EXT.)
Ø C (INT.)
BEAK
BEAK. Circular aluminium extract valve. 85 25 21
100 115 30 37
12.5
1.5
141 35 55
97 25 15
Mounting
8
23 125 128 30 26
53 152 35 35
With metal mounting ring (-AM). 150 25 13
160 200 30 22
Model Ø A Ø B ØC 233 35 29
BEAK-80 75 120 100
BEAK-100 95 160 140 LEGEND
BEAK-125 120 160 140
BEAK-160 155 200 180 Q (m3/h): Air flow.
Unit mm LwA [dB(A)]: Sound power level.
∆Pt (Pa): Total pressure loss.
56 57
CDPR General dimensions
Ø D2
ØD
ØD
100
H
ØC
137
CDPR CDPR-C
Ø D1 ØA
CDPR-HD
Diffuser ØD Ø D1 Ø D2 Diffuser ØA ØC ØD H
Multi-directional 100
125
98
123
240
240
200
200
100
125
240
240
103
128
98
123
290
315
round diffuser 160
200
158
198
300
360
260
320
160
200
300
360
163
203
158
198
350
390
250 248 460 420 250 460 253 198 390
315 313 540 500 315 540 318 248 440
400 398 540 500 400 540 403 313 505
Unit size in mm - diffuser only Unit size in mm - diffuser + plenum
Product description Others models
KOOLAIR, CDPR, size _ mm (Ø connection) CDPR-HD. Perforated plate round diffuser with
perforated plate round diffuser, hanged from the perforations arranged in a decreasing concentric Selection Table Technical data corresponding to
CDPR model without plenum
ceiling. The configuration of the diffuser allows the circle design. Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) Vk (m/s)
radial air jet supply to be configured in 1, 2 or 3 CDPR-C. Plate round diffuser with a smooth design
140 24 13 1,3 2,0
directions to suit the needs of the end user. (no perforations).
100 180 32 22 1,7 2,6
Removable faceplate to allow the interior of the diffuser CDPR-R. Perforated plate round diffuser for air 235 40 37 2,2 3,4
to be cleaned and provide access to the control return. 160 24 13 1,4 2,1
damper and the air jet setting system. CDPR-HD-R. Perforated plate circular diffuser for 125 205 32 21 1,9 2,7
It can incorporate plenum connection with regulation return air with perforations arranged in a decreasing 260 40 35 2,4 3,5
damper. concentric circle design. 200 24 9 1,7 2,2
Finish in RAL colour of choice. CDPR-C-R. Plate round diffuser for return air with a 160 260 32 16 2,1 2,8
335 40 26 2,8 3,6
smooth design (no perforations).
260 24 7 1,9 2,2
58 59
Swirl
diffusers
DFRO (62) DF-TR-R/DF-TR-V (74) DFRT (84)
DFRE-C-PR (92)
DFRA-OV (66)
DTP-C-Q (96)
DFRE (78)
DRLT (88)
DFRE-GR (80)
DFRA-OV-PR (70)
DTP-GT (98)
DFRE-GR-PR (90)
DAFT (82)
DFRQ (72)
3
Express Park
(Bridgwater, Somerset - United Kingdom)
Security grilles KSG-1,
boxes for constant air volume KSV and KSVL
and boxes for variable air volume KS and KSL.
DFRO Catalogue Series 40.2
General dimensions
A B
50 50
15
ØC
D
F
E OPENING WITHOUT PLENUM BOX = E-25
Diffuser A B C D E F
Adjustable
12
16
20
288
388
488
270
370
470
159
199
199
250
300
300
294
394
494
290
390
490
blade swirl 24 / 32 / 4860
36
588
616
570
598
249
249
350
350
594
623
590
618
diffuser
40
48
663
788
645
770
314 OVAL
314
350
410
670
794
665
790 Unit mm
Selection table
Product description Mounting Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) B (m)
Adjustable blades swirl diffuser, KOOLAIR, model PDL-RE. Plenum with side connection without 140 24 15 1,2
DFRO, size _, plate dimension of _x_. It incorporates insulation for square panel,with manual damper 12 190 32 26 1,7
240 40 43 3,0
a plenum box with side connection made in accessible from false ceiling.
galvanised steel sheet, with spigot inlet volume PDL-A-RE. Plenum with side connection internally 210 24 9 1,5
16 270 32 15 2,7
control damper. insulated for square panel,with manual damper
360 40 26 3,6
Made in steel sheet. Finished in any RAL colour accessible from false ceiling.
300 24 10 2,5
upon request. PDL-RL. Plenum with side connection without
20 390 32 18 3,5
Recommended installation height between 2.5 insulation for square panel,with manual damper 510 40 30 4,3
and 3.5 m. accessible from room.
400 24 9 3,2
PDL-A-RL. Plenum with side connection internally 24 530 32 16 4,2
Other models insulated for square panel,with manual damper
accessible from room.
690 40 27 5,5
470 24 10 3,0
DFRO-__60. Circular diffuser integrated in a plate PCDL-RL. Plenum with side connection without 32 610 32 17 4,1
of 595x595, to be installed in a modular false ceiling insulation for round panel,with manual damper 790 40 29 4,8
(up to size 4860). accessible from room. 480 24 10 3,1
DFRO-E. Circular swirl diffuser for plaster ceiling plate. PCDL-A-RL. Plenum with side connection internally 4860 620 32 17 4,2
DFRO-C. Circular swirl diffuser for circular plate. insulated for round panel,with manual damper 810 40 31 4,9
DFRO-A. Circular swirl diffuser in plate, without accessible from room. 490 24 11 3,0 LEGEND
blades. RPM. Damper equipped to allow motorization. 36 640 32 18 4,0
830 40 31 5,0 Q (m3/h): Air flow.
PM. Mounting bridge.To be installed without plenum
600 24 10 3,2 LwA [dB(A)]: Sound power level.
in plaster ceilings, good for returning air or just
40 790 32 18 4,3 ∆Pt (Pa): Total pressure loss.
Note: On request, top plenum available insulated/ decorative.
1030 40 30 5,0 B (m): Distance between diffuser axis for
uninsulated (PDS-A-RE/PDS-RE).
730 24 10 3,7 a maximum velocity at the occupied zone
48 950 32 17 4,5 of 0.15 m/s, height installation of 2.7 m
1240 40 29 5,4
and ∆T = 0ºC.
62 63
DFRA Catalogue Series 40.2
General dimensions
A B
50 50
15
ØC
D
F
E OPENING WITHOUT PLENUM BOX = E-25
Diffuser A B C D E F
Adjustable
12
16
288
388
270
370
159
199
250
300
294
394
290
390
blade swirl 20
24 / 32 / 4860
488
588
470
570
199
249
300
350
494
594
490
590
diffuser
DFRA-AS 32 588 570 314 410 594 590
36 616 598 249 350 623 618
40 663 645 314 OVAL 350 670 665
48 788 770 314 410 794 790
Unit mm
64 65
DFRA-OV Catalogue Series DFRA-OV
General dimensions
A
50 50 275
15
ØD
H
1195 295
Type Slots A ØD H
Adjustable DFRA-OV-12
DFRA-OV-16
12 450
16 450
200
200
311
311
blade Swirl
DFRA-OV-24 24 450 200 311
DFRA-OV-26-E 26 900 250 356
DFRA-OV-34 34 780 200 311
diffuser DFRA-OV-40 40 1100 200 311
Unit mm
Selection table
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
180 24 9 1,3
Product description Mounting
12
240 32 16 1,7
310 40 27 2,2
Oval adjustable blades swirl diffuser, KOOLAIR, PFL-RE. Fixed plenum box without internal 190 24 8 1,3
model DFRA-OV, size _ , dimension plate of insulation, made in galvanised steel sheet. 16 250 32 10 2,3
1195x295 mm, to be installed in false ceiling PFL-A-RE. Fixed plenum box with side connection 330 40 23 2,2
It incorporates a plenum box with side connection internally insulated, made in galvanised steel sheet. 220 24 7 2,0
made in galvanised steel sheet, with spigot inlet PDL-RE. Removable plenum box with side 24 290 32 13 2,7
volume control damper. connection, internally non-insulated, made in 380 40 17 2,9
Made entirely in steel sheet. Finished in any RAL galvanised steel sheet. 415 24 9 2,2
colour upon request. PDL-A-RE. Removable plenum box with side 26-E 535 32 16 2,8 LEGEND
connection, internally insulated, made in galvanised 730 40 29 3,8
Q (m3/h): Air flow.
steel sheet. 260 24 8 2,0
Other models 34 340 32 14 2,6
LwA [dB(A)]: Sound power level.
∆Pt (Pa): Total pressure loss.
DFRA-OV-E. Swirl diffuser integrated in a plate of 440 40 23 3,4
X (m): Throw for a maximum velocity
1220x320 mm, to be installed in false plaster ceiling. 290 24 9 2,0 of 0.25 m/s at the occupied zone
DFRA-OV dimensions LxH. Swirl diffuser to be 40 380 32 16 2,7 ∆T = –10 ºC (cold), installed at 3 m
500 40 27 3,4
integrated in plate of dimension ( to be determined ) of height, with ceiling effect.
to be installed in false ceiling. Available with different number of vanes for greater flow capacity.
Consult the Technical Department
66 67
DFRA-OV-44 General dimensionss
575
287.5 960
A
174.5
455
485
ISOLATED 5 FACES
30
A’
595 1195
Adjustable
blade swirl
diffuser Selection table LEGEND
Q (m3/h): Air flow.
Size Q (m /h) LwA [dB(A)]
3
∆Pt (Pa) X (m) LwA [dB(A)]: Sound power level.
∆Pt (Pa): Total pressure loss.
970 30 21 2,4
X (m): Throw for a maximum velocity
44 1250 38 28 3,2
of 0.25 m/s at the occupied zone
1600 45 44 4,1
∆T = –10 ºC (cold), installed at 3 m
of height, with ceiling effect.
68 69
DFRA-OV-PR General dimensions
A
50 50 H1 80
15
Ø199
5 SIDES
310
47
24
L H
Swirl diffuser
6
with movable
Custom plenums available to suit reduced heights above false ceilings.
DFRA-OV-PR-16
Slots A
16 450
H1
230
perforated
DFRA-OV-PR-24
DFRA-OV-PR-34
24
34
550
780
230
230
plate
90º
DFRA-OV-PR-40 40 1100 230
Unit mm
Selection table
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
185 24 9 1,1
Product description Other models 16 240 32 11 2,0
320 40 25 1,9
Oval swirl diffuser with movable blades and foldable DFRA-OV-E-PR. Swirl diffuser integrated in
215 24 8 1,7
perforated plate, KOOLAIR model DFRA-OV-PR, 1220x320 mm plate for installation in plaster false 24 280 32 14 2,3 LEGEND
size _, plate size 1195x295 mm for installation in ceilings. 365 40 19 2,5
modular false ceiling. DFRA-OV-PR dimensions LxH. Swirl diffuser Q (m3/h): Air flow.
250 24 9 1,7
LwA [dB(A)]: Sound power level.
Incorporates a galvanized steel plenum with lateral integrated in plate, dimensions to be confirmed, for 34 330 32 15 2,2
∆Pt (Pa): Total pressure loss.
connection. Includes a regulating damper to installation in false ceiling. 425 40 25 2,9
X (m): Throw for a maximum velocity
guarantee correct air distribution. 275 24 10 1,7 of 0.25 m/s at the occupied zone
It is designed and manufactured to adapt to any
type of plate and roof profile, including the number
Mounting
40
350
450
32
40
16
27
2,2
2,8
∆T = –10 ºC (cold), installed at 3 m
of height, with ceiling effect.
of vanes (effective free area) in accordance with the PFL-RE. Fixed plenum box without internal
flow rate requirements. insulation, made in galvanised steel sheet.
Made entirely of sheet steel. Painted finish in any PFL-A-RE. Fixed plenum box with side connection
RAL colour. internally insulated, made in galvanised steel sheet.
PDL-RE. Removable plenum box with side
connection, internally non-insulated, made in
Note: On request, top plenum available insulated/ galvanised steel sheet.
uninsulated (PDS-A-RE/PDS-RE). PDL-A-RE. Removable plenum box with side
connection, internally insulated, made in galvanised
steel sheet.
70 71
DFRQ Catalogue Series 40.2
General dimensions
A B
50 50
15
ØC
D
F
E OPENING WITHOUT PLENUM BOX = E-25
Adjustable Diffuser
28
A
488
B
470
C
199 300
D E
494
F
490
blade swirl
36
40
588
663
570
645
249
314 OVAL
350
350
594
670
590
665
diffuser
Unit mm
48 788 770 314 410 794 790
72 73
DF-TR-R/DF-TR-V Catalogue Series DF-TR
General dimensions
588 570
Ø249
350
594
DFTR-R
DFTR-R
Custom plenums available to suit reduced heights above false ceilings.
588 570
Thermo-
adjustable
Ø249
350
swirl diffuser
594
DFTR-V
Product description Mounting Custom plenums available to suit reduced heights above false ceilings.
Variable geometry swirl diffuser, KOOLAIR, model PDL-RE. Plenum with side connection without
DF-TR-R / DF-TR-V, plate dimension of 595x595 insulation for square panel,with manual damper
Selection table (horizontal discharge)
mm, thermally regulated without the need of a motor, accessible from false ceiling.
Q (m3/h) LwA [dB(A)] ∆ Pt (Pa) X (m)
to supply hot air vertically and cold air horizontally PDL-A-RE. Plenum with side connection internally
It includes connection plenum box made in insulated for square panel,with manual damper 500 32 18 2.4
670 40 31 3.2
galvanised steel sheet, with volume control damper. accessible from false ceiling.
900 48 55 4.3
Finished in any RAL colour upon request. PDL-RL. Plenum with side connection without
Recomended height installation between 3.5 to 5 m insulation for square panel,with manual damper
for DF-TR-R model. accessible from room. Selection table DFTR-R (vertical discharge)
Recomended height installation between 4.5 to 8 m PDL-A-RL. Plenum with side connection internally
for DF-TR-V model. insulated for square panel,with manual damper Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Y0,5 (m) Y0,3 (m) Ymax (m)
accessible from room.
440 32 21 2.2 2.7 3.1
PCDL-RL. Plenum with side connection without L EGEND
Other models insulation for round panel,with manual damper
570 40 34 2.9 3.6 4.0
Q (m3/h): Air flow.
750 48 59 3.7 4.7 5.2
DFTR-R-E / DFTR-V-E. Thermo-adjustable circular accessible from room. LwA [dB(A)]: Sound power level.
swirl diffuser for plaster ceiling plate. PCDL-A-RL. Plenum with side connection internally ∆Pt (Pa): Total pressure loss.
DFTR-R-C / DFTR-V-C. Thermo-adjustable swirl insulated for round panel,with manual damper Selection table DFTR-V (vertical discharge) X (m): Throw for a maximum velocity
diffuser integrated in round plate of Ø 595 mm. of 0.25 m/s at the occupied zone
accessible from room.
Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Y0,5 (m) Y0,3 (m) Ymax (m) ∆T = 0 ºC et hauteur de l’installation 3 m.
Y0,5- Y0,3- Ymax (m): Vertical penetration
Note: On request, top plenum available insulated/ 450 32 23 2.9 3.4 3.7
for a maximum air vein velocity of
uninsulated (PDS-A-RE/PDS-RE). 600 40 40 3.9 4.6 4.9
0.5, 0.3 and 0 m/s respectively and
810 48 72 5.3 6.2 6.6
∆T = +10º C (hot).
74 75
DAFC Catalogue Series 40.3
General dimensions
3x120º
20
C
D
A
B
E
F
Type A B C D E F
Fixed curved
125 138 124 99 171 146 171
160 173 159 124 196 188 213
200 213 199 159 231 239 264
blade Swirl
250
315
263
328
249
314
199
199
271
271
301
380
326
405
diffuser
355
400
368
413
354
399
249
249
321
321
430
485
455
510
500 513 499 314 386 569 594
Unit mm
Selection table
Product description Mounting
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
Swirl diffuser with fixed curved blades, KOOLAIR, PCDL-RE. Removable plenum box with side
40 24 11 0.5
model DAFC, size _ , plate dimensions of _x_. connection, internally non-insulated, made in
125 50 32 21 0.7
Incorporates plenum box made of galvanised steel galvanised steel sheet, with manual damper 70 40 38 0.9
sheet with volume control damper. accessible from false ceiling. 50 24 9 0.6
Made in steel sheet. Finished in any RAL colour PCDL-A-RE. Removable plenum box with side 160 80 32 17 0.9
upon request. connection, internally insulated, made in galvanised 100 40 32 1.2
Recommended installation height between 2.5 steel sheet, with manual damper accessible from 80 24 7 0.8
and 3.5 m. false ceiling. 200 110 32 14 1.1
160 40 27 1.6
PCDL-RL. Removable plenum box with side
110 24 5 1.0
connection, internally non-insulated, made in
Other models galvanised steel sheet, with manual damper
250 160 32 11 1.4
230 40 21 1.9
DAFC-Q. Swirl diffuser with fixed curve blades, accessible from room. 190 24 8 1.3
integrated in plate of 595x595 mm, to be installed in PCDL-A-RL. Removable plenum box with side 315 250 32 15 1.8
false ceiling. connection, internally insulated, made in galvanised 340 40 27 2.4
DAFC-C. Swirl diffuser with fixed curve blades, steel sheet, with manual damper accessible 220 24 7 1.4
355 300 32 13 1.9 LEGEND
integrated in round plate. from room.
410 40 24 2.6 Q (m3/h): Air flow.
DAFC-E. Swirl diffuser with fixed curve blades, RPM. Damper equipped to allow motorization.
250 24 6 1.4 LwA [dB(A)]: Sound power level.
integrated in plate to be installed in plaster ceiling. PM. Mounting bridge. To be used when installation is
400 340 32 12 2.0 ∆Pt (Pa): Total pressure loss.
DAFC-Q-PR. Swirl diffuser with fixed curve blades, without a plenum. 470 40 22 2.7 X (m): Throw for a maximum velocity
integrated in perforated plate dimensions 595x595 350 24 6 1.7 of 0.25 m/s at the occupied zone
mm. 500 480 32 12 2.2 ∆T = –10 ºC (cold), installed at 3 m
650 40 22 3.0
of height.
76 77
DFRE Catalogue Series 40.3
General dimensions
3x120º
20
D
C
A
B
E
F
Type Ø A Ø B Ø C D E F
Fixed Blade
355 368 354 249 321 430 455
400 413 399 314 386 485 510
500 513 499 314 386 569 594 Unit mm
Swirl diffuser Selection table
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
40 24 17 0,5
100 58 32 35 0,7
Product description Mounting 82 40 70 0,9
47 24 12 0,4
Fixed blade swirl diffuser, KOOLAIR, model DFRE, PCDL-RE. Removable plenum box with side
125 70 32 26 0,6
size _ , plate dimension of _x_. Incorporates side connection, internally non-insulated, made in 95 40 47 0,9
connection plenum box made in galvanised steel galvanised steel sheet, with manual damper 65 24 10 0,5
sheet, with volume control damper on the spigot. accessible from false ceiling. 160 95 32 22 0,8
Made in steel sheet. Finished in any RAL colour PCDL-A-RE. Removable plenum box with side 135 40 44 1,1
upon request. connection, internally insulated, made in galvanised 115 24 9 0,8
Recommended installation height between 2.5 steel sheet, with manual damper accessible from 200 165 32 19 1,1
and 3.5 m. false ceiling. 235 40 38 1,6
PCDL-RL. Removable plenum box with side 170 24 8 1,0
connection, internally non-insulated, made in 250 245 32 17 1,5
Other models galvanised steel sheet, with manual damper
350 40 34 2,1
78 79
DFRE-GR Catalogue Series 40.3
General dimensions
3x120º
20
C
D
F
A
B
Model A B C D E F
100 99 99 175 150
125 130 124 99 197 200 175
160 165 159 124 222 253 228
200 205 199 159 257 303 278
250 255 249 199 297 353 328
315 320 314 249 347 418 393
355 360 354 249 347 458 433
Fixed Blade
400
500
405
505
399
499
314
314
412
412
503
603
478
578
Unit mm
Swirl diffuser Selection table
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
40 24 7 0,5
100 55 32 14 0,7
Product description Mounting 80 40 30 1,0
55 24 12 0,6
Fixed blade swirl diffuser with external coanda PCDL-RE. Removable plenum box with side
125 78 32 24 0,9
ring, KOOLAIR, model DFRE-GR, dimension _. connection, internally non-insulated, made in 110 40 48 1,2
Incorporates side connection plenum box made galvanised steel sheet, with manual damper
80 24 13 0,7
in galvanised steel sheet, with spigot inlet volume accessible from false ceiling. 160 115 32 27 1,0
control damper. PCDL-A-RE. Removable plenum box with side 160 40 52 1,4
Diffuser made in steel sheet and decorative ring in connection, internally insulated, made in galvanised 125 24 13 0,9
aluminum. Finished in any RAL colour upon request. steel sheet, with manual damper accessible from 200 175 32 26 1,3
Recommended installation height between 2.5 and false ceiling. 245 40 51 1,9
3.5 m and ideal for circular visible ducts. PCDL-RL. Removable plenum box with side 190 24 10 1,2
connection, internally non-insulated, made in 250 260 32 19 1,6
375 40 40 2,3
galvanised steel sheet, with manual damper
Other models accessible from room. 330 24 8 1,6
315 460 32 16 2,2
DFRE-GR-Q. Swirl diffuser with external coanda PCDL-A-RL. Removable plenum box with side
660 40 32 3,1
ring, integrated in plate of 595x595 mm to be connection, internally insulated, made in galvanised
375 24 7 1,6
installed in false ceilings. steel sheet, with manual damper accessible 355 575 32 14 2,3
from room. 740 40 28 3,2 LEGEND
RPM. Damper equipped to allow motorization. 485 24 8 1,9
Q (m3/h): Air flow.
PM. Mounting bridge. To be used when installation is 400 660 32 14 2,5
LwA [dB(A)]: Sound power level.
without a plenum. 925 40 28 3,6
∆Pt (Pa): Total pressure loss.
640 24 6 2,0
X (m): Throw for a maximum velocity of 0.25 m/s
Note: On request, top plenum available insulated/ 500 890 32 12 2,8
at the occupied zone ∆T = –10 ºC (cold), installed
uninsulated (PDS-A-RE/PDS-RE). 1250 40 23 4,0
at 3 m of height.
80 81
DAFT Catalogue Series 40.3
General dimensions
3x120º
20
C
D
A
B
F
L
Model L A B C D F
Fixed blade
325 323 273 260 159 229 298
400 398 356 344 199 269 373
500 498 450 438 199 269 473
swirl diffuser
600
625
595
623
553
553
541
541
249
249
319
319
570
598
Unit mm
82 83
DFRT Catalogue Series 40.3
General dimensions
3x120º
20
C
D
A
B
F
L
Model L A B C D F
Fixed blade
325 323 304 294 159 230 314
400 398 370 358 199 270 380
500 498 413 402 199 270 423
swirl diffuser
600
625
595
623
546
546
533
533
249
249
320
320
556
556
Unit mm
84 85
DFRE-GR-TR Catalogue Series DFRE-GR-TR
General dimensions
3x120º
20
D
C
D
A
B
F
E
DFRE-GR-TR-PCFL-RE
Model A B C D E F
Adjustable
160
200
165
205
159 124 320
199 159 355
253 228
303 278
Blade Swirl
250
315
355
255
320
360
249 199 395
314 249 445
354 249 445
353 328
418 393
458 433
diffuser
400
500
405
505
399 314 510
499 314 510
503 478
603 578 Unit mm
Adjustable blade swirl diffuser, KOOLAIR, model DFRE-GR-MT. Adjustable blade swirl diffuser with 250 25 14 2,6 85 25 15 0,8
DFRE-GR-TR, available from Ø160 to Ø500 160 350 35 27 3,7 160 130 35 34 1,2
electric actuator T/N (24v or 230v). Available from
(temperature-adjustable version). It can incoporate 475 45 50 5,0 195 45 78 1,7
Ø315 to Ø500.
side entry plenum box, with volume control damper DFRE-GR-MT-Q. Adjustable blade swirl diffuser 370 25 13 3,1 130 25 14 1,0
on the spigot or direct conexión against circular 200 500 35 23 4,2 200 195 35 32 1,5
with electric actuator T/N (24v or 230v), in 595x595
duct. 660 45 40 5,5 300 45 76 2,3
mm plate for installation in modular false ceilings.
