Detailed Structural Engineering Assessment

Report of Boiler Exhaust stand 2


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-
MEEM GROUP
Date of Submission2/18/2023
Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

Client: Creative Collection Ltd.


Factory Operator: Boiler Exhaust stand 2(Creative Collection Ltd.)
HA-MEEM GROUP
Address: Boiler Exhaust stand 2(Creative Collection Ltd.)
HA-MEEM GROUP
Nishatnagar, Tongi, Bangladesh.
.

Building Type: Steel Building.

Product: N/A
Other Establishment in the No other establishment
building
Building ownership Own Building
Date of Inspection

Chief Advisor Engr. Jibon Krishna Paul, Rajuk/70


Assessors Engr. Md. Moniruzzaman, M/32242
Engr. Souptik Barman Tirtho, M/32353
Engr. ShamimHossain, M/36034
Engr. TanvirIshtiakShaon, B.Sc. Engr. Civil

Structural Engineering Assessment Report 2


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

(SUBMISSION LETTER)

To
Managing Director
Creative Collection Ltd.
Nishatnagar, Tongi, Bangladesh.

Subject: Detailed Structural Engineering Assessment Report on Boiler Exhaust stand


2(Creative Collection Ltd.) HA-MEEM GROUP

Dear Sir,

With reference to above subject, a detailed structural and comprehensive survey, inspection and
testing etc. made on Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM GROUP,
following related international standards to evaluate structural safety status of the said industry.
Summary of the report is presented on Executive Summary and details are presented in subsequent
chapters for your kind consideration and next actions.

Our company is committed to provide such services at highest level of integrity, standard and
professional skills.

Thanks.

Managing Director
ECLECTIC

Structural Engineering Assessment Report 3


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

AUTHORIZATION AND FORMATION OF TEAM

Following team is formed and authorized to (i) conduct a detailed structural and comprehensive
survey, inspection and testing on Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP. According to specified standards (ii) prepare a complete Detailed Engineering Audit
report and (iii) finally sign the report under the guidance and leadership of the team leader.

FORMATION OF TEAM

Sl. Name Position Qualification Signature


No.

1. Engr. Md. Moniruzzaman Team Leader B.Sc. in Civil Engg.


(BUET),
MIEB-32242

2. Dr. Jahidul Islam Team Member PhD (DEAKIN UNI),


M.Eng.(NUS),
B.Sc.Eng.(BUET)
MIEB-M/28037PhD
(DEAKIN UNI),
M.Eng.(NUS),
B.Sc.Eng.(BUET)
MIEB-M/28037

3. Engr. Md. Nazmul Islam Team Member B. Sc. in Civil Engg.


(IUBAT)

4. Engr. Md. Siful Islam Team Member B. Sc. in Civil Engg.


(UAP)

Structural Engineering Assessment Report 4


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

TABLE OF CONTENTS
(SUBMISSION LETTER) .............................................................................................................. 3
AUTHORIZATION AND FORMATION OF TEAM ................................................................... 4
EXECUTIVE SUMMARY ............................................................................................................ 6
1.1 SCOPE OF ASSESSMENT ................................................................................................. 7
2. DATA COLLECTION AND FIELD TESTING ........................................................................ 7
2.1 SITE DESCRIPTION ........................................................................................................... 8
2.2BUILDING RECOPRDS& DESCRIPTIONS ...................................................................... 8
2.3 AS-BUILT SURVEY OF THE PROJECT........................................................................... 8
3 STRUCTURAL ANALYSIS OF BUILDING ............................................................................ 9
3.1 DESIGN INFORMATION AND CRITERIA ...................................................................... 9
3.1.1 MATERIAL PROPERTY: ............................................................................................ 9
3.1.2 CODES OF PRACTICE: ............................................................................................... 9
3.1 LOAD CONSIDERATION SUMMARY ............................................................................ 9
3.2.1 WIND LOAD: ..............................................................Error! Bookmark not defined.
3.2.2 EARTHQUAKE LOAD: ............................................................................................... 9
3.2.3 DEAD & LIVE LOAD: ............................................................................................... 10
3.2.4 BNBC ANALYSIS LOADING COMBINATION: .................................................... 10
4 ANALYSES ............................................................................................................................... 10
4.1 ANALYSIS OF New Compressor building (Creative Wash Ltd.) HA-MEEM GROUP .. 11
4.1MEMBER CAPACITY STUDY FROM DEA MODEL .................................................... 13
4.2 Vertical Deflection Study: (BNBC Model)......................................................................... 14
4.3 Lateral Deflection Study: (BNBC Model) ...........................Error! Bookmark not defined.
5. CONCLUDING REMARKS .................................................................................................... 15
6.1MEMBER CAPACITY STUDY FROM DEA MODEL .....Error! Bookmark not defined.
6.2 Vertical Deflection Study: (BNBC Model)..........................Error! Bookmark not defined.
6.3 Lateral Deflection Study: (BNBC Model) ...........................Error! Bookmark not defined.
7. CONCLUDING REMARKS ....................................................... Error! Bookmark not defined.

