Professional Documents
Culture Documents
CABLE MARKING Manuf. standard identification, Name of cable manufacturer, Conductor number and size of cable, Rated Voltage, Cable grade (IEC 60332-3), Year
of fabrication, Cable Type, Cable Length every 1 meter.
OTHER
CABLE MARKING Manuf. standard identification, Name of cable manufacturer, Conductor number and size of cable, Rated Voltage, Cable grade (IEC 60332-3), Year
of fabrication, Cable Type, Cable Length every 1 meter.
OTHER
CABLE MARKING Manuf. standard identification, Name of cable manufacturer, Conductor number and size of cable, Rated Voltage, Cable grade (IEC 60332-3), Year
of fabrication, Cable Type, Cable Length every 1 meter.
OTHER
OTHER
AC- LV CABLE Lighting & Small Power (NON-ARMOUR, INDOOR CABLES ONLY)
PROJECT DATA
SERVICE CONDITIONS VENDOR'S NOTE
Min. / Max. Temperature : 24 / 38 °C (Ambient Condition) `
Design Temperature : 40 °C
Min / Max. Humidity : 80 / 100 % (Ambient Condition)
Operating Voltage : 400 VAC ± 5% ± 15%
ENVIRONMENT (Steady State) (Transient) (Note-5)
Frequency : 50 Hz ± 2% ± 5%
CONDITION
Earthing System : TN-S TT
IT
Clean Moist Corrosive,
Dusty Conditioned Room Salt Laden
DESIGN REQUIREMENT VENDOR'S RESPONSE
Manufacturer : TBA
Applicable Standard : IEC 60502, IEC 60038 , IEC 60332-3, IEC 60228
Material Design : Cu/XLPE/LSZH/LSZH, Flame Retardant
GENERAL
Voltage Grade : 600/1000 V
Temperature Design : 90 deg C (Continous)
250 deg C (Short Circuit)
Conductor : Class 5 high conductivity, plain copper, fully annealed, circular, non-compacted, copper wires free from silver,
splinters, scales, or other imperfections.
Number of core : 2C,3C,4C (Refer to Cable Schedule)
Insulation : XLPE
Insulation Colour : Black, Light Blue and Green/Yellow (2C+E)
: Black, Brown, Grey and Green/Yellow (3C+E)
: Black, Brown, Grey, Blue and Green/Yellow (4C+E)
CONSTRUCTION
Inner Sheath Material : Not applicable
Armour : No
Outer Sheath Material : LSZH
Outer sheath Colour : Black
Sheath Type : Flame Retardant Cat. A As per IEC 60332-3-22 02
: LSZH as per IEC 61034
Earthing Conductor : Yes, Required
- HYDROCARBON RESISTANCE COMPLYING TO IEC 60811
- NON PROPAGATING FIRE COMPLYING TO IEC 60332-1/2/3
SPECIAL
- LOW CORROSIVE GAS EMISSION COMPLYING TO IEC 60754-1 and 60754-2
CHARACTERISTIC
- LOW SMOKE EMISION (OPTICAL DENSITY) COMPLYING TO IEC 61034-1 and 61034-2
- MATERIAL DESIGN: FLAME RETARDANT CAT. A COMPLYING TO IEC 60332-3-22
- UV RESISTANT
- ANTI RAT
- ANTI TERMITE
- ALIPHATIC HYDROCARBON RESISTANT COMPLYING TO IEC 60811
Every 1 meter
CABLE MARKING Manuf. standard identification, Name of cable manufacturer, Conductor number and size of cable, Rated Voltage, Cable grade (IEC 60332-3), Year
of fabrication, Cable Type, Cable Length every 1 meter.
OTHER
CABLE MARKING Manuf. standard identification, Name of cable manufacturer, Conductor number and size of cable, Rated Voltage, Cable grade (IEC 60332-3), Year
of fabrication, Cable Type, Cable Length every 1 meter.
OTHER
REFERENCES
NOTES:
2. DC LV Power Cables are 1C for Battery Cables to Inverter and PV Modules to String Combiner Cables, 2C for String Combiner to Inverter Cables
3. Cu = Copper, XLPE = Cross-Linked Poly Ethylene, SWA = Steel Wire Armour, LSZH = Low Smoke Zero Halogen, GSWA = Galvanized Steel Wire Armour