Made in steel sheet. Finished in any RAL colour Available from Ø315 to Ø500. 540 25 11 3,6 200 25 11 1,2
upon request. 250 730 35 20 4,9 250 300 35 26 1,9
Recommended installation height between 3.5 975 45 36 6,5 460 45 61 2,8
and 6 m. Mounting 800 25 9 4,3 350 25 9 1,7
PCFL-RE. Fixed plenum box without internal 315 1075 35 17 5,7 315 515 35 20 2,4
1480 45 32 7,9 775 45 46 3,7
Other models insulation, with manual damper.
PCFL-A-RE. Fixed plenum box with side connection 850 25 10 4,0 395 25 8 1,7
DFRE-GR-RM. Swirl diffuser with manually internally insulated, with manual damper. 355 1175 35 20 5,5 355 600 35 18 2,6
adjustable movable blades, Ø160 to Ø500 (manual 1600 45 36 7,5 900 45 42 3,9
PCDL-RE. Removable plenum box with side
version). connection, internally non-insulated, made in 950 25 9 3,7 500 25 8 1,9
DFRE-GR-TR-Q. Thermo-adjustable swirl diffuser galvanised steel sheet, with manual damper 400 1300 35 17 5,1 400 765 35 19 2,9
integrated in 595x595 mm plate for installation in 1800 45 33 7,1 1150 45 43 4,4
accessible from false ceiling.
modular false ceilings. PCDL-A-RE. Removable plenum box with side 1050 25 5 3,1 650 25 6 2,1
DFRE-GR-RM-Q. Swirl diffuser with manually 500 1450 35 10 4,3 500 975 35 14 3,1
connection, internally insulated, made in galvanised
adjustable movable blades integrated in 595x595 1950 45 18 5,8 1500 45 34 4,8
steel sheet, with manual damper accessible from
mm plate for installation in modular false ceilings. false ceiling. LEGEND
DFRE-GR-PR-TR. Thermo-adjustable swirl diffuser
integrated in punched plate of dimensions LxH to be Note: On request, top plenum available insulated/ Q (m3/h): Air flow. Y (m): Vertical penetration for a terminal air vein velocity of 0.25 m/s and ∆T = +10º C (hot).
installed in false ceiling. uninsulated (PCFS-A-RE/PCFS-RE / PDS-A-RE/ LwA [dB(A)]: Sound power level. X (m): Throw for a maximum velocity of 0.25 m/s at the occupied zone ∆T = –10 ºC (cold), installed
PDS-RE). ∆Pt (Pa): Total pressure loss. at 3 m of height
86 87
DRLT General dimensions
595 Ø A + 13 (INT.) 80
1200
ØD
595
300
H
SIZES FROM 160 TO 400 SIZES FROM 160 TO 250
ØA ØA
77
86
1200 x 300 / 594 x 594 594 x 594
Diffuser Ø A Ø D H
20
C
D
A
B
L1
L2
Fixed Blade
200 205 199 159 258
250 255 249 199 298 594 x 1194 594 x 594
315 320 314 199 298 625 x 625
Swirl diffuser
355
400
360
405
354
399
249
249
348
348
500 505 499 314 413
Unit mm
Selection table
Product description Mounting
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
Fixed blade swirl diffuser, KOOLAIR, model PCFL-RE. Fixed plenum box without internal
40 24 9 0,5
DFRE-GR-PR-Q, size _ , integrated in hinged insulation, with manual damper.
125 60 32 17 0,7
perforated plate of dimensions 595x595 mm. PCFL-A-RE. Fixed plenum box with side connection
80 40 33 1,0
Incorporates side connection plenum box and volume internally insulated, with manual damper.
60 24 8 0,5
control damper. 160 90 32 15 0,7
Note: On request, top plenum available insulated/ 120 40 29 1,0
Made in steel sheet. Finished in any RAL colour
uninsulated (PCFS-A-RE/PCFS-RE).
upon request. 110 24 8 0,8
Recommended installation height between 2.5 200 150 32 15 1,1
200 40 29 1,4
and 3.5 m.
160 24 8 1,0
250 220 32 15 1,3
Other models 290 40 27 1,8
240 24 8 1,2
DFRE-GR-PR dimensions LxH. Swirl diffuser 315 320 32 15 1,5
integrated in punched plate of dimensions _x_ to be 420 40 26 2,0
installed in false ceiling. 290 24 8 1,3
DFRE-GR-PR-C. Swirl diffuser integrated in circular 355 380 32 14 1,7
510 40 24 2,2 LEGEND
punched plate. The perforated plate and the swirl
320 24 6 1,2 Q (m3/h): Air flow.
diffuser are not removable.
400 440 32 11 1,7 LwA [dB(A)]: Sound power level.
DFRE-GR-Q-PR. Swirl diffuser with no outer ring 610 40 20 2,3 ∆Pt (Pa): Total pressure loss.
integrated in 595x595 mm perforated foldable plate. 415 24 7 1,3 X (m): Throw for a maximum velocity of 0.25 m/s at
Incorporates side connection plenum box and volume 500 570 32 13 1,8 the occupied zone ∆T = –10 ºC (cold), installed at
control damper. 775 40 24 2,5
3 m of height.
90 91
DFRE-C-PR Catalogue Series 40.3
General dimensions
ØA
ØC
D
ØB
45
Custom plenums available to suit reduced heights above false ceilings.
swirl diffuser
160
200
173
213
360
403
124
159
195
230
335
337
with perforated
250
315
263
328
450
503
199
249
270
320
423
475
plate
355 368 550 249 320 523
400 413 594 314 385 567
500 513 633 315 385 605
Unit mm
92 93
HDPR Catalogue Series 40.3
General dimensions
3x120º
20
C
D
A
B
F
E
Swirl
Diffuser A B C D E F Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
125 137 124 99 198 270 245 45 24 8 0,5
diffuser
160
200
250
172
212
262
159
199
249
124
159
199
223
258
298
298
363
403
273
338
378
125
65
90
32
40
16 0,7
31 0,9
94 95
DTP Catalogue Series DTP
General dimensions
ØD
H
DTP-C-Q
ØB ØB
A A
DTP-C-Q DTP-PR
DTP-Q Custom plenums available to suit reduced heights above false ceilings.
Micronozzle Model
DTP-C-Q-16
A ØB ØD H
diffuser
125 200
DTP-C-Q-24
DTP-C-Q-32
160 235
DTP-C-Q-36 594 580
DTP-C-Q-48
DTP-C-Q-54 200 275
96 97
DTP-GT Catalogue Series DTP-GT
General dimensions (DTP-GT-Q)
A B
50 50
15
ØC
D
F
E
Micronozzle Model A B C D E F
diffuser DTP-GT-Q-16
DTP-GT-Q-24
288
368
270
350
125
125
225
225
594
594
570
570
DTP-GT-Q-36 428 410 160 250 594 570
DTP-GT-Q-48 506 488 200 300 594 570
DTP-GT-Q-64 568 550 200 300 594 570
DTP-GT-16 288 270 125 225 294 290
Product description Mounting DTP-GT-24 368 350 125 225 444 370
DTP-GT-36 428 410 160 250 494 430
Micronozzle diffuser for high flows, KOOLAIR PDL-RE. Plenum with side connection without DTP-GT-48 506 488 200 300 554 508
DTP-GT model, size __, plate dimensions __x__. insulation for square panel,with manual damper DTP-GT-64 568 550 200 300 594 570
Composed of small nozzles, individually adjustable in accessible from false ceiling.
Unit mm
all directions. PDL-A-RE. Plenum with side connection internally
Micronozzles manufactured in ABS-VO white plastic insulated for square panel,with manual damper
and steel plate. accessible from false ceiling.
Selection table (DTP-GT-Q 2 directions)
Standard finish in glossy RAL9010. Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) VK (m/s)
98 99
Long throw
diffusers
DF-47 (102)
DF-89 (116)
DF-47-NARROW (104)
DF-49-MT-3-I/R (120)
DF-48 (108)
DGV (122)
DF-49 (110)
DVP (124)
DF-49-ROT (114)
BMW plant
(Swindon - United Kingdom)
Long-throw nozzle DF-49. 4
DF-47 Catalogue Series DF-47
General dimensions
A
LxH
L= Opening Length
B
H= Opening Height
E C DF-47
L x H A B C D E
305 x 165 348 210 284 82 58,5
610 x 165 652 210 588 82 58,5
610 x 267 652 310 588 147 78,5
1219 x 267 1262 310 1198 147 78,5
1067 x 380 1110 422 1046 229 102
Unit mm
Long-throw A
rectangular
diffuser L= Opening Length
LxH
B
D
H= Opening Height
DF-47-C
C
Product description Other models
L x H A B C D
Rectangular, long-throw diffuser KOOLAIR, model DF-47-TR. Rectangular long-throw diffuser
334 x 165 367 215 274 82
DF-47, dimension of _x_. It can incorporate volume autoregulated by thermal element. 637 x 165 671 215 578 82
control damper (-O). The diffuser can be manually DF-47-CC. Rectangular long-throw diffuser 637 x 267 673 304 578 147
1247 x 267 1283 304 1188 147
adjusted to be vertically positioned at an angle of adaptable to round duct. 1090 x 390 1171 472 1036 229
(±20º). The unit is equipped with deflecting blades DF-47-CC-TR. Rectangular long-throw diffuser Unit mm
for distributing the air in horizontal fan-shape adaptable to round duct autoregulated by thermal
or concentrating the inlet airflow in the desired element. Selection table
direction. DF-47-MT. Rectangular long-throw diffuser with
Finished in anodised aluminium or any RAL colour motorised mechanism. Size Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X0,3 X0,5 X1,0 Vk
upon request. Recomended instalation height DF-47-CC-MT. Rectangular long-throw diffuser 530 32 33 16,1 9,7 4,8 7,5
between 2.5 and 6 m. adaptable to round duct with motorised mechanism. 23 305 x 165 690 40 55 21,0 12,6 6,3 9,7
880 48 90 26,8 16,1 8,0 12,4
930 32 26 20,3 12,2 6,1 6,7
Mounting 26 610 x 165 1200 40 44 26,2 15,7 7,9 8,7
1550 48 48 >30 20,3 10,2 11,2
With screws (-T). Without indication the diffuser is LEGEND
1390 32 23 20,2 12,1 6,1 6,3
always screw-mounted. Q (m3/h): Air flow.
36 610 x 267 1790 40 38 26,0 15,6 7,8 8,1
MM. Mounting frame (-MM). Fixed with screws. 2310 48 64 >30 20,1 10,1 10,5 LwA [dB(A)]: Sound power level.
H
PAC. Integrated in plenum box with connection to ØDUCT 2490 32 19 25,7 15,4 7,7 5,7 ∆Pt (Pa): Total pressure loss.
round duct. 312 1219 x 267 3210 40 31 >30 19,9 9,9 7,4 X0,3-X0,5-X1,0 (m): Throw for terminal
L 4140 48 52 >30 25,6 12,8 9,5 velocity of the air stream of 0.3, 0.5,
L= Opening Length
H= Opening Height 2990 32 18 22,4 13,4 6,7 5,5 and 1.0 m/s, respectively, in isothermal
410 1067 x 380 3860 40 29 28,9 17,3 8,7 7,1 conditions (∆T = 0º C).
PAC 4980 48 49 >30 22,3 11,2 9,2
Vk (m/s): Effective velocity.
102 103
DF-47-NARROW Cat. DF-47-NARROW
General dimensions
52 20
DF-47-NARROW
L x H1
H2
H
6 L + 15
DF-47-NARROW-CC
AxC
AIR PASSAGE
B
High-induction L = Opening Length
for medium-
Custom plenums available to suit reduced heights above false ceilings.
DF-47-NARROW-CC
to-long throw
LENGTH C D
AIR PASSAGE 500 500 525
600 600 625
NOMINAL 15 20 30 40 50 700 700 725
(Ø DUCT) A B A B A B A B A B 800 800 825
200 85 113 88 115 97 123 97 120 - - 900 900 925
250 84 113 89 118 97 123 106 133 115 138 1000 1000 1025
300 84 113 89 118 97 126 106 133 115 141 1100 1100 1125
315 83 113 89 118 97 126 106 133 116 143 1200 1200 1225
355 83 113 88 118 97 126 107 136 116 146 Unit mm
400 83 113 88 118 97 126 107 136 117 146
450 83 114 88 119 96 126 106 136 117 146 DF-47-NARROW
Product description DF-47-NARROW-I/R. Linear diffuser for medium-to-
long throw, for supply/return. Custom designs based
500
560
83 114 88 119 96 126 106 136 117 146
83 114 88 119 96 126 106 136 117 146 H H1 H2
High-induction linear diffuser for medium-to-long 630 83 114 88 119 96 127 104 135 116 146
on flow rate and aesthetic requirements. 710 83 114 88 119 96 127 104 135 116 146 15 85 100
throw, Koolair DF-47-NARROW model, with length 800 83 114 88 119 96 127 104 135 116 146 20 90 105
__ mm and slot __ mm for air passage. Accessories 900 83 114 88 119 96 127 104 135 116 146 30
40
100 115
110 125
Allows ± 30º vertical core rotation (linear nozzle). Unit mm 50 120 135
Because the slot is narrow, medium-to-long throws MM. With Mounting frame.
T. With holes for fixing screws. Unit mm
can be covered to achieve comfortable conditions
with cold and hot air supplies, while ensuring PM. With mounting bridge.
PFL-RL. Fixed plenum box made in galvanised steel
Selection table (Flow rate per linear metre of diffuser)
excellent aesthetics.
Suitable for both ceiling and wall installation. sheet, without insulation.
PFL-A-RL. Fixed plenum box made in galvanised Size Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X0,3 X0,5 X1,0 Vk (m/s)
Manufactured entirely of extruded aluminium
sections. steel sheet, insulated. 280 24 20 8,3 5,0 2,5 7,2
PDL-RL. Removable plenum box made in 15 1000 450 32 51 13,4 8,0 4,0 11,6
Recommended installation height of 2.5 to 6 m. galvanised steel sheet, without insulation.
700 40 124 20,8 12,5 6,2 18,0
PDL-A-RL. Removable plenum box made in
galvanised steel sheet, insulated. 400 24 21 10,3 6,2 3,1 7,7 DF-47-Narrow - I/R
Other models RFS06. Slide control damper. 20 1000 570 32 43 14,7 8,8 4,4 11,0
DF-47-NARROW-S. Medium-long throw linear O. With opposed blade control damper. 800 40 85 20,7 12,4 6,2 15,5
diffuser with narrow 14mm wide frame. G. 2nd row of individually moving vertical blades.
PR. Complete with decorative perforated sheet 485 24 14 9,0 5,4 2,7 4,8 LEGEND
DF-47-NARROW-IC. Linear diffuser for medium-to- 30 1000 675 32 27 12,5 7,5 3,8 6,7
long throw, integrated with exposed circular duct . metal painted in black to block vision through Q (m3/h): Air flow.
DF-47-NARROW-CC. Linear diffuser for medium-to- sections of diffuser with no plenum (decorative or 925 40 51 17,1 10,3 5,1 9,2
unconnected return). LwA [dB(A)]: Sound power level.
long throw, with exposed circular duct adaption. 600 24 12 9,6 5,8 2,9 4,5
∆Pt (Pa): Total pressure loss.
DF-47-NARROW-TR. Linear diffuser for medium-to- 40 1000 825 32 22 13,2 7,9 4,0 6,1
long throw, self-adjusting by thermal component. Note: On request, top plenum available insulated/ X0,3-X0,5-X1,0 (m): Throw for terminal
1150 40 43 18,4 11,0 5,5 8,5
Available in -CC and -IC versions. uninsulated (PFS-A-RE/PFS-RE / PDS-A-RE/PDS- velocity of the air stream of 0.3, 0.5,
DF-47-NARROW-MT. Linear diffuser for medium-to- RE). 625 24 8 8,9 5,4 2,7 3,7 and 1.0 m/s, respectively, in isothermal
long throw, motor-driven. 50 1000 925 32 19 13,2 7,9 4,0 5,5
conditions (∆T = 0º C).
Available in -CC and -IC versions. 1350 40 40 19,3 11,6 5,8 8,0
Vk (m/s): Effective velocity.
104 105
DF-47-NARROW-LT Cat. DF-47-NARROW
General dimensions
H3 80 L-3
15
H2
H1
ØD
12.5
HP
15
Plasterboard screw Pladur thickness 12.5 and 15
Fill filler Connection profile sections and
58
fixing to plasterboard
H 120
NOMINAL
L = Opening Length
H = Opening Height
NOMINAL <= 1000 (with 1 spigot), NOMINAL > 1001 (with 2 spigots)
Hidden high H H1 H2 H3 ØD HP
induction 15
20
81
86
136
141
110
115
Ø159
Ø199
285
325
77.5
linear diffuser
30 96 151 125 Ø249 375
40 106 161 190 Ø314 (oval) 325
50 116 171 190 Ø314 (oval) 325
for medium- H = Slot width Unit mm
DF-47-NARROW-LT + RFS06
88.5
280 24 20 8,3 5,0 2,5 7,2
15 1000 450 32 51 13,4 8,0 4,0 11,6
700 40 124 20,8 12,5 6,2 18,0
DF-47-NARROW-LT + G
400 24 21 10,3 6,2 3,1 7,7
Product description T-DF-47-NARROW-LT. Decorative invisible linear
diffuser in the shape of a “T” at 90° devised to form
20
1000
570
800
32
40
43
85
14,7 8,8 4,4 11,0
20,7 12,4 6,2 15,5
Invisible high induction linear diffuser for medium- a continuous line with other active or decorative 485 24 14 9,0 5,4 2,7 4,8
long throw, Koolair DF-47-NARROW-LT model, with 30 1000 675 32 27 12,5 7,5 3,8 6,7
sections. 925 40 51 17,1 10,3 5,1 9,2
77.5
length __ mm and slot __ mm for air passage. MITRED-CORNER-DF-47-NARROW-LT. 600 24 12 9,6 5,8 2,9 4,5
Characterised by the lack of profile on show. Decorative invisible linear slot diffuser in the shape 40 1000 825 32 22 13,2 7,9 4,0 6,1
Because the slot is narrow, medium-to-long throws of an elbow at 90° devised to form a continuous line 1150 40 43 18,4 11,0 5,5 8,5
can be covered to achieve comfortable conditions with other active or decorative sections. 625 24 8 8,9 5,4 2,7 3,7 DF-47-NARROW-LT + PR
50 1000 925 32 19 13,2 7,9 4,0 5,5
with cold and hot air supplies, while ensuring 1350 40 40 19,3 11,6 5,8 8,0
excellent aesthetics. Accessories
Suitable for both ceiling and wall installation.
Made with aluminium profiles, all painted in RAL PFL-RL. Fixed plenum box made in galvanised steel Selection table (Vertical supply, from ceiling)
9005. sheet, without insulation.
For installation heights over 3.5 m in ceilings and PFL-A-RL. Fixed plenum box made in galvanised H Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Ymax Vk (m/s)
between 2.5 m and 3.5 m on walls. steel sheet, insulated. 220 20 12 4,3 5,6 LEGEND
RFS06. Slide control damper. 15 1000 280 24 20 5,4 7,2 Q (m3/h): Air flow.
350 28 31 6,8 9,0
Note: Possible to form continuous lines (Maximum O. With opposed blade control damper. LwA [dB(A)]: Sound power level.
330 20 14 5,2 6,4
length per section 2000 mm). G. 2nd row of individually moving vertical blades. 20 1000 390 24 20 6,1 7,5 ∆Pt (Pa): Total pressure loss.
On request, top plenum available insulated/ PR. Complete with decorative perforated sheet 470 28 29 7,4 9,1 X (m): Throw for terminal velocity of
uninsulated (PFS-A-RL/PFS-RL). metal painted in black to block vision through
420 20 10 4,0 4,2
the air stream of 0.3, 0.5, and 1.0 m/s,
30 1000 490 24 14 4,7 4,9
sections of diffuser with no plenum (decorative or 575 28 20 5,5 5,7 respectively, in isothermal conditions
Other models unconnected return). 500 20 8 3,9 3,7 (∆T = 0º C).
40 1000 590 24 11 4,5 4,4
CROSS-DF-47-NARROW-LT. Decorative invisible 700 28 16 5,4 5,2 Vk (m/s): Effective velocity.
linear slot diffuser in the shape of a cross at 90° 530 20 6 3,5 3,15 Ymax (m): Maximum vertical penetration
devised to form a continuous line with other active or 50 1000 630 24 9 4,1 3,7 at ΔT = +10 ºC (heating).
765 28 13 5,0 4,5
decorative sections.
The Selection Table shows a summary of dimensions. Other sizes available.
Consult the Sales Department.
106 107
DF-48 Catalogue Series DF-48
General dimensions
D D F
ØA
ØG
ØB
ØB
ØC
ØC
ØE
ØE
ØC = Opening
DF-48 DF-48-B
spherical
3
5
132
205
107
182
80
143
44
91
40
65
26
48
61
123
diffuser
8
10
276
324
254
301
215
265
129
150
100
136
50
79
198
248
12 380 356 322 201 165 74 313
16 495 470 425 249 230 113 398
20 553 533 500 296 300 135 498
Unit mm
Product description Other models
Long-throw spherical diffuser, KOOLAIR, model DF-48-B. Long-range nozzle with neck for flexible Selection table
DF-48, size _. The configuration allows the diffuser duct connection of commercial dimensions (Ø100,
to be swiveled in any direction up to a maximum Ø160, Ø200, Ø250, Ø400 mm depending on the Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X0,3 X0,5 X1,0 Vk
of (±35º) in the horizontal or vertical direction. It size of the nozzle). 60 32 109 8.4 5.0 2.5 12.8
has a volume control damper at the outlet. Made 3 80 40 175 6.7 4.0 2.0 17.1
in aluminium. Finished in anodised aluminium or 110 48 331 14.7 8.8 4.4 23.5
painted in any RAL colour upon request.
Mounting 140 32 82 11.7 7.0 3.5 11.8
With screws (-T). Without indication the diffuser is 5 180 40 138 15.1 9.1 4.5 15.2
240 48 245 20.1 12.1 6.0 20.2
always screw-mounted.
AM. With metal mounting ring. 290 32 64 15.9 9.6 4.8 10.2
PAC AC 8 380 40 107 20.6 12.4 6.2 13.4
AC. Integrated in flat plate for connection to round 500 48 185 27.1 16.3 8.1 17.6
duct. Depending on the size, 6 is the maximum
460 32 46 18.4 11.0 5.5 8.8
number of diffusers, (to be consulted). 10 650 40 91 26.0 15.6 7.8 12.4
PAC. Integrated in plenum box with connection 910 48 179 >30 21.8 10.9 17.4
to round duct. Depending on the size, 6 is the 690 32 48 22.7 13.6 6.8 9.0 LEGEND
maximum number of diffusers, (to be consulted). 12 900 40 82 29.6 17.8 8.9 11.7 Q (m3/h): Air flow.
