Professional Documents
Culture Documents
net/publication/258140202
CITATIONS READS
33 9,319
3 authors:
A Z A Saifullah
International University of Business Agriculture and Technology
21 PUBLICATIONS 214 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by A Z A Saifullah on 09 January 2016.
A Field Study on Thermal Comfort of Occupants and Acceptable Neutral Temperature at the National
Museum in Malaysia
Y. H. Yau, B. T. Chew and A.Z.A. Saifullah
Indoor and Built Environment published online 5 December 2011
DOI: 10.1177/1420326X11429976
Published by:
http://www.sagepublications.com
On behalf of:
Additional services and information for Indoor and Built Environment can be found at:
Subscriptions: http://ibe.sagepub.com/subscriptions
Reprints: http://www.sagepub.com/journalsReprints.nav
Permissions: http://www.sagepub.com/journalsPermissions.nav
What is This?
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
Original Paper
Indoor and Built Accepted: October 23, 2011
Environment Indoor Built Environ 2011;000;000:1–12
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
decay. Biological deterioration may also occur in the This research aims to provide:
collection. Lower temperature is associated with higher
. Measurement and characterization of occupants’ ther-
RH. This improves growth conditions for microbial
mal perceptions in a museum in Malaysia.
organisms. Hence, caution must be taken to control the
. Comparison between predicted and observed values of
temperature of the museum to be within a suitable range.
the percentage of the occupants dissatisfied.
The most important factors with regard to damage to the
. Determination of the acceptable neutral temperature in
collections are the indoor temperature and RH of the
the museum.
museum.
. Measurement of the indoor thermal environmental
Most museums require a RH of 40–55% and a
parameters by sensors.
temperature of 18–248C, with daily fluctuations of 3%
. Determination of strategies in designing HVAC systems
RH and 38C, respectively. A filtration design is necessary
with low energy consumption for a thermally comfor-
to remove at least 50% of particulates and contaminants
table environment expected by the occupants of
in order to achieve comfort and health [11]. For general
museum buildings in the tropics.
museums, the American Society of Heating, Refrigerating
and Air Conditioning Engineering (ASHRAE) Handbook
2007 recommends a temperature range of 15–258C and a
RH of less than 60% [12]. Theory on Thermal Comfort
According to Plenderleith and Werner, the museum
room temperature suitable for the occupants within the Thermal comfort standards play a great role in building
limits of 16–258C should be determined first, and then the sustainability as these are the determining factors for
RH should be decided with regard to the collections [13]. energy consumption of a building’s environmental
Thomson suggests an upper and lower limit of RH of 65% systems. Thermal comfort is a measurement of the level
and 45% for moisture-absorbing materials [14]. Ascione of comfort of the indoor environment as perceived by the
[3] and Bellia [15] suggest an air temperature of 22 18C occupants, and gives an indication of the proportion of
and 50 5% RH for exhibition rooms. The Museums occupants that notice warmth or coolness in a space. The
Australia Victoria recommends that the temperature range classical approach, called the T–RH method, of control-
for a museum should be 18–228C [16]. Temperatures lower ling or measuring air temperature and humidity is not
than 188C put museum collections at risk. The lower level practically feasible for the assessment of the museum’s
of the temperature range is decided by the comfort of the environment. People’s thermal comfort depends on both
museum staff and visitors. It is more difficult to maintain personal and environmental factors. The parameters that
the recommended humidity level when the temperature is determine indoor thermal conditions are mainly tempera-
below 108C, and there may be problems associated with ture and sensation indices.
condensation. The higher the temperature level, the faster Fanger created the predicted mean vote (PMV) model to
the degradation processes. Thus, the people’s comfort and determine the thermal comfort conditions for working and
the preservation of the collections determine the tempera- living spaces. Based on thermo-neutrality, the PMV model
ture range of 18–228C. The temperature of the areas expresses the mean value of the votes by a large group of
seldom visited by staff and visitors may be kept lower (in persons on a seven-point thermal scale, which describes the
cases where heating is required). thermal perceptions of the occupants. The PMV index is a
Besides indoor air temperature and RH, effective function of four environmental parameters – air tempera-
outdoor air ventilation is necessary for providing a ture, partial pressure of water vapour, relative air velocity
comfortable environment for the occupants. Excessive and mean radiant temperature, and two environmental
flow of outdoor air could lead to particle and gaseous parameters – metabolic rate and clothing insulation.
