PAGE: 1 (6)
SYSTEM: AUTROPRIME INTERACTIVE FIRE DETECTION SYSTEM
PRODUCT:
TOPIC: AUTROPRIME SOFTWARE VERSION 2.1.6
CONTENT
FAULT CORRECTIONS ................................................................................................................................................ 2
FAULT IN MONITORING OPERATIONAL STATUS OF DETECTORS .................................................................................................... 2
UNABLE TO REPORT AN ALARM DURING LOOP SCAN AFTER A SHORT CIRCUIT ................................................................................ 2
UPGRADE NOTES ...................................................................................................................................................... 3
UPGRADE AUTROPRIME RUNNING SW VERSION 2.1.0 AND LATER............................................................................................. 3
UPGRADE AUTROPRIME RUNNING SW VERSION 2.1.5 ............................................................................................................ 3
UPGRADE AUTROPRIME RUNNING ANY SW VERSION 1.0.4 - 2.0.3 TO VERSION 2.1.0 OR LATER .................................................... 3
LOGGING OF SYSTEM DATA................................................................................................................................................. 4
COPY CONFIGURATION AND LOG DATA.................................................................................................................................. 4
LIMITATIONS ............................................................................................................................................................ 4
NUMBER OF V-430/AP UNITS ON A LOOP ............................................................................................................................ 4
CHANGE OF INSTALLED V-430 PROTECTOR HEAD TO DIFFERENT TYPE ......................................................................................... 5
KNOWN PROBLEMS.................................................................................................................................................. 5
V-430 OPERATION CLASS “HEAT ONLY” ............................................................................................................................... 5
CONNECTING TO AUTROMASTER ........................................................................................................................................ 5
USB MEMORY STICKS ON AUTROPRIME SW 2.0.3 AND PREVIOUS VERSIONS .............................................................................. 5
AUTROPRIME SW UPGRADE ON SW 2.0.0 AND PREVIOUS VERSIONS......................................................................................... 6
POLLUTION AND SMV DATA .............................................................................................................................................. 6
SOUND PATTERNS ............................................................................................................................................................ 6
For further information on our systems and products, please visit www.autronicafire.com
Fault corrections
Fault in monitoring operational status of detectors
SW version 2.1.5 had a fault in monitoring the operational status of detectors.
Other types of loop units were not affected by this fault.
If a detector was removed from its base, and the detector was connected to a loop branch, the panel did not make a
fault message informing that the “Loop unit is not responding”.
The duration of the scan depends on the number of loop units and may for a maximum loop of 127 units last for up
to 95 seconds.
Upgrade Notes
If the system to be upgraded is running and SW version 1.0.4 – 2.0.3, please use an USB stick that is known to work well with
these SW versions. We also recommend to reformat the USB. Use FAT32, Standard allocation size.
Ref. “Bulletin 29-2015” regarding recommended USB sticks and formatting.
When upgrading to SW version 2.1.0 and later, we also recommend to do the following:
1. Before the upgrade is started, do action in the chapter “Logging of system data”.
2. After the upgrade is completed, do actions in the chapter “Copy configuration and log data”.
1. Copy the file Autroprime_2.1.6.0.agz to your USB (copy to USB root, not into a folder).
2. Connect the USB stick to the BSA-200 main board.
Shortly after, the USB with the new SW version is detected and the upgrade starts and completes automatically.
If the system is running SW 2.1.5 and the system has any of the new V-430/AP loop units installed the following procedure must
be executed:
1. Complete the step described in “Upgrade Autroprime running SW version 2.1.0 and later”
If the system has any of the new V-430/AP loop units installed, step 2 must also be executed.
If no V-430/AP loop units are installed, step 2 is not required.
2. When the system has completed the upgrade to SW version 2.1.6, go to the “System Setting” menu and run the
command “Restore Factory Settings”
Upgrade Autroprime running any SW version 1.0.4 - 2.0.3 to version 2.1.0 or later
1. Copy the following 2 files to your USB (copy to USB root, not into a folder):
Autroprime_2.1.6.0.agz
bsa200_boot.inf
2. Reboot the system by pressing the HW Reset Switch S1 in the lower left corner of the BSA-200 main board 1).
3. After the system has started showing the System Topology - connect the USB to the BSA-200 main board.
After some time (less than 30 seconds 2) ) the USB with new SW version is detected and the upgrade starts.