1170 48 138 >30 23.1 11.6 15.2 LwA [dB(A)]: Sound power level.
PLC. Integrated in plate with 45 ° full saddle tap for
AM INJ PLC 1220 32 40 28.8 17.3 8.7 8.2
lateral connection to round duct. Depending on the ∆Pt (Pa): Total pressure loss.
16 1590 40 68 >30 22.5 11.3 10.6 X0,3-X0,5-X1,0 (m): Throw for terminal
size, 6 is the maximum number of diffusers, (to be 2060 48 114 >30 29.2 14.6 13.8 velocity of the air stream of 0.3, 0.5,
consulted).
1930 32 35 >30 21.0 10.5 7.6 and 1.0 m/s, respectively, in isothermal
INJ. 45° full saddle tap for lateral connection to 20 2500 40 58 >30 27.2 13.6 9.8 conditions (∆T = 0º C).
exposed circular duct. One adapter per diffuser. 3260 48 98 >30 >30 17.7 12.8
Vk (m/s): Effective velocity.
108 109
DF-49 Catalogue Series DF-49
General dimensions
L
ØA
10
P x R (OPENING)
D C
15
H
15
DF-49-AR
Dimensions (DF-49-AR)
Long throw NOZZLES
nozzle
1 2 3 4 5 6 7
L P L P L P L P L P L P L P H R A C D
5” 225 160 450 385 675 610 900 835 1125 1060 1350 1285 1575 1510 225 160 55 225 113
8” 275 225 550 500 825 775 1100 1050 1375 1325 1650 1600 1925 1875 275 225 90 275 138
10” 350 275 700 625 1050 975 1400 1325 1750 1675 350 275 123 350 175
Product description Other models 12” 380 325 760 705 1140 1085 1520 1465 1900 1845 380 325 155 380 190
Long-throw nozzle, KOOLAIR, model DF-49-A, DF-49-MT. Long-throw nozzle with motorised 16” 525 450 1050 975 1575 1500 525 450 220 525 263
size _, used for diffusion large areas. The mechanism (sizes 8 to 16). Unit mm
condiguration allows the nozzle to swivel in all DF-49-B. Long-range nozzle with neck for flexible
directions up to a maximum of (±30º). duct connection of commercial dimensions (Ø100,
It incorporates a decorative ring, that hides the Ø160, Ø200, Ø250, Ø400 mm depending on the Selection table
mounting screws. Made in aluminium. Painted in any size of the nozzle).
RAL colour upon request. DF-49-TR. Rectangular long-throw nozzle Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X0,3 X0,5 X1,0 Vk
autoregulated by thermal element. 60 24 81 13 8 4 13,5
3 80 32 147 18 11 5 18,1
Mounting
110
110
40
24
266
80
24
17
14
10
7
5
24,4
12,2
With screws (-T). Without indication the diffuser is 5 140 32 129 21 13 6 15,5
always screw-mounted. 185 40 225 28 17 8 20,5
PAC AC
AM. With metal mounting ring. 235 24 61 22 13 6 10,8
AC. Integrated in flat plate for connection to round 8 305 32 103 28 17 8 14,1
duct. Depending on the size, 6 is the maximum 400 40 175 37 22 11 18,4
number of diffusers, (to be consulted). 480 32 69 >30 18 9 10,6
PAC. Integrated in plenum box with connection 10 610 40 112 >30 23 12 13,4
780 48 183 >30 >30 15 17,2 LEGEND
to round duct. Depending on the size, 6 is the
maximum number of diffusers, (to be consulted). 820 32 76 >30 26 13 12,4 Q (m3/h): Air flow.
PLC. Integrated in plate with 45 ° full saddle tap for 12 1070 40 130 >30 >30 17 16,1 LwA [dB(A)]: Sound power level.
AM INJ PLC lateral connection to round duct. Depending on the 1400 48 222 >30 29 15 21,1
∆Pt (Pa): Total pressure loss.
size, 6 is the maximum number of diffusers, (to be 1360 32 48 >30 28 14 9,7
16 X0,3-X0,5-X1,0 (m): Throw for terminal
consulted). 1770 40 81 >30 >30 24 12,6
INJ. 45° full saddle tap for lateral connection to 2300 48 136 >30 >30 24 16,4 velocity of the air stream of 0.3, 0.5,
exposed circular duct. One adapter per diffuser. 2500 32 35 >30 >30 19,1 9,6 and 1.0 m/s, respectively, in isothermal
AR. Integrated in flat plate for installation in wall or 20 3300 40 61 >30 >30 25,2 12,7 conditions (∆T = 0º C).
square ductwork. Maximum number of diffusers 4250 48 102 >30 >30 >30 16,3
Vk (m/s): Effective velocity.
according to size (see table on next page).
110 111
DF-49
D H D G D H D G
ØF
ØF
ØC (OPENING)
ØJ (OPENING)
ØA
ØA
ØB
ØE
ØB
ØC
ØA
ØE
ØC
ØA
5 55 135 155 21 99 209 63 106 5 55 145 160 28 99 210 151 210 173
8 90 208 225 34 159 268 100 144 8 90 215 230 39 159 268 179 240 236
10 123 257 275 48 199 317 132 202 10 123 264 282 48 199 317 202 263 286
12 155 314 330 56 249 376 132 224 12 155 318 335 53 249 376 241 300 341
16 220 417 440 78 399 511 156 236 16 220 425 445 88 399 511 300 360 476
20 290 493 510 100 399 584 173 265 Unit mm
Unit mm
Dimension DF-49-3
49 4
Ø105
Ø80
Ø40
Ø108
25,5
112 113
DF-49-ROT Catalogue Series DF-49-ROT
General dimensions
D H D G
ØF
ØA
ØA
ØC
ØB
ØE
ØC
DF-49-B-ROT DF-49-A-ROT ØC = Opening
Dimensions (DF-49-ROT)
Model ØA ØB ØC D ØE ØF H G
8 90 208 217 34 159 268 144 100
10 123 257 268 48 199 317 202 132
12 155 314 323 56 249 376 224 132
16 220 417 433 78 399 511 236 156
20 290 493 510 100 399 584 265 170
D D
nozzle
ØF
ØE
ØC
ØC
Product description Other models
ØA
ØA
Long-throw nozzle with swirl element, KOOLAIR, DF-49-B-ROT. Long-throw nozzle, with swirl
model DF-49-A-ROT, size _, used for diffusion large element, allows a flexible duct of standard DF-49-B-ROT-TR DF-49-A-ROT-TR ØC = Opening
areas for small jet penetration . The configuration dimensions to be coupled directly to each nozzle.
allows the nozzle to swivel in all directions up to a DF-49-ROT-TR. Rectangular long-throw nozzle, with Dimensions (DF-49-ROT-TR)
maximum of (±30º) for the orientation of the air jet. swirl element, autoregulated by thermal element.
It incorporates a decorative ring, that hides the Available up to size 16. Model ØA ØC D ØE ØF
mounting screws. Made in aluminium. Painted in any 8 90 230 39 159 268
10 123 282 48 199 317
RAL colour upon request. Mounting 12 155 335 53 249 376
16 220 445 88 399 511
With screws (-T). Without indication the diffuser is
always screw-mounted. Unit mm
PAC AC
AM. With metal mounting ring.
AC. Integrated in flat plate for connection to round
Selection table
duct. Depending on the size, 6 is the maximum
Size Q (m3/h) LwA [dB(A)] ∆P (Pa) X0,3 X0,5 X1,0 Vk
number of diffusers, (to be consulted).
220 32 56 16 10 5 10,1
PAC. Integrated in plenum box with connection 8 290 40 98 21 13 6 13,4
to round duct. Depending on the size, 6 is the 375 48 164 28 17 8 17,3
maximum number of diffusers, (to be consulted). 360 32 48 18 11 5 7,9
10 460 40 79 23 14 7 10,1 LEGEND
AM INJ PLC PLC. Integrated in plate with 45 ° full saddle tap for 575 48 123 29 17 9 12,7 Q (m3/h): Air flow.
lateral connection to round duct.. Depending on the 600 32 55 25 15 7 9,1
12 770 40 90 >30 19 10 11,6 LwA [dB(A)]: Sound power level.
size, 6 is the maximum number of diffusers, (to be
1000 48 152 >30 25 12 15,1 ∆P (Pa): Total pressure loss.
consulted).
975 32 35 27 16 8 6,9 X0,3-X0,5-X1,0 (m): Throw for terminal
INJ. 45° full saddle tap for lateral connection to 16 1250 40 57 >30 21 10 8,9
1650 48 108 >30 27 14 11,7 velocity of the air stream of 0.3, 0.5,
exposed circular duct. One adapter per diffuser.
1800 32 33 >30 22 11 6,9 and 1.0 m/s, respectively, in isothermal
20 2350 40 56 >30 29 14 9,0 conditions (∆T = 0º C)
3100 48 98 >30 >30 19 11,9
Vk (m/s): Effective velocity.
114 115
DF-89 Catalogue Series DF-89
General dimensions
ØA
ØB
ØD
ØB
ØD
ØE
ØC
ØC
F F G
ØC = Opening
DF-89-A DF-89-B
5
Ø A
205
Ø B
182
Ø C
55
Ø D
143
Ø E
123
Ø F
68
ØG
48
nozzle
8
10
276
324
254
301
90
123
215
265
198
248
80
105
50
79
12 380 356 155 322 313 132 74
16 495 470 220 425 398 170 113
20 553 533 290 506 498 185 135
Long-throw nozzle, KOOLAIR, model DF-89-A, DF-89-B. Long-range nozzle with neck for flexible
size _, used for diffusion large areas. The duct connection of commercial dimensions (Ø100,
configuration allows the nozzle to swivel in all Ø160, Ø200, Ø250, Ø400 mm depending on the
directions up to a maximum of (±30º), for the size of the nozzle). Selection table
orientation of the air jet.
It incorporates a decorative ring, that hides the
mounting screws. Made in aluminium. Painted in any
Mounting Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X0,3 X0,5 X1,0 Vk
110 24 80 17 10 5 12,2
RAL colour upon request. With screws (-T). Without indication the diffuser is 5 140 32 129 21 13 6 15,5
always screw-mounted. 185 40 225 28 17 8 20,5
AM. With metal mounting ring. 235 24 61 22 13 6 10,8
PAC AC AC. Integrated in flat plate for connection to round 8 305 32 103 28 17 8 14,1
duct. Depending on the size, 6 is the maximum 400 40 175 37 22 11 18,4
number of diffusers, (to be consulted). 480 32 69 >30 18 9 10,6
PAC. Integrated in plenum box with connection 10 610 40 112 >30 23 12 13,4
to round duct. Depending on the size, 6 is the 780 48 183 >30 >30 15 17,2
820 32 76 >30 26 13 12,4 LEGEND
maximum number of diffusers, (to be consulted).
12 1070 40 130 >30 >30 17 16,1 Q (m3/h): Air flow.
PLC. Integrated in plate with 45 ° full saddle tap for
1400 48 222 >30 29 15 21,1 LwA [dB(A)]: Sound power level.
lateral connection to round duct.. Depending on the
AM INJ PLC 1360 32 48 >30 28 14 9,7
size, 6 is the maximum number of diffusers, (to be ∆Pt (Pa): Total pressure loss.
16 1770 40 81 >30 >30 24 12,6
consulted). X0,3-X0,5-X1,0 (m): Throw for terminal
2300 48 136 >30 >30 24 16,4
INJ. 45° full saddle tap for lateral connection to velocity of the air stream of 0.3, 0.5,
2500 32 35 >30 >30 19,1 9,6
exposed circular duct. One adapter per diffuser. and 1.0 m/s, respectively, in isothermal
20 3300 40 61 >30 >30 25,2 12,7
conditions (∆T = 0º C).
4250 48 102 >30 >30 >30 16,3
Vk (m/s): Effective velocity.
116 117
DF-49-MT-3 Catalogue Series DF-49-MT-3
General dimensions
A
= J x 100 =
LxH
N x 100
B
=
L = Nominal length (opening)
DF-49-MT-3-SB H = Nominal heigth (opening)
Selection table
Multinozzle
325
Column No.
3
A
353
J
2
Diffuser
Size
Q (m3/h) LwA [dB(A)]
150 24
∆Pst (Pa)
71
X0,3 X0,5 X1,0
12.1 7.2 3.6
425
525
4
5
453
553
3
4
325 x 125 210 32 128 16.2 9.7 4.9 625 6 653 5
280 40 232 21.8 13.1 6.6 725 7 753 6
230 24 60 14.4 8.6 4.3 825 8 853 7
525 x 125 320 32 109 19.3 11.6 5.8 925 9 953 8
420 40 196 26.0 15.6 7.8 1025 10 1053 9
270 24 56 15.2 9.1 4.6
Unit mm
DF-49-MT-3 625 x 125 370 32 102 20.5 12.3 6.2
500 40 186 27.7 16.6 8.3
350 24 51 16.8 10.1 5.0 H Range No. B N
Product description DF-49-MT-3-CC. Long throw multinozzle for circular 825 x 125 470 32 93 22.7 13.6 6.8
duct. Maximum two rows of nozzles. 630 40 169 >30 18.3 9.1 125 1 153 0
Multinozzle plate with high induction and long throw. 225 2 253 1
420 24 48 18.1 10.9 5.4
KOOLAIR, model DF-49-MT-3, dimensions _ x _, 1025 x 125 560 32 87 24.4 14.6 7.3 325 3 353 2
with _ nozzles of _ rows. The nozzles can be pointed 760 40 157 >30 19.7 9.9 Unit mm
separately, in all directions, up to a maxium of 30º, Mounting 270 24 56 15.2 9.1 4.6
they are made in ABS (VO). Plate made in steel T. Plate with screw holes. Ready to be screwed. 325 x 225 370 32 102 20.5 12.3 6.2
sheet. finished painted in RAL 9010, 9005 or 9006. 500 40 186 27.7 16.6 8.3
MM. Mounting frame. Fixed with clips.
Recomended instalation height between 2.5 With plenum box made of galvanised steel sheet, 420 24 48 18.1 10.9 5.4
and 6 m. 525 x 225 560 32 87 24.4 14.6 7.3
with side or top spigot connection (-PE21/20). (-A.
760 40 157 >30 19.7 9.9
internally insulated).
490 24 45 19.3 11.6 5.8
Other models 625 x 225 660 32 82 25.9 15.6 7.8 LEGEND
890 40 148 >30 21.0 10.5
DF-49-MT-3-E. Long throw multinozzle to be Q (m3/h): Air flow.
620 24 41 21.2 12.7 6.4 LwA [dB(A)]: Sound power level.
installed in plaster ceiling. Plate´s width of 1.5 mm.
DF-49-MT-3-CC 825 x 225 840 32 75 28.6 17.2 8.6
DF-49-MT-3-SB. Long throw multinozzle without ∆Pst (Pa): Estatique pressure loss.
1130 40 135 >30 23.1 11.6
frame, plate´s width of 6 mm. Rows Minimum duct Maximum duct X0,3-X0,5-X1,0 (m): Throw for terminal
750 24 38 22.9 13.7 6.9 velocity of the air stream of 0.3, 0.5,
DF-49-MT-3-CB. Long throw multinozzle with frame. 1 315 900 1025 x 225 1010 32 69 >30 18.5 9.3
and 1.0 m/s, respectively, in isothermal
2 630 1400 1360 40 126 >30 24.9 12.5
conditions (∆T = 0º C).
118 119
DF-49-MT-3-I/R General dimensions
= J x 100 = 33
6
Nozzles L H A B J
3T 330 192 353 305 2
74.5
4T 430 192 453 405 3
L = Length (opening) 5T 530 192 553 505 4
HxL
225
H = Heigth (opening) 6T 630 192 653 605 5
15
75
7T 730 192 753 705 6
B
8T 830 192 853 805 7
24 24
A 9T 930 192 953 905 8
10T 1030 192 1053 1005 9
Unit mm
= J x 100 = 33
6
Nozzles L H A B J
74.5
3T 330 367 353 305 2
4T 430 367 453 405 3
100
L = Length (opening) 5T 530 367 553 505 4
HxL
400
H = Heigth (opening) 6T 630 367 653 605 5
7T 730 367 753 705 6
150
15
8T 830 367 853 805 7
24
24 B 24
A
10T 1030 367 1053 1005 9
Unit mm
Diffuser Selection table
supply / return Supply Return
Size Q (m3/h) LwA [dB(A)] ∆Pst (Pa) X0,3 X0,5 X1,0 LwA [dB(A)] ∆Pst (Pa)
150 24 71 12,1 7,2 3,6 23 7
330 x 192 210 32 128 16,2 9,7 4,9 31 15
280 40 232 21,8 13,1 6,6 39 26
230 24 60 14,4 8,6 4,3 22 6
530 x 192 320 32 109 19,3 11,6 5,8 30 11
420 40 196 26,0 15,6 7,8 37 19
DF-49-MT-3-I/R 270 24 56 15,2 9,1 4,6 22 6
630 x 192 370 32 102 20,5 12,3 6,2 30 10
Product description
500
350
40
24
186
51
27,7 16,6 8,3
16,8 10,1 5,0
38
23
19
5
KOOLAIR multi-nozzle diffuser, model DF-49-MT-3-E-I/R-45. Long reach multi-nozzle 830 x 192 470 32 93 22,7 13,6 6,8 30 10
DF-49-MT-3-I/R, with linear grille for supply and return diffuser set in a flat 1.5 mm thick plate for installation 630 40 169 >30 18,3 9,1 38 17
integrated in plate, dimensions _x_ mm. Incorporates in plaster. Includes a linear return grille with blades at 420 24 48 18,1 10,9 5,4 21 4
1 or 2 rows of nozzles individually adjustable in all 45º. 1030 x 192 560 32 87 24,4 14,6 7,3 28 7
directions up to a maximum of 30°, manufactured in DF-49-MT-3-SB-I/R-45. Long reach multi-nozzle 760 40 157 >30 19,7 9,9 36 14
ABS (VO) and finished in RAL 9010, 9005 or 9006. diffuser without frame and a 6 mm thick plate.
Includes linear grille without frame for return air with 270 24 56 15,2 9,1 4,6 25 7
Includes a linear return grille with blades at 45º.
blades fixed at an angle of 0º or 45º. Plate made of 330 x 367 370 32 102 20,5 12,3 6,2 33 13
sheet steel, finished in RAL colour of choice. Option to 500 40 186 27,7 16,6 8,3 41 25
incorporate regulating damper on supply (-RFS06) or 420 24 48 18,1 10,9 5,4 25 6
return (-O). Recommended installation height between
2.5 and 6 m.
Mounting 530 x 367
560
760
32
40
87
157
24,4 14,6 7,3
>30 19,7 9,9
33
41
11
21
T. Pre-drilled plate ready for fastening with screws. 490 24 45 19,3 11,6 5,8 24 5
LEGEND
PFS. Fixed front connection plenum for supply and/ 630 x 367 660 32 82 25,9 15,6 7,8 31 9
Models or return air, at 180º with respect to the air outlet. 890 40 148 >30 21,0 10,5 39 17 Q (m3/h): Air flow.
DF-49-MT-3-E-I/R. Long reach multi-nozzle diffuser (-A. Interior insulated) Consult for design. 620 24 41 21,2 12,7 6,4 24 5 LwA [dB(A)]: Sound power level.
set in a flat 1.5 mm thick plate for installation in plaster. PFL. Fixed lateral connection plenum for supply and/ 830 x 367 840 32 75 28,6 17,2 8,6 32 9 ∆Pst (Pa): Estatique pressure loss.
Includes a linear return grille with blades at 0º. or return air, at 180º with respect to the air outlet. 1130 40 135 >30 23,1 11,6 39 15 X0,3-X0,5-X1,0 (m): Throw for terminal
DF-49-MT-3-SB-I/R. Long reach multi-nozzle diffuser (-A. Interior insulated) Consult for design.
750 24 38 22,9 13,7 6,9 24 4 velocity of the air stream of 0.3, 0.5,
without frame and a 6 mm thick plate. Includes a linear 1030 x 367 1010 32 69 >30 18,5 9,3 32 8 and 1.0 m/s, respectively, in isothermal
return grille with blades at 0º. 1360 40 126 >30 24,9 12,5 39 14
conditions (∆T = 0º C).
120 121
DGV Catalogue Series DGV
General dimensions
F
ØA
ØC
Nominal Ø A Ø C F
Variable
250
315
425
500
249
314
440
440
geometry
400
500
600
730
399
499
440
440
diffuser 630 900 629 580
Unit mm
LEGEND
Q (m3/h): Air flow.
LwA [dB(A)]: Sound power level.
∆Pt (Pa): Total pressure loss.
Y (m): Vertical penetration for a terminal air vein velocity of 0.20 m/s and ∆T = +10º C.
X (m): Throw for a maximum velocity of 0.25 m/s at the occupied zone, with ceiling effect.
122 123
DVP Catalogue Series DVP
General dimensions
C ØB
Model OPENING Ø A Ø B C
160 215 159 253 155
OPENING
200 255 199 303 174
ØA
250 305 249 353 200
315 370 314 418 240
355 410 354 458 250
400 455 399 503 265
500 555 499 600 320
630 685 629 730 380
800 855 799 900 555
Unit mm
Adjustable
Selection table Selection table
blade variable (Vertical discharge) (Horizontal discharge)
geometry Size
Tamaño Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Y (m) Size
Tamaño Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
diffuser
160
160
220
25
35
12
23
1,5
2,1
160
125
175
25
35
23
44
1,0
1,4
310 45 45 3,0 250 45 90 2,1
250 25 12 1,7 190 25 21 1,3
200 350 35 23 2,4 200 260 35 39 1,8
465 45 41 3,2 310 45 55 2,1
Product description Other models 475 30 24 2,2 330 30 25 2,1
250 575 35 36 2,7 250 400 35 36 2,5
The adjustable blade variable geometry diffuser, DVP-TR. Variable geometry diffuser autoregulated by 675 40 49 3,1 475 40 51 3,0
KOOLAIR, model DVP provides an optimum thermal element. (From Ø250 to Ø630). 950 35 30 3,2 675 35 45 3,7
discharge in cooling (horizontal discharge) and DVP-MT. Variable geometry diffuser with motorised 315 1.250 45 52 4,2 315 925 45 85 4,7
heating (vertical discharge) enabling the diffuser to mechanism. (From Ø160). 1.500 50 75 5,0 1.080 50 116 5,4
meet the required comfort criteria. Made in steel DVP-Q. Diffuser of variable blade geometry built into 1.050 35 23 2,6 750 35 36 3,5
sheet. Finished painted in RAL to define. 595x595-mm plate (up to Ø500). 355 1.475 45 45 3,7 355 1.050 45 71 4,9
1.750 50 63 4,3 1.200 50 93 5,6
DVP-Q-TR. Diffuser of variable blade geometry, self-
1.550 40 30 3,4 1.000 40 42 4,6
regulating, fitted with thermal component built into
Mounting 595x595-mm plate. (Ø250 to Ø500).