pollution. Furthermore, it would cause an unreasonably Assuming steady-state laboratory conditions in its
high latent heat load in a humid climate and, thereby, derivation, the PMV model makes an oversimplification
cause unacceptably high energy consumption. Thus, out- of its sensitivity to the metabolic rates and the clo-values.
side air flow should be kept to the minimum required for Thus, thermal impressions are underestimated and the
supplying fresh air to the occupants and pressurizing the swings of these impressions get undervalued. Transitional
collection areas. It is advisable to keep the outdoor air spaces are excluded for thermal comfort predictions by the
flow rate lower than the maximum limit of 0.25 ms1 PMV model as the physical conditions and the met values
recommended by the ASHRAE Standard 55 [17]. are unstable and dynamic in nature [18]. The psychological
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
and the behavioural adaptations in the real world are not temperature or an acceptable range of temperature and
considered in the PMV model [19]. outdoor meteorological parameters.
The PMV equation is only applicable where human Comfort zones are defined by the International
beings remain at constant conditions for a long period Standards ISO 7730 [24] and the ASHRAE Standard
with a constant metabolic rate. The PMV model does not 55-92 [25] by the application of Fanger’s lab-oriented
give good results due to inaccurate specifications of some PMV-predicted percent dissatisfied (PPD) method. The
of its input parameters. Buratti and Ricciardi collected thermal comfort standard by adaptive thermal comfort
data by experimental measurements with special microcli- has been claimed to be energy saving in comparison to that
matic acquisition systems and also distributed a series of by the traditional PMV–PPD-based thermal comfort [26].
specific questions to respondents. Comparison of PMV This led to the update of the ASHRAE Standard 55 by the
values obtained from both the cases showed that the Adaptive Comfort Standard American National Standard
information gathered from the questionnaire has a Institute (ANSI)/ASHRAE 55-2004 [17].
tendency to overestimate/estimate higher discomfort con- The adaptive principle of thermal comfort requires a
ditions [20]. Becker and Paciuk reported that the PMVs field-survey for collecting data on the thermal environ-
calculated by the Fanger’s PMV model were markedly ment as well as thermal responses of the subjects. A
lower than the actual thermal sensation votes [21]. statistically significant relationship between the indoor air
Because of the inaccuracy of the PMV model, the temperature and the indoor neutral temperature was
adaptive predicted mean vote (aPMV) model, based on found by Humpreys [19]. The outdoor climate significantly
different conditions, was created. According to van Hoof, influences the prevailing indoor air temperature. The
there are two ways for improvement: one is the correction adaptive model shows that the thermal comfort tempera-
or adjustment of the model itself, and the other is the ture is a function of the outdoor air temperature.
introduction of methods to increase the accuracy of input According to Brager and de Dear, the PMV and the
parameters of the model [18]. Humphreys and Nicol AMV established from the subjects’ responses are
complementary to each other [27], and the thermal and
clarified how the variables used in the calculation of PMV
non-thermal effects on occupants’ responses in real
cause the difference between the actual vote and the PMV
buildings can only be estimated by creating a compromise
[22].
between both types of modelling approaches [19,26]. The
Based on the different opinions for a warm climate
aPMV model is helpful for applying the PMV method in
leading to disagreement between the actual mean vote
various buildings with the consideration of the local
(AMV) and the PMV, Fanger and Toftum placed an
climate, culture and social backgrounds, as well as
extended PMV model with the incorporation of an
behavioural habits, styles and so on. The aPMV model
‘‘expectancy factor, e’’. This mainly explains that in a
is also useful for studying the dynamic thermal comfort set
warm climate, a discrepancy occurs between the AMV and
points, which are some of the key factors that affect
the PMV for naturally ventilated buildings due to over-
building energy consumption.
