F. Tillenkamp
Axima Lab, Switzerland
N. Heijmans
Belgian Building Research Institute, Belgium
F. Nicol
London Metropolitan University, UK
E. Maldonado
Instituto de Engenharia Mecânica, Portugal
M. Almeida
University of Minho, Portugal
G. Guarracino
ENTPE/CNRS Vaulx-en-Velin, France
L. Roche
Building Research Establishment, UK
process of solution searching because it helps to tilation and the design of openings. The natural
avoid that a fuzzy defined problem becomes an ventilation potential is the possibility to ensure,
ill defined one. at a given urban site, an acceptable indoor air
Although designing by examples is widely quality by natural ventilation only, provided that
used in practice, the research dedicated to this the building is appropriately designed. A multic-
approach is very rare. The evaluation of the de- riteria methodology for assessing the natural
gree of suitability of existing examples to a new ventilation potential was developed during the
situation is done by experts based mainly on URBVENT project (Germano et al., 2002; Rou-
qualitative reasoning and intuition. let et al., 2002; Germano and Ghiaus, 2003;
URBVENT project developed two methods Germano et al., 2005).
to formalize decision taking based on examples.
2.1 Driving forces
One assesses the climatic suitability and the
other one makes a classification of the suitabil- Natural ventilation is driven by wind and buoy-
ity of a new site in comparison with known ancy. The wind is reduced in the urban envi-
sites. ronment, especially in the street canyons
Climatic suitability of natural ventilation is (Ghiaus and Allard, 2003). Its reduction may be
defined as a measure of the energy saved for estimated by using the algorithm presented in
cooling when ventilation is used. The climate section 0. The other driving force, the buoy-
should be taken into account in relation with the ancy, depends on the temperature difference
building thermal behavior and the anticipated between indoor and outdoor. The outdoor tem-
thermal comfort. The thermal behavior of the perature may be significantly higher in urban
building may be characterized by the free- environment than in the rural adjacent suburbs
running temperature. This is defined as the in- (see section 0).
door temperature of the building in thermal bal-
2.2 Constraints
ance with the outdoor environment when neither
heating nor cooling is used. Furthermore, it is Among the barriers to the application of natural
assumed that the free-running temperature is ventilation, the urban constraints are pollution
defined for the minimum ventilation rate needed and noise. The level of these constraints may be
for indoor air quality, which implies that the specified quantitatively or qualitatively. The
building is almost airtight. With these assump- second specification is easier to understand by
tions, it may be accepted that, for a given month the non-specialists and can be determined by
of the year, the indoor temperature of the mean measurements by subjective answers given to
value of the free-running building is a function questionnaires.
of the hour of the day and its dispersion is a
2.3 Multicriteria analysis
function of the building. Based on these as-
sumptions, the probabilistic distribution of de- The driving forces and the constraints are inte-
gree-hours in function of outdoor temperature grated in time obtaining wind-time, stack-time,
may be estimated. The comparison of these dis- pollution-time and noise-time indicators. Then,
tributions gives an indication of the climatic a multicritera analysis is performed by using
suitability of the natural ventilation (Ghiaus and Qualiflex method. The result is a classification
Allard, 2002; Ghiaus, 2003). of the suitability of natural ventilation in the
given site for the buildings considered in the
evaluation.
2. NATURAL VENTILATION POTENTIAL
The most influential decisions are taken in the
3. WIND VELOCITY IN STREET CANYONS
very first stages of urban and building design.
The architectural solutions planned during this Wind in street canyons was studied for all types
phase have a major influence on the application of wind flow outside the canyon (parallel, verti-
of natural ventilation. cal and oblique to the main axis) and a large
To support these decisions, during the range of velocity (0 to 13 m/s) of the undis-
URBVENT project it was developed a method- turbed wind speed. in configurations that are
ology for assessing the potential of natural ven- rarely treated in literature: oblique direction of
International Conference “Passive and Low Energy Cooling 31
for the Built Environment”, May 2005, Santorini, Greece
wind and low velocity of undisturbed wind. mated or identified experimentally (Nicol et al.,
When the wind speed outside the canyon is be- 2002; Nicol and Wilson, 2004; Wilson et al.,
tween 0.5 m/s and 4 m/s, although the flow in- 2005).
side the street canyon seemed to have chaotic
characteristics, extended analysis of the experi- 6. POLLUTION
mental data resulted in two empirical models, Outdoor air pollution is commonly considered
one for wind blowing along the canyon and an- as another barrier to natural ventilation since
other for the wind blowing perpendicular or filters cannot be used as in mechanical or air-
oblique to the canyon (Georgakis and Santa- conditioning systems.
mouris, 2004; Georgakis and Santamouris, In the joint framework of URBVENT project
2005). If the wind speed outside the canyon is and the French program PRIMEQUAL, an ex-
higher than 4 m/s, the wind inside the canyon perimental study of outdoor - indoor pollution
depends on the incidence angle and its velocity transfer was conducted in nine schools. The
is given by simple models already described in pollutants studied were ozone, nitrogen dioxide
the literature (Georgakis and Santamouris, and 15 sizes of particle matter. Three maps were
2003). calculated for every pollutant: the I/O ratio, the
precision of this estimation and the degree of
4. TEMPERATURE IN URBAN ENVIRON- confidence in the I/O ratio and precision. The
MENT ratio of indoor - outdoor concentration was de-
termined as a function of airflow through the
The temperature distribution in the urban can- facade and of the outdoor concentration. The
opy layer is greatly affected by the radiation indoor concentration was smaller inside than
balance. Solar radiation incident on urban sur- outside. Ozone presented the lowest I/O ratio
faces is absorbed and then transformed into sen- (0.1-0.4). The I/O ratio for nitrogen dioxide was
sible heat. Most of the solar radiation impinges between approximately zero and 0.95. The I/O
on roofs and on the vertical walls of buildings; ratio for particle matter depended on the particle
only a relatively small part reaches ground size. The most important variation, 0.25 to 0.70,
level. The heat island effect reveals in higher was measured for particles of small size (0.3-
temperatures in urban area as compared with the 0.4µm); particles of larger size (0.8 - 3µm) rep-
surrounding suburbs. But the temperature meas- resented lower, but comparable, variation of the
ured inside the canyon streets was with about I/O ratio, 0.3 to 0.7 (Iordache, 2003; Ghiaus et
5°C lower than that of the canopy layer, par- al., 2005).
tially compensating the effect of the urban heat
island (Georgakis and Santamouris, 2005). 7. OPTIMAL OPENINGS DESIGN
Natural ventilation of buildings is affected by
5. NOISE the urban environment, the building configura-
Noise is intense in street canyons but it is re- tion and the type of façade (Georgakis et al.,
duced with the height of the buildings. If the 2004). The airflow through an external opening
sound power is assumed proportional to the is strongly dependent upon the wind-induced
number of vehicles per hour, the sound level pressure difference across it. This wind-induced
may be expressed as an expression in which the pressure depends on the detailed knowledge of
coefficients may be obtained by regression of pressure coefficients on each building surface.
the experimental data. Furthermore, if it is ac- Reliable pressure coefficient values for complex
cepted that the traffic intensity is correlated to urban layouts and/or complex façades can only
the street width, noise reduction may be ex- be obtained through wind tunnel studies for
pressed as a function of the height above the each specific case, a technique that is still the
street. Although the parameters obtained by rule for such cases today. General studies are
regression are specific to the experiment con- thus only possible for cases that do not depend
ducted in Athens during the URBVENT project, on pressure coefficients: single sided ventilation
the methodology is applicable to other towns, and cross-ventilation of apartments with open-
provided that the specific parameters are esti- ings in a single façade plus a chimney linking
32 International Conference “Passive and Low Energy Cooling
for the Built Environment”, May 2005, Santorini, Greece