Structural Engineering Assessment Report 5


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

EXECUTIVE SUMMARY

Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM GROUP is located in Nishatnagar, Tongi,
Bangladesh.

The primary purpose of the assessment was to confirm the structural integrity, risk and to
determine the necessary steps for retrofitting of the factory. Detail Engineering Assessment
Included-
• Preparation of As-built drawings
• Structural analysis to assess safety and serviceability against loading as set out in Alliance
Standards.

According to the need of assessment our Sr. Engineers and team of Jr. Engineers have done the
assessment.
The following findings have been identified during assessment:
• We have prepared as-built structural drawings to conduct the structural analysis.
• We have considered 36Ksi for all members.

A 3D finite element model has been developed to check the actual superstructure using
STAAD.Pro V8i SS5 & RCC Grade Beam, Short Column analysis by STAAD.Pro V8i SS6(ACI-
318 1999). Geometry, Loading and design Codes are followed as per Alliance regulation and
guideline. Material properties such as element-wise compressive strength of concrete and tensile
strength of rebar are strictly followed according to the site investigation and scanning report. The
prepared As-built drawings (Appendix 1) are taken into consideration in developing the model. In
the entire structure, critical structural elements such as transfer column or very long span beam are
not found. The analysis has been run for different load combination and load cases as per Alliance
guideline for day-to-day loading.

Based on actual drawing as per site inspection, analysis and design of superstructure are
performed. Separate hand calculations are also conducted for verification where necessary. Using
the model and hand calculation, the key findings may be illustrated as follows:
Superstructure &Substructure

➢ Steel Columns are adequate according to BNBC 2006 load combination.


➢ All Steel beams are adequate according to BNBC 2006 load combination.
➢ Structure is adequate in Displacement.

Structural Engineering Assessment Report 6


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

1. INTRODUCTION

After a preliminary investigation on structural integrity done by Alliance, it was recommended to


perform a Detailed Engineering Assessment (DEA) to identify performance of the structure. The
following chapters include the methodology and results obtained from the testing and analysis of
Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM GROUP.

1.1 SCOPE OF ASSESSMENT


The scope of assessment as specified by Alliance is mentioned below-

1. Prepare As-Built Structural and Architectural Drawings of the Building.


2. A geotechnical Report describing ground conditions and commenting on foundation
systems used/proposed.
3. Conducting Steel Test to confirm the strength of the Steel.
4. The Engineering teams are to carry out supporting calculations with a model-based design
check to assess the safety and serviceability of the building against loading as set out in
Alliance Standard Part 8.
5. A report on Engineering tests carried out to justify material strengths and reinforcement
content in all key elements studied.
6. Detailed load plans shall be prepared for each level showing current and potential future
loading with all key equipment items shown with associated loads.

2. DATA COLLECTION AND FIELD TESTING


The first phase of work involved a review of the original designs (if available) and construction
documents, soil test report and drawings with the necessary approvals. These were used to

• Assess the structural layout of the buildings


• Check the as-built configuration with the provided drawings (If Available).
• Identify the specified loads to assess usage and possibility of overloading.
• Verify if unauthorized addition or alteration have been carried out in the building
structures.

Based on these evaluations, the following field surveys were carried out:

I. Preparation of As-Built Drawings


II. Spot Check of Foundation by Excavation.
III. Soil test to confirm the actual ground condition.
IV. Preparation of Model and Analysis.
V. Preparation of Report, Recommendations/ Suggestions (If Any).

Structural Engineering Assessment Report 7


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

2.1 SITE DESCRIPTION


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM GROUP is located in Nishatnagar, Tongi,
Bangladesh.
. There are Eight buildings in the premise.

2.2BUILDING RECOPRDS& DESCRIPTIONS


The Building records for Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP are shown in Table 2.2.1.