estimation of the PMV for thermal sensation of the
occupants. Conventional heat-balance theory applied to
laboratory research gives rise to the thermal index of
Methodology
PMV, which could become widely applied with the help of
this expectancy factor [23]. A museum preserves the displayed materials and also
Besides that, Yao et al. also proposed an aPMV model, provides thermal comfort to the visitors and the employees
which is expressed by Equation (1) where ‘‘’’ is termed as simultaneously. With a view to measuring and character-
the ‘‘adaptive coefficient’’ [19]. izing occupants’ thermal perceptions in the Muzium
PMV Negara, the National Museum located in Kuala Lumpur
aPMV ¼ : ð1Þ in Malaysia, a field study was conducted using a subjective
1 þ PMV
questionnaire survey and also thermal–environmental
This aPMV model explicitly describes how ISO 7730 parameter monitoring. The aim of the subjective meas-
overestimates or underestimates thermal sensation occur- urement was to determine the discrepancies between the
ring in the heat-balance model of PMV in warm and cool subjects’ AMV and Fanger’s equation based on PMV. The
conditions, respectively. It is a linear regression model statistical analysis led to the implementation of a practical
expressing the relationship between indoor design thermal comfort temperature.
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
Subjective Measurement costs is preferable, but the minimization must not be given
In the museum, 28 subjects were chosen in four prime importance.
different galleries during field measurement. The partici- The ISO 7730 awards the PMV of the occupants’
pants were 8 females (28.57%) and 20 males (71.43%). thermal sensation a higher value on the ASHRAE scale in
Their mean age was 23.71 years with an age range of 22–28 the warm conditions of the tropics, since the PMV model
years. A total of five males and two females were selected does not account for the psychological and behavioural
from each gallery. adaptations in the real world. This leads to an excessive
The thermal–environmental survey had covered several use of A/C, thus increasing energy consumption.
demographics such as name, gender, age and so on. The The AMV was determined from the subjects’ ques-
ASHRAE seven-points Thermal Sensation Scale tionnaire survey. Obviously, the neutral operative tem-
(TSENS), current clothing garment and metabolic activity perature calculated by the AMV is higher than that
checklist also had been included in the survey. Figure 1 calculated by the PMV. The PMV model is, thus, not
shows the questionnaire on the thermal environment and applicable in a museum in the tropical country of
occupants’ thermal comfort that was distributed to the Malaysia, because a slight increase in the neutral operative
subjects participating in the study. The TSENS was used temperature could allow significant energy saving. An
to simulate occupants’ thermal response to their environ- acceptable neutral temperature was determined. Different
ment; the scale for the rating was as follows: hot (3), warm energy-saving strategies suitable for a museum in the
(2), slightly warm (1), neutral (0), slightly cool (1), cool tropics were also discussed.
(2) and cold (3). Table 1 shows a descriptive summary
of the subject occupants participated in the questionnaire Indoor Environment
in the four galleries in the National Museum. Mean Table 3 shows statistical summaries of the indoor
metabolism and mean insulation in each gallery were 1.7 measurements for the Galleries A, B, C and D in the
met and 0.47 clo, respectively. National Museum of Malaysia. These include air tem-
perature, radiant temperature, operative temperature, RH,
Measurement of Indoor Environment air velocity, effective temperature (ET), standard effective
Ambient temperature, mean radiant temperature, RH temperature (SET), TSENS, PMV and PPD.