400 1.800 45 41 4,0 400 1.200 45 61 5,6
2.150 50 58 4,7 1.400 50 83 6,5
PCFL-RE. Side entry plenum box with volumen
2.400 40 25 4,1 1.400 40 32 5,2
control damper in the spigot conection. 500 2.800 45 35 4,7 500 1.700 45 47 6,3
3.400 50 51 5,7 2.000 50 65 7,4
3.750 40 20 4,5 2.000 40 26 5,2
630 4.500 45 29 5,4 630 2.400 45 37 6,2
5.400 50 42 6,5 2.800 50 51 7,3
7.300 45 23 6,2 3.300 45 30 6,2
800 8.500 50 32 7,2 800 3.900 50 42 7,3
9.500 55 40 8,0 4.500 55 55 8,5
LEGEND Y (m): Throw for a terminal velocity of the air stream of 0.25 m/s, with
Q (m /h): Air flow.
3 ∆T = +10º C.
LwA [dB(A)]: Sound power level. X (m): Throw for a maximum velocity of 0.25 m/s at the occupied zone,
∆Pt (Pa): Total pressure loss. in isothermal conditions ∆T = 0º C.
124 125
Square
diffusers
NEW
56-FR (132)
52-FR-4-STAMP (130) KLD-Q-I/R (138)
54-FR-I-4 (134)
KCD-Q (140)
Convention Centre
5
(Dublin – Ireland)
Variable geometry diffuser DGV,
linear diffusers LK-70,
long-throw diffuser DF-47
and step swirl diffusers DF-CP-MT.
50-FR-4 Catalogue Series 50
General dimensions
LxH
82
(L + 144) x (H + 144)
46
(L + 75) x (H + 75)
SM 59-MM
diffuser
128 129
52-FR-4-STAMP Catalogue Series 50
General dimensions (side connection plenum)
A B 80
15
ØD
C
75
A
Square
225
300
290
365
270
345
249
269
159
199
diffuser
375
450
440
515
420
495
339
404
249
314
500 590 570 404 314
525 590 570 404 314
600 665 645 444 354
Unit mm
Product description
Stamped square diffuser with stationary central core
Selection table
S
Mounting
300
340
460
24
32
8
14
1,5
2,0
2,2
2,9
PDS-RE. Top connection plenum box made in 650 40 28 2,8 4,2
galvanised steel sheet, without insulation. Dimensions 435 24 4 1,8 2,4
PDL-RE. Side connection plenum box made in 375 590 32 7 2,4 3,3
Nominal A P S X 840 40 15 3,4 4,7
galvanised steel sheet, without insulation.
150 215 295 182 190 525 24 3 1,9 2,4 LEGEND
PDS-A-RE. Top connection plenum box made in
225 290 370 257 265 450 710 32 6 2,6 3,2
galvanised steel sheet, insulated. Q (m3/h): Air flow.
300 365 445 332 340 990 40 11 3,6 4,5
PDL-A-RE. Side connection plenum box made in LwA [dB(A)]: Sound power level.
375 440 520 407 415 715 24 4 2,3 2,4
galvanised steel sheet, insulated. ∆Pt (Pa): Total pressure loss.
450 515 595 482 490 500 / 525 990 32 7 3,2 3,4
1350 40 13 4,3 4,6 X (m): Throw for a maximum velocity
500 590 625 557 565
1250 24 6 3,4 3,1 of 0.25 m/s at the occupied zone
525 590 670 557 565
600 1750 32 11 4,7 4,3 ∆T = –10 ºC (cold), installed at a
600 665 745 632 640
2500 40 23 6,8 6,2 height of 3m.
Unit in mm Vk (m/s): Effective velocity.
130 131
56-FR General dimensions
ØA
25
ØD
C
H
ØD
110
ExE
E 80
ØD
C
POSITION 1 POSITION 2
15
A
6
B
Square Custom plenums available to suit reduced heights above false ceilings.
160 - 300
A
251
B
299
C
250
ØD
160
E
256
diffusers
200 - 400
250 - 500
351
451
399
499
300
355
200
250
356
456
315 - 600 547 595 425 315 552
315 - 625 576 624 425 315 581
Unit mm
Product description Other models
Square perforated face diffuser, Koolair, model 54-FR-I-1. One direction square perforated face
56-FR-I-4, dimension _x_. Incorporates interior diffuser of dimension LxH.
directional plates for supplying air in four directions. 54-FR-I-2. Two directions square perforated face
It incorporates plenum box made in galvanised steel diffuser of dimension LxH.
sheet. 54-FR-I-0. Square perforated face diffuser for
Finished painted in any RAL colour upon request. vertical air supply, of dimension LxH.
Selection table
It’s possible to install it in false ceilings 54-FR-R. Square perforated face diffuser for Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Vk (m/s) X (m)
of 600x600 mm. returning air, of dimension LxH.
140 24 7 1.3 0.9
Recommended installation height between 2.5
300 x 300 180 32 11 1.7 1.1
and 4 m. 230 40 18 2.1 1.4
250 24 6 1.2 1.1
Mounting 400 x 400 320 32 9 1.5 1.4
410 40 15 1.9 1.8
390 24 5 1.1 1.3
PFS. Top connection plenum box made in LEGEND
500 x 500 500 32 8 1.4 1.7
galvanised steel sheet. Q (m3/h): Air flow.
640 40 14 1.8 2.2
PFL. Side connection plenum box made in LwA [dB(A)]: Sound power level.
550 24 5 1.1 1.5
galvanised steel sheet. ∆Pt (Pa): Total pressure loss.
600 x 600 700 32 7 1.3 2.0
PFS-A. Top connection plenum box internally X (m): Throw for a maximum velocity
900 40 12 1.7 2.5
insulated made in galvanised steel sheet. of 0.25 m/s at the occupied zone
PFL-A. Side connection plenum box internally 600 24 5 1.0 1.6
∆T = –10 ºC (cold), installed at a
625 x 625 760 32 7 1.3 2.0
insulated made in galvanised steel sheet. height of 3m.
980 40 12 1.7 2.6
Vk (m/s): Effective velocity.
134 135
KLD-Q-PANEL Catalogue Series KFD-KLD
General dimensions
C
H
16 A
NOMINAL
Nominal N. of slots Ø D A C H
Square
675 x 675 1
2, 3 and 4
199
670
249
661 320
diffuser Unit mm
Other models
KLD-Q. Four ways diffuser of 1 to 4 slots, central
core made in steel sheet painted in RAL colour upon
request.
KLD-Q-FLASH. Four ways diffuser of 2 slots, with
luminaires integrated at the central core.
136 137
KLD-Q-I/R Catalogue Series KFD-KLD
General dimensions
C
ø 248
ø 248
375
16
A
Nominal N. of slots A C
diffuser
Other models
KLD-Q-I/R-PF. Four-way square diffuser for supply
and extract air with folding central core and frame to
hold filter.
138 139
KCD-Q General dimensions
B B
15
øD
H
8
AxA
Nominal A B ØD H
Other models
KCD-Q-I/R. Four-way square diffuser with 2 or 3
ways, to integrate supply and extract air in the same
plate. Perforated sheet metal central core.
KCD-Q-I/R-PF. Four-way square diffuser with 2 or 3
ways, to integrate supply and extract air in the same
plate. Foldable perforated sheet metal central core
with frame to hold filter.
KCD-Q-FLASH. Four-way square diffuser with 2
ways, with integrated luminaire in the central core.
140 141
Linear
diffusers
LK-70 (144) DF-KR (158)
NEW
DF-KLT (160)
LK70-C (146) NEW
KLR-NARROW (162)
S-74-18 (148)
KLR (164)
S-74-25 (150)
KLR-Curved (166)
S-72-21/18 (152)
DF-LIT-E-3.0 (170)
KFD (156)
6
long throw multinozzle MT3.CC-T,
outside air inlet louvres 210-TA,
overpressure dampers 230-SP,
air volume control dampers AOBD-102-E
and rectangular fire dampers SFR2-TH-70.
LK-70 General dimensions
E (L – 3) B 50 B 50
15
15
ØD
ØD
H
H
C C-8
(L + 15) x C
Linear slot
A A-10
LK70 LK70-S
diffuser
From active length > 1185 mm: 2 SPIGOTS
144 145
LK70-C Catalogue Series LK-70
Selection table (Flow rate per linear metre of diffuser)
Linear slot
625 45 15 7.1
400 30 4 4.0
490 35 6 4.9
diffuser
LK70-C 1000-6
595
750
40
45
8
13
6.2
7.5
integrated
LK70-C 1000-10
450
560
30
35
3
5
4.1
5.1 LEGEND
into a circular
690
870
40
45
8
12
6.4
7.9 Q (m3/h): Air flow.
LwA [dB(A)]: Sound power level.
duct
500 30 3 3.0
620 35 5 5.2 ∆Pt (Pa): Total pressure loss.
LK70-C 1000-12
780 40 7 6.6 X (m): Throw for a maximum velocity
960 45 11 8.1 of 0.25 m/s at the occupied zone
570 30 3 4.3 ∆T = 0 ºC (isothermal conditions),
700 35 4 5.4 installed at a height of 3m.
LK70-C 1000-14
880 40 6 6.8
Product description Incorporates slide type damper. 1070 45 9 8.2
The data presented by meter and duct
Interior insulated (optional).
Supply linear slot diffuser, model LK70-C, suitable The Selection Table shows a summary of dimensions. Other sizes available. velocity of Vp < 6 m/s
Consult the Sales Department.
for variable and constant volume. Integrated into
a circular duct made in galvanised sheet steel, Other models
equipped with adjustable blades by means of a LK-70-AC. Linear diffuser integrated in curved plate to
Dimensions
wheel mechanism, allowing multiple air patterns. adapt to circular duct. Ø Nominal Nº of Rows D
The diffuser is suitable for large airflows at low Incorporates slide type damper.
125 2 – – – – – – 123
velocities into the occupied zone. Recommended
160 2 4 – – – – – 158
installation height between 2.5 and 4m. 200 2 4 – – – – – 198
225 2 4 – – – – – 223
General dimensions
250
300
2
2
4
4
–
6
–
–
–
–
–
–
–
–
248
298
315 2 4 6 – – – – 313
L 355 2 4 6 8 – – – 353
75 40 400 2 4 6 8 – – – 398
450 2 4 6 8 – – – 448
500 2 4 6 8 10 12 14 498
630 2 4 6 8 10 12 14 628
710 2 4 6 8 10 12 14 708
ØD
ØD
146 147
S-74-18/S-72-18 Catalogue Series 70.1
General dimensions
L–3 B B
ØD
ØD
H
H
C C
L + 25
Linear Slot Custom plenums available to suit reduced heights above false ceilings.
Nº of Slots A B C Ø D H
Diffuser
1
2
75
111
40
76
48
84
124
159
225
275
3 147 112 120 199 325
4 183 148 156 199 325
5 219 184 192 249 375
6 255 220 228 249 375
Unit mm
148 149
S-74-25/S-72-25 Catalogue Series 70.1
General dimensions
L–3 B B
ØD
ØD
H
H
C C
L + 25
25 28,5 25 18
28,5 L = ACTIVE LENGTH
A A-21
S72-25 S72-25-18
FROM ACTIVE LENGTH > 1174 mm: 2 SPIGOTS FIXED PLENUM AND WITOUT PLENUM = C
REMOVABLE PLENUM FOR OPENING SIZE 18 FRAME 28.5 = C + 18
Linear Slot Custom plenums available to suit reduced heights above false ceilings.
Nº of Slots A B C Ø D H
Diffusers
1
2
82
125
47
90
55
98
124
159
225
275
3 168 133 141 199 325
4 211 176 184 199 325
5 254 219 227 249 375
6 297 262 270 249 375
Unit mm
150 151
S-72-21/18 Catalogue Series 70.1
General dimensions
(L + 15) x C
B 50
L-3
15
ØD
H
C
18 21
L = ACTIVE LENGTH 17
A
S-72-21-18
Active length > 1199 mm: 2 SPIGOTS
Linear diffuser Custom plenums available to suit reduced heights above false ceilings.
Nº of Slots A B C Ø D H
1 57 80 53 159 275
2 96 119 92 199 325
3 135 158 131 199 325
4 174 197 170 199 325
5 213 236 209 249 375
Product description Mounting 6 252 275 248 249 375
Linear diffuser with narrow external frame and air PFL-RL. Fixed side connection plenum box, without Unit mm
passage of 21 mm per slot, Koolair S-72-21/18 internal insulation made in galvanised sheet steel.
model, of _slots, of length _ mm with moveable PFL-A-RL. Fixed side connection plenum box,
directional slats for lateral or vertical air discharge. internally insulated made in galvanised sheet steel.
Lateral connection plenum box in galvanized PDL-RL. Removable, by bridges, side connection
steel sheet; includes volume control damper. plenum box, without insulation and made in
Manufactured of extruded aluminium sections.
Natural anodized aluminum finish or painted in RAL
galvanised sheet steel. Selection table (Flow rate per linear metre of diffuser)
PDL-A-RL. Removable, by bridges, side connection
colour upon request. plenum box, internally insulated and made in Nº of Slots Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) VK(m/s)
Recommended installation height of 2.5 to 4 m. galvanised sheet steel.
115 24 8 2,4 2,7
PM. Mounting bridge.
1 1000 165 32 17 3,5 3,9
210 40 28 4,4 5,0
Other models Note: Possible to form continuous lines (Maximum 190 24 6 2,8 2,3
LEGEND
S-72-21-Plate. Linear diffuser, built into plate of length per section 2000 mm). 2 1000 255 32 10 3,8 3,0
345 40 19 5,1 4,1 Q (m3/h): Air flow.
dimensions LxH, for installation in modular drop On request, top plenum available insulated/
LwA [dB(A)]: Sound power level.
ceiling. uninsulated (PFS-A/PFS / PDS-A/PDS). 275 24 5 2,8 2,2
∆Pt (Pa): Total pressure loss.
S-71-21-18. Linear diffuser with narrow external 3 1000 370 32 10 3,7 2,9
X (m): Throw for a maximum velocity
frame and air passage of 21 mm per slot. For 485 40 16 4,9 3,9
of 0.25 m/s at the occupied zone
returning air. 340 24 5 3,6 2,0
∆T = 0 ºC (isothermal conditions),
4 1000 450 32 8 4,7 2,7
installed at a height of 3 m.
600 40 14 6,3 3,6
Vk (m/s): Effective velocity.
The Selection Table shows a summary of dimensions. Other sizes available.
Consult the Sales Department.
152 153
KLD Catalogue Series KFD-KLD
General dimensions
L + 25
L–2 B 50
ØD
2 Spigots for Lenghts
bigger than 1175 mm.
H
R = End caps
28.5 mm (Standard)
8.7 mm (Under
C
R L R request)
A
Linear Slot
Custom plenums available to suit reduced heights above false ceilings.
Diffusers
Nº of Slots
1:0 / 0:1
A
60
B
79
C
50
Ø D
159 275
H
KLD-FF. Linear diffuser with filterholder hinged galvanised sheet steel. 230 24 4 3,2 3,5
LEGEND
2 1000 300 32 8 4,3 4,6
toward the outside. For returning air. PBL-A-RE. Removable, by screws, side connection Q (m3/h): Air flow.
400 40 14 5,8 6,2
KLD-Plate. Linear diffuser integrated in plate of plenum box, internally insulated and made in LwA [dB(A)]: Sound power level.
300 24 3 3,5 3,1
dimensions LxH, to be installed in false ceiling. galvanised sheet steel. ∆Pt (Pa): Total pressure loss.
3 1000 400 32 6 4,7 4,1
PM. Mounting bridge. 550 40 11 6,2 5,5
X (m): Throw for a maximum velocity
Note: Possible to form continuous lines (Maximum RFS06. Include a volume control damper. of 0.25 m/s at the occupied zone
360 24 3 3,7 2,8
length per section 2000 mm). ∆T = 0 ºC (isothermal conditions),
4 1000 470 32 5 4,9 3,7
On request, top plenum available insulated/ Note: Connection plenum box can be equipped installed at a height of 3 m.
650 40 9 6,6 5,0
uninsulated (PFS-A/PFS / PDS-A/PDS). with VCD on the spigot accessible from the room, Vk (m/s): Effective velocity.
The Selection Table shows a summary of dimensions. Other sizes available.
available upon request.
Consult the Sales Department.
154 155
KFD Catalogue Series KFD-KLD
General dimensions
L + 25
B 80
L–2
ØD
2 Spigots for Lenghts
H
bigger than 1175 mm.
R = End caps
28.5 mm (Standard)
8.7 mm (Under
R L R C
request)
A
Linear slot
Nº of Slots
1
A
80
B
83
C
70
Ø D
159
H
275
diffuser
2
3
130
181
134
185
121
171
199
249
330
330
4 232 236 222 249 330
Unit mm
156 157
DF-KR Catalogue Series DF-KR
General dimensions
1167 288 80
Ø249
315
1195 295
Selection table
LEGEND
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
4 Way Linear
Q (m3/h): Air flow.
210 24 4 1.9
LwA [dB(A)]: Sound power level.
1 300 32 8 2.7
∆Pt (Pa): Total pressure loss.
slot diffuser
420
330
40
24
16
5
3.8
1.6
X (m): Throw for a maximum velocity
of 0.25 m/s at the occupied zone
2 470 32 9 2.3 ∆T = –10 ºC (cold), installed at a
670 40 19 3.2
height of 2.8 m.
Vk (m/s): Velocidad efectiva.
Other models
DF-KR-E. Linear diffuser integrated in plate of
1227x327 mm for plasterboard ceiling.
158 159
DF-KLT General dimensions
1098 232 80
15
32.5
ØD
H
14 1199 14
265
299
31
integrated in plate
55 R R 55
1100 299
Size Ø D H
15 159 230
20 199 270
33 249 320
40 249 320
50 314 (oval) 320
KOOLAIR double hidden linear diffuser integrated PFL-RE. Side connection plenum box without
in 1199x299 mm rectangular plate with adjustable internal insulation, made in galvanised sheet steel.
deflector blades, model DF-KLT, with _ air passage PFL-A-RE. Side connection plenum box internally
slot. Characterised by the lack of profile on show. insulated, made in galvanised sheet steel.
Each diffuser has an adjustable blade to discharge air PFS-RE. Top connection plenum box, without
horizontally and vertically with multiple combinations internal insulation, made in galvanised sheet steel.
PFS-A-RE. Top connection plenum box, internally Selection table
possible. Incorporates a lateral connection plenum
complete with regulating damper in the inlet spigot. insulated, made in galvanised sheet steel.
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) Vk (m/s)
Diffusers manufactured from aluminium profiles
160 24 6 2,0 2,0
painted matt black (RAL 9005) and sheet steel plate 15 220 32 10 2,7 2,8
painted in RAL colour of choice. Recommended 330 40 22 3,9 4,0
installation height between 2.5 and 4 m. 210 24 10 2,1 1,8
20 300 32 11 3,0 2,5
420 40 22 4,2 3,5
320 24 8 2,4 1,6 LEGEND
Other models 33 460 32 17 3,5 2,3 Q (m3/h): Air flow.
620 40 32 4,7 3,1
DF-KLT-E. Linear diffuser integrated in 1227x327 LwA [dB(A)]: Sound power level.
plate for suspended drywall ceilings. 360 24 6 2,5 1,6 ∆Pt (Pa): Total pressure loss.
40 520 32 12 3,6 2,3 X (m): Throw for a maximum velocity
700 40 21 4,9 3,0
of 0.25 m/s at the occupied zone
440 24 6 2,8 1,7 ∆T = –10 ºC (cold), installed at a
50 600 32 11 3,8 2,3
height of 2.8 m.
800 40 19 5,0 3,1
Vk (m/s): Velocidad efectiva.
160 161
KLR-NARROW General dimensions KLR-NARROW
(L + 1) x C (HOLE) 85 80
L–3 70 80
10
10
Ø 123
Ø 98
200
175
46
46
L 15 30
No. of slots C
1 16
2 31
10
10
Ø 123
Ø 98
200
175
Product description Other models
KLR-NARROW-CB. With 12,5 mm wide frame.
KOOLAIR high-induction slot diffuser with a high
46
46
1.2
KLR-NARROW-Curved. Linear slot diffuser forming
1.2
level of aesthetics, model KLR-NARROW with 1
40 55
or 2-openings; length _ mm, air passage through curved lines. 17 L 17
opening 8 mm, complete with movable directional 2 Spigots for Lenghts bigger than 1199 mm.
blades every 100 mm to configure air discharge Mounting Custom plenums available to suit reduced heights above false ceilings.
horizontally, vertically or at an angle. Ideal for
installation in suspended ceilings with a slot width PFL-RL. Fixed side connection plenum box No. of slots C
equal to or greater than 15 mm due to its small uninsulated.
1 26
dimensions. Includes sheet steel fixed plenum for PFL-A-RL. Fixed side connection plenum box
2 41
lateral connection. Made from extruded aluminium insulated.
Unit in mm
profiles. Anodised aluminium finish or painted in PDL-RL. Removable side connection plenum box
RAL colour (to be defined). Directional blades made uninsulated. Selection table (Flow rate per linear metre of diffuser)
of plastic, standard in RAL 9005. Recommended PDL-A-RL. Removable side connection plenum box
installation height between 2.5 and 4 m. insulated. No. of slots Dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) VK(m/s)
PM. Mounting bridges. LEGEND
45 24 9 1,3 3,2
Note: Possible to form continuous lines (Maximum 1 1000 65 32 17 1,8 4,5 Q (m3/h): Air flow.
LwA [dB(A)]: Sound power level.
length per section 2000 mm). 90 40 33 2,4 6,3
∆Pt (Pa): Total pressure loss.
On request, top plenum available insulated/ 85 24 7 1,7 2,9
X (m): Throw for a maximum velocity
uninsulated (PFS-A/PFS / PDS-A/PDS). 2 1000 115 32 14 2,3 4,0
of 0.25 m/s at the occupied zone.
155 40 26 3,1 5,5
∆T = -10 ºC (cold), installed at 2.8 m of
The Selection Table shows a summary of dimensions. Other sizes available. height.
Consult the Sales Department. Vk (m/s): Effective velocity.
KLR Catalogue Series KLR
General dimensions (KLR-15)
L + 10
L–3 B 80
15
ØD
H
C
41
10 L 10 15
2 Spigots for Lenghts
A
bigger than 1200 mm.
Linear Slot Custom plenums available to suit reduced heights above false ceilings.
1 55 71 45 124 225
2 81,5 97,5 71,5 159 275
3 108 124 98 199 325
4 135 151 125 199 325
Linear slot diffuser, KOOLAIR, model KLR, of _ slots, PFL-RL. Fixed side connection plenum box
length _mm with 15 or 24 mm wide air passage uninsulated.
adjustable vanes by rotation for horizontal, inclined PFL-A-RL. Fixed side connection plenum box
or vertical discharge. Incorporates side connection insulated.
plenum box made in sheet steel. PDL-RL. Removable side connection plenum box
Frames made in extruded aluminium. Finished in uninsulated.
anodised aluminium or painted in RAL colour upon PDL-A-RL. Removable side connection plenum box
Selection table KLR-15 (Flow rate per linear metre of diffuser)
164 165
KLR
General dimensions (KLR-24) Selection table KLR-24 (Flow rate per linear metre of diffuser)
15
1 1000 115 32 16 4,9 3,9
160 40 31 6,8 5,4
150 24 7 4,5 2,5
2 1000 210 32 14 6,3 3,5
ØD
290 40 26 8,7 4,9
H
250 24 8 6,1 2,8
C
3 1000 350 32 17 8,6 3,9
480 40 31 11,8 5,4
51
290 24 6 6,2 2,4
10 L 10 24
A 2 Spigots for Lenghts 4 1000 400 32 12 8,5 3,3
bigger than 1200 mm. 560 40 24 11,9 4,7
LEGEND
KLR-24 removable plenum
Q (m3/h): Air flow.
