Product: N/A
Other Establishment in the No other establishment
building
Building ownership Own Building
Date of Inspection
(SUBMISSION LETTER)
To
Managing Director
Creative Collection Ltd.
Nishatnagar, Tongi, Bangladesh.
Dear Sir,
With reference to above subject, a detailed structural and comprehensive survey, inspection and
testing etc. made on Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM GROUP,
following related international standards to evaluate structural safety status of the said industry.
Summary of the report is presented on Executive Summary and details are presented in subsequent
chapters for your kind consideration and next actions.
Our company is committed to provide such services at highest level of integrity, standard and
professional skills.
Thanks.
Managing Director
ECLECTIC
Following team is formed and authorized to (i) conduct a detailed structural and comprehensive
survey, inspection and testing on Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM
GROUP. According to specified standards (ii) prepare a complete Detailed Engineering Audit
report and (iii) finally sign the report under the guidance and leadership of the team leader.
FORMATION OF TEAM
TABLE OF CONTENTS
(SUBMISSION LETTER) .............................................................................................................. 3
AUTHORIZATION AND FORMATION OF TEAM ................................................................... 4
EXECUTIVE SUMMARY ............................................................................................................ 6
1.1 SCOPE OF ASSESSMENT ................................................................................................. 7
2. DATA COLLECTION AND FIELD TESTING ........................................................................ 7
2.1 SITE DESCRIPTION ........................................................................................................... 8
2.2BUILDING RECOPRDS& DESCRIPTIONS ...................................................................... 8
2.3 AS-BUILT SURVEY OF THE PROJECT........................................................................... 8
3 STRUCTURAL ANALYSIS OF BUILDING ............................................................................ 9
3.1 DESIGN INFORMATION AND CRITERIA ...................................................................... 9
3.1.1 MATERIAL PROPERTY: ............................................................................................ 9
3.1.2 CODES OF PRACTICE: ............................................................................................... 9
3.1 LOAD CONSIDERATION SUMMARY ............................................................................ 9
3.2.1 WIND LOAD: ..............................................................Error! Bookmark not defined.
3.2.2 EARTHQUAKE LOAD: ............................................................................................... 9
3.2.3 DEAD & LIVE LOAD: ............................................................................................... 10
3.2.4 BNBC ANALYSIS LOADING COMBINATION: .................................................... 10
4 ANALYSES ............................................................................................................................... 10
4.1 ANALYSIS OF New Compressor building (Creative Wash Ltd.) HA-MEEM GROUP .. 11
4.1MEMBER CAPACITY STUDY FROM DEA MODEL .................................................... 13
4.2 Vertical Deflection Study: (BNBC Model)......................................................................... 14
4.3 Lateral Deflection Study: (BNBC Model) ...........................Error! Bookmark not defined.
5. CONCLUDING REMARKS .................................................................................................... 15
6.1MEMBER CAPACITY STUDY FROM DEA MODEL .....Error! Bookmark not defined.
6.2 Vertical Deflection Study: (BNBC Model)..........................Error! Bookmark not defined.
6.3 Lateral Deflection Study: (BNBC Model) ...........................Error! Bookmark not defined.
7. CONCLUDING REMARKS ....................................................... Error! Bookmark not defined.
EXECUTIVE SUMMARY
Boiler Exhaust stand 2(Creative Collection Ltd.) HA-MEEM GROUP is located in Nishatnagar, Tongi,
Bangladesh.
The primary purpose of the assessment was to confirm the structural integrity, risk and to
determine the necessary steps for retrofitting of the factory. Detail Engineering Assessment
Included-
• Preparation of As-built drawings
• Structural analysis to assess safety and serviceability against loading as set out in Alliance
Standards.
According to the need of assessment our Sr. Engineers and team of Jr. Engineers have done the
assessment.
The following findings have been identified during assessment:
• We have prepared as-built structural drawings to conduct the structural analysis.
• We have considered 36Ksi for all members.
A 3D finite element model has been developed to check the actual superstructure using
STAAD.Pro V8i SS5 & RCC Grade Beam, Short Column analysis by STAAD.Pro V8i SS6(ACI-
318 1999). Geometry, Loading and design Codes are followed as per Alliance regulation and
guideline. Material properties such as element-wise compressive strength of concrete and tensile
strength of rebar are strictly followed according to the site investigation and scanning report. The
prepared As-built drawings (Appendix 1) are taken into consideration in developing the model. In
the entire structure, critical structural elements such as transfer column or very long span beam are
not found. The analysis has been run for different load combination and load cases as per Alliance
guideline for day-to-day loading.
Based on actual drawing as per site inspection, analysis and design of superstructure are
performed. Separate hand calculations are also conducted for verification where necessary. Using
the model and hand calculation, the key findings may be illustrated as follows:
Superstructure &Substructure
1. INTRODUCTION
Based on these evaluations, the following field surveys were carried out:
2 Occupancy type
3 Floor Construction Prefabricated steel structure
a. Steel.
The structures are designed in accordance to the following Codes, Standards and technical
literatures:
4 ANALYSES
A 3D finite element model has been developed to check the actual superstructure using
STAAD.Pro V8i. Geometry, Loading and design Codes are followed as per Accord regulation and
guideline. The prepared As-built drawings (Appendix 1) are taken into consideration in
developing the model. In the entire structure, critical structural elements such as transfer column
or very long span beam are not found. The analysis has been run for different load combination
and load cases as per Alliance guideline for day to day loading.
For DL+LL Loads combination, Vertical Drifts must be limited to Span/180. The above ratio
shows that the drift value is not within allowable limit. Therefore, the building is adequate due to
Vertical drift. (Reference: AISC Design manual).
5. CONCLUDING REMARKS
Based on actual drawing as per site inspection, analysis and design of superstructure are
performed. Separate hand calculations are also conducted for verification where necessary. Using
the model and hand calculation, the key findings may be illustrated as follows:
Superstructure &Substructure