and air velocity were used as the thermal comfort The mean air temperatures of the four sampling zones
parameters to evaluate indoor air conditions of the were: 18.4, 17.7, 21.1 and 18.48C. The minimum and the
museum. These variables were measured by TSI maximum air temperature in 8C of the zones were: (17.7,
VELOCICALC Anemometer, KANOMAX-model 2211 19.2), (16.6, 18.7), (20.8, 21.4) and (17.8, 19.4), respect-
IAQ Monitor and Globe thermometer. Table 2 shows ively. Air temperature at certain points in Gallery A,
equipment used for the thermal comfort measurements Gallery B and Gallery D and the mean air temperature in
with their respective functions. Measurements of these Gallery B were below the lower limit of the temperature
parameters were carried out at different points in the range of 18–228C as recommended by Museums Australia
galleries at 1.1 m height from the floor. Victoria [16]. This simply indicates that in Malaysia, a
A globe thermometer was used to measure the mean country with a warm climate, the occupants would feel a
radiant temperature (MRT). It has a normal dry bulb cooler sensation, especially in Gallery B and at certain
thermometer inserted through a rubber stopper to the areas of Gallery A and Gallery D. This was further
centre of a matte-black copper sphere of 150 mm diameter, supported by the subjective questionnaire survey of
whose absorptivity approaches that of the skin. adaptive thermal comfort. Energy was used unnecessarily
to produce excessive A/C.
The mean MRT in the four galleries were 24.58C,
Results and Discussion 23.38C, 25.08C and 23.98C. The lowest MRT was 22.68C
at a point in Gallery B and the highest MRT was 25.48C at
Bioclimatic, environmentally friendly and energy-con- a point in Gallery C. The minimum and the maximum RH
scious design is crucial in most museums. The sustain- in the four zones were (60.9%, 63.3%), (62.3%, 68.9%),
ability factors of museums can be improved by a better (73.2%, 75.1%) and (65.8%, 71.8%); the mean RH were
exhibition of the display materials with maximum visual, 62.6%, 65.3%, 72.4% and 69.4%, respectively. The
acoustic and thermal comfort and a better IAQ. A lower humidity value of Gallery A was less than 65% RH. It
energy consumption with reduced respective operational was mentioned earlier that suitable thermo-hygrometric
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
Fig. 1. Questionnaire used to determine the thermal environment and occupants’ thermal comfort.
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
Table 1. A descriptive summary of the subject occupants participated in the questionnaire in four galleries in the National Museum
Gallery Gallery A Gallery B Gallery C Gallery D
Sample size 7 7 7 7
Gender
Male 5 5 5 5
Female 2 2 2 2
Mean age (year)
(Mean, standard deviation) (23.71, 2.71) (23.71, 2.71) (23.71, 2.71) (23.71, 2.71)
(Minimum, maximum) (22, 28) (22, 28) (22, 28) (22, 28)
Mean metabolism (met)
(Mean, standard deviation) (1.7, 0) (1.7, 0) (1.7, 0) (1.7, 0)
(Minimum, maximum) (1.7, 1.7) (1.7, 1.7) (1.7, 1.7) (1.7, 1.7)
Mean clothing insulation (clo)
(Mean, standard deviation) (0.47, 0.09) (0.47, 0.09) (0.47, 0.09) (0.47, 0.09)
(Minimum, maximum) (0.43, 0.68) (0.43, 0.68) (0.43, 0.68) (0.43, 0.68)
Table 2. Equipment used for thermal comfort measurements HVAC system and the seasons [15]. With a temperature
Type of instrument Measurement 4208C, RH 4 65% intensifies the development of mycete
parameter/function colonies and promotes the life cycle of harmful insects.
Energy savings of 40% can be obtained by changing the
TSI VELOCICALC (Anemometer) Dry bulb temperature (DBT)
Air velocity indoor RH range from 50 2% to 50 10% [3]. The
Flow rate limiting values of RH for summer conditions in a museum
IAQ Monitor Dry bulb temperature environment according to ANSI/ASHRAE Standard 55
(KANOMAX-model 2211) Wet bulb temperature
CO concentration (ppm) are 50% and 65% [17].