Nº of Slots A B C Ø D H LwA [dB(A)]: Sound power level.
1 70 86 60 124 225 ∆Pt (Pa): Total pressure loss.
2 112.5 128.5 102.5 159 275 X (m): Throw for a maximum velocity of 0.25 m/s at the occupied zone.
3 155 171 145 199 325 ∆T = 0 ºC (isothermal conditions), installed at 2.8 m of height.
4 197.5 213.5 187.5 199 325 Vk (m/s): Effective velocity.
Unit mm
Diffuser KLR-Curved
166 167
HIDE Catalogue Series HIDE
General dimensions
L–3 B 80
ØD
H
21 2 Spigots for Lenghts
1.5 L 1.5
A bigger than 1199 mm.
Diffuser
1
2
38.5
77.5
80
119
124
159
211
246
3 116.5 158 199 286
4 155.5 197 199 286
Unit mm
directional blades allows directing the airflow from 0° 110 24 8 1.9 2.6
to 180°. 1 1000 150 32 14 2.6 3.6
Incorporates connection plenum box made in steel
Mounting 200 40 25 3.5 4.8
sheet with regulation damper in the spigot. PFL-RL. Fixed side connection plenum box 175 24 5 2.2 2.1
LEGEND
Finished in anodised aluminium or painted in RAL uninsulated. With damper. 2 1000 250 32 10 3.1 3.0
Q (m3/h): Air flow.
PFL-A-RL. Fixed side conection plenum box, 320 40 16 4.0 3.8
colour upon request. The directional blades are in LwA [dB(A)]: Sound power level.
black. insulated. With damper. 240 24 4 2.4 1.9
∆Pt (Pa): Total pressure loss.
PFS-RL. Fixed top connection plenum box 3 1000 320 32 7 3.2 2.5
Recomended instalation height between 2.5 and 4 X (m): Throw for a maximum velocity
425 40 13 4.3 3.4
m. uninsulated. With damper. of 0.25 m/s at the occupied zone
PFS-A-RL. Fixed top conection plenum box, 275 24 3 2.4 1.6
∆T = 0 ºC (isothermal conditions),
4 1000 360 32 5 3.2 2.2
Note: Possible to form continuous lines (Maximum insulated. With damper. installed at 2.8 m of height.
500 40 10 4.4 3.0
length per section 2000 mm). ESD. Supports for hanging diffuser. Vk (m/s): Effective velocity.
The Selection Table shows a summary of dimensions. Other sizes available.
Consult the Sales Department.
168 169
DF-LIT-E-3.0 General dimensions
A
15
A B 50
ØD
F
15
47.4
A’
13
L+2 1 Spigot for L ≤ 1200 mm
2 Spigots for L > 1200 mm
L = AIR PASSAGE SECTION A-A’
H
12.5
1800 1800 1798 2
Invisible linear
2000 2000 1998 Plasterboard screw Connection profile sections
600 600 598 Fill filler HOLE and fixing to plasterboard
S
1000 1000 998 1
slot diffuser
1200 1200 1198
20 132 160 275
1500 1500 1498
1800 1800 1798 2
HOLE
2000 2000 1998 HOLE S H
600 600 598
1000 1000 998 1 15 70,5 47,4
1200 1200 1198 20 75,5 47,4
33 145 160 275
1500 1500 1498
33 88,5 47,4
1800 1800 1798 2
40 99,5 47,4
Product description Other models 2000
600
2000
600
1998
598 50 105,5 47,4
1000 1000 998 1
Invisible linear slot diffuser with good aesthetic, CROSS-DF-LIT-E-3.0. Decorative invisible linear 1200 1200 1198 Unit mm
40 152 200 315
KOOLAIR, model DF-LIT-E-3.0, length _ mm and diffuser in the shape of a cross at 90° devised to 1500 1500 1498
1800 1800 1798 2
slot __ mm for air passage. It is characterized by the form a continuous line with other active or decorative 2000 2000 1998
absence of visible profiles. With an adjustable blade sections. 600 600 598
that allows both vertical and horizontal discharge. T-DF-LIT-E-3.0. Decorative invisible linear diffuser 1000
1200
1000
1200
998
1198
1
Incorporates side plenum box with manual control in the shape of a “T” at 90° devised to form a 50
1500 1500 1498
162 200 315
damper accessible from room. continuous line with other active or decorative 1800 1800 1798 2
DF-CP-MT (176)
DSA (174)
DSA-HV (174)
DAFC-P-C (178) DFRE-PC (180)
ØA
1.5
E
135
Size ØA ØB E (min) E (max)
DSA 150 190 150 14 50
ØB (HOLE)
200 240 200 19 50
DSA
Unit mm
Ø235
Ø195
DSA-PR
30-50
115
Ø165
Ø210
DSA-HV 200
Floor diffuser
Size
h0,25(m)
Q (m3/h) LwA [dB(A)] ∆Pest (Pa) ∆T= -4º ∆T= -6º ∆T= -8º VK(m/s)
174 175
DF-CP-MT Catalogue Series Floor
General dimensions
LxH
76
7
L= Opening Length
H= Opening Height
Step
Model
2
L x H
165 x 65
A
212.5
micro-swirl
3
4
250 x 65
340 x 65
300
387.5
diffuser
5
6
425 x 65
450 x 65
475
500
Unit mm
Product description
Multiple rotational diffuser for riser, KOOLAIR, model
Selection table
DF-CP-MT, of dimensions _x_, formed by a frontal
Diffusers Nominal dimension Q (m3/h) LwA [dB(A)] ∆Pt (Pa) VX (m/s)
rectangular plate that incorporates _ swirl
micro-diffusers. 22 20 10 0.14
2 165 x 65 27 26 16 0.17
Made in steel sheet. Finished painted in RAL colour
35 32 26 0.23
upon request.
31 20 9 0.16
3 250 x 65 39 26 15 0.21
Mounting 49 32 23 0.26
39 20 8 0.18
Without indication, mounted directy by screws.
4 340 x 65 49 26 13 0.22
PF. Connection plenum box made of galvanised 63 32 21 0.29
steel sheet. Please consult us for design details.
47 20 8 0.19 LEGEND
5 425 x 65 59 26 12 0.24
Q (m3/h): Air flow par plaque.
75 32 19 0.31
LwA [dB(A)]: Sound power level.
54 20 7 0.20
∆Pt (Pa): Total pressure loss.
6 450 x 65 69 26 11 0.26
VX (m/s): Maximum velocity of the air
88 32 18 0.33
stream at 0.70 m from the diffuser.
176 177
DAFC-P Catalogue Diffuser DAFC-P
General dimensions
ØB
ØD
120
A
64
6
ØA
DAFC-P DAFC-P-C
DAFC-P
Nominal A B D
Unit mm
Selection table
DAFC-P-C
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Vx (m/s)
Other models
DAFC-P-C. Swirl diffuser for riser integrated in a
circular plate, size_,diameter Ø _.
Mounting
PM. Mounted directy by mounting bridge.
PD. Connection plenum box made of galvanised
steel sheet. Please consult us for design details.
178 179
DFRE-P Catalogue Diffuser DFRE-P
General dimensions
ØB
ØD
120
64
A
6
ØA
DFRE-P DFRE-P-C
DFRE-P
Nominal A B D
Selection table
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) Vx (m/s)
DFRE-P-C
30 20 10 0.08
100 37 26 15 0.10
Other models
DFRE-P-C. Swirl diffuser for riser integrated in a
circular plate, size_,diameter Ø _.
Mounting
PM. Mounted directy by mounting bridge.
PD. Connection plenum box made of galvanised
steel sheet. Please consult us for design details.
180 181
Fire
dampers
BDK (192)
LV (204)
SMLD (198)
8
Barceló Aranjuez Hotel
(Madrid – Spain)
Linear diffusers S-70-18,
long-throw nozzle DF-49
and swirl diffusers DFRO.
SCFC Catalogue Series SF
Accessories
TH-70. Fusible link. B RUP 24V/48V AC-FC. Electromagnetic pull coil
TH-70-FC. Fusible link + end of stroke switch. (normally de-energized) 24V/48V AC, with end of
TH-70-PC/FC. Fusible link + beginning and end of stroke switch.
stroke switch. B RUP 220V-FC. Electromagnetic push coil
B IMP 24V/48V DC-FC. Electromagnetic push coil (normally de-energized) 220V AC, with end of
(normally de-energized) 24V/48V DC, with end of stroke switch.
stroke switch. MOTOR-24-T. Servomotor 24V AC/DC with thermo-
B IMP 24V/48V AC-C. Electromagnetic push coil fuse + beginning and end of stroke switch.
normally de-energized) 24V/48V AC, with end of MOTOR-230-T. Servomotor 230V AC with thermo-
stroke switch. fuse + beginning and end of stroke switch.
SCFC-PD
B IMP 220V-FC. Electromagnetic push coil (normally
de-energized) 220V AC, with end of
stroke switch.
B RUP 24V/48V DC-FC. Electromagnetic pull coil
(normally de-energized) 24V/48V DC, with end of
damper
General dimensions (SCFC-PD)
25
reset in all versions. EI-180 (ho i o) S (500 Pa) or ceiling/floor slab.
The operating mechanism components are For sizes from Ø 200 to Ø 800 mm
manufactured of zinc coated steel and built into a EI-180 (ve i o) S (500 Pa) for wall. Operating shaft
97 S2
plastic casing.
The mechanism assembly is offset from the pivot Motor-driven circular fire dampers SCFC-PD and
shaft of the slat, which allows access to the unit for SCFC-GD can be incorporated into KOOLAIR’s
maintenance and inspection. KOOLCOM system for managing and monitoring fire
Ø Nominal S2
The Koolair fire dampers have the CE marking in dampers.
accordance with the Construction Products Directive 100 –
305/2011/EU, following the standard EN15650:2010 125 –
and classification in accordance with 160 –
EN 13501-3:2005. Also available with “NF” marking. 200 –
Option for fire dampers to be supplied with class C 250 –
air tightness in compliance with UNE-EN 1751. 315 25
355 50
Unit mm
184 185
SCFC Selection table (SCFC-GD)
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) VP (m/s)
3980 45 20 10,5
400 4960 50 31 13,0
6170 55 47 16,2
4650 45 13 9,5
450 5790 50 21 11,8
7210 55 32 14,7
Selection table (SCFC-PD) 5490 45 12 8,9
500 6830 50 18 11,1
Size Q (m3/h) LwA [dB(A)] ∆Pt (Pa) VP (m/s) 8500 55 29 13,8
75 25 18 4,2 6590 45 11 8,4
100 95 30 27 5,2 560 8200 50 16 10,4
115 35 41 6,4 10210 55 25 13,0
165 30 19 5,3 7980 45 9 7,9
125 205 35 30 6,6 630 9930 50 15 9,8
250 40 45 8,1 12360 55 23 12,3
380 35 22 6,8 8590 45 10 8,0
160 465 40 34 8,4 650 10690 50 15 9,9
575 45 51 10,4 13300 55 23 12,3
800 40 22 8,7 9510 45 9 7,6
200 985 45 33 10,8 700 11840 50 13 9,4
1210 50 50 13,3 14730 55 21 11,7
1350 40 22 9,0 9680 45 8 7,5
250 1660 45 34 11,1 710 12040 50 13 9,3
2050 50 52 13,7 14990 55 20 11,6
2290 40 16 9,3 10530 45 8 7,2
315 2830 45 25 11,5 LEGEND 750 13110 50 12 9,0 LEGEND
3490 50 38 14,2 16310 55 19 11,2
Q (m /h): Air flow.
3
Q (m3/h): Air flow.
2770 40 13 8,7 11720 45 8 7,0
∆Pt (Pa): Pressure drop. ∆Pt (Pa): Pressure drop.
355 3410 45 20 10,8 800 14580 50 13 8,8
LwA [dB(A)]: Sound power level. LwA [dB(A)]: Sound power level.
4210 50 30 13,3 18140 55 20 10,9
VP (m/s): Effective velocity. VP (m/s): Effective velocity.
186 187
SCFR/SFR Catalogue Series SF
Accessories
TH-70. Fusible link. B RUP 24V/48V DC-FC. Electromagnetic pull coil
TH-70-FC. Fusible link + end of stroke switch. (normally de-energized) 24V/48V DC, with end of
TH-70-PC/FC. Fusible link + beginning and end of stroke switch.
stroke switch. B RUP 24V/48V AC-FC. Electromagnetic pull coil
B IMP 24V/48V DC-FC. Electromagnetic push coil (normally de-energized) 24V/48V AC, with end of
(normally de-energized) 24V/48V DC, with end of stroke switch.
stroke switch. B RUP 220V-FC. Electromagnetic push coil
B IMP 24V/48V AC-FC. Electromagnetic push coil (normally de-energized) 220V AC, with end of
normally de-energized) 24V/48V AC, with end of stroke switch.
stroke switch. MOTOR-24-T. Servomotor 24V AC/DC with thermo-
B IMP 220V-FC. Electromagnetic push coil (normally fuse + beginning and end of stroke switch.
SCFR-PD
de-energized) 220V AC, with end of MOTOR-230-T. Servomotor 230V AC with thermo-
stroke switch. fuse + beginning and end of stroke switch.
Rectangular
fire damper General dimensions (SCFR-PD)
400 L + 60
30 L 30
Product description Models
265 135
Operating shaft
30
Rectangular fire dampers, KOOLAIR brand, model SCFR-PD S/UNE-EN 1366-2:2000. Clasification:
SCFR, are certified under the norm UNE EN 1366- EI-120 (ve i o) S (500 Pa) for wall,
2:2000. Dimensions LxH. The housing is composed EI-180 (ho i o) S (500 Pa) for ceiling/floor slab, S1 S2
30
of a single body of steel sheet with an innercutout EI-120 (ve i o) S (500 Pa) for flexible wall.
H + 60
H
reinforced by a slotted perforated frame that Damper dimension from 200x100 mm to
25
eliminates completely the thermal bridge. 800x600 mm.
The dampers are closed when the thermal fuse blows SCFR-GD S/UNE-EN 1366-2:2000. Clasification:
or trips at temperatures above 70ºC and are manually EI-120 (ve i o) S (500 Pa) for wall. 91
reset in all versions. EI-120 (ho i o) S (500 Pa) for ceiling/floor slab.
30
The operating mechanism components are Damper dimension from L>800 mm or H>600 mm to
manufactured of zinccoated steel and built into 1500x800 mm.
a plastic casing. SCFR-3H S/UNE-EN 1366-2:2000. Clasification: H S1 S2
The mechanism assembly is offset from the pivot EI-180 (ve i o) S (300 Pa) for wall.
shaft of the slat, which allows access to the unit for Damper dimension from 200x200 mm to 100 - -
maintenance and inspection. 1500x800 mm. 150 - -
The Koolair fire dampers have the CE marking in 200 - -
accordance with the Construction Products Directive Motor-driven rectangular fire dampers SCFR-PD, 250 - -
305/2011/EU, following the standard EN15650:2010 SCFR-GD and SCFR-3H can be incorporated into 300 - -
and classification in accordance with KOOLAIR’s KOOLCOM system for managing and 350 - 14
EN 13501-3:2005. monitoring fire dampers. 400 - 64
Also available with “NF” marking (SCFR-PD and 450 - 89
SCFR-GD). 500 - 114
Option for fire dampers to be supplied with class C 550 10 139
air tightness in compliance with UNE-EN 1751. 600 35 164
Unit mm
188 189
SCFR/SFR
190 191
BDK Catalogue Series BDK
Accessories
FC. End stroke switch.
GPD-Ø. Extract valves and mounting frame.
AM. Mounting ring.
General dimensions
ØD
60 A
damper
100
125
98,5
123,5
20
33
150
175
200x200
225x225
150 148,5 41 200 250x250
160 158,5 51 210 260x260
180 178,5 61 230 280x280 Ø Hole1: Rigid wall
200 198,5 71 250 300x300
Hole2: Flexible wall
Product description Models Unit mm
The Koolair BDK butterfly fire dampers are certified BDK-60: Butterfly firewall dampers with fire integrity
according to the Technical Building Code as per UNE and insulation rated at 60 min plus smoke tightness.
Selection table
EN 1366-2. EI 60 (ve i o) S.
Size Q (m3/h) LwA [dB(A)] ∆Pst (Pa) VP (m/s)
They are used inside circular HVAC ducts in wall BDK-120: Butterfly firewall dampers with fire integrity
88 30 17 3,1
pass-throughs to fire propagation. and insulation rated at 120 min plus smoke tightness. 100 109 35 27 3,9
EI 120 (ve i o) S. 136 40 41 4,8
168 45 61 6,0
Operation 150 30 17 3,4
125 186 35 26 4,2
The BDK damper remains open because of the fuse 1 231 40 40 5,2
link. When the temperature exceeds 72ºC, the fuse 287 45 61 6,5
link melts and the mechanism is released, such that 231 30 16 3,6
3 150 287 35 25 4,5
the fins close automatically. 4
357 40 38 5,6
Two bands ensure that the damper remains closed. 444 45 59 7,0
270 30 16 3,7
After closure, the damper fins are mechanically 160 335 35 24 4,6
secured in the closed position and can only be 2 417 40 38 5,8
opened manually. 518 45 58 7,2
357 30 15 3,9
5 180 444 35 24 4,8
1. Neck. 552 40 37 6,0 LEGEND
2. Fin. 6 686 45 57 7,5
4 Q (m3/h): Air flow.
3. Adhesive. 460 30 15 4,1
7 200 571 35 23 5,1 ∆Pt (Pa): Pressure drop.
4. Intumescent gasket. 710 40 36 6,3 LwA [dB(A)]: Sound power level.
5. Fuse link, 72ºC. 882 45 56 7,8 VP (m/s): Effective velocity.
6. Rubber gasket.
7. Band.
192 193
CEVH Catalogue Series CEVH
General dimensions
Ln
Ln
Ht
P
Hn
Lt
Smoke
evacuation
Lt
damper
Free area (dm2)
Height Length Ln (in mm)
Hn
Product description Operation
(in mm) 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100
The mechanism(s) will be installed in a specific area, 400 9.24 10.76 12.28 13.80 15.3 16.8 18.4 19.9 21.4 22.9 24.4 26.0 27.5 29.0 30.5
Smoke evacuation damper, hinged, to be used for
in the middle of the damper. 450 10.76 12.53 14.30 16.07 17.8 19.6 21.4 23.2 24.9 26.7 28.5 30.2 32.0 33.8 35.5
new air and smoke evacuation in public buildings
Smoke evacuation damper, hinged, electromagnetic 500 12.28 14.30 16.32 18.34 20.4 22.4 24.4 26.4 28.4 30.5 32.5 34.5 36.5 38.5 40.6
and tall buildings; EN 1366-10 approved. Designed
operation at 24/48V by current emission. 550 13.80 16.07 18.34 20.61 22.9 25.2 27.4 29.7 32.0 34.2 36.5 38.8 41.0 43.3 45.6
as per EN 12101-8 specifications.
Option to include position contacts to indicate the 600 15.32 17.84 20.36 22.88 25.4 27.9 30.4 33.0 35.5 38.0 40.5 43.0 45.6 48.1 50.6
Composed of a structure of refractory material 650 16.84 19.61 22.38 25.15 27.9 30.7 33.5 36.2 39.0 41.8 44.5 47.3 50.1 52.9 55.6
open and/or closed positions (optional).
externally and steel plate internally, and composed 700 18.36 21.38 24.40 27.42 30.4 33.5 36.5 39.5 42.5 45.5 48.6 51.6 54.6 57.6 60.6
of two hinged sections in refractory material. 750 19.88 23.15 26.42 29.69 33.0 36.2 39.5 42.8 46.0 49.3 52.6 55.9 59.1 62.4 65.7
Application: by a wall- or duct-recessed mounting 800 21.40 24.92 28.44 31.96 35.5 39.0 42.5 46.0 49.6 53.1 56.6 60.1 63.6 67.2 70.7
frame. Front panel with specific protection grille for 850 22.92 26.69 30.46 34.23 38.0 41.8 45.5 49.3 53.1 56.9 60.6 64.4 68.2 71.9 75.7
smoke evacuation, in anodized aluminium. 900 24.44 28.46 32.48 36.50 40.5 44.5 48.6 52.6 56.6 60.6 64.6 68.7 72.7 76.7 80.7
950 25.96 30.23 34.50 38.77 43.0 47.3 51.6 55.9 60.1 64.4 68.7 72.9 77.2 81.5 85.7
UNE-EN-1366-10 certificate. EN 13501-4
classification: EI 120 (ved i<->o) S 1500 AA multi. Installation 1000 27.48 32.00 36.52 41.04 45.6 50.1 54.6 59.1 63.6 68.2 72.7 77.2 81.7 86.2 90.8
1050 29.00 33.77 38.54 43.31 48.1 52.9 57.6 62.4 67.2 71.9 76.7 81.5 86.2 91.0 95.8
The CEVH smoke evacuation dampers have CE 1100 30.52 35.54 40.56 45.58 50.6 55.6 60.6 65.7 70.7 75.7 80.7 85.7 90.8 95.8 101
Ln x Hh
Mark No. 0370-CPR-1687, in conformity with
FREE AREA FORMULA ((Ln-96) x (Hn-96))/10000
Construction Products Directive 89/106/EC, as per
EN12101-8. Pressure loss ≤ 20 Pa if velocity at damper is ≤ 8 m/s
LEGEND FORMULARY
MINIMUM 100
194 195
CEVH-1P Catalogue Series CEVH-1P
General dimensions
Ht
Hn
Hn
Hn
Ht
Smoke Lt 155 36 Lt 155 7 Ln
evacuation
damper
Free area (m2)
Height Length Ln (in mm)
Hn
Product description Operation (in mm) 300 350 400 450 500 550 600 650 700
Activation (opening) by means of electric shunt release 385 0,12 0,13 0,15 0,17 0,19 0,21 0,23 0,25 0,27
Smoke evacuation damper with 1-blade (1P)
coil with manual/motorised reset (closing). Optional
swivelling closure, designed to be used for the 400 0,12 0,14 0,16 0,18 0,20 0,22 0,24 0,26 0,28
end of run limit switch/es. Types of coil (electromagnet)
supply of primary air and smoke evacuation in 450 0,14 0,16 0,18 0,2025 0,225 0,2475 0,27 0,2925 0,315
available:
public buildings and high-rise buildings. Approved in 500 0,15 0,18 0,20 0,225 0,25 0,275 0,30 0,325 0,35
- Electric shunt release 24 V – DC.
accordance with EN 1366-10. Designed according to
- Electric shunt release 48 V – DC. 550 0,17 0,19 0,22 0,2475 0,275 0,3025 0,33 0,3575 0,385
EN 12101-8 specifications.
- Electric shunt release 24 V – AC. 600 0,18 0,21 0,24 0,27 0,30 0,33 0,36 0,39 0,42
Composed of a structure with a refractory material
- Electric shunt release 48 V – AC. 650 0,20 0,23 0,26 0,2925 0,325 0,3575 0,39 0,4225 0,455
externally, sheet steel internally and a hinged door
- Electric shunt release 220 V – AC.
made of a refractory material. For installation in 700 0,21 0,25 0,28 0,315 0,35 0,385 0,42 0,455 0,49
The activation and reset mechanism is incorporated
vertical smoke evacuation ducts, with the option of a 750 0,23 0,26 0,30 0,3375 0,375 0,4125 0,45 0,4875 0,525
in the lower front part of the damper protected from
metal mounting frame previously fixed to the duct. 800 0,24 0,28 0,32 0,36 0,40 0,44 0,48 0,52 0,56
passing smoke and high temperatures.
