Professional Documents
Culture Documents
com
User’s
Manual EJX and EJA-E Series
Differential Pressure and
Pressure Transmitters
Installation Manual
CD-ROM included
IM 01C25A01-01E
Contents
1. Introduction 1
1.1 For Safe Use of Product..............................................2
1.2 Warranty ......................................................................3
1.3 ATEX Documentation..................................................4 2
2. Handling Cautions
2.1
2.2
Model and Speciications Check.................................6
Selecting the Installation Location ..............................6
3
2.3 Pressure Connection ..................................................6
2.4 Installation of an Explosion-Protected Instrument ......6
2.5 EMC Conformity Standards ..................................... 15 4
2.6 Pressure Equipment Directive (PED) ...................... 16
2.7 Safety Requirement Standards................................ 17
3. Installation 5
3.1 Mounting................................................................... 18
3.2 Mounting the Diaphragm Seals ......................................18
3.3 Diaphragm Seals Installation Consideration............ 19 6
3.4 Mounting the Flushing Connection Ring .................. 20
3.5 Afixing the Telon Film ............................................. 21
3.6
3.7
Rotating Transmitter Section.................................... 22
Changing the Direction of Integral Indicator............. 22 7
4. Installing Impulse Piping
4.1 Impulse Piping Installation Precautions ................... 23 8
4.2 Impulse Piping Connection Examples ..................... 25
4.3 Process Piping Installation Precautions (EJ115)26
5. Wiring
5.1 Wiring Precautions ................................................... 28
5.2 Connections of External Wiring to Terminal Box...... 28
5.3 Wiring ....................................................................... 30
5.4 RTD Cable Connection (EJX910A/EJX930A) ......... 31
5.5 Grounding ................................................................ 34
5.6 Power Supply Voltage and Load Resistance........... 34
6. Operation
6.1 Preparation for Starting Operation ........................... 35
6.2 Zero Point Adjustment .............................................. 36
6.3 Local Parameter Setting .......................................... 37
7. Errors and Countermeasures
8. Parameter Summary
IM 01C25A01-01E
8th Edition
Downloaded from https://www.rsmanuals.com
<1. Introduction> 1
1. Introduction
Thank you for purchasing the DPharp electronic pressure Models Document No. Style
transmitter. EJX910A S2
IM 01C25R01-01E
EJX930A S1
This manual provides the basic guidelines for installation
EJX910A and EJX930A HART
and wiring procedures of the DPharp EJX Series IM 01C25R02-01E —
Communication Type
and EJA-E Series with BRAIN and HART protocols.
EJX910A and EJX930A Fieldbus
It does not provide the product speciic functional IM 01C25R03-01E —
Communication Type
speciications and explanations, maintenance,
troubleshooting, FOUNDATION FieldbusTM and PROFIBUS
Models Document No. Style
PA communication operating procedures and handling
EJA110E, EJA120E
precautions of safety transmitters. For the items which
EJA130E, EJA310E, EJA430E IM 01C25B01-01E S1
are not covered in this manual, see the applicable user’s and EJA440E
manuals in the CD-ROM attached to this manual as listed EJA210E IM 01C25C01-01E S1
in Table 1.1. EJA510E and EJA530E IM 01C25F01-01E S1 1
EJA118E and EJA438E IM 01C25H01-01E S1
● Installation manual (this document) EJA115E IM 01C25K01-01E S1
Introduction
EJX and EJA-E series common manual DPharp HART 5/HART 7
IM 01C25T01-06EN —
<Contents> Communication Type
• Installation DPharp Fieldbus Communication
IM 01C25T02-01E —
• Impulse piping installation Type
• Wiring DPharp BRAIN Communication
• Zeroing IM 01C25T03-01E —
Type
DPharp PROFIBUS PA
IM 01C25T04-01EN —
Communication Type
● Attached CD-ROM includes PDF manuals for:
• Product specific manuals, 6 PDFs by model code
• Communication manuals, 6 PDFs
Regarding This Manual
• This manual should be passed on to the end user.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<1. Introduction> 2
• Yokogawa assumes no responsibilities for this 1.1 For Safe Use of Product
product except as stated in the warranty.
• If the customer or any third party is harmed by the use For the protection and safety of the operator and the
of this product, Yokogawa assumes no responsibility instrument or the system including the instrument, please
for any such harm owing to any defects in the product be sure to follow the instructions on safety described
which were not predictable, or for any indirect in this manual when handling this instrument. In case
damages. the instrument is handled in contradiction to these
instructions, Yokogawa does not guarantee safety.
