You are on page 1of 2

Risk assessment report for a structure due to lightning flashes

based on IEC 62305-2:2010 standard.


PSM LAB-Online Risk assessment tool (http://psm.ucy.ac.cy)

General Properties
Structure dimension Length (m) 12
Width (m) 22
Height (m) 7
Protrusion Height (m)
Lightning protection measures Lightning protection system (LPS) NO LPS
Equipotential bonding (SPD) SPD LPL III-IV

Power Line
Installation information Buried line unshielded
Length (m) 45
Line type Low Voltage

Telecommunication Line
Installation information Buried line unshielded
Length (m) 45

Zone 1
Zone Characteristics Activity Office
Protection against shock Effective soil equipotentialization
Fire Provisions No provisions
Power Wiring Internal wiring Unshielded cable
Coordinated SPDs Class I SPD system
Protection against shock Warning notices
Telecommunication Wiring Internal wiring Unshielded cable
Coordinated SPDs No coordinated SPD system
Protection against shock Warning notices

Page 1/2
Risk assessment report for a structure due to lightning flashes
based on IEC 62305-2:2010 standard.
PSM LAB-Online Risk assessment tool (http://psm.ucy.ac.cy)

Risk assessment results


Type of loss Value Tolerable risk
R1-Risk of Loss of human Life: 1.0E-7 10^-5
R2p-Risk of Loss of Power service: 0.00093 10^-3
R2t-Risk of Loss of Telecom service: 9.0E-5 10^-3
R3-Risk of Loss of Cultural heritage: 0 10^-4
Cost of total economic Loss: 0,94€/year

Page 2/2

You might also like