TABLE 2.2.1: BUILDING RECORDS –

Serial Documents/Items Observations


No.
1 Building type Steel Building

2 Occupancy type
3 Floor Construction Prefabricated steel structure

4 Foundation Type Isolated Column Footings for factory building


5 Location and environment Built in industrial zone
6 No. of story constructed Steel Building
7 Roof Usage N/A
8 Location of generator or heavy vibratory Separate Utility Building
equipment
9 Is design compliant with code? comply with BNBC

2.3 AS-BUILT SURVEY OF THE PROJECT


As-built survey of the building was carried out using measuring tapes, slide calipers, ultrasonic
distance meter. The building interiors were measured with a steel tape. The purpose of the As-built
survey was to determine numbers of columns, beams and their sizes, block sizes, equipment
positions etc. their alignment and placement to prepare as-built drawings of the building according
to NTP standard. Based on the as-built survey of the building as-built drawings have been prepared
which is attached in the Appendix 1.

Structural Engineering Assessment Report 8


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

3 STRUCTURAL ANALYSIS OF BUILDING


This analysis and design checking work includes the analysis and design check of existing Single-
Storied Steel buildings of Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

3.1 DESIGN INFORMATION AND CRITERIA

3.1.1 MATERIAL PROPERTY:

a. Steel.

Steel members are considered to be= 36 ksi.


b. Reinforcement.
Rebar Strength has been considered as 60 ksi
c. Concrete.
Concrete (Brick Chips) Strength has been considered as 2.045 ksi

3.1.2 CODES OF PRACTICE:

The structures are designed in accordance to the following Codes, Standards and technical
literatures:

Steel Structure Design Analysis: AISC-LRFD-93


RCC Structure Design Analysis: ACI -318-220

3.1 LOAD CONSIDERATION SUMMARY


This is an open structure. So, no effect of wind in this structure.
3.2.2 EARTHQUAKE LOAD:
Earthquake Load Calculation:
Earth load calculation of the building has been performed based on the Part 6, Chapter 2 Titled
“Loads” of the Bangladesh National Building Code (BNBC 2006).
The Factors considered for earthquake load

Seismic zone co-efficient, Z Table 6.2.22 Zone-2


Structural importance co- Table 6.2.23 Standard Occupancy
efficient, I Structures 1.00
Ct 2.5.6.2 a. Method A 0.083 (MKS unit)
Response modification co- Table 6.2.24 OMRF=6
efficient, R

Structural Engineering Assessment Report 9


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

Site co-efficient, S Table 6.2.25 S3 = 1

Seismic Dead Load Considering Table:

Ser. Load Types Load


1 Dead Load 2 psf

3.2.3 DEAD & LIVE LOAD:


Proposed Loading on Structure: The proposed loading as per guideline is presented in
tabular form as given below.
Dead Load: For BNBC Model Analysis.
Seismic Load Considering table which explain above.

Live Load: According to BNBC Loading.

Ser. Load Types Load


1 Live Load 20 psf

3.2.4 BNBC ANALYSIS LOADING COMBINATION:


Load Combination of BNBC Guideline for Retrofitting Analysis.

4 ANALYSES
A 3D finite element model has been developed to check the actual superstructure using
STAAD.Pro V8i. Geometry, Loading and design Codes are followed as per Accord regulation and
guideline. The prepared As-built drawings (Appendix 1) are taken into consideration in
developing the model. In the entire structure, critical structural elements such as transfer column

Structural Engineering Assessment Report 10


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

or very long span beam are not found. The analysis has been run for different load combination
and load cases as per Alliance guideline for day to day loading.

4.1 ANALYSIS OF Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM


GROUP

3D Finite Element Model of the Superstructure (render)


Using STAAD.Pro V8i

Structural Engineering Assessment Report 11


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

3D Model of the Steel Structure (Full Sections)

Structural Engineering Assessment Report 12


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

4.1MEMBER CAPACITY STUDY FROM DEA MODEL

Figure: All Member Utilization Ratio


Some Beam having stress ratio More than 1.0 so those members are adequate according to
BNBC 2006

Structural Engineering Assessment Report 13


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

4.2 Vertical Deflection Study: (BNBC Model)

For DL+LL Loads combination, Vertical Drifts must be limited to Span/180. The above ratio
shows that the drift value is not within allowable limit. Therefore, the building is adequate due to
Vertical drift. (Reference: AISC Design manual).

Structural Engineering Assessment Report 14


Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP

5. CONCLUDING REMARKS
Based on actual drawing as per site inspection, analysis and design of superstructure are
performed. Separate hand calculations are also conducted for verification where necessary. Using
the model and hand calculation, the key findings may be illustrated as follows:

Superstructure &Substructure

➢ Steel Columns are adequate according to BNBC 2006 load combination.


➢ All Steel beams are adequate according to BNBC 2006 load combination.
➢ Structure is adequate in Displacement.

Structural Engineering Assessment Report 15