Professional Documents
Culture Documents
PVP2011
July 17-21, 2011, Baltimore, Maryland, USA
PVP2011-57017
Abstract high noise and vibration causing nausea and other medical
This paper presents investigational findings and a problems. Onsite vibration and sound measurements took place
discussion of recommendations relating to sound and vibration in March 2010. The vibration and sound data were acquired
measurements performed in connection with a fluid induced during steady state operating conditions of the blowers. During
vibration issue on two air blowers and attached exhaust piping these measurements only two blowers were operating, blower
at an industrial facility. These vibration and sound “B” and blower “C”.
measurements were prompted by recent check valve failures
for the air blower units, and unacceptable sound levels
emanating from these units and affecting nearby residents. This
data was acquired during steady state operating conditions of
the blowers under normal operating conditions. An FFT data
acquisition system, a piezoelectric microphone and three
piezoelectric triaxial accelerometers were used to collect
vibration measurements at each of the 70 locations on the
blowers, motors, blower bases, and exhaust piping, while
sound measurements were simultaneously acquired with the Damage
microphone. Piping and blower vibration readings were used to
construct an operating deflection shape analysis of the blowers,
foundations and attached piping system. The resulting vibration Damage
and sound analysis revealed that acoustic excitation of the
piping system appeared to be the likely source of the high
vibration, high sound pressure levels; piping cracks and check
valve failures. Corrective actions were implemented that
reduced the sound pressure levels, vibration levels, and
reduced/eliminate the piping damage and valve failures.
INTRODUCTION
Metrix was retained by plant management to provide
Photos 1 and 2: Check Valve Damage
vibration and acoustic diagnostics expertise to analyze elevated
noise and vibration levels of four air blowers. This project
Recent check valve failures and repair of cracked exhaust
encompasses sound and vibration measurements of aeration
piping were causing forced outages of the blower units and
blowers and attached exhaust piping for an MBBR wastewater
severely disrupting the water treatment process. Economic
treatment plant within a large industrial plant. This
impact of the potential cracked valves and piping while in
investigation was prompted by recent check valve component
service were causing waste treatment plant downtime and were
failures for these blower units, and unacceptable sound levels
estimated to be exceeding $100,000 for 2010. Potential
emanating from these blower units which potentially would
complaints about objectionable noise levels from nearby
affect nearby residents (photos 1 and 2). Plant maintenance
residents were also a concern. By correctly identifying root
workers were also hesitant to work around these units due to
INSTRUMENTATION
Throughout the body of this paper, the following
conventions will be used; regarding sensor naming and
orientation. Blowers are “viewed” as being with the “X”
direction, or axial direction, along the shafts of the motors and
Blower B
blowers. The positive “X” direction is along the blower driven
Blower A
shaft from blower C towards blower B. Likewise, the “Y”
direction will be perpendicular to the “X” direction in the
horizontal plane, see figures 1 and 2. The “Z” direction is
vertical, perpendicular to both the “X” and “Y” directions;
+X Direction
forming a “right hand” coordinates system for these vibration
measurements. The triaxial accelerometer sensor directions
follow this same coordinate system. For instance, a vibration
measurement at location 1 in the vertical direction will be Blower C
referred to as a vibration amplitude (velocity and displacement)
“1Z” in the following vibration summary tables later in this Blower D
paper. +Y Direction
120
S10, 10
X: 3.585k
Y: 104.5
Misalignment (coupling misalignment)
100 Impellers/lobes rubbing
80 Worn bearings and gears
Unbalance
dBMag, SPL_(A)
60
40 Blower looseness
20
Piping resonances (standing wave pressure
0
pulsations)
-20
Foreign material buildup
0 10k 20k
CPM
30k 40k
Casing strain
Figure 3: Sound Pressure Spectrum,
