System Version 5.0 SP1

Release Notes
IndustrialIT
800xA - System
800xA for Harmony
System Version 5.0 SP1

Release Notes
NOTICE
This document contains information about one or more ABB products and may include a
description of or a reference to one or more standards that may be generally relevant to
the ABB products. The presence of any such description of a standard or reference to a
standard is not a representation that all of the ABB products referenced in this document
support all of the features of the described or referenced standard. In order to determine
the specific features supported by a particular ABB product, the reader should consult the
product specifications for the particular ABB product.

The information in this document is subject to change without notice and should not be
construed as a commitment by ABB. ABB assumes no responsibility for any errors that
may appear in this document.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB be
liable for incidental or consequential damages arising from use of any software or hard-
ware described in this document.

This document and parts thereof must not be reproduced or copied without written per-
mission from ABB, and the contents thereof must not be imparted to a third party nor used
for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.

This product meets the requirements specified in EMC Directive 89/336/EEC and in Low
Voltage Directive 72/23/EEC.

TRADEMARKS
All rights to copyrights, registered trademarks, and trademarks reside with their respec-
tive owners.

Copyright © 2003-2007 by ABB.


All rights reserved.

Release: July 2007


Document number: 3BUA000112R5011
Table of Contents

Section 1 - Release Notes


Introduction .......................................................................................................................7
Functionality Changes .......................................................................................................7
Composer...........................................................................................................................8
Product Support .................................................................................................................8
Fixed Problems ..................................................................................................................9
Installation..............................................................................................................9
Operational ...........................................................................................................10
Known Problems .............................................................................................................11
Installation............................................................................................................11
Administration......................................................................................................14
Configuration .......................................................................................................14
Operational ...........................................................................................................16

Section 2 - Upgrade and Update


Introduction .....................................................................................................................19
SV3.1 SP2 to SV5.0 SP1 Upgrade ..................................................................................19
SV4.1 to SV5.0 SP1 Upgrade..........................................................................................20
Node Order...........................................................................................................20
Procedure .............................................................................................................20
SV5.0 to SV5.0 SP1 Update............................................................................................22
Node Order...........................................................................................................22
Procedure .............................................................................................................23
Domain Path Modification ..............................................................................................24

3BUA000112R5011 5
Table of Contents

6 3BUA000112R5011
Section 1 Release Notes

Introduction
This document represents the release notes for the Industrial IT™, 800xA - System,
800xA for Harmony, System Version 5.0 SP1 software.
This document provides a brief overview on functionality. It lists the problems that
existed in the previous version or service pack that were fixed and corrected in this
release. It also enumerates known problems encountered in the final testing of this
product release and identifies workarounds that help overcome the problem. The
document contains additional notes that may be valuable to customers and service
personnel working with the product. It replaces the existing release notes for the
prior release and is included on the product CD.
Fixed and Known Problems are divided into functional categories:
• Installation.
• Administration.
• Configuration.
• Operational.
• Instruction Manual Changes.
• Miscellaneous.

Functionality Changes
• Enhanced Operator Action Event Format. Tuning operations performed
using the Block Details utility may now be logged to the historical event log
using an enhanced format. The enhanced format provides additional
information on the item that was changed, how it was changed, and the user
that made the change. The use of the enhanced format is optional and may be
configured via a setting on the Configuration aspect of the Harmony Server

3BUA000112R5011 7
Composer Section 1 Release Notes

object. Refer to the Industrial IT, 800xA - System, 800xA for Harmony,
Configuration (3BUA000157Rxxxx) instruction for more information.
• Increased Number of Connectivity and Harmony Configuration Servers.
The number of Connectivity and Harmony Configuration Servers has increased
to support up to eight nonredundant or eight redundant. These Servers are
supported by either a single Harmony Configuration Server or up to four
Harmony Configuration Servers.
• Harmony Executive Service. This is an 800xA service that controls
underlying 800xA for Harmony services. Once configured, it requires no user
interaction. Refer to the Industrial IT, 800xA - System, Post Installation
(3BUA000156Rxxxx) for details on configuration.

