---- SDV

790337
Closed Before
Pump Stop No Hazards

0.99812 1.00 0.000101464

VX790009
Normal (pass 10%) Gas trapped (Vol V1)
SDV 790337 (TSO)
NRV VX790007
Normal (Pass 10%) 0.434 1.00 0.000000047
0.98655
NRV VX790009
0.566 Fail (Pass 10%-100%) Gas Trapped (Vol V2)

SDV 790337 Delayed


Closed After Pump Stop 0.566 1.00 0.000000061

VX790009
0.00188 Normal (pass 10%) Gas Trapped Vol (V2)

NRV VX790007
Fail (Pass 10%-100%) 0.566 1.00 0.000000047

NRV VX790009
0.434 Fail (Pass 10%-100%) Gas Trapped Volume (v3)

0.434 1.00 0.000000036

VX790009
Normal (pass 10%) 0.1% Revers Flow

NRV VX790007
Normal (Pass 10%) 0.566 1.00 0.000000074

NRV VX790009
SDV 790337 0.566 Fail (Pass 10%-100%) 0.5% Reverse Flow
Close (PALL OK)

SDV 790337
(Not TSO 10% Pass) 0.434 1.00 0.000000057
0.99

VX790009
0.00225 Normal (pass 10%) 0.5% Revers Flow

NRV VX790007
Fail (Pass 10%-100%) 0.566 1.00 0.000000057

NRV VX790009
0.434 Fail (Pass 10%-100%) 2.5% Reverse Flow

0.434 1.00 0.000000044

VX790009
Normal (pass 10%) 5% Revers Flow

NRV VX790007
Fail (Pass 10%-100%) 0.566 1.00 0.000000327

NRV VX790009
0.50 Fail (Pass 10%-100%) 25% Reverse Flow

Pump Trip SDV 790337


Stuck Open 0.434 1.00 0.00000025

0.114
VX790009
0.0112 Normal (pass 10%) 1% Revers Flow

NRV VX790007
Normal (Pass 10%) 0.566 1.00 0.000000327

NRV VX790009
0.50 Fail (Pass 10%-100%) 5% Reverse Flow

0.434 1.00 0.00000025

VX790009
Normal (pass 10%) 5% Revers Flow

NRV VX790007
Fail (Pass 10%-100%) 0.566 1.00 0.000000256

NRV VX790009
0.434 Fail (Pass 10%-100%) 25% Reverse Flow

SDV 790337
Open (PALL FAIL) 0.434 1.00 0.000000196

VX790009
0.01 Normal (pass 10%) 1% Revers Flow

NRV VX790007
Normal (Pass 10%) 0.566 1.00 0.000000333

NRV VX790009
0.566 Fail (Pass 10%-100%) 5% Reverse Flow

0.434 1.00 0.000000256


SDV 790337
Closed Before
Pump Stop No Hazards

0.99812 1.00 0.000233136

VX790009
Normal (pass 10%) Gas trapped (Vol V1)
SDV 790337 (TSO)
NRV VX790007
Normal (Pass 10%) 0.434 1.00 0.000000108
0.99775
NRV VX790009
0.566 Fail (Pass 10%-100%) Gas Trapped (Vol V2)

SDV 790337 Delayed


Closed After Pump Stop 0.566 1.00 0.000000141

VX790009
0.00188 Normal (pass 10%) Gas Trapped Volume (V2)

NRV VX790007
Fail (Pass 10%-100%) 0.566 1.00 0.000000108
SDV 790337
PALL Successs Close (OK) NRV VX790009
0.434 Fail (Pass 10%-100%) Gas Trapped Volume (V3)

Injection 0.99 1.00


(once every 3 years) 0.434 1.00 0.000000083

VX790009
0.000913 Normal (pass 10%) 0.1% Revers Flow

NRV VX790007
Normal (Pass 10%) 0.566 1.00 0.000000169

NRV VX790009
0.566 Fail (Pass 10%-100%) 0.5% Reverse Flow

SDV 790337
(Not TSO 10% Pass) 0.434 1.00 0.000000129

VX790009
Pump Damage 0.00225 Normal (pass 10%) 0.5% Revers Flow
(BD, EL, IL, LO)
NRV VX790007
Fail (Pass 10%-100%) 0.566 1.00 0.000000129
0.259
NRV VX790009
0.434 Fail (Pass 10%-100%) 2.5% Reverse Flow

0.434 1.00 0.000000099

VX790009
Normal (pass 10%) 1% Revers Flow
Start
NRV VX790007
Normal (Pass 10%) 0.566 1.00 0.000000758

NRV VX790009
0.566 Fail (Pass 10%-100%) 5% Reverse Flow

PALL Fail 0.434 1.00 0.000000581

VX790009
0.01 Normal (pass 10%) 5% Revers Flow

NRV VX790007
Fail (Pass 10%-100%) 0.566 1.00 0.000000581

NRV VX790009
0.434 Fail (Pass 10%-100%) 25% Reverse Flow

0.434 1.00 0.000000445

Pump OK No Hazards

0.627 1.00 0.000572451

No Injection No Hazards

0.999087 1.00 0.999087