CO2 concentration (ppm) Only the RH of Gallery A is permissible with a great
Relative humidity reservation, while the other galleries have significantly too
Absolute humidity
Dew point temperature
high RH, thus potentially damaging the artefacts. It is
Globe thermometer Radiant heat temperature obvious that the A/C system of the museum is not
functioning properly in terms of humidity control. It is
recommended to keep a control of the indoor RH of the
National Museum of the tropical country, Malaysia, at
conditions for artefacts and occupants require the lowest 55 5% in order to achieve moderate preservation of the
acceptable temperature with the maximum admissible RH. display materials, comfort of the occupants and rational
Note that the ASHRAE Handbook 2007 suggests a use of energy.
temperature range of 15–258C and a RH of less than The mean air velocities of the four zones measured were
60% for a general museum [12]. This indicates that the air 0.14, 0.14, 0.15 and 0.15 ms1. These are within the
temperature measured was within the lowest acceptable acceptable range of 0.10–0.25 ms1 for a museum as
threshold limit recommended by ASHRAE [12]. However, recommended by ANSI/ASHRAE Standard 55 [17]. The
the RH exceeds the threshold limit recommended by the average air velocities suitable for the artwork conservation
just mentioned standard. Hence, in the examined cases, it and the occupants’ thermal comfort lie within the range of
is clear that the strategy of the lowest acceptable 0.1–0.15 ms1 [29]. Air velocity of less than 0.15 ms1 is
temperature with the maximum possible RH is used to considered as low-air-movement [30]. Huh et al. showed
design the HVAC system in the National Museum. that low air flow rates with RH below the upper comfort
Hong Kong has a warm and humid climate. Thus, limit allow for less energy consumption [31]. The mean air
buildings there require cooling throughout almost the velocities of the four zones are fairly acceptable.
whole year [28]. The indoor design temperature and RH in
a modern museum in Hong Kong are 24 18C and Thermal Sensation
55 5% [28]. According to Ascione [3] and Bellia [15], the Figure 2 indicates the distribution of frequency for
RH should be 50 5% RH for exhibition rooms. Ambient TSENS responses. Figure 3 is the comparative illustra-
RH must never fall below 40–65% irrespective of the tion of TSENS response frequency of the four galleries
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
Table 3. Statistical summaries of indoor measurements
Gallery Gallery A Gallery B Gallery C Gallery D
of the museum. Just a few occupants in the four comfortable, which is neutral. In all 32% of occupants
galleries felt cold, adding up to 4%. No one in the four felt slightly cool and 14% of occupants felt slightly
galleries reported feeling hot. The conditions described warm inside the galleries. Only a few occupants felt
as slightly cool, neutral and slightly warm are that the indoor condition was not comfortable, includ-
considered acceptable. In all 32% of occupants of the ing 4% of occupants felt cold, 7% of occupants felt
four galleries felt that the inside condition was cool and 11% of occupants felt warm.
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
60%
Gallery A operative temperature calculated from the MTSV by using
Gallery B Equations (2)–(5) was 22.58C. In contrast, the neutral
50%
operative temperature calculated from the PMV by using
Gallery C
Equations (6)–(9) was 22.28C. Hence, the PMV model by
40% Gallery D
Fanger is not appropriate for use in the tropics, because a
% of Observation
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
Fig. 4. Calculation of preferred temperature.
Fig. 5. Calculation of neutral temperature of Gallery A. Fig. 6. Calculation of neutral temperature of Gallery B.
their opinion and individual perception. The comfort if they feel uneasy with the thermo-hygrometric
ANSI/ASHRAE Standard 55-2004 on ‘‘Thermal condition. These behavioural adjustments are not con-
Environmental Conditions for Human Occupancy’’ is the sidered in the PMV model. Furthermore, in the field
basis of the work presented in this section. Besides this, a studies, determination of the occupants’ activity level and
well-designed HVAC system needs to control temperature, insulation due to clothing are not accurately possible.
humidity, air motion and radiant sources within specified Behavioural, physiological and psychological adjustments
limits with the consideration of non-environmental factors, are not considered in a realistic sense.
such as the occupants’ activity level and dress.