Adjacent to Blower C, 111 dBA Overall Vibration levels were consistently higher in the vertical
direction compared to the axial and lateral directions,
Since the blowers input shaft are turning at 1800 rpm and particularly for blower B. This appeared to be likely caused by
each shaft has 2 lobes, pressure pulsations from the exhaust of downward exhaust pressure pulsations (forces) in the exhaust,
these blowers occurred at 3600 cpm or 60 Hz. This naturally which exits downward from beneath each blower [5], vibrating
explains the high sound level component at 3600 cpm. both the blower and piping vertically. This motion was plainly
Unfortunately, this frequency also roughly matches the length visible in the operating deflection shape of each blower, seen in
of a ½ wavelength potential standing wave in the vertical pipe later section of this paper. These measurements also showed
section of each blower exhaust. To suppress these pressure that vibration frequency components at blower running speed
pulsations, a discharge (exhaust) silencer was considered to be (1800 rpm) and below were poorly correlated (low coherence)
twice blower running speed (3600 rpm) and above did correlate Y: 125.9m
LogMag, in/s
speed, like blower unbalance…, was not responsible for the 1.0m
Locations ips Peak ips Peak ips Peak Figure 4A: Auto Power Spectrum, Blower B,
Coupling End, OA 0.693 0.368 0.342 Driven Shaft, Coupling End Bearing,
Drive Shaft Bearing Vibration Velocity in Axial Direction
Coupling End, 1X 0.018 0.091 0.045
Drive Shaft Bearing
Blind End, Drive OA 0.624 0.604 0.463 1.0
S5, 5
X: 1.800k
Shaft Bearing Y: 213.7m
LogMag, in/s
Shaft Bearing 1.0m
Shaft Bearing
Blind End, Idle 1X 0.044 0.190 0.032 1.0µ
10k 20k 30k 40k
CPM
Shaft Bearing
Figure 4B: Auto Power Spectrum, Blower B,
Notes:
OA = Overall Direct (unfiltered) vibration amplitude, Driven Shaft, Coupling End Bearing,
inches per second (ips) peak Vibration Velocity in Vertical Direction
1X = Synchronous (once-per-revolution) filtered vibration amplitude,
inches per second peak
S6, 6
Table 1 1.0 X: 1.800k
Y: 140.0m
100m
10m
LogMag, in/s
Blower “C”
Figure 7: Operating Deflection Shape at 3600 cpm Figure 10: Operating Deflection Shape at 3600 cpm
Isometric View Axial View
Blower “C”
Blower “B”
Figure 8: Operating Deflection Shape at 3600 cpm Blower “B” Blower “C”
Top View
Since the blowers could not be shut down for more than 5 Blower “C”
minutes without compromising the bacteria in the process,
adequate modal measurements could not be performed to
identify any natural frequencies of the piping or blowers. This Blower “B”
was recommended as testing to be conducted during a future
outage.
Figure 12: Operating Deflection Shape at 3600 cpm
Top View
Magnitude
400m
200m
Blower “B” 0
0 200 400 600 800
Hz
1.0
400m
200m
0
0 200 400 600 800
Figure 14: Operating Deflection Shape at 3600 cpm Hz
In July 2010, Blower C experienced problems with silencer Photo 5: Location of Installed Silencers
packing material escaping without any detectable mechanical
Photo 7: Disassembled silencer showing Economic impact of the potential cracked valves and
loss of packing material without piping while in service causing waste treatment plant downtime
physical damage to silencer was estimated as exceeding $100,000 for 2010. Potential
complaints about noise levels from nearby residents were also
averted. By correctly identifying root cause(s) of the high
vibration and noise levels, this cost was avoided.
REFERENCES
1. ISO-3746, “Acoustic – Determination of Sound Power
Levels of Noise Sources Using Sound Pressure – Survey
Method Using an Enveloping Measurement Surface Over a
Reflecting Plane”, 1995-08-15.
Figure 16: New silencer design 4. Blevins, R.D., ”Formulas for Natural Frequency and Mode
Shape”, 2001, pg. 340.
SUMMARY
The above case history clearly shows that integration of 5. Yeon-Whan K, Young-Shin L., “Damage prevention design
sound and vibration measures along with an operating of branch pipe under pressure pulsation transmitted from main
deflection shape analysis and presentation of the vibration data steam header”, JMST, Volume 22, Number 4, Pg 647-652.
proved to be an effective methodology for solving piping
related issues. 6. Bently, D. E., Hatch, C. T., “Fundamentals of Rotating
Machinery Diagnostics”, 2002, pg. 1-19.