Composer
Composer engineering workstation supports configuring and editing the project tag
database and associated lists for 800xA for Harmony (tag database, engineering
units, alarm comments, and logic state descriptors). These Composer based files are
directly usable in 800xA for Harmony for the 800xA System. The following can be
configured in the Composer project: area, unit, and equipment structures (these will
be maintained in the Functional Structure of 800xA System). Other Composer
console data such as Historian servers, group and trend displays are not usable in
800xA for Harmony for the 800xA System.
It is recommended that Composer be installed on a separate workstation.

Product Support
Contact ABB technical support for assistance in problem reporting.

8 3BUA000112R5011
Section 1 Release Notes Fixed Problems

Fixed Problems
Installation
Table 1 lists the critical or major installation issues that have been corrected since
the previous version or service pack. A brief description of the correction has also
been given.

Table 1. Corrected Installation Issues

Issue Correction or Fix


Uninstallation of Harmony failed to complete on Updates to the License Client Provider service
an Aspect Server. are included in this release. The previously
documented workaround is no longer required.
800xAHAR-IN-5000-001
The following licensing error was displayed by a 800xA for Harmony will no longer generate the
Harmony Connectivity Server node after invalid license message when the system is
installation and prior to adding the node to the being installed.
800xA system:
Invalid License Granted: The Client
is not in the same System as the
active SFA.

800xAHAR-IN-4100-025
During installation or reinstallation of a Harmony Microsoft hot fix KB913441 had to be manually
Connectivity Server or a Harmony Configuration installed by the user on Harmony Connectivity
Server, it was possible to have a warning dialog Servers and Harmony Configuration Servers
appear with the following message: before the 800xA for Harmony installation.
IIsWebServiceObj.AddExtension The hot fix file has been included in Windows
File returned error: 0x80070034. Server 2003 SP2 and is no longer required to be
manually installed by the user.
800xA-HAR-IN-5000-008

3BUA000112R5011 9
Operational Section 1 Release Notes

Table 1. Corrected Installation Issues (Continued)

Issue Correction or Fix


When upgrading a System Version 3.1 service This has been corrected for upgrades from
pack 2 or System Version 4.1 system to System System Version 4.1 and System Version 5.0.
Version 5.0, some manual configuration steps Users performing upgrades from System Version
were required after the upgrade was complete. 3.1 should contact ABB technical support for
more information.
800xAHAR-IN-5000-017

Operational
Table 2 lists the major system or product operational issues that have been corrected
since the previous version or service pack. A brief description of the correction has
also been given.

Table 2. Corrected Operational Issues

Issue Correction or Fix


The Operating Parameters and Block The aspects had to be relaunched to restore the
Details aspects stopped updating live data if live data connection with the Harmony Connectivity
the system time had been changed by more Server. This has been corrected.
than 5 minutes.

800xAHAR-OL-4100-009
The Advanced Harmony Control System This has been corrected.
Monitoring asset monitors inhibit logic did
not handle Harmony Asset Monitors for
offline nodes.

800xAHAR-OL-5010-001
Tag Importer Exporter screen would appear The Tag Importer Exporter now performs the
to freeze when a large number of individual requested operation while remaining in an
tags were selected from a larger tag list. operational state.

800xAHAR-OL-5000-010

10 3BUA000112R5011
Section 1 Release Notes Known Problems

Table 2. Corrected Operational Issues (Continued)

Issue Correction or Fix


When importing Harmony tags with the Tag Tags had to be limited to less than 6,000 when
Importer Exporter, a Stack Overflow error selecting from a larger list for import. Now, there is
may have occurred if more than 6,000 no problem importing more than 6,000 tags or
individual tags were selected from a larger more.
tag list.

800xAHAR-OL-5000-006
Some nodes in the Loop Topology display For the most complete results, the Loop Topology
appeared as Unknown in the 800xA for had to be run from a Harmony Module Status tag
Harmony display, but were displayed as assigned to an ICI. This has been corrected.
PCU or CIU in the Conductor VMS loop
topology display.