Energy-saving Strategies
Comparison Between Predicted Indices and Observed All A/C systems are the preferable solution in order
Data to achieve optimal microclimatic conditions, especially
Figures 5–8 show that there was a difference between ambient RH, for museums. Two types of A/C systems
the PMV value and the MTSV value for the four different exist for cooling and dehumidification. One is the
galleries in the museum. The reason is that the heat- traditional constant air volume (CAV) system with
balance of the occupants in the museum was being separate temperature and humidity controls by cooling–
adjusted by other parameters, such as clothing and activity reheating, and the other is a dedicated outdoor air system
level. People react in different ways to restore their (DOAS) integrated with a CAV system. Both types of
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
introduced simultaneously through the implementation of
surrounding plantation, which will keep the outdoor
environment cooler. Besides, a green roof garden could
be planted on the top of the museum, which in this way
would absorb less solar heat and thus reduce the cooling
load for the A/C, consuming less energy.
Environmental and energy targets in a museum include
the reduction of energy consumption and CO2 emissions
by applying advanced energy features. Renewable energy
may be integrated in museum buildings for the enhance-
ment of comfort and improvement of overall quality.
Fig. 7. Calculation of neutral temperature of Gallery C.
Conclusions
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012
The findings of this research with the consideration of support provided for Research Project Science Fund 16-02-03-
occupants’ thermal comfort are useful in designing a low 6004. Thanks are also extended to University of Malaya (MU),
who awarded an FRGS Grant FP049/2007C to the authors for
energy consumption HVAC system for museums in
research work to be conducted at the University of Malaya. In
tropical countries. addition, special thanks are extended to Mr. S.H. Chu, Mr. S.C.
Lee, Mr. K.S. Ng, Miss. M.M. Cheang, Mr. J.K. Teoh and Mr.
C.Y. Pong, former final-year students at the Department of
Acknowledgments Mechanical Engineering, University of Malaya, for their help
during critical portions of the project. Special thanks are also
extended to Dr. Anke Freeman, Scientific Editor at ULPA,
The authors would like to thank the Ministry of Science,
University of Malaya, for proof-reading the manuscript.
Technology and Innovation, Malaysia, for the full financial
References
1 Budaiwi I, Al-Homoud M, Abdou A: Heating, Refrigerating and Air-conditioning 25 ANSI/ASHRAE Standard 55-1992: Thermal
Implementation of a multi-phase approach Engineers, Inc, 2007. Environmental Conditions for Human
for investigating and remedying a thermal 13 Plenderleith HJ, Werner AEA: The Occupancy. Atlanta, American Society of
comfort problem in an office building: Indoor Conservation of Antiquities and Works of Heating, Refrigerating and air-conditioning
Built Environ 2009;18(1):52–65. Art. London, Oxford University Press, 1971. Engineers Inc., 1992.
2 Dahlan ND, Jones PJ, Alexander DK, Salleh 14 Thomson G: The Museum Environment, 1st 26 de Dear RJ, Brager GS: Thermal comfort in
E, Dixon D: Field measurement and subjects’ edn. London, Butterworths, 1978. naturally ventilated buildings: revisions to
votes assessment on thermal comfort in high- 15 Bellia L, Capozzoli A, Mazzei P, Minichiello ASHRAE standard 55: Energ Build
rise hostels in Malaysia: Indoor Built Environ F: A comparison of HVAC systems for 2002;34(6):549–561.
2008;17(4):334–345. artwork conservation. International Journal 27 Brager GS, de Dear RJ: Thermal adaptation in
3 Ascione F, Bellia L, Capozzoli A, Minichiello of Refrigeration 2007;30(8):1439–1451. the built environment: a literature review:
F: Energy saving strategies in air-conditioning 16 Scottish Museums Council Fact Sheet – Energ Build 1998;27(1):83–96.
for museums: Appl Therm Eng Adapted for Use in Australia: Monitoring the 28 Fong KF, Chow TT, Li C: Comfort zone of air
2009;29(4):676–686. museum environment. Australia, Museums speeds and temperatures for air-conditioned
4 Daghigh R, Adam NM, Sahari BB: Australia Victoria, 2003. environment in the subtropical Hong Kong:
Ventilation parameters and thermal comfort 17 ANSI/ASHRAE Standard 55-2004: Thermal Indoor Built Environ 2010;19(3):375–381.