The face that is on display within the room has the
850 0,26 0,30 0,34 0,3825 0,425 0,4675 0,51 0,5525 0,595
option of a decorative plate made of a refractory
material (CEVH-1P + DECO) and/or a protective and Installation 900 0,27 0,32 0,36 0,405 0,45 0,495 0,54 0,585 0,63
decorative grille specific for smoke evacuation, model 950 0,29 0,33 0,38 0,4275 0,475 0,5225 0,57 0,6175 0,665
RPK, made of anodised aluminium profiles. Certified CEVH-1P 1000 0,30 0,35 0,40 0,45 0,50 0,55 0,60 0,65 0,70
in accordance with standard UNE-EN-1366-10. 1050 0,32 0,37 0,42 0,4725 0,525 0,5775 0,63 0,6825 0,735
Classified in accordance with EN 13501-4: EI 120 1100 0,33 0,39 0,44 0,495 0,55 0,605 0,66 0,715 0,77
(ved i o) S 1500 AA multi.
CEVH-1P smoke evacuation dampers carry CE Pressure loss ≤ 20 Pa if velocity at damper is ≤ 8 m/s
marking No. 0370-CPR-3051 in accordance with VERTICAL SMOKE
Lh x Hh
EVACUATION DUCT
the European Construction Products Regulation ACCORDING TO 1366-08
RPC-305, according to EN12101-8. LEGEND FORMULARY
P = Blade depth. P =Ln+110
Lh = Ln +10
Lt = Overall length.
Dimensions Hh = Hn +10
Ht = Overall height.
CEVH-1P+DECO CEVH-1P+RPK
Lt = Ln + 50 Lt = Ln + 94
The CEVH 1P damper is available with the following Lh = Duct internal length.
Ln + 110 > 110 Ht = Hn + 50 Ht = Hn + 70
dimensions: Hh = Duct internal height.
Minimum dimension LxH (mm) - 300x385 Ln = Damper Nominal length.
Maximum dimension LxH (mm) - 700x1100.
For more information refer to catalogue. Hn = Damper nominal height.
196 197
SMLD Catalogue Series SMLD
General dimensions
H SECTION
MOUNTING FRAME (OPTIONAL)
Hm
Hh
Ht
Hn
Hn
Smoke Ln
198
MOUNTING FRAME (OPTIONAL)
evacuation
damper
L SECTION Mounting
frame
Duct Standard UNE-EN 1366-8
≥100
Lh
Product description Dimensions
209
Multiblade smoke evacuation damper, appropriate Length: 360, 530 and 700 mm Blades Ln Lt Lm Lh
for applications in shallow ducts, EN 1366-10 Height: 200 mm to 1000 mm, in 50-mm increments. Mounting 2 354 418 427 429
Ln
approved. frame 3 527 591 600 602
Lt RPK
Designed as per EN 12101-8 specifications. 4 700 764 773 775
Composed of a refractory structure, externally
Operation Lm
Unit mm
enclosed with steel plate; composed of various The mechanism(s) will be installed in a specific area
refractory blades in the passage area. at the top of the damper and protected from smoke
Application: by a wall- or duct-recessed mounting and temperature. Free area (dm2)
frame. Multiblade smoke evacuation damper,
Front panel with specific protection grille for smoke electromagnetic operation at 24/48V by make circuit. Height Hn (mm)
Ln
evacuation, in anodized aluminium. Option to include position contacts to indicate the
(mm) 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
Blades
UNE-EN-1366-10 certificate. open and/or closed positions (optional).
EN 13501-4 classification: Motor drive option. 2 354 4.9 6.1 7.3 8.5 9.8 11.0 12.2 13.4 14.6 15.9 17.1 18.3 19.5 20.7 22.0 23.2 24.4
3 527 7.3 9.2 11.0 12.8 14.6 16.5 18.3 20.1 22.0 23.8 25.6 27.5 29.3 31.1 32.9 34.8 36.6
EI 120 (ved i<->o) S 1500 AA multi.
4 700 9.8 12.2 14.6 17.1 19.5 22.0 24.4 26.8 29.3 31.7 34.2 36.6 39.0 41.5 43.9 46.4 48.8
The SMLD smoke evacuation dampers have CE
Mark No. 0370-CPR-1688, in conformity with Motor-driven smoke evacuation dampers SMLD can Pressure loss ≤ 40 Pa if velocity at damper is ≤ 8 m/s
Construction Products Directive 89/106/EC, as per be incorporated into KOOLAIR’s KOOLCOM system
LEGEND
EN12101-8. for managing and monitoring fire dampers.
L = Length Ht =Total height FORMULARY
H = Height Lm = Mounting frame length H = Hn
Ln = Nominal length Hm = Mounting frame height Ht = Hn + 249
Hn = Nominal height Lh = Opening length Hm = Hn + 255
Lt = Total length Hh = Opening height Hh = Hn + 257
198 199
RPK Catalogue Series RPK
General dimensions
RPK
HAND GEAR
Mounting
frame
Smoke evacuation
RPK damper
A
A
A
smoke evacuation
H (EXT.)
H (EXT.)
H (EXT.)
Product description Dimensions
A
A
A
RPK RPK-1A RPK-2A
Protection grille, in anodized aluminium, to be used The grilles adapt to the dimensions of the smoke
FIXED GRILLE AND VISIBLE SCREWS REMOVABLE GRILLE AND VISIBLE SCREWS REMOVABLE GRILLE AND HIDDEN SCREWS
for smoke evacuation or SMLD and CEVH damper evacuation damper.
protection.
Excellent aesthetics. Reduced pressure drop.
Standard natural anodized aluminium finish.
L (EXT.) L (EXT.) L (EXT.)
Models 40 40 60 60 48 48
A
RPK. Protection grille with fixed core and visible
A
A
screws.
RPK-1A. Protection grille with removable core and
H (EXT.)
H (EXT.)
H (EXT.)
visible screws.
RPK-2A. Protection grille with removable core and
18
hidden screws.
26
26
RPK-S. Protection grille with fixed core and visible
screws.
A
A
36 36 37
RPK-P. Protection grille with fixed core and hidden RPK-S RPK-P RPK-X
screws. FIXED GRILLE AND VISIBLE SCREWS FIXED GRILLE AND HIDDEN SCREWS FOLDING GRILLE
RPK-X. Protection grille with folding core and hidden AND HIDDEN SCREWS
screws.
200 201
SCDC Catalogue Series SCDC
General dimensions
366
L + 60
30
NOMINAL + 60
NOMINAL + 20
H + 60
H
H
S2
S1
30
L
NOMINAL H S1 S2
Smoke
200
250
200
250
0
25
0
0
evacuation
300
350
300
350
50
75
0
0
damper
400
450
400
450
100
125
0
0
500 500 150 0
550 550 175 7
Product description Activation 600 600 200 32
650 650 225 57
KOOLAIR’s rectangular smoke evacuation damper, - Automatic actuation and reset by servomotor: 700 700 250 82
model SCDC, is composed of a single body of heat- SCDC smoke extract dampers are activated and 750 750 275 107
resistant material, with steel flanges on either side reset by means of a servomotor with a supply 800 800 300 132
(optional) to facilitate mounting in rectangular ducts, voltage of 24 V AC/DC (model BLE24) or 230 V AC Unit mm
and a single heat resistant closing blade. (model BLE230). These motors include start and
Tunnel type damper for in-line installation in end of stroke limit switches to monitor the opening/
Free area (dm2)
horizontal ducts for use with both supply and closing status of the damper. Height Length L (in mm)
extract, certified according to EN 1366-10, classified Other activation options: H
(in mm) 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200
according to EN 13501-4; EI 120 (ved i o) - Manual reset, activation by electric coil. Optional
200 2,9 3,7 4,5 5,3 6,0 6,8 7,6 8,4 9,1 9,9 10,7 11,5 12,2 13,0 13,8 14,6 15,3 16,1 16,9 17,7 18,4
S 1500 AA multi. end of run limit switch:
250 3,9 4,9 5,9 7,0 8,0 9,0 10,0 11,1 12,1 13,1 14,1 15,2 16,2 17,2 18,2 19,3 20,3 21,3 22,3 23,4 24,4
The SCDC smoke damper has the 0370 - CPR 24V electric drive coil DC 300 4,8 6,1 7,4 8,7 9,9 11,2 12,5 13,8 15,0 16,3 17,6 18,9 20,1 21,4 22,7 24,0 25,2 26,5 27,8 29,1 30,3
- 2600 certificate of constancy of performance 48V electric drive coil DC 350 5,8 7,3 8,8 10,4 11,9 13,4 14,9 16,5 18,0 19,5 21,0 22,6 24,1 25,6 27,1 28,7 30,2 31,7 33,2 34,8 36,3
according to EU Regulation (CE marking). 24V electric drive coil AC 400 6,7 8,5 10,3 12,1 13,8 15,6 17,4 19,2 20,9 22,7 24,5 26,3 28,0 29,8 31,6 33,4 35,1 36,9 38,7 40,5 42,2
Designed according to EN 12101-8 specifications. 48V electric drive coil AC 450 7,7 9,7 11,7 13,8 15,8 17,8 19,8 21,9 23,9 25,9 27,9 30,0 32,0 34,0 36,0 38,1 40,1 42,1 44,1 46,2 48,2
- Automatic reset by means of servomotor 500 8,6 10,9 13,2 15,5 17,7 20,0 22,3 24,6 26,8 29,1 31,4 33,7 35,9 38,2 40,5 42,8 45,0 47,3 49,6 51,9 54,1
BL24-48, with a supply voltage of 550 9,6 12,1 14,6 17,2 19,7 22,2 24,7 27,3 29,8 32,3 34,8 37,4 39,9 42,4 44,9 47,5 50,0 52,5 55,0 57,6 60,1
600 10,5 13,3 16,1 18,9 21,6 24,4 27,2 30,0 32,7 35,5 38,3 41,1 43,8 46,6 49,4 52,2 54,9 57,7 60,5 63,3 66,0
24 ... 48 V AC/DC, activation by previously
650 11,5 14,5 17,5 20,6 23,6 26,6 29,6 32,7 35,7 38,7 41,7 44,8 47,8 50,8 53,8 56,9 59,9 62,9 65,9 69,0 72,0
mentioned electric coils. An end of run limit switch
700 12,4 15,7 19,0 22,3 25,5 28,8 32,1 35,4 38,6 41,9 45,2 48,5 51,7 55,0 58,3 61,6 64,8 68,1 71,4 74,7 77,9
can be optionally incorporated.
750 13,4 16,9 20,4 24,0 27,5 31,0 34,5 38,1 41,6 45,1 48,6 52,2 55,7 59,2 62,7 66,3 69,8 73,3 76,8 80,4 83,9
The SCDC smoke damper, can be associated with 800 14,3 18,1 21,9 25,7 29,4 33,2 37,0 40,8 44,5 48,3 52,1 55,9 59,6 63,4 67,2 71,0 74,7 78,5 82,3 86,1 89,8
KOOLCOM’s KOOLAIR management and monitoring
system for fire dampers. LEGEND
L = Interior length of damper.
H = Interior height of damper.
Pressure loss <35 Pa if velocity at damper is ≤ 8 m/s
202 203
LV Catalogue Series LV
General dimensions
H–2
Installation
2
1. Opening L–
2. Intumescent grille 44
3. Grille-to-wall gasket
Intumescent 4. Outer grille
transfer
(L – 2) x (H – 2)
LxH
Product description Models
The intumescent grilles, KOOLAIR LV models, are Resistance to fire and hot gases for up to 60
used for compartmentation of small spaces that are minutes.
designed for natural ventilation. LVV40. EI30/EI60 intumescent rectangular grille with
Excellent air conduction characteristics, due to straight fins and no frame.
optimal noise levels in standard application. LVC40. EI30/EI60 intumescent round grille with
Two-way air flow. straight fins and no frame.
Easy to install. Resistance to fire and hot gases for up to 120
Free area equal to 60% of nominal area. minutes.
Products for all applications: doors, walls, ducts, LVH44. EI90/EI120 intumescent rectangular grille
floors and ceilings. with straight blades and no frame.
Full sealing achieved in about five minutes, as per BS LVHC44. EI90/EI120 intumescent round grille with
476: Pts 20 and 22 and UNE-EN 1634-1 2000. straight blades and no frame.
Dimensions
LV and LVH rectangular models:
Length: 100 to 600 mm
Height: 100 to 600 mm
204 205
VAV/ VAC
KS/KSL (208)
RCQK (216)
RVV-Q (222)
KCRK (212)
Archaeological Museum
(Madrid – Spain)
Grille S-20, linear grille S-30,
9
linear floor grille 31-1-F,
swirl diffuser DFRO,
long-throw nozzle DF-49,
linear diffusers KLD, swirl floor diffuser DAFC-P
and boxes for variable air volume KS.
KS/KSL Catalogue Series KS
Selection table
Regenerated noise Radiated noise
Size Q (m3/h) ∆Pmin (Pa) Sound pressure LPA dB(A) Sound pressure LPA2 dB(A)
∆P = 100 Pa ∆P = 500 Pa ∆P = 100 Pa ∆P = 500 Pa
80 1 <20 26 <20 21
100
400 6 31 43 28 39
125 1 <20 31 <20 22
200
625 11 35 47 32 40
200 1 22 36 <20 23
400
1000 16 38 51 33 41
275 1 25 39 <20 25
600
1375 22 40 54 35 43
325 1 26 40 <20 25
800
1625 23 41 55 35 43
Terminal unit
500 1 29 44 <20 26
1200
2500 27 43 58 36 45
VAV
800 1 32 47 <20 28
1600
4000 33 45 60 38 47
1000 1 33 48 20 29
2000
5000 34 40 61 39 48
1250 1 24 50 21 29
3000
6250 36 47 62 40 48
Product description Accessories
4000
1700 1 27 51 22 31
8500 45 48 63 42 50
Variable air volume terminal unit, KOOLAIR Actuator/Regulator: Mention model, max &
model KS, KSL, KSR & KSLR length dimension min project airflow. The minimum pressures for 2000 1 28 52 23 31
6000
610/1360mm respectively. Casing made in equipment setup depend on the actuator sensor 10000 44 47 63 47 51
galvanised steel sheet, insulated thermo-acoustically accuracy. 3250 1 37 54 25 34
with 30 mm fibreglass and black glass film. Outlet plenum. Plenum with Multiple outlets 8000
16250 50 48 64 44 53
Equipped with volume control damper, differential available upon request (see catalogue C2 or visit our
pressure cross sensor and regulator-actuator motor, web-site).
model to be advised. W. LPHW low pressure hot water battery. LEGEND
The insulation used is thermoacoustic, erosion E. Reheat electric battery. Q (m3/h): Air flow.
resistant and environmentally friendly preventing LPA: Sound pressure level of the regenerated noise, in dB(A), considering a room attenuation of 10 dB/oct.
the cultivation of microorganisms, and fire resistant, Note: Possibility of calibration and connecting for the LPA2: Sound pressure level of the radiated noise, in dB(A), considering a room attenuation of 10 dB/oct.
non-combustible M0. implementation of constant flow and forced closure
∆Pmin: Minimal differential pressure in Pa.
Can be equipped with a LPHW or Reheat battery functions.
∆P = 100/500 Pa: Differential pressure in Pa (measured at the inlet and outlet of the unit).
and plenum box with multiple outlets. Especially
designed for low ceiling void installations. Each can
be used for supply or return air (KSR). Dimensions General dimensions
Nominal A B ØD
Other models 100 240 254 99 L = 610
KS. Variable air volume terminal unit of length 200 265 254 124 L = 915 (WITH SIDE SPIGOTS)
610 mm. 400 300 254 159
KSL. Variable air volume terminal unit of length 600 320 254 179
1360 mm. 800 340 254 199
1200 420 254 249*
KSR. Variable air volume terminal unit of length
ØD
A
B
610 mm. 2000 585 254 354*
KSLR. Variable air volume terminal unit of length 3000 655 254 399*
1360 mm. 4000 735 254 499*
6000 710 458 499* 150
8000 915 458 629*
* OVAL SPIGOT
Unit mm
* Oval spigot
208 209
KSV/KSVL Catalogue Series KSV
General dimensions
L
A
D
KSV with RCCK
L
Type A B C D Without lateral outlets With lateral oval spigots KSVL
100 240 Ø 100
200 265 Ø 125
480
400 300 Ø 160
600 320 Ø 200
Terminal
800 340 254 200 x 200 610 915 1360
1200 420 300 x 200
1600 520 485 400 x 200
210 211
KCRK Catalogue Series KCRK
General dimensions
Dimensions
Size Ø D (mm) L (mm) M (kg)
80 78 94 0,07
ØD
100 98 113 0,12
125 122 145 0,18
150 146 160 0,27
160 156 171 0,3
200 196 201 0,49
250 246 242 0,8
L
Unit mm
Installation requirements
Constant
1xD
air flow
adjustment
3xD
1xD 3xD
Installation requirements
Product description
Constant air flow adjustment, KOOLAIR KCRK model, Selection table
of circular cross-section of size Ø_ for air supply or
return. Regenerated noise
Manufactured in ABS AF312A-class plastic material Size Q (m3/h) Sound pressure LPA dB(A)
with flammability V0. ∆P = 50 Pa ∆P = 100 Pa ∆P = 150 Pa ∆P = 200 Pa
Automechanical, with no need for outside power, 22 28 34 37 40
ensuring constant air flow regardless of the pressure 80 55 30 35 39 41
variations experienced by the system. Housings and 1. Body. 85 30 36 39 42
blade of high-quality plastic. 2. Blade. 30 27 34 38 40
3. Shock absorber. 100 52 29 36 39 42
They are regulated from a pressure loss of 30 Pa, 120 32 38 42 45
4. Gasket.
except diametre 80 that regulates in 50 Pa. 40 27 34 39 42
5. A djustment scale.
Can be installed in horizontal or vertical position. 125 89 29 37 41 44
192 32 39 44 47
52 26 33 37 40
Range of air flows, m /h 3 150 100 28 35 39 42
225 31 38 42 45
LEGEND
Size 1 2 3 4 5 6 7 8 9 10 11 12 61 27 35 40 43
160 145 29 37 41 45 Q (m3/h): Air flow..
80 22 30 37 45 55 70 85 LPA: Sound pressure level of the
282 30 38 43 46
100 30 35 40 52 60 75 95 120 regenerated noise. in dB(A). considering a
98 26 35 40 43
125 40 47 56 67 77 89 110 130 150 192 room attenuation of 10 dB/oct.
200 225 28 37 42 45
150 52 60 70 78 95 100 125 145 165 195 225 466 30 38 43 47 ∆P = 50/200 Pa: Differential pressure
160 61 72 81 96 117 133 154 180 210 245 282
168 25 33 38 41 in Pa (measured at the inlet and outlet of
200 98 112 125 150 186 225 271 307 326 364 409 466 250 392 27 35 40 43 the unit).
250 168 216 254 289 336 392 423 466 500 559 613 723 723 28 36 41 44
212 213
RCCK Catalogue Series RCC
General dimensions
B D Model Ø A B C D
55 C 55 ØA 61
80 78 139
100 98 159
125 123 184
160 158 400 290 219
150
200 198 259
250 248 309
315 313 374
355 353 414
400 450
398 340 459
Unit mm
Selection table
Constant Regenerated noise Radiated noise
Air Volume Size
Q (m3/h) ∆Pmin (Pa) Sound pressure LPA dB(A)
∆P = 100 Pa ∆P = 500 Pa
Sound pressure LPA2 dB(A)
∆P = 100 Pa ∆P = 500 Pa
Regulator
80
40
100
50
50
25
31
38
44
<20
22
33
38
140 50 33 46 24 40
80 50 30 42 <20 34
100 200 50 36 48 23 39
300 50 38 51 26 41
Product description Models 135 50 33 46 <20 33
125 325 50 39 52 24 39
Constant air volume circular regulator, Koolair model RCCK. Constant Volume circular regulator without
500 50 42 54 27 42
RCCK, for use in supply or extract systems. The insulation equipped with adjustment mechanism box.
RCCK-D. Constant Volume circular regulator with 235 50 36 49 <20 33
unit is self regulating and will operate independant of
insulation equipped with adjustment mechanism box. 160 520 50 42 55 25 39
pressure variations within the system. 800 50 45 58 28 42
RCCK-MT. Uninsulated mechanical circular constant
flow regulator with electric servomotor (All-or- 370 50 38 52 20 34
Casing and damper blade are manufactured from Nothing-Control or 0-10V). 200 820 50 43 57 26 40
galvanised sheet steel. Air flow rate is factory set, RCCK-D-MT. Insulated mechanical circular constant 1375 50 46 60 30 43
and the unit is easily adjustable on site to a high rate flow regulator with electric servomotor (ON-OFF 520 50 37 53 21 33
of accuracy. Minimum inlet pressure required Control or 0-10V). 250 1300 50 42 57 28 41
is 50 Pa.
Can be mounted either horizontally or vertically. Installation requirements
2100
865
50
50
44
42
60
56
32
23
44
35
Can be supplied with 50 mm of thermoacoustic 315 2050 50 46 60 30 42
Air direction
insulation (RCCK-D). D = duct diameter 3300 50 48 62 34 46
1000 50 42 55 23 35
Option to include circular silencer to attenuate 355 2500 50 47 60 31 43
regenerated noise in flow rate regulator (RCCK + 4000 50 50 63 35 47
ASK).
1200 50 43 56 24 35
3xd e
f 400 3150 50 49 62 32 44
The constant volume flow controller, model RCCK, L min
=
5000 50 52 65 36 48
meets the specifications set out in EN 1751,
CK
obtaining class “C” (optional) air tightness for the RC LEGEND
casing of the controller. Q (m3/h): Air flow.
LPA: Sound pressure level of the regenerated noise. in dB(A). considering a room attenuation of 10 dB/oct.
LPA2: Sound pressure level of the radiated noise. in dB(A). considering a room attenuation of 10 dB/oct.
∆Pmin: Minimal differential pressure in Pa.
Possibility of horizontal and vertical installation.
∆P = 100/500 Pa: Differential pressure in Pa (measured at the inlet and outlet of the unit).
214 215
RCQK Catalogue Series RCC
General dimensions
400 20 L (Int.) 20
20
150
H + 40
H (Int.)
L + 40 45
Regulator
200 x 200
300 x 100
500 x 200
500 x 250
500 x 400
500 x 500
600 x 500
Constant air volume rectangular regulator, RCQK. Constant Volume rectangular regulator Unit mm
Koolair model RCQK, for use in supply or extract without insulation equipped with adjustment Installation requirements
systems. The unit is self regulating and will operate mechanism box.
Air direction
independant of pressure variations within the RCQK-D. Constant Volume rectangular regulator
system. Casing and damper blade are manufactured with insulation equipped with adjustment mechanism
from galvanised sheet steel. Air flow rate is factory box.
set, and the unit is easily adjustable on site to a high RCQK-MT. Uninsulated mechanical rectangular
rate of accuracy. Minimum inlet pressure required is constant flow regulator with electric servomotor (All-
50 Pa. or-Nothing-Control or 0-10V). xd
=3
Can be mounted either horizontally or vertically. RCQK-D-MT. Insulated mechanical rectangular L min
Can be supplied with 50 mm of thermoacoustic constant flow regulator with electric servomotor (ON- QK
RC
insulation (RCQK-D). OFF Control or 0-10V).
