The MIT1020/2 in use at an industrial complex Delta wye transformer being testing with a MIT520/2
substation
MIT510/2, MIT520/2 and MIT1020/2
5-kV and 10-kV Insulation Resistance Testers
n The MIT1020/2 incorporates the ability to apply test Short Circuit/Charge Current
voltage up to 10 kV, making it fully conformable to the 3 mA
requirements of IEEE 43:2000. Current Measurement
Range: ±0.01 nA to ±5 mA
n Industry best guard terminal performance to insure
Accuracy (23ºC): ±5% ±0.2 nA at all voltages
highest accuracy of measured values.
Capacitance Measurement
n For greater ease of use and downloading, an RS232 or Range: 10 nF to 50 µF (for voltages > 500 V)
USB interface is available (MIT520/2 and MIT1020/2 Accuracy (23ºC): ±5% ±5 nF
only).
Capacitor
n Alarm limit mode (MIT520/2 and MIT1020/2 only) Charge Time: 5 seconds per µF at 3 mA
allows for faster testing and less ambiguous result Discharge Time: 5 seconds per µF to discharge from:
interpretation. MIT510/2 and MIT520/2: 5000 V to 50 V
MIT1020/2: 10,000 to 50 V
SPECIFICATIONS Display
Analog/digital 3 digits
Test Voltage
MIT510/2: 250 V, 500 V, 1000 V, 2500 V, 5000 V Timer Range
MIT520/2: 50 V to 1 kV in 10 V steps, 1 kV to 5 kV in 25 V steps Count up to 99 minutes and 59 seconds from start of test
MIT1020/2: 50 V to 1 kV in 10 V steps, 1 kV to 10 kV in 25 V steps Memory Capacity (MIT520/2 and MIT1020/2)
Insulation Resistance Range 32 kB
Digital display: Industry-Standard Tests
MIT510/2 and MIT520/2: 10 kΩ to 15 TΩ MIT510/2: Auto IR
MIT1020/2: 10 kΩ to 35 TΩ MIT520/2: Auto IR, PI, DAR, SV, and DD
Analog display: MIT1020/2: Auto IR, PI, DAR, SV, and DD
MIT510/2, MIT520/2 and MIT1020/2: 100 kΩ to 1 TΩ
Interference Rejection
Accuracy (23º C) 2 mA rms at 200 V and above
±5% to 1 TΩ
±20% to 10 TΩ (MIT520/2) Guard Terminal
±20% to 20 TΩ (MIT1020/2) 2% error guarding 500 kΩ leakage with 100 mΩ load
0 Weight
0 1 2 3 4 5 6 7 8 9 10 15 lb. (6.75 kg)
M Ohms
Improved enclosure
It’s virtually indestructible, yet ergonomic
and lightweight. It features an oversized
rubber handle and removable lid for
effective use in tight places. A lid mounted
lead storage bag is also included.
Easier operation
Use a “Quick Start” guide conveniently located
in the lid, always there for easy reference.
MIT510/2, MIT520/2 and MIT1020/2
5-kV and 10-kV Insulation Resistance Testers
Rechargeable n n n
10.0 kV n
5.0 kV n n n
2.5 kV n n n
500 V n n n
250 V n n n
10 V steps 50 V to 1 kV,
n n
25 V steps 1 kV to max test voltage
Max reading 15 TΩ 15 TΩ 35 TΩ
Min reading 10 kΩ 10 kΩ 10 kΩ
Measurements Voltage n n n
Leakage current n n n
Auto IR n n n
Polarization index n n
Dielectric discharge n n
Timer control n n
Timer display n n n
RS232 output n n
Guard terminal performance 2% error guarding 500 kΩ leakage with a 100 MΩ load
11
2
10
3
4
4
5
9
6 7 8
Ordering Information