of naturally and mechanically ventilated Environmental Conditions for Human 29 Ascione F, Minichiello F: Microclimatic con-
offices: Indoor Built Environ 2009;18(2):113– Occupancy. Atlanta, American Society of trol in the museum environment: air diffusion
122. Heating, Refrigerating and air-conditioning performance: Int J Refrig 2010;33(4):806–814.
5 Kwong QJ, Adam NM: Perception of thermal Engineers Inc., 2004. 30 McQuiston FC, Parker JD, Spitler JD:
comfort in the enclosed transitional space of 18 van Hoof J: Forty years of Fanger’s model of Heating, Ventilating, and Air Conditioning:
tropical buildings: Indoor Built Environ 2011; thermal comfort: comfort for all? Indoor Air Analysis and Design, 6th edn. USA, New
20(5):524–533 2008;18(3):182–201. York, John Wiley & Sons; 2005.
6 Al-Tamimi NAM, Fadzil SFS: Thermal per- 19 Yao R, Li B, Liu J: A theoretical adaptive 31 Huh JH, Michael JB: Optimization of air-
formance analysis for ventilated and unventi- model of thermal comfort – adaptive predicted conditioning system operating strategies for
lated glazed rooms in Malaysia (comparing mean vote (aPMV): Build Environ hot and humid climates: Energ Build
simulated and field data): Indoor Built 2009;44(10):2089–2096. 2008;40(7):1202–1213.
Environ 2011;20(5):534–542. 20 Buratti C, Ricciardi P: Adaptive analysis of 32 Maria LG, Giovanni L, Gianfranco R,
7 Papadopoulos AM, Avgelis A, Santamouris thermal comfort in university classrooms: Gianluca S: Conflicting needs of the thermal
M: Energy study of a medieval tower, restored Correlation between experimental data and indoor environment of museums: in search of a
as a museum: Energ Build 2003;35(9):951–961. mathematical models: Build Environ practical compromise: J Cult Herit
8 Lim JY. The Malay House: Rediscovering 2009;44(4):674–687. 2008;9(2):125–134.
Malaysia’s Indigenous Shelter System. Penang: 21 Becker R, Paciuk M: Thermal comfort in 33 Han J, Zhang G, Zhang Q, Zhang J, Liu J,
Institut Masyarakat, 1987. residential buildings – failure to predict by Tian L, Zheng C, Hao J, Lin J, Liu Y,
9 Wilson M, Viljoen A, Nicol JF: Environments standard model: Build Environ Moschandreas DJ: Field study on occupants’
in archeological museums in the Mediterranean 2009;44(5):948–960. thermal comfort and residential thermal envir-
region: in Sayigh AAA (ed): World Renewable 22 Humphreys MA, Nicol JF: The validity of onment in a hot-humid climate of China: Build
Energy Congress, 1-7 2000, Part 1, Brighton, ISO-PMV for predicting comfort votes in Environ 2007;42(12):4043–4050.
Pergamon, 2000, pp. 412–419. everyday thermal environments: Energ Build 34 Zhang LZ, Niu JL: Effectiveness correlations
10 Haiad JC, Druzik J, Ayres JM, Lau H: 2002;34(6):667–684. for heat and moisture transfer processes in an
Museum environmental requirements: a litera- 23 Fanger PO, Toftum J: Extension of the PMV enthalpy exchanger with membrane cores: J
ture survey: ASHRAE Transact 1990;96:112– model to non-air-conditioned buildings in warm Heat Transf 2002;124(5):922–929.
121. climates: Energ Build 2002;34(6):533–536. 35 Wang SW, Jin XQ: CO2-based occupancy
11 Chicora Foundation: Managing the Museum 24 ISO 7730: Moderate Thermal Environments – detection for on-line outdoor air flow control:
Environment. Columbia, Chicora Foundation, Determination of PMV and PPD Indices and Indoor Built Environ 1998;7:165–181.
Inc, 1994. Specification of the Condition for Thermal
12 ASHRAE: ASHRAE Handbook, HVAC Comfort. Geneva, International Organization
Applications. Atlanta, American Society of for Standardization, 1994.
Downloaded from ibe.sagepub.com at University of Texas at San Antonio on May 16, 2012