800xAHAR-OL-5000-012

Known Problems
Installation
Table 3 lists issues that may exist and affect the installation and upgrade of the
system or product at time of release. Workarounds, clarifications, or helpful hints
have been provided for each issue wherever possible.

Table 3. Installation Issues

Issue Workarounds, Clarifications, and Helpful Hints


If 800xA for Harmony software is reloaded Uninstall and then reinstall the 800xA for Harmony
on a Harmony Configuration Server node, software on all 800xA for Harmony Connectivity
the 800xA for Harmony Restore Server nodes that are assigned to the 800xA for
Configuration operation will not succeed. Harmony Configuration Server prior to performing
the Harmony Restore Configuration operation.
800xAHAR-IN-5010-002

3BUA000112R5011 11
Installation Section 1 Release Notes

Table 3. Installation Issues (Continued)

Issue Workarounds, Clarifications, and Helpful Hints


Database replication for Harmony It may be necessary to restart the Harmony
Configuration and Harmony Connectivity Connectivity Servers that do not have the Harmony
Server nodes may not automatically start ConfigServer if they are offline and do not come
after installation or upon a restore of the online.
Harmony Configuration Server database. An additional reboot(s) of the Harmony Connectivity
Servers may be required before database replication
800xAHAR-IN-5000-002 is successful.

It is not possible to upgrade all 800xA for Refer to Section 2, Upgrade and Update for detailed
Harmony node types using System Installer. information.

800xAHAR-IN-5000-015
When upgrading from System Version 4.1, it Utilizing the System Version 5.0 SP1 800xA
is possible to observe that inherited and Consistency Checker Tool on the Harmony OPC
copied aspects are inconsistently upgraded. Network objects will correct either issue. This tool
can be launched from a Workplace within the
800xAHAR-IN-5000-016 system.
NOTE: The Consistency Checker Tool can take a
long period of time to run depending on the quantity
of data contained within the aspect system. It is
recommended that the tool be run on a subset of
data (a node (PCU) within the control structure) to
evaluate the time needed prior to selecting the entire
OPC Network.
EbDataSyncService and EbServerBroker Before starting the update of a 800xA for Harmony
processes do not stop during Auto-uninstall. Server (SV5.0 to SV5.0 SP1), stop the 800xA for
Harmony services.
800xAHAR-IN-5010-003 Select Start > Control Panel > Administrative
Tools > Services and disable the following Harmony
services:
– ABBDiagnosticService.
– EbDataSyncService.
– EbServerBroker.
– SoapSymTagAtomSrv.
– Time synchronization daemon.
Restart the node and then start the 800xA update.

12 3BUA000112R5011
Section 1 Release Notes Installation

Table 3. Installation Issues (Continued)

Issue Workarounds, Clarifications, and Helpful Hints


An error message is generated for an There is a limitation of 31 characters in total length
Automated Installation on a Single Node when entering the domain name and user name in a
System where the domain/user name or Domain or the machine name and user name in a
machine/user name is more than 31 Workgroup.
characters in length. Also, if a Single Node System with Asset
Optimization is planned using System Installer, the
800xAHAR-IN-5010-004 automatic default names that are created will be 34
characters. In this case, you must manually edit the
name using the System Planner to be less than 31
characters in total length.
(ABB20070223-0097) Creating Server If an 800xA System with 800xA for Harmony installed
has more than one 800xA for Harmony Configuration
objects via Objectlist results in an incorrect
server path. Server, the domain paths for these Servers and
Event Concentrators will not be correct. The Reset
800xAHAR-IN-5010-005 button available within the Server tab of the Tag
Config Aspect of these Servers will not correct the
paths. The Server paths must be manually corrected
within each Servers Tag Configuration.
Refer to Domain Path Modification on page 24 for
more information on how to modify the domain paths.

3BUA000112R5011 13
Administration Section 1 Release Notes

Administration
Table 4 lists the issues that may exist and affect administration at time of release
including user, node, and service structure related problems. Workarounds,
clarifications, or helpful hints have been provided for each issue wherever possible.