• When describing the model name like EJ110 Please give your attention to the followings.
in this manual, it shows the applicability for both
EJX110A and EJA110E. The same representations (a) Installation
are used for the other models, too.
• The instrument must be installed by an expert
engineer or a skilled personnel. The procedures
NOTE described about INSTALLATION are not permitted for
operators.
For FOUNDATION Fieldbus and PROFIBUS PA protocol • In case of high process temperature, care should
versions, please refer to manuals in the attached CD- be taken not to burn yourself because the surface of
ROM, in addition to this manual. body and case reaches a high temperature.
• The instrument installed in the process is under
• The following safety symbol marks are used in this pressure. Never loosen the process connector bolts
manual: to avoid the dangerous spouting of process luid.
• During draining condensate from the pressure
detector section, take appropriate care to avoid
WARNING contact with the skin, eyes or body, or inhalation of
vapors, if the accumulated process luid may be toxic
Indicates a potentially hazardous situation which, if not
or otherwise harmful.
avoided, could result in death or serious injury.
• When removing the instrument from hazardous
processes, avoid contact with the luid and the interior
of the meter.
• All installation shall comply with local installation
CAUTION requirement and local electrical code.
Indicates a potentially hazardous situation which, if not (b) Wiring
avoided, may result in minor or moderate injury. It may
also be used to alert against unsafe practices. • The instrument must be installed by an expert
engineer or a skilled personnel. The procedures
described about WIRING are not permitted for
operators.
IMPORTANT • Please conirm that voltages between the power
supply and the instrument before connecting the
Indicates that operating the hardware or software in
power cables and that the cables are not powered
this manner may damage it or lead to system failure.
before connecting.
(c) Operation
NOTE • Wait 5 min. after power is turned off, before opening
the covers.
Draws attention to information essential for • Do not open the cover in wet weather or humid
understanding the operation and features. environment. If the cover is opened, stated enclosure
protection is not applicable.
Direct current
Caution
This symbol indicates that the operator must
refer to an explanation in the user’s manual
in order to avoid the risk of injury or death of
personnel or damage to the instrument.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<1. Introduction> 3
(d) Maintenance 1.2 Warranty
• Please do not carry out except being written to • The warranty shall cover the period noted on the
maintenance descriptions. When these procedures quotation presented to the purchaser at the time of
are needed, please contact nearest YOKOGAWA purchase. Problems occurred during the warranty
ofice. period shall basically be repaired free of charge.
• Care should be taken to prevent the build up of drift,
dust or other material on the display glass and name • In case of problems, the customer should contact the
plate. In case of its maintenance, soft and dry cloth is Yokogawa representative from which the instrument
used. was purchased, or the nearest Yokogawa ofice.
(e) Explosion Protected Type Instrument • If a problem arises with this instrument, please inform
us of the nature of the problem and the circumstances
• Users of explosion proof instruments should refer irst under which it developed, including the model
to section 2.4 (Installation of an Explosion Protected speciication and serial number. Any diagrams,
Instrument) of this manual. data and other information you can include in your
• The use of this instrument is restricted to those who communication will also be helpful.
have received appropriate training in the device.
• Take care not to create sparks when accessing the • Responsible party for repair cost for the problems 1
instrument or peripheral devices in a hazardous shall be determined by Yokogawa based on our
investigation.
Introduction
location.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<1. Introduction> 4
1.3 ATEX Documentation
This is only applicable to the countries in European Union.