216 217
RCQK
Selection table Selection table
Regenerated noise Radiated noise Regenerated noise Radiated noise
Size Q (m3/h) ∆Pmin (Pa) Sound pressure LPA dB(A) Sound pressure LPA2 dB(A) Size Q (m3/h) ∆Pmin (Pa) Sound pressure LPA dB(A) Sound pressure LPA2 dB(A)
∆P = 100 Pa ∆P = 500 Pa ∆P = 100 Pa ∆P = 500 Pa ∆P = 100 Pa ∆P = 500 Pa ∆P = 100 Pa ∆P = 500 Pa
LEGEND LEGEND
Q (m /h): Air flow.
3
Q (m3/h): Air flow.
LPA: Sound pressure level of the regenerated noise. in dB(A). considering a room attenuation of 10 dB/oct. LPA: Sound pressure level of the regenerated noise. in dB(A). considering a room attenuation of 10 dB/oct.
LPA2: Sound pressure level of the radiated noise. in dB(A). considering a room attenuation of 10 dB/oct. LPA2: Sound pressure level of the radiated noise. in dB(A). considering a room attenuation of 10 dB/oct.
∆Pmin: Minimal differential pressure in Pa. ∆Pmin: Minimal differential pressure in Pa.
∆P = 100/500 Pa: Differential pressure in Pa (measured at the inlet and outlet of the unit). ∆P = 100/500 Pa: Differential pressure in Pa (measured at the inlet and outlet of the unit).
218 219
RVV Catalogue Series RVV
General dimensions
L
Nominal Ø A RVV RVV-L
L
80 78 340 690
100 98
125 123 365 730
160 158 400 800
200 198 440 880
ØA
250 248 490 980
315 313 555
355 353 595
400 398 640
450 448 690 1000
500 498 740
630 628 870
Unit mm
Selection table
Variable
Size Q (m3/h) ∆Pmin (Pa)
Regenerated noise
Sound pressure LPA dB(A)
Radiated noise
Sound pressure LPA2 dB(A)
Air Volume ∆P = 100 Pa ∆P = 500 Pa ∆P = 100 Pa ∆P = 500 Pa
Regulator
18 2 21 27 <20 29
80 162 76 43 49 25 40
270 210 49 55 27 42
28 1 21 30 <20 27
100 255 69 44 51 24 38
425 191 50 56 26 41
220 221
RVV-Q Catalogue Series RVV-Q/JVR
General dimensions
L + 40 H + 150
20 L (100 a 600)
20
H (100 a 300)
H + 40
Minimum dimension from 200x100 to 1000x300 in steps of 50 mm.
Selection table
Regenerated noise Radiated noise
Size Q (m3/h) ∆Pmin (Pa) Sound pressure LPA dB(A) Sound pressure LPA2 dB(A)
∆P = 100 Pa ∆P = 500 Pa ∆P = 100 Pa ∆P = 500 Pa
72 1 26 40 11 25
Air Volume
200 x 200
144
720
1440
1
11
46
30
45
51
44
59
65
16
35
48
30
48
61
Regulator
300 x 200
216
1080
1
9
32
46
46
60
19
39
32
53
2160 35 52 66 57 71
324 1 34 47 22 35
300 x 300 1620 7 47 60 46 59
3240 26 53 66 58 71
Product description Models 288 1 33 47 21 34
400 x 200 1440 7 47 60 44 57
Rectangular Variable Air Volume regulator, KOOLAIR RVV-Q. Rectangular Variable Air Volume regulator. 2880 28 52 66 56 69
brand, model RVV-Q, size LxH, incorporating RVV-Q-D. Rectangular Variable Air Volume regulator 432 1 34 48 23 36
regulating damper with gasket in its perimeter with Thermoacoustic insulation 50 mm thickness. 400 x 300 2160 5 47 60 53 66
cruciform sensor measuring differential pressure and RVV-Q-DL. Rectangular Variable Air Volume 4320 21 53 66 58 72
proportional actuator, upper and lower limits to be regulator with Thermoacoustic insulation 50 mm 360 1 34 47 22 35
500 x 200 1800 6 47 60 48 61
factory calibrated. RVV variable volume regulator is thickness and enlarge casing. 3600 24 53 66 54 67
suitable for both supply and return work, they may 540 1 35 48 25 38
incorporate thermal and sound insulation (RVV-Q-D).
Option to include square silencer to attenuate
Accessories 500 x 300
2700
5400
5
18
47
52
60
65
53
59
66
72
regenerated noise in regulator (RVV-Q + PAK). Actuator/Servomotor. Maximum and minimum 432 1 34 48 23 36
air-flow must be indicated, as well as actuator 600 x 200 2160 5 47 60 53 66
4320 21 53 66 58 71
The variable volume flow controller, model RVV-Q, brand/model. The minimum pressures for equipment
540 1 35 48 25 38
meets the specifications set out in EN 1751, setup depend on the actuator sensor accuracy. 600 x 250 2700 5 47 60 53 66
obtaining class “C” (optional) air tightness for the 5400 18 52 65 59 72
casing of the controller. Note: Possibility of calibration and connecting for the 648 1 35 48 26 39
implementation of constant flow and forced closure 600 x 300 3240 4 47 60 50 63
6480 16 52 65 59 71
functions.
LEGEND
Q (m3/h): Air flow.
LPA: Sound pressure level of the regenerated noise, in dB(A), considering a room attenuation of 10 dB/oct.
LPA2: Sound pressure level of the radiated noise, in dB(A), considering a room attenuation of 10 dB/oct.
∆Pmin: Minimal differential pressure in Pa.
∆P = 100/500 Pa: Differential pressure in Pa (measured at the inlet and outlet of the unit).
222 223
JVR Catalogue Series RVV-Q/JVR
General dimensions
L + 40 400
L (100 a 600) 20
20
H (100 a 300)
H + 40
Minimum dimension from 200x200 to 1200x1050 in steps of 50 mm.
Selection table
Regenerated noise Radiated noise
Size Q (m3/h) ∆Pmin (Pa) Sound pressure LPA dB(A) Sound pressure LPA2 dB(A)
∆P = 100 Pa ∆P = 500 Pa ∆P = 100 Pa ∆P = 500 Pa
576 1 37 50 27 40
Air Volume
500 x 500
900
4500
1
3
37
48
50
61
30
53
43
66
9000 13 53 66 58 70
Regulator
600 x 600
1296
6480
1
2
37
47
49
60
34
51
46
64
12960 10 52 64 56 68
1260 1 37 49 33 46
700 x 500 6300 3 47 60 49 62
12600 10 52 65 54 67
Product description Models 1512 1 36 49 36 48
700 x 600 7560 2 47 59 51 63
Variable Air Volume regulator KOOLAIR brand, model JVR. Rectangular Variable Air Volume regulator. 15120 9 51 64 55 68
JVR of rectangular section has a wide range of JVR-DS. Rectangular Variable Air Volume regulator 1764 1 36 49 32 44
sizes from 200x100 to 1200x1050 mm JVR body with Thermoacoustic insulation 50 mm thickness. 700 x 700 8820 2 46 59 51 63
incorporates an air inlet connection equipped with a 17640 8 51 63 55 67
cruciform sensor to measure differential pressure and 1440 1 37 49 35 48
aerodynamic opposed blade regulating damper. JVR
Accessories 800 x 500 7200 2 47 60 51 64
14400 9 51 64 56 68
includes internal airtight seals around its perimeter to Actuator/Servomotor. Maximum and minimum air-
1728 1 36 49 38 51
ensure excellent tightness. flow must be indicated, as well as actuator 800 x 600 8640 2 46 59 51 63
Aerodynamic opposed blade are operated by a brand/model. The minimum pressures for equipment 17280 8 51 63 56 68
gear mechanism to achieve proper friction JVR can setup depend on the actuator sensor accuracy. 2304 1 36 48 45 58
be fitted with fibreglass thermal-acoustic insulation 800 x 800 11520 2 45 58 49 61
Note: Possibility of calibration and connecting for the 23040 7 49 62 54 66
internally (JVR-DS) upon request.
2160 1 36 48 32 45
Option to include square silencer to attenuate implementation of constant flow and forced closure
1000 x 600 10800 2 45 58 48 60
regenerated noise in regulator (JVR + PAK). functions. 21600 7 50 62 54 66
3600 1 34 46 31 43
The variable volume flow controller, model JVR, 1000 x 1000 18000 1 43 55 48 60
meets the specifications set out in EN 1751, 36000 5 47 59 52 64
224 225
Acoustics
PAK (228)
KAT-Z (232)
ASK-1 (229)
KAT-T (232)
250-TAA (229)
Ortiz Building
(Madrid – Spain)
Grille 20-45-H,
linear floor grille 31-15-F,
linear grille 31-1,
long-throw nozzle DF-49,
linear diffusers S-74-25,
10
circular floor swirl diffusers DSA-S,
extract valves GPD and 46-SV,
dampers for round duct CCC,
boxes for variable air volume KSL
and fire dampers SFR2 and SFC2.
Acoustic Catalogue Series SK
Circular silencers
Circular silencers KOOLAIR brand, model ASK-1
(without core) or ASK-2 (with core).
The acoustic material comprises glass fibre density
suitable for heat resistant and protected against
erosion by perforated sheet galvanized plate. For the
construction of the central core (ASK-2) are used
the same materials. The maximum recommended
temperature is 135° C.
Note: For more information refer to catalogue and/or Technical Department. Note: For more information refer to catalogue and/or Technical Department.
228 229
ASK-1 PAK Attenuation. 600mm length
Selection table Selection table
fm in Hz
Dimension ØA Qmin (m /h)
3
Qmax (m /h)
3
∆Pmin (Pa) ∆Pmax (Pa) Dimension B x H Q (m3/h) Vf (m/s) ∆P (Pa) P 63 125 250 500 1k 2k 4k 8k
80 69 206 7 67 400 x 200 1200 4.2 18 50 6 12 21 33 35 40 25 21
100 109 326 6 54 400 x 300 1600 3.7 15 75 4 9 16 26 31 37 19 16
125 171 513 5 43 500 x 300 2200 4.1 18 100 4 8 16 19 27 30 16 14
160 282 847 4 34 500 x 400 2500 3.5 13 125 3 7 12 17 24 23 14 12
180 358 1075 3 30 600 x 300 3000 4.6 23 150 3 7 10 15 19 21 12 11
200 443 1330 3 28 600 x 400 4000 4.6 23 175 2 6 10 15 17 19 12 9
250 696 2087 2 22 600 x 600 5000 3.9 16 200 2 4 9 12 15 15 11 7
315 1108 3324 2 18 800 x 500 6000 4.2 18
355 1409 4228 2 17 800 x 600 7000 4.1 17 Attenuation. 1200mm length
400 1792 5375 2 15 900 x 600 8000 4.1 18
450 2270 6810 2 14 900 x 900 10000 3.4 12 fm in Hz
500 2805 8415 1 12 1200 x 600 12000 4.6 23 P 63 125 250 500 1k 2k 4k 8k
560 3521 10564 1 11 LEGEND 1200 x 1200 18000 3.5 13
630 4460 13381 1 10 50 10 21 41 50 50 50 45 31
Qmin (m3/h): Air flow for a duct velocity 1500 x 1200 22500 3.5 13
710 5669 17007 1 9 75 7 15 31 50 50 50 43 31
of 4 m/s 1800 x 1500 25000 2.6 7
800 7202 21606 1 8 100 6 12 28 40 50 50 35 26
Qmax (m3/h): Air flow for a duct velocity 1800 x 1800 30000 2.6 7
900 9120 27361 1 7 125 5 11 25 35 45 47 28 21
of 12 m/s 2100 x 1500 40000 3.5 13
1000 11265 33794 1 7 150 5 11 20 34 38 40 28 20
∆P (Pa): Total pressure loss. 2100 x 1800 45000 3.3 12
175 4 10 18 27 36 37 25 18
200 3 9 17 23 30 31 22 17
LEGEND
Q (m3/h): Air flow. Unit mm
∆P (Pa): Total pressure loss (L: 1000 mm). P: Airway in mm.
Attenuation. 500mm length Attenuation. 1000mm length Vf (m/s): Air veloicty based on BxH section. fm (Hz): Octave band frequency.
fm in Hz fm in Hz Note: The sound attenuation data provided corresponds to the use
Dimension 63 125 250 500 1k 2k 4k 8k
Dimension 63 125 250 500 1k 2k 4k 8k of 200 mm wide interior baffles.
80 5 9 12 14 28 44 35 24 80 6 13 19 27 47 50 50 36 Other models
100 4 7 10 13 27 43 34 23 100 5 11 17 26 46 50 50 35 PAK-H. Rectangular silencer for fancoil installation.
125 4 7 10 13 27 42 22 11 125 5 10 15 24 44 50 39 21
160 4 7 9 12 25 35 18 10 160 5 9 13 21 41 48 28 17
180 4 7 9 11 24 30 16 10 180 5 9 13 20 40 43 26 17
200 3 5 6 11 24 24 15 9 200 4 7 11 18 39 33 22 14
250 3 5 6 9 22 19 13 9 250 4 6 10 15 36 26 18 14
315 2 4 5 8 15 15 9 8 315 3 6 8 16 30 21 13 12
355 2 4 5 8 14 14 9 8 355 3 5 7 14 27 20 12 11
400 2 4 5 7 13 13 8 7 400 3 5 6 14 27 19 11 11
450 2 4 5 7 11 12 7 7 450 3 5 5 14 18 19 11 11
500 2 3 4 7 8 7 6 5 500 2 5 5 12 17 13 10 8
Unit mm 560 2 5 5 12 17 12 10 7
630 1 4 5 11 16 11 8 5
fm (Hz): Octave band frequency.
Unit mm
fm (Hz): Octave band frequency.
230 231
KAT Catalogue Series KAT
General dimensions (KAT-Z)
KAT-Z
25 75 5
L2
6 69
25 A
43
43
B
36.2x(L)
43
43
11
A
400
36.2x(L)
43
A’
L1
400
L
KAT-T L2
12.5 12.5
25 50 25
100
65 5
Sound
36.2
43
attenuation air
transfer units 25 50
100
25
25 KAT-Z WITH 31-1 OR WITH PERFORATED PLATE
KAT-Z KAT-T
L L1 L2 L L1 L2
Product description Models 500 499 508 500 499 508
1.000 999 1.008 1.000 999 1.008
The KAT sound attenuation air transfer units, KAT-Z. Sound attenuation air transfer units for wall
KOOLAIR brand, model KAT, offers a high sound thicknesses of 100 mm. Unit mm Unit mm
absorption level, low pressure loss, easy installation KAT-T. Sound attenuation air transfer units for wall
and attractive design. thicknesses of 125 mm.
General dimensions (KAT-T)
Air is moved to adjacent rooms by the transfer unit BAK. Acoustic box. L1
by the pressure difference between the rooms. A
43
reduction to guarantee conversation privacy.
36.2x(L)
36.2x(L)
A’
The sound reduction of the equipment is
L
independent of the wall material. L2
43
painted in RAL color to be defined. 125
43
B
36.2
43
43
25 75 25
A
125
BAK
12.5
KAT-T WITH 31-1 OR WITH PERFORATED PLATE 25 5
Note: For more information refer to catalogue and/or Technical Department.
232 233
Air/Water
VFK-600 (236)
IHK (242)
VFK-Q (238)
VPK (244)
Titanic Building
(Belfast – United Kingdom)
Boxes for variable air volume KSL. 11
VFK-600 Catalogue Series VFK 600
General dimensions
350
C Ø124
1/2”
84
Ø124
200
60
A 10 595
B
595
184
88
VFK-600 Length from 600 to 1800
5 different connection arragements are
available, depending on the connection
Active chilled E E 60
of the primary air.
beam
350
C Ø124
1/2”
84
Product description VFK-600 is provided with hanging brackets to easy
Ø 124
200
its installation. Standard finish RAL 9010, other finish
60
Active chilled beam, KOOLAIR brand, model available unpon request. Optionally VFK-600 can A 10 595
VFK-600, length L, width 600 mm and height 200 be equipped with control valve / balancing and dew B
595
184
88
Hinged perforate plate face, available in different
patterns to access the battery and get its cleaned. VFK-600 Length from 2100 to 3000
The unit is equipped internally with nozzles (size 3 different connection arragements
P/M/G) on both sides of the primary plenum box, are available, depending on the
E D E 60 connection of the primary air.
incorporating as an option nozzle control system.
Hot or chilled water (two-pipe installation), or hot
and chilled water (four pipe installation) coil copper
tubes and Aluminum fins and water connection dia
1/2”. One or two air connections (front/side or top), Size A B C E Size A B C D E
Dia-124 mm. 600 572 592 522 261 2100 2072 2092 2022 1011 506
900 872 892 822 411 2400 2372 2392 2322 1161 581
1200 1172 1192 1122 561 2700 2672 2692 2622 1311 656
1500 1472 1492 1422 711 3000 2972 2992 2922 1461 731
1800 1772 1792 1722 861
Unit mm
Note: For more information refer to catalogue and/or Technical Department. Unit mm
236 237
VFK-Q Catalogue Series VFK-Q
General dimensions
200 595
595
511
485
1/2”
Ø124
PRIMARY AIR
Active chilled
beam PRIMARY AIR + ROOM AIR
ROOM AIR
385
105
511
Hinged perforate plate face, available in different
595
patterns to access the battery and get its cleaned.
The unit is equipped internally with nozzles (size
P/M/G) on both sides of the primary plenum box,
incorporating as an option nozzle control system.
Hot or chilled water (two-pipe installation), or hot
and chilled water (four pipe installation) coil copper 1085
Ø124
tubes and Aluminum fins and water connection dia 1/2”
PRIMARY AIR
1/2”. One or two air connections (front/side or top),
Dia-124 mm.
ROOM AIR
Note: For more information refer to catalogue and/or Technical Department.
238 239
VFK-300 Catalogue Series VFK-300
General dimensions
31.5
91
31.5
31.5
1/2”
C
243
33
Ø124
200
Active chilled
beam B 11.5 295
Size A B C
Product description 900 895 872 874
Active chilled beam, KOOLAIR brand, model VFK, 1200 1195 1172 1174
length from 600 to 3000, width 300 mm and 1500 1495 1472 1474
height 200 mm, integrated in the false ceiling or 1800 1795 1772 1774
plasterboard. 2100 2095 2072 2074
2400 2395 2372 2374
The unit incorporate a plenum of primary air, with 2700 2695 2672 2674
3000 2995 2972 2974
one or two circular connections of the primary air
and some nozzles; a chilled water battery (two- Unit mm
pipe installation) or chilled and hot water (four pipe
installation); and linear diffusers, one on each side
of the battery, for supplying and diffusing the mixed
primary airflow and induced air.
240 241
IHK Catalogue Series IHK
General dimensions
A 175
580
Ø124
IHKV
A 700
Inductor 40 600 60
unit
Ø124
280
Product description The unit is provided with fixing brackets. Standard B
IHKF
finish RAL 9010 or grilles painted matte anodized Front spigot
Horizontal Inductor unit to supply air in one aluminum.
direction, IHK model, brand KOOLAIR, length
(900/1200/1500) mm, width 700 mm and height 200 Optionally IHK can be equipped with control valve /
mm, for installation in false ceilings. Incorporates balancing and dew point sensor. 830
air discharge grille available in different designs, for A
40 730 60
horizontal air diffusion Coanda effect air mixture See website www.koolair.com & Komfortair-Water
(primary and secuandaro). program for technical data.
Ø124
Induction grille available in different designs, hinged
200
or removable for battery cleaning purpose. The unit
integrates inner plenum nozzles (type P/M/G) for
supply of primary air. Internal battery in horizontal
B
position (2/4) pipes for cooling and / or heating with IHKF
copper piping connections outside diameter 12 mm Side spigots
242 243
VPK Catalogue Series VPK
General dimensions
C D
1/2’’
57
120
65 A B
E
VPK
beams E
100
Product description Finished
300
180
The ceiling-mounted terminal units known as passive The housing and perforated plate are manufactured
chilled beams, VPK model, without air supply, are from galvanized steel.
used to offset internal loads in an area. The heat exchanger unit consists of copper pipes A B
20
Passive chilled beams use water to carry cooling and an aluminium fin pack, with galvanized flanges. D
power to the various areas, which is an advantage, The standard surface finish is pure white (RAL 9010) VPK-E
as the units save on energy and space, in with a powder finish. Both plate perforation and
comparison to all-air systems. colours can be modified upon request.
Passive chilled beams may be installed flush with a In addition, light fixtures, speakers, sprinklers, etc., VPK-E
drop ceiling or in a hanging position. may be installed in the beam.
Model A B C D E A B C D E
244 245
TFK Catalogue Series TFK
General dimensions
100 37
2
Ø1
MICROPERFORATED PLATE
564
595
500
(WITH ACOUSTIC PAD)
L 75 SMOOTH PLATE
Model L
1200 1195
Chilled ceiling
1800
2400
1795
2395
3000 2995
Unit mm
246 247
Displacement
units
12
Gas Natural Building
(Madrid – Spain)
Regulators KCR
and active chilled beam VFK.
S90 Catalogue Series 90
General dimensions
ØA
ØD
Size A C H D
H
500 680 665 2000 500
630 810 795 2000 630
S90-C
Unit mm
Displacement
units
Selection table
Model Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m)
Product description Other models 225 25 15 2.7
The S-90 diffusers are displacement units for floor S-90-C. Round. Dimensions between Ø 125 to 125 270 30 21 3.5
installation. The unit includes upper and lower 630 mm. 310 35 30 4.0
covers and a perforated air distribution face plate. S-90-SC. Semicircular. Dimensions between 320 25 13 2.5
Connections can be made through the upper or Ø 160 to 630 mm. 160 380 30 17 3.0
460 35 25 3.6
lower cover. S-90-CC. Quadrant. Dimensions between Ø 160
The units are of galvanised steel sheet construction to 630 mm. 460 25 10 3.0
200 550 30 14 4.0
with aluminium sections and include an air equalising S-90-R. Rectangular. Standard dimensions LxH;
650 35 20 4.7
plate (painted in black) inside, as well as static L: 600-1200 mm and H: 800-2000 mm.
650 25 9 3.7
pressure measurement to obtain the supply flow S-90-R-3. 3-Way Rectangular. Standard dimensions
250 770 30 12 4.6
rate. The standard finish is RAL 9010 white paint, LxH; L: 600-1200 mm and
930 35 17 5.5
although any RAL colour is available upon request. H: 800-2000 mm.
1,000 25 7 2.8
The S-90 displacement diffusers can be used in both S-90-RT. Horizontal Rectangular. Standard 315 1,100 30 10 3.1
comfort and industrial environments. Air is supplied dimensions LxH; L: 800-2000 mm and 1,350 35 14 4.8
from the occupied area level at a slow outlet velocity H: 200-800 mm. 1,400 25 6 3.3
(< 0.8 m/s) to minimise turbulence. Depending on S-90-R-E. Flush-mounted Rectangular. Standard 400 1,650 30 8 3.8 LEGEND
the size, the units can also supply large air volumes. dimensions LxH; L: 400-900 mm and 1,950 35 12 4.5
Q (m3/h): Air flow.
Air is supplied at a temperature difference of –1 to H: 400-600 mm. 1,950 25 5 4.1
LwA [dB(A)]: Power noise level.
–6º C with respect to the ambient temperature. 500 2,300 30 7 5.9
∆Pt (Pa): Pressure loss.
See S-90 catalog for technical data. 2,800 35 10 6.0
X (m): Horizontal throw of the air jet, when
2,800 25 4 5.5 the velocity in the occupied area is 0.20
630 3,400 30 6 6.9 m/s for a temperature difference
4,000 35 8 8.0
of ΔT = -3 ºC.
