n  EN 81-72 2003 Fire fighting lifts


n  EN81-73 Behaviour of lifts in the
event of fire
n  FprCEN/TS 81-76:2010 Evacuation of
disabled persons using lifts

12 12 2006 Adrian Shiner 2


EN 81-72 2003 Adrian Shiner

n  Referenced in UK BS 9999 standard


for the fire protection of buildings
n  Car communication system
•  Interactive 2 way
•  Between car, fire service access level, machine
room or emergency operation panel.
•  Machine room coms has a press to talk button
on microphone.
•  Protected to the same degree as the lift, e.g. 2
hours. Wiring must be within the lift well.
12 12 2006 Adrian Shiner 3
EN 81-72 2003 Adrian Shiner

n  Note
n  The firefighting lift does NOT have to
serve every floor of the building.
•  An airport control tower does not need
an obstruction to clear 360 degree
vision!

12 12 2006 Adrian Shiner 4


Adrian Shiner
EN 81-73 Behaviour of lifts in the event of fire

Applies to all types of lifts in all types


of buildings (Lifts Directive) (but!)
•  To reduce the risk of passengers being
trapped in the lift if there is a fire in the
building
•  To show to the firefighters that lift does not
contain trapped passengers
•  To reduce the risk of passengers being
exposed to fire and smoke
•  Does not apply to firefighting lifts
12 12 2006 Adrian Shiner 5
FprCEN/TS 81-76:2010 Adrian Shiner

n  A positive formal vote in April 2011


n  Operation of lift during evacuation is
similar to a firefighting lift
•  Under control of an evacuation assistant

12 12 2006 Adrian Shiner 6


FprCEN/TS 81-76:2010 Adrian Shiner

•  Car interactive 2 way communication


system
n  Between car, evacuation exit floor(s) and any
machine room and emergency or rescue panel
n  Built in speaker and microphone, not a
telephone handset
n  Fire protected, including wiring, to same degree

as lift well
n  Must remain operational for at least 1 hour

during any evacuation or in case of loss of


power supply.