Shortly after, the operator panel display writes “PLEASE REMOVE USB STICK !”
5. The system now continues programming the new SW. The previous running configuration will be restored and the
system should start with the same operational state as before the upgrade was started.
• Note 1)
If the system does not reboot when S1 is pressed, power off the system and then power on the system.
• Note 2)
With SW versions 2.0.3 and earlier, the time spent for the system to detect the UBS increases with the storage capacity
of the USB. If the system does not detect your USB within 30 seconds, please read the notes in “Known Problems”.
Important
If you want to upgrade another system running any SW versions 1.0.4 – 2.0.3 to version 2.1.0 or later,
make a new copy of bsa200_boot.inf (ref. step 1.) to your USB-Stick before continuing with step 2.
With SW version 2.1.0 and later, the Autroprime supports logging to USB.
Create a folder named “AutroPrimeDebugLogs” on your USB root and connect the USB to the Autroprime. The logging is started
automatically.
If this folder is found on your USB when the system is upgraded and is restarting, or the system is already running on SW version
2.1.0 (or later), log data will be written to the USB. In case of problems these log data may be used to find potential problems.
There is no need for any action on the panel before connecting or disconnecting the USB.
When the system starts up with the new system SW, the Config.xml is automatically updated.
We always recommend to keep a copy of the updated configuration and log data.
Wait no less than 1 minute after the system has started, then enter the Service menu, “Export and Import” and run commands
“Export Configuration” and “Export Log”.
Limitations
Number of V-430/AP units on a loop
The number of V-430/AP unit is limited to max 127 for each detection loop.
If the protector head has additional functionality (Sounder and/or VAD) the number of units that can be installed will typically be
in the range 60-80 units on each detection loop, depending on the mix of the V-403*/AP types and the loop driver current
configuration. Refer to data sheet AutroGuard® V-100/AP base for Autroprime for details.
1. Disable the loop, replace the protector head and enable the loop.
This is the preferred way of doing physical changes on a detection loop.
2. Replace one single protector head only, without disabling the loop.
In both cases the system will have fault messages stating that the old unit(s) is not responding and that a new loop unit has been
found. Save the configuration (remove the old unit when suggested by the system) and restart the system.
Known Problems
V-430 operation class “Heat only”
If the V-430 protector (installed on base unit V-100/AP) is set to operation class “Heat Only”, the led “Reduced
Detection” (located on the lower left side of the operator panel) will be constantly turned on.
If the intention is to have the loop unit to operate as the older BDH-200/-300 unit it is recommended to install the
spare part variant, eg. BDH-300/SPARE.
Connecting to AutroMaster
When configuring users and clients for remote connection to an Autromaster it has been reported occasional
problems to establish the connection. In that case we recommend the following workaround:
The system may sometimes fail to detect or access a USB memory stick when it is connected, in particular if the USB
stick contains many files and folders. If such a problem occurs, the following actions should be taken:
3. Reformat the USB stick (FAT32, Standard allocation size) before re-connecting the USB to Autroprime.
Ref. “Bulletin 29-2015” regarding recommended USB sticks and formatting.
When the automatic upgrade has extracted all files from the USB stick the operator is asked to “PLEASE REMOVE
USB-STICK!“. Sometimes the system does not recognize that the USB stick has been removed, and the operator must
reboot the system by pressing the HW reset button S1 (located in the lower left corner of the BSA-200 main board),
or by powering the system OFF and then power the system ON.
Sound Patterns
If the system is restarted with an imported-configuration or a backup-configuration, all sound patterns in use should
be confirmed. This is because any changes in the sound pattern in the configuration (imported or backup) will NOT
update the loop sounders with the changed patterns.
Access all sound patterns in use and accept the values, or alternatively change the patterns. If patterns were
accepted (without any changes) it will not be necessary to save the panel configuration or to restart the system.
It is recommended to always do a test of sound patterns, especially evacuate, after starting the panel with an
imported- or backup-configuration.