Table 4. Administration Issues

Workarounds, Clarifications, and Helpful


Issue
Hints
An Internet Explorer error will be generated 1. Launch Internet Explorer and select Tools >
when attempting to launch the Server Internet Options.
Diagnostics application from the Windows 2. Select the Security tab.
Based Server Explorer utility.
3. Ensure that Local Intranet is selected then
click the Custom Level button.
800xAHAR-AD-5000-005
4. Select Enable for Initialize And Script ActiveX
Controls Not Marked As Safe.
5. Repeat this for every user account.

Configuration
Table 5 lists the issues that may exist and affect configuration of the system or
product at time of release. Workarounds, clarifications, or helpful hints have been
provided for each issue wherever possible.

Table 5. Configuration Issues

Issue Workarounds, Clarifications, and Helpful Hints


The TagConfig Aspect can be launched Do not launch more than one TagConfig Aspect per
multiple times for the same tag within the tag within the same Workplace.
same Workplace. In this case, only the last
edit changes submitted will be saved.

800xAHAR-CN-4100-018

14 3BUA000112R5011
Section 1 Release Notes Configuration

Table 5. Configuration Issues (Continued)

Issue Workarounds, Clarifications, and Helpful Hints


When synchronization has been started in The Harmony Synchronizer aspect can either be
the Harmony Synchronizer aspect, the pinned or launched and pinned in a separate window
progress indicator will not update if you to prevent being overwritten by another Aspect view.
move to view another aspect and come
back to the Synchronizer aspect. The
synchronization operation will run to
completion, but no progress will be
indicated.

800xAHAR-CN-4100-019
There is an extra diagnostic message box While the Copy/Paste operation is disabled, an extra
displayed by the Harmony Synchronizer diagnostics message is displayed. Click on the OK
when attempts to Copy/Paste within the button to dismiss the message box.
Control Structure are made.

800xAHAR-CN-4100-020
Harmony tag objects that were added with a
Harmony tag objects should only be added to the
Cut/Paste operation did not successfullyFunctional Structure with the Insert Object operation.
connect to the Harmony Control system for
Or, select the Functional Structure Objects option of
data. the Harmony Synchronizer aspect when
synchronizing the Configuration database with the
800xAHAR-CN-4100-021 Aspect Directory.
When performing a Harmony Restore on a Restarting the Harmony Connectivity Server nodes
running system, it is possible to end up with will ensure that the correct server objects are to be
duplicate server objects in the Harmony used.
Configuration Server.

800xAHAR-CN-5000-007
Operating Parameters does not display Harmony control systems installed with Plant Loop
information for Module Status tags when are not able to utilize the Harmony diagnostic
running in Plant Loop mode. The pages displays to their full capacity.
have static information, but no fields are
updated with tag information such as
address, module type, etc.

800xAHAR-CN-5000-009

3BUA000112R5011 15
Operational Section 1 Release Notes

Operational
Table 6 lists the issues that may exist and affect operations of the system or product
at time of release. Workarounds, clarifications, or helpful hints have been provided
for each issue wherever possible.

Table 6. Operational Issues

Issue Workarounds, Clarifications, and Helpful Hints


The Harmony Block Details, Module Restarting the Operator Workplace will clear the
Details, Operating Parameters, and the internally cached name.
Infinet Diagnostics aspects do not show
data for a Harmony tag object whose name
has been changed.

800xAHAR-OL-4100-011
800xA for Harmony tracking events show The corresponding 800xA audit trail message shows
the wrong actor identity (user) for faceplate the actor identity (user) correct.
operations.

800xAHAR-OL-5000-004
If a mirror node switch occurs while Block or Refresh the window.
Module Details windows are open, they stop
updating dynamically.

800xAHAR-OL-5000-003
Tag Summary may not work when launched From the Start menu select:
from the Start menu. 1. ABB Industrial IT 800xA > 800xA for OCS
Systems > Harmony > Diagnostics > Server
800xAHAR-OL-5000-013 Explorer.
2. Select the desired Harmony Server and right-click
the name.
3. Select Tag Summary.