GB SK
CZ
DK
I LT
E LV
EST
NL
PL
SF
SLO
P
BG
RO
S
M
GR
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
2. Handling Cautions
When the transmitter is delivered, visually check them EJ110 B
to make sure that no damage occurred during shipment. EJ120 1 D
Also check that all transmitter mounting hardware shown EJ130 2 G
- -
EJ310 3 J
in Figure 2.1 is included. If the transmitter was ordered
EJ430 4 K
without the mounting bracket or without the process EJ440 M
connector, the transmitter mounting hardware is not
included. 1
B
2
Table 2.1 Applicable Model Code for Mounting 1 D
3
Hardware EJX910A 2 G
4
- - J
EJX930A 3
Applicable B
Sufix code Part name Qty 4 K
model C
M
D
EJ110 Process connector bolt 4
1
EJ120 Process Process connector 2
2
EJ130 connections EJ210 - -
Process connector 3
EJX910A 1,2,3 and 4 2
gasket 4
EJX930A
EJ210 Process connector bolt 2
EJ510 2
Process EJ530 F
EJ310 Process connector 1 - -
connections EJX610A L
Handling Cautions
EJ430 Process connector EJX630A
1,2,3 and 4 1
EJ440 gasket
EJ110 EJ118 B
- -
EJ120 U-bolt 1 EJ438 J
EJ130
EJ310 B
U-bolt nut 2 D
EJ430 EJ115 - -
Mounting bracket J
EJ440
B,D,G,J,K and M K
EJ118 Mounting bracket
1
EJ438 (L or lat type) F0201.ai
EJ115
EJX910A Transmitter mounting Cable gland and RTD cable
4 (EJX910A and EJX930A only)
EJX930A bolt
EJ510 U-bolt (L and S) 1 ea. Bolt
EJ530 Mounting bracket U-bolt nut (L and S) 2 ea. Process connector
EJX610A F and L Process connector
EJX630A Mounting bracket 1
Gasket
External U-bolt
temperature input
B, C and D RTD cable 1
EJX910A
EJX930A External
temperature input
1, 2, 3 and 4 Cable gland 2
Mounting bracket
EJ210 Telon ilm 1 (Flat type)
Option code /TF1
EJ438 Fluorinated oil 1 Mounting bracket
Telon ilm 2 (L type)
EJ118 Option code /TF1
Fluorinated oil 2 U-bolt nut Transmitter mounting bolt
U-bolt nut (L)
Teflon film
Fluorinated oil
Mounting bracket
U-bolt (S)
U-bolt (L)
F0202.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
WARNING
• Never loosen the process connector bolts when an
WARNING
instrument is installed in a process. The device is The range setting switch must not be used in a
under pressure, and a loss of seal can result in a hazardous area.
sudden and uncontrolled release of process luid.
• When draining toxic process luids that have
condensed inside the pressure detector, take
appropriate steps to prevent the contact of such
luids with the skin or eyes and the inhalation of
vapors from these luids.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Handling Cautions
• Applicable Standard: FM3600, FM3610, FM3611,
installed in a Class II, III, Group E, F and G
FM3810
environments.
• Intrinsically Safe for Class I, Division 1, Groups A,
• Associated apparatus manufacturer’s installation
B, C & D. Class II, Division 1, Groups E, F & G and
drawing must be followed when installing this
Class III, Division 1, Class I, Zone 0 in Hazardous
apparatus.
Locations, AEx ia IIC
• The maximum power delivered from the barrier
• Nonincendive for Class I, Division 2, Groups
must not exceed 1 W.
A, B, C & D. Class II, Division 2, Groups F & G
• Note a warning label worded “SUBSTITUTION
and Class I, Zone 2, Groups IIC, in Hazardous
OF COMPONENTS MAY IMPAIR INTRINSIC
Locations.
SAFETY,” and “INSTALL IN ACCORDANCE WITH
• Outdoor hazardous locations: NEMA TYPE 4X
DOC. No. IFM022-A12”
• Temperature Class: T4
• Ambient temperature: –60 to 60°C Note 4. Maintenance and Repair
• The instrument modiication or parts replacement
Note 2. Entity Parameters
by other than authorized representative of
• Intrinsically Safe Apparatus Parameters
Yokogawa Electric Corporation is prohibited and
[Groups A, B, C, D, E, F and G]
will void Factory Mutual Intrinsically safe and
Vmax = 30 V Ci = 6 nF
Nonincendive Approval.
Imax = 200 mA Li = 0 µH
Pmax = 1 W [Intrinsically Safe]
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Handling Cautions
Isc=Voc/R. * –15°C when /HE is speciied.
• The safety barrier must be CSA certiied. • Supply Voltage: 42 V dc max.
• Input voltage of the safety barrier must be less • Output Signal: 4 to 20 mA dc
than 250 Vrms/Vdc.
• Installation should be in accordance with Canadian Note 2. Wiring
Electrical Code Part I and Local Electrical Code. • All wiring shall comply with Canadian Electrical
• Dust-tight conduit seal must be used when Code Part I and Local Electrical Codes.
installed in Class II and III environments. • In hazardous location, wiring shall be in conduit as
• The instrument modiