You are on page 1of 1

Quick Start – Simatic Manager Standard Diagnosis online

1 Hardware

PROFINET 1.4 Note: This example assumes


(BW2528) Quick-Setup
an S7 – 300 and a “BWU2238”
stainless steel Profinet Gateway.
Diagnosis The same applies for Profibus
and all Safety Gateways.
Slave Adr Tool

1.2 Pressing the “OK” key takes you to 1.5 For Gateways with integrated
the Gateway menu. Go to “Quick-Setup” safety monitor we recommend first
and run the “Store+Run” command. This referring to the “Quick Start –
1.1 Connect for example a EMERGENCY STOP”.
projects the slaves and brings them into
Bihl+Wiedemann AS-i light button
the data exchange. 1.3 Connect your PLC to the stainless steel
module (BW2528) having Address 1 to
Gateway and assign a unique name.
the Gateway.

2 Creating the device configuration

2.1 PLC configuration: To start with, a 2.2 Double-click on “PN-IO” → 2.3 Use “Options” → “Install GSD file” 2.4 You will find the Gateway installed
PLC projected in the hardware “Settings” → “New” to add a new to install the corresponding GSD file. under 3.3 in the hardware catalog
configuration is used. network. under “PROFINET IO” → “Additional
Field Devices” → “Gateway” → “AS-i”.
Use drag&drop to add it to the PN-IO
network.

2.5 To get the I/O data for the first AS-i 2.6 By double-clicking on “Asi-GW” in Slot 0 2.7 Click on “Save and compile” and close 2.8 Right click an insert with 'Insert New
network into cyclical data exchange, you can you can from the “General” tab set the the hardware configuration. Object' → 'Organisation Block' OB82, OB85
also drag&drop the module “K1: 16 Byte DEA name assigned in 1.3 and from the and OB86. Click on 'load'.
(0-31)” to Slot 1 of the Gateway. “Parameters” tab select the Diagnosis lists.
r
ro
T

en e
j m le
v
co INE

er

pr ab

e
pr cti

od
ig
PR r
F

a
e

i
S-
O

nf
w

-i

g
AS
A
po

2.9 PLC Diagnosis: For example to cause 2.10 The Gateway causes a configuration 2.11 Click on the “Offline < > Online” button. 2.12 Double-clicking on the corresponding
a configuration error, disconnect the slave error. The “config error” LED on the Simatic Manager switches to online mode. Gateway opens a window that displays the
having Address 1 from the AS-i bus. Gateway and the “SF” LED on the PLC The Gateway with the diagnosis message is module status.
change to red. indicated by a red .

2.16 Note:
1. Handling the diagnostics alarms for
the PLC requires that you use
organization module OB82
(diagnostics alarm) in the PLC
2. program.

2.13 Double-clicking on “IO-Device 2.14 Under point 1 you can see the user 2.15 Clicking on “Display” shows you an exact
Diagnosis” provides you with exact diagnostics and exactly which slave is causing description of the message for the channel
information about pending diagnostics the error. The channel-specific diagnostics are diagnostic.
messages. shown under 2. and thereby which error is
currently present on the Gateway.

4 Important Note! Bihl+Wiedemann GmbH


Floßwörthstr. 41
This document is intended only as an aid for users of safety equipment. It does not
preclude proper testing, which is your own responsibility. Please therefore observe the D - 68199 Mannheim
corresponding safety instructions in the User's Manual. Tel.: (+49) 621/33996-0
Fax: (+49) 621/3392239
eMail: mail@bihl-wiedemann.de

You might also like