16 3BUA000112R5011
Section 1 Release Notes Operational

Table 6. Operational Issues (Continued)

Issue Workarounds, Clarifications, and Helpful Hints


Alarms are not removed from the Alarm List Restart the Alarm Manager and Harmony Event
when an object is deleted. This can lead to Collectors by performing the following:
misleading information if a new object is 1. From the Service Structure select: Alarm
added with the same name in Harmony. Manager, Service > Basic, Service Group.
2. In the Aspects window, deselect the Enabled
800xAHAR-OL-5000-011
check box and click Apply.
3. Select the Enabled check box and click Apply.
4. On each pair of Harmony Connectivity Servers
listed under the Service Structure, select Event
Collector Service.
5. In the Aspects window, deselect the Enabled
check box and click Apply.
6. Select the Enabled check box and click Apply.
800xA for Harmony system alarms will be The existing message class for Harmony hardware
processed as process alarms within System alarms (ie. ICI communications) will appear in the
800xA. process alarm event lists. Users will not see these
alarms in other system only configured event lists.
800xAHAR-OL-5010-006

3BUA000112R5011 17
Operational Section 1 Release Notes

18 3BUA000112R5011
Section 2 Upgrade and Update

Introduction
Special considerations must be applied when upgrading 800xA for Harmony from
SV3.1 SP2 to SV5.0 SP1, SV4.1 to SV5.0 SP1, and when updating 800xA for
Harmony from SV5.0 to SV5.0 SP1.
The term upgrade refers to moving from one 800xA release to a later 800xA
release, whether it be a major or minor release.
The term update refers to adding service packs, patches, hot fixes, or rollups to an
existing 800xA System.

SV3.1 SP2 to SV5.0 SP1 Upgrade


This sections details the procedures for upgrading an existing SV3.1 SP2 system to
SV5.0 SP1.
System Installer does not support upgrading an 800xA SV 3.1 SP2 System where
800xA for Harmony is installed on any node.

Upgrading from SV3.1 SP2 to SV5.0 SP1 is a two step process as follows:
1. Upgrade 800xA for Harmony from SV 3.1 SP2 to SV 5.0 by performing the
procedures as described in Industrial IT, 800xA - System, Upgrade SV5.0
(3BSE036342R5001).
Refer to the Industrial IT, 800xA - System, 800xA for Harmony, Release Notes,
SV5.0 (3BUA000112R5001) for additional upgrade information.
2. Update 800xA for Harmony SV5.0 to SV5.0 SP1 by performing the procedures
described in SV5.0 to SV5.0 SP1 Update of this instruction.

3BUA000112R5011 19
SV4.1 to SV5.0 SP1 Upgrade Section 2 Upgrade and Update

SV4.1 to SV5.0 SP1 Upgrade


This sections details the procedures for upgrading an existing SV4.1 system to
SV5.0 SP1.

Node Order
This node order is different than what is described in the Industrial IT, System -
800xA, Upgrade (3BSE036342Rxxxx) and Industrial IT, System - 800xA,
Automated Installation (3BSE034679Rxxxx) instructions.
The update is a node-by-node procedure that must been performed in the following
node order:
• Clients.
• Aspect Servers.
Perform on the redundant Aspect Server nodes first and then the primary Aspect
Server nodes.
• Configuration Servers.
• Combined Configuration and Connectivity Servers.
• Connectivity Servers.
• Application Servers.

Procedure
Perform the procedure as follows:
1. Create a backup so that the system can be restored to its original state if
necessary. Refer to Backups in the Industrial IT, System - 800xA, Upgrade
(3BSE036342Rxxxx) instruction for more information.
2. Some 800xA System software requires preparatory steps before shutting down
800xA System processes. Perform the applicable procedures in Preparing the
Node in the Industrial IT, System - 800xA, Upgrade (3BSE036342Rxxxx)
instruction.

20 3BUA000112R5011
Section 2 Upgrade and Update Procedure

3. During installation of the 800xA System software, uncheck the ABB 800xA
for Harmony Connectivity Server and the ABB 800xA for Harmony
Configuration Server checkboxes (Figure 1).

Figure 1. Installation Wizard Checkboxes

4. Complete the installation following the procedures outlined in the Industrial IT,
System - 800xA, Automated Installation (3BSE034679Rxxxx) instruction.
5. Reboot.
For 800xA for Harmony Client type nodes, continue to Step 8.