250 251
S90 General dimensions General dimensions
C
A A A
ØD
ØD
H
H
S90-CC
S90-SC
Size A H Ø D
Size A H Ø D
125 250 900 125
160 335 900 160
160 335 900 160
200 375 900 200
200 375 900 200
250 430 1200 250
250 430 1200 250
315 495 1500 315
315 495 1500 315
400 580 1800 400
400 580 1800 400
500 680 2000 500
500 680 2000 500
630 810 2000 630
630 810 2000 630
Unit mm
Unit mm
252 253
S90 General dimensions General dimensions
F Bx F Bx
C C
50
50
H
H
S90-R S90-R3
A A
Size A H F B C
254 255
S90 General dimensions General dimensions
Bx
175 C
A
C 12
H
100
H
S90-RT
A
S90-RE
Size A H C Size A H B C
1250 x 200 1250 200 350 400 x 400 402 402 250 50
1250 x 350 1250 350 400 500 x 500 502 502 350 50
1450 x 500 1450 500 500 600 x 600 602 602 450 50
1450 x 650 1450 650 700 900 x 600 902 602 600 60
Unit mm Unit mm
256 257
LADES Catalogue Series 90
General dimensions
Ø315 Ø315
60º
1300
1000
1300
1000
Long-Throw
Displacement
Unit
810
terminal is fitted with multiple nozzles for hot
550
air supply.
The lower section has a perforated detachable front
housing for cold air supply. For even distribution of
air, the interior is equipped with an equalising plate. Lades
Lades-I
The multiple nozzle section and the perforated
section are separated by a volume control damper
controlled by an electric motor, a manual control
or a thermal component. The LADES diffuser is
manufactured of galvanised steel sheet. The multiple Selection table
nozzles are manufactured of class V0 ABS material,
in accordance with UL 94. The entire terminal is Configuration Q (m3/h) LwA [dB(A)] ∆Pt (Pa) X (m) Vk (m/s)
LEGEND
painted in RWMZ-60 grey. By special order, the unit 1000 25 11
Q (m3/h): Air flow.
can be painted in other colours. Cold 1175 30 15
LwA [dB(A)]: Puissance acoustique.
1375 35 21
∆Pt (Pa): Total pressure loss.
470 25 9 4.1 5.2
X (m): Maximum velocity of the air stream
Hot 570 30 13 5.0 6.3
at 0.50 m from the diffuser.
690 35 19 6.1 7.6
Vk (m/s): Effective velocity.
258 259
S-90-GV Catalogue Series S-90-GV
General dimensions
ØA
ØB
Nominal Ø A ØB
50
315 313 259
355 353 299
400 398 344
450 449 394
1000
500 498 444
560 558 504
630 628 574
Unit in mm
geometry unit
250
615
715
35
40
16
22
2,6
3,1
250
615
750
35
40
16
24
1,2
1,5
835 45 30 3,6 900 45 35 1,8
915 35 13 3,1 980 35 14 1,6
315 1070 40 17 3,6 315 1200 40 22 1,9
1250 45 23 4,3 1425 45 30 2,3
Product description The recommended minimum installation height
1120 35 11 3,4 1250 35 13 1,5
is 3 m, until maximum installation heights of 8 m.
355 1315 40 15 4,0 355 1500 40 19 1,8
The S-90-GV diffusers are variable geometry units
1535 45 20 4,6 1800 45 27 2,2
for installation at considerable heights.
They are used in industrial environments, in both
Finished 1475 35 10 3,9 1650 35 13 1,8
400 1720 40 14 4,6 400 2000 40 19 2,2
heating and cooling systems
They are made of galvanised steel sheet with built-in 2010 45 19 5,4 2400 45 28 2,6
They consist of a perforated cylinder, inner discs,
equalizing air discs and damper. 1805 35 29 4,3 2050 35 38 2,0
and a damper to change the discharge air flow.
The standard finish is RAL 9010 white paint, 450 2010 40 37 4,8 450 2400 40 52 2,3
The air flows into the cylinder guide through the 2460 45 55 5,9 2875 45 75 2,8
although any RAL colour is available upon request.
orifice plate, when contacting the damper changes
Stainless steel and lateral connection are available as 2165 35 28 4,6 2400 35 38 2,1
the discharge air stream. 500 2530 40 38 5,4 500 2900 40 49 2,6
an option.
In cooling mode the air is discharged horizontally 2950 45 51 6,3 3500 45 71 3,1
and spreads in a radial pattern. 2500 35 23 4,8 3000 35 33 2,3
In heating the damper is closed and the air is 560 2900 40 31 5,5 560 3500 40 45 2,7
discharged downwards. 3375 45 42 6,4 4250 45 66 3,3
The damper can be adjusted manually, by motor- 3030 35 21 5,1 3250 35 24 2,2
driven means or by a temperature-adjustable item. 630 3540 40 28 6,0 630 3950 40 35 2,7
4135 45 39 7,0 4700 45 50 3,2
The unit is connected by means of a circular spigot
LEGEND
in the upper cover.
Q (m3/h): Air flow.
The diffusers may be suspended or fixed to columns
LwA [dB(A)]: Puissance acoustique.
or walls, on a duct bend or take-off below the main
∆Pt (Pa): Total pressure loss.
duct.
Y (m): Maximum penetrarion of the air stream of with ΔT = +10º C
Throw for a maximum velocity of 0,20 m/s at the occupied zone, with ΔT = -6º C.
260 261
Hospitals
Clean rooms
Móstoles Hospital
(Madrid - Spain)
Grilles 20-SHO, 20-45-H and 22-5,
linear floor grille 31-1-F,
square diffuser 50-FR-1,
long throw multinozzle MT3.SB,
swirl diffusers, DFRO, DFRA-OV, DFRO-C and KFD,
extract valves 46-SV,
boxes KS and KSV,
regulators KCR, RCQK and KD-RCQK,
air volume control dampers AOBD-102-E,
13
absolute filter plenum KPA,
silencers PAM,
active chilled beam VFK-Q 600
and rectangular fire dampers SFR3K1GT + motor and
SFR4 + motor.
KPA Catalogue Series KPA
General dimensions
ExF
CxD
High Models DFRO/DFRA: (D+6) x (C+6) Circular side entry
performance Custom plenums available to suit reduced heights above false ceilings and air flow per unit.
Consult Technical Dept.
filter plenum
Filter C D E F Ø G J
Other models 762 x 762 x 68 827 827 810 810 248 530
762 x 762 x 90 827 827 810 810 313 617
KPA - PDS. Circular top entry plenum.
915 x 915 x 68 969 969 955 955 313 596
KPA - PDL. Circular side entry plenum.
915 x 915 x 90 969 969 955 955 313 617
KPA - PDLR. Rectangular side entry plenum.
Unit mm Other sizes of filters available
264 265
TURBULENT FLOW
KPA-DFRO KPA-54-FR-I-4
KOOLAIR terminal unit with high-efficiency air filter, model KPA-DFRO. KOOLAIR terminal unit with high-efficiency filter, model KPA-54FRI4.
Incorporates LxWxH mm high efficiency particulate air filter (H13, H14, U15, Incorporates LxWxH mm high efficiency particulate air filter (H13, H14, U15,
U16), adjustable blade swirl diffuser model DFRO, size__, filter holder plenum U16), square diffuser made from perforated sheet metal with deflecting mesh for
with either lateral or top, rectangular or circular connection, manufactured in air supply in 4 directions model 54-FR-I-4, size__, filter holder plenum with either
galvanised sheet steel with painted interior and exterior, integrated differential lateral or top, rectangular or round connection, manufactured in galvanised
pressure connection. Painted finish in RAL defined by Project Management. sheet steel with painted interior and exterior, integrated differential pressure
connection. Painted finish in RAL defined by Project Management.
LEGEND LEGEND
Q (m3/h): Air flow. Q (m3/h): Air flow.
LwA [dB(A)]: Power noise level. LwA [dB(A)]: Power noise level.
∆Pfilter (Pa): Pressure loss in the filter. ∆Pfilter (Pa): Pressure loss in the filter.
∆Pdiffuser (Pa): Pressure loss in the diffuser. ∆Pdiffuser (Pa): Pressure loss in the diffuser.
∆Ptotal (Pa): Total pressure loss. ∆Ptotal (Pa): Total pressure loss.
266 267
KTF Catalogue Series KTF
General dimensions KTF
30
Lm x Hm
L1 x H1
H+10
LxH
25
450 L+10 150
2067
1339 2067 2736
2067
Filtration
2736
2677
1550
1550
2100
1000
2008
2618
2982
1800
ceiling KTF 2,5x1,5
2736
KTF 2x2 KTF 2,5x2
3405
KTF 2,5x2,5
3580
KTF 3x2
3287
2950
3287
2350
3287
Product description Other models 4074
KTF 3x2,5 KTF 3,5x3 KTF 4x3
The filtration ceiling is an air diffusion element for KTF-DIF. For supplying sterile, particle-free air in
high efficiency filtering of unidirectional flow to a vertical descending laminar flow (unidirectional).
comply with all applicable hospital regulations. The Differentiating different supply velocities in order
to minimise and combat the negative effects of
55
KTF filtration ceiling is suitable for Level 3 and 4 risk 30 150
areas in accordance with NF S 90-351. It complies turbulence caused by surgical lamps. This sterile, SYMBOLS
with ISO class 5 requirements for ambient air quality particle-free flow of stabilised air protects the patient, A : Filter
inside operating rooms in accordance with EN- medical equipment and the surgical instrument table,
200
B : Perforated grille
or the test or work area in the case of clean rooms.
450
ISO-14644-1 and with leakage test requirements in C : Plenum
accordance with ISO 14644-3. Incorporates high-efficiency particulate air filters D : Lateral air inlet
195
H13, H14, U15 or U16. E : Light pendant opening
KTF-SL. Filtration ceiling with no central core to 25
Finished integrate lamp with a higher filtering capacity.
L1 x H1
Note: For more information refer to catalogue and/or Technical Department. Unit mm
268 269
General dimensions KTF-SL Selection table using flow rate
KTF
FILTERS Q (m3/h) ∆Pfilter (Pa) ∆Pdiffuser (Pa) ∆Ptotal (Pa) Lwa [dB(A)]
SIZE
UNITS SIZE max min max min max min max min max min
30
2,5 x 1,5 3 1200x610x68 4350 2190 160 40 1 1 161 41 <20 <20
2 610x305x68
2 x 2 4 915x610x68 4800 2200 160 40 1 1 161 41 <20 <20
2 610x610x68
Lm x Hm
2,5 x 2
L1 x H1 4 1220x610x68 6800
H+10
3420 160 40 1 1 161 41 <20 <20
LxH
2 915x610x68
1 1220x610x68 7550
3 x 2 3780 160 40 1 1 161 41 <20 <20
7 915x610x68
2,5 x 2,5 10 915x610x68 9000 4500 160 40 1 1 161 41 <20 <20
8 1220x610x68 11800
3 x 2,5 5940 160 40 1 1 161 41 <20 <20
2 915x610x68
25
2067
1339 2067 2736
2067 KTF-SL
F ILTERS Q (m /h) ∆Pfilter (Pa)
3
∆Pdiffuser (Pa) ∆Ptotal (Pa) Lwa [dB(A)]
SIZE
2618
2618
2008
1550
1550
2100
1000
2982
1800
2736
UNITS SIZE max min max min max min max min max min
2,5 x 1,5 4 1200x610x68 5000 2520 160 40 1 1 161 41 <20 <20
2 x 2 6 915x610x68 5400 2700 160 40 1 1 161 41 <20 <20
KTF-SL 2,5x1,5 KTF-SL 2x2 KTF-SL 2,5x2 KTF-SL 2,5x2,5 KTF-SL 3x2 2,5 x 2 6 1200x610x68 7500 3780 160 40 1 1 161 41 <20 <20
2736 3405 3580 2,5 x 2,5 8 1200x610x68 10000 5041 160 40 1 1 161 41 <20 <20
3 x 2 9 915x610x68 8100 4050 160 40 1 1 161 41 <20 <20
3 x 2,5 4 1220x610x68 12200 6120 160 40 1 1 161 41 <20 <20
8 915x610x68
3,5 x 3 5 1220x610x68 15250
2350
3287
2350
3287
3287
30 150
SYMBOLS ∆Pfilter (Pa): Pressure loss in the filter.
A : Filter ∆Pdiffuser (Pa): Pressure loss in the diffuser.
200
C : Plenum
D : Lateral air connection
Selection table using air velocity through filter
195
25 L1 x H1
KTF KTF-SL
LxH
Model Air velocity through filter (m/s) Air velocity through filter (m/s)
Model Hole Total dimension Spigot No. of parts 0,2 0,3 0,4 0,2 0,3 0,4
L1 H1 L x H x A Lm x Hm 2,5 x 1,5 1880 2820 3760 2150 3220 4290
2,5 x 1,5 1309 2706 1329 x 2726 x 450 1000 x 200 1 2 x 2 2150 3220 4290 2420 3620 4830
2 x 2 2037 1978 2057 x 1998 x 450 1550 x 200 2 2,5 x 2 2950 4430 5900 3220 4830 6430
2,5 x 2 2037 2588 2057 x 2608 x 450 1550 x 200 2
3 x 2 3350 5030 6700 3620 5430 7240
3 x 2 2037 2952 2057 x 2972 x 450 1800 x 200 2
2,5 x 2,5 4020 6030 8040 4290 6430 8580
2,5 x 2,5 2706 2588 2726 x 2608 x 450 2100 x 200 2
3 x 2,5 2706 3257 2726 x 3277 x 450 2350 x 200 4 3 x 2,5 5100 7640 10190 5360 8040 10720
3,5 x 3 3375 3257 3395 x 3277 x 450 2950 x 200 4 3,5 x 3 6430 9650 12860 6700 10050 13400
4 x 3 4044 3257 4064 x 3277 x 450 3580 x 200 4 4 x 3 7770 11660 15540 8040 12060 16080
270 271
KRH Catalogue Series KRH
General dimensions
28
A
28
B 61
Grille Grille
Model Filter A B Model Filter A B
Filterholder
KRH 3015 R 305 x 150 x 48 415 260 KRH 6130 R 610 x 305 x 48 720 415
KRH 3915 R 395 x 150 x 48 505 260 KRH 3949 R 395 x 490 x 48 505 600
return grille
KRH 3030 R
KRH 3039 R
305 x 305 x 48
305 x 395 x 48
415 415
415 505
KRH 3961 R
KRH 4949 R
395 x 610 x 48
490 x 490 x 48
505
600
720
600
KRH 3049 R 305 x 490 x 48 415 600 KRH 4961 R 490 x 610 x 48 600 720
KRH 4930 R 490 x 305 x 48 600 415 KRH 6161 R 610 x 610 x 48 720 720
KRH 3939 R 395 x 395 x 48 505 505 KRH 4991 R 490 x 915 x 48 600 1025
Product description Finished KRH 3061 R 305 x 610 x 48 415 720 KRH 7676 R 762 x 762 x 48 872 872
Filterholder return grille brand Koolair, model KRH for Standard finish in galvanized steel, epoxy paint, RAL Unidad en mm
installation in clean rooms, pharmaceutical 9010 color.
industries and hospital settings. By special order, other RAL colours can be
Possibility of G4 to F7 filtration (48 mm) or G4 (13 requested. Selection table Selection table
mm) + F7 (34 mm) double filtration. Optional AISI 304 stainless steel. (1 grille) (2 grilles)
They are used for air evacuation in surgical theatres Model Q (m3/h) Lower grille Upper grille Q (m3/h)
and rooms with high cleanliness requirements.
Accessories
KRH 3015 R 200 KRH 3030 R KRH 3015 R 500
This filter is easy to clean and can be seen from the PFS. Plenum box with upper discharge. KRH 3915 R 320 KRH 3939 R KRH 3915 R 850
room, which makes clogging easy to check for fast, PFL. Lateral discharge plenum. KRH 3030 R 500 KRH 3061 R KRH 3030 R 975
simple maintenance. PFE. Pyramidal plenum box with lateral discharge KRH 3039 R 540 KRH 3961 R KRH 3939 R 1225
Filters installed flush with the grille to prevent “dead O. Control damper in discharge. KRH 3049 R 800 KRH 4961 R KRH 4930 R 1600
KRH 4930 R 800 KRH 6161 R KRH 6130 R 2000
areas” with quick 1/4-turn tab changes.
KRH 3939 R 840 KRH 4991 R KRH 4949 R 2350
Lateral or top connection plenum manufactured.
Models KRH 3061 R 970
Total reference flow
Differential pressure meter included. KRH 6130 R 970
Possibility of ceiling mount. KRH. Filterholder return grille with G4 filtration.
KRH 3949 R 1000
Air evacuation from surgical theatres with F5 filtration KRH-2. Filterholder return grille with G4+F7 double KRH 3961 R 1220
as recommended in NF S 90-351. filtration. KRH 4949 R 1220
KRH 4961 R 1560
KRH 6161 R 1950
KRH 4991 R 2340
KRH 7676 R 3030
Note: For more information refer to catalogue and/or Technical Department.
272 273
More…
NEW
230-SP (280)
PE-40/41 (283)
AOBD (277)
CSP-C (281)
PE-45 (284)
210-TA (278)
14
swirl diffusers DFRO, DFRA-OV and DFTR-R,
linear diffusers LK-70,
long throw multinozzle DF-49-MT3-SB,
regulators RCCK and RCQK
and rectangular fire dampers SFR.
AOBD-C3 AOBD Catalogue Series 100-200
Airtight
regulating
damper
Product description and 100 mm are available to fit the entire range
of standard duct dimensions increasing in 50mm
KOOLAIR regulating damper with opposed and increments. Anodised aluminium finish.
aerodynamic blades, model AOBD-C3. Meets
specifications established in EN 1751 achieving
class “C” air tightness through the casing and class Models
AOBD Ready to be motorized
Regulating Damper
“3” air tightness through the blades of the damper AOBD-C3-RPM. Capable of being motor-driven.
by means of a V1 classified self-extinguishing PVC AOBD-C3-M. With manual operating mechanism. Product description motor-driven operation.
AOBD-C3-MT. Type of servo motor to be specified Vanes are available with 50 mm vane axis distances,
gasket. Regulating damper with opposed and aerodynamic
on order: All-or-nothing or proportional with to complete the entire range of standard duct
The movement of the blades is ensured via gears vanes, manufactured in aluminium (AOBD). The dimensions. Finishes in natural aluminium.
command signal 0-10 V body of the damper has built-in air tight gaskets
that achieve the proper level of friction. Manual or
motor-driven operation. Blade heights of 75 mm all around its inner perimeter to ensure a tight seal.
The movement of the vanes is ensured by means
General dimensions of gears, achieving a proper friction, with manual or
General dimensions
L 200 300 400 500 600 700 800 900 1000 1200 1500 2000 2400
H
100
150
200
H (100 to 2000)
250
H + 60
300
500
800
L (100 to 2400)
1000 L + 60
120 L (100 to 2400)
1200
L + 60
1500 Model AOBD-102-C3 double length (L>1200)
2000
Note: For more information refer to catalogue and/or Technical Department.
Manufactured in 50mm length and height increments.
Note: For more information refer to catalogue and/or Technical Department.
210-TA Catalogue Series 100-200 TAC-200 Catalogue Series 100-200
General dimensions
General dimensions Nominal Ø A Ø B Ø C E
68 L + 66
E 125 181 121 145
40
ØC (Hole)
ØB 500 560 480 500
ØA
Unit mm
Note: For more information refer to catalogue and/or Technical Department. Note: For more information refer to catalogue and/or Technical Department.
230-SP Catalogue Series 100-200 CSP-C
Round
overpressure
Overpressure damper
damper
Product description Static pressure loss
Product description Other models Round overpressure damper, KOOLAIR CSP-C through the damper table
model. ΔPst (Pa)
Overpressure damper, KOOLAIR 230-SP model. 230-SPI. Overpressure damper with U-frame and Standard housing finish in galvanized steel sheet; fin Model Vc (m/s) = 2 Vc (m/s) = 4
Includes sealing strip in fins for more efficient closure interconnected fins, for wall mounting. in aluminium.
and sound absorption. By special order, they can 230-SPU. Overpressure damper with U-frame for CSP-C 100 78 85
be supplied with a U-frame, with inverted fins, alternating installation. CSP-C 125 56 64
interconnected fins, etc. 230-SPUI. Overpressure damper with U-frame and CSP-C 150 33 40
The frame includes drilled holes for flush-mounting interconnected fins, for alternating installation. General dimensions CSP-C 160 30 33
or duct attachment with bolts or rivets. CSP-C 200 15 14
Manufactured in extruded aluminium, standard CSP-C 250 13 15
natural aluminum finish. CSP-C 315 11 11
CSP-C 355 9 10
32
32
32
(L + 20) x (H + 20)
121 49 63
1. Airtight gasket between damper and duct (2 parts as of CSP-C 150 146 62 76
H + 64
LxH
LxH
LxH
LxH
Note: For more information refer to catalogue and/or Technical Department. Note: For more information refer to catalogue and/or Technical Department.
PE-20/21 PE-40/41
Models
Models
PE-20. Upper connection plenum, removable
for attachment by clips to the grille. Standard PE-40. Upper connection plenum. Standard
uninsulated finish and without flap at inlet uninsulated finish and without flap at outlet.
Manufactured in galvanized steel sheet. Manufactured in galvanized steel sheet.
PE-21. Lateral connection plenum, removable PE-41. Lateral connection plenum. Standard
for attachment by clips to the grille. Standard uninsulated finish and without flap at outlet.
Manufactured in galvanized steel sheet.
Connection plenum for Plenum for square
uninsulated finish and without flap at outlet.
Manufactured in galvanized steel sheet.
Available with insulation (-A) and damper at outlet,
S-20 and S-30 grilles Available with insulation (-A) and damper at outlet,
upon request.
diffusers upon request.
15
L+2 H+2
ØD
ØD
C
LxH
PE-41
150
Nominal (L x H) A B C ØD
150 x 150 150 180 239 124
225 x 225 225 255 274 159
300 x 300 300 330 314 199
PE-20 L= Nominal Length (Opening) 375 x 375 375 405 364 249
450 x 450 450 480 429 314
H= Nominal Heigth (Opening) 525 x 525 525 555 469 354
600 x 600 600 630 514 399
L+2 H+2 Unit in mm
B A
ØD
ØD + 25
50
ØD
ØD + 150
120
LxH
PE-40
Nominal (L x H) A B ØD
150 x 150 152 152 124
PE-21
L= Nominal Length (Opening) 225 x 225 227 227 159
H= Nominal Heigth (Opening) 300 x 300 302 302 199
375 x 375 377 377 249
450 x 450 452 452 314
525 x 525 527 527 354
Please consult us for dimension details. 600 x 600 602 602 399
Unit in mm
Material
Expanded polystyrene for isolation to UNE EN
13163.
Class E1 fire-resistant material, with a density of 45
mg/m2 and grey colour.
Transmission coefficient of 0.031 W/mk.
General dimensions
ØC
320
590
595
KOOLAIR (Morocco)
KOOLAIR BENELUX (Belgium, N°139. R22
Netherlands and Luxembourg) Lot. Elouarda
Tel: +32 478237630 20600. Casablanca - Morocco
e-mail: bruno.dewever@koolair.com Tel: +212 (0) 522 706 785
Tel: +32 475727098 e-mail: latifa.jarmouni@koolair.com
e-mail: mikael.lavole@koolair.com e-mail: othman.gahiri@koolair.com
www.koolair.com
Koolair S.L reserves the right to change publisher datas and drawings
at any time without prior notice written. CEN-GST-0319-02