6. Windows services related to the 800xA System must be stopped on each server
to be updated. Perform the procedures in Stopping 800xA System Processes in
the Industrial IT, System - 800xA, Upgrade (3BSE036342Rxxxx) instruction.

3BUA000112R5011 21
SV5.0 to SV5.0 SP1 Update Section 2 Upgrade and Update

7. Execute the 800xA for Harmony setup.exe program from located on DVD 1 in
the following folder:
DVD 1\800xA Connectivities\800xA for Harmony
Complete the 800xA for Harmony installation by referring to the procedures
described in the Industrial IT, System - 800xA, Installation (3BSE034678Rxxxx)
instruction.
8. Load the system extension by performing the procedures outlined in System
Extension Maintenance in the Industrial IT, System - 800xA, Upgrade
(3BSE036342Rxxxx) instruction.
9. Perform any post installation steps that are required. Refer to the Industrial IT,
System - 800xA, Post Installation (3BUA000156Rxxxx) instruction.

SV5.0 to SV5.0 SP1 Update


This sections details the procedures for updating an existing SV5.0 system to SV5.0
SP1. It is not possible to perform an online update of the 800xA for Harmony nodes.

Node Order
The update is a node-by-node procedure that must been performed in the following
node order:
• Clients.
• Aspect Servers.
Perform on the redundant Aspect Server nodes first and then the primary Aspect
Server nodes.
• Configuration Servers.
• Combined Configuration and Connectivity Servers.
• Connectivity Servers.
• Application Servers.

Procedure
Perform the procedure as follows for an automated update. This procedure includes
a combination of manual steps and automated procedures. Please follow these

22 3BUA000112R5011
Section 2 Upgrade and Update Procedure

procedures as presented. If a manual update is required, please contact ABB


Technical support.
1. Create a system 800xA Backup so that the system can be restored to its original
state if necessary. Refer to Backups in the Industrial IT, System - 800xA,
Upgrade (3BSE036342Rxxxx) instruction for more information.
2. Run the system Update Wizard as documented in Section 5 in the Industrial IT,
System - 800xA, Automated installation (3BSE034679Rxxxx) instruction.
3. Some 800xA System software requires preparatory steps before shutting down
800xA System processes. Perform the applicable procedures in Preparing the
Node in the Industrial IT, System - 800xA, Upgrade (3BSE036342Rxxxx)
instruction. Peeforming a Harmony Configuration Server database backup is
required to update the system.
4. Perform Steps 3 through 9 in the Updating the Node in the Industrial IT, System
- 800xA, Upgrade (3BSE036342Rxxxx) instruction.
5. Insert the 800xA System Installation DVD 1 into the drive and launch the
Installation AUTORUN.exe program to install SV5.0 SP1.
The Installation AUTORUN program may start automatically causing no need to
launch the AUTORUN.exe program.
6. During installation of the 800xA System software on Configuration and
Connectivity servers, uncheck all ABB 800xA for Harmony checkboxes
(Figure 1).
7. Complete the installation following the procedures outlined in the Industrial IT,
System - 800xA, Automated Installation (3BSE034679Rxxxx) instruction.
8. Reboot.
For 800xA for Harmony Client type nodes, continue to Step 14.

9. Windows services related to the 800xA System must be stopped on each server
to be updated. Perform the procedure in Stopping 800xA Processes in the
Industrial IT, System - 800xA, Upgrade (3BSE036342Rxxxx) instruction.
10. Install 800xA for Harmony using the AUTORUN program.

3BUA000112R5011 23
Domain Path Modification Section 2 Upgrade and Update

11. The following option must be selected: Manual Installation>New


Installation>Connectivities>800xA for Harmony>Harmony Connect.
Do not use the Automated Installation option or the Manual Installation>Update
from SV 5.0. Selecting the wrong option will require uninstall/reinstall of all
Harmony Configuration and Connectivity servers.
12. Complete the 800xA for Harmony installation by referring to the procedures in
the Industrial IT, System - 800xA, Automated installation (3BSE034679Rxxxx)
instruction
13. Reboot.
14. If the node is the Primary Aspect Server, load the system by performing the
procedure outlined in System Extension Maintenance in the Industrial IT,
System - 800xA, Upgrade (3BSE036342Rxxxx) instruction.
15. Repeat Steps 4 through 14 for each node in the system.
16. Once all nodes have been updated, perform all post installation steps. Refer to
the Industrial IT, System - 800xA, Post Installation (3BUA000156Rxxxx)
instruction. The Harmony Configuration Database Backup taken in Step 3 will
need to be restored after all nodes have been updated.

Domain Path Modification


The incorrect domain paths will be formed using the System Definition Object, the
Node Object Name, and the Server Object Name. The following shows a Primary
Harmony Server tags path:
Harmony-Add-On/<ConnectivityServer>/<ConnectivityServer>-
Harmony-Server
Substitute <ConnectivityServer> with the installed 800xA for Harmony
Primary Connectivity Server node name in the example above. The correct domain
path for a Harmony Server has the general form (CFGSRV-<ConfigServer>/GRP-
<PrimaryConnectivityServer>/<ConnectivityServer>/Harmony-Server).
Substitute <ConfigServer> with the 800xA for Harmony ConfigServer node
name that needs to be associated with the particular Harmony Server(s),
<PrimaryConnectivityServer> with the installed 800xA for Harmony

24 3BUA000112R5011
Section 2 Upgrade and Update Domain Path Modification

Primary Connectivity Server node name, and <Connectivity Server> with the
800xA for Harmony Connectivity Server node name in the above example.
The <PrimaryConnectivityServer> and <ConnectivityServer> will be
the same in the case of a 800xA for Harmony Primary Connectivity Server and
they will differ in the case of a secondary server.
The following example shows the Server tags for a system with two 800xA for
Harmony ConfigServers, both with redundant 800xA for Harmony Servers:
The first 800xA for Harmony ConfigServer is named Cfg1. Cfg1 has two 800xA for
Harmony Connectivity Servers associated with it. The primary server is named
Conn1 and the secondary server is named Conn2.
The second 800xA for Harmony ConfigServer is named Cfg2. Cfg2 has two 800xA
for Harmony Connectivity Servers associated with it. The primary server is named
Conn3 and the secondary server is named Conn4.
The proper paths for the example are as follows:
CFGSRV-Cfg1/GRP-Conn1/Conn1/Harmony-Server
CFGSRV-Cfg1/GRP-Conn1/Conn1/ClientEvent-Concentrator
CFGSRV-Cfg1/GRP-Conn1/Conn1/LocalEvent-Concentrator
CFGSRV-Cfg1/GRP-Conn1/Conn2/Harmony-Server
CFGSRV-Cfg1/GRP-Conn1/Conn2/ClientEvent-Concentrator
CFGSRV-Cfg1/GRP-Conn1/Conn2/LocalEvent-Concentrator
CFGSRV-Cfg2/GRP-Conn3/Conn3/Harmony-Server
CFGSRV-Cfg2/GRP-Conn3/Conn3/ClientEvent-Concentrator
CFGSRV-Cfg2/GRP-Conn3/Conn3/LocalEvent-Concentrator
CFGSRV-Cfg2/GRP-Conn3/Conn4/Harmony-Server
CFGSRV-Cfg2/GRP-Conn3/Conn4/ClientEvent-Concentrator
CFGSRV-Cfg2/GRP-Conn3/Conn4/LocalEvent-Concentrator

3BUA000112R5011 25
Domain Path Modification Section 2 Upgrade and Update

26 3BUA000112R5011
3BUA000112R5011. Printed in Sweden July 2007
Copyright © 2003-2007 by ABB. All Rights Reserved
® Registered Trademark of ABB.
™ Trademark of ABB.

http://www.abb.com

Automation Technology Products Automation Technology Products Automation Technology Products


Wickliffe, Ohio, USA Västerås, Sweden Mannheim, Germany
www.abb.com/controlsystems www.abb.com/controlsystems www.abb.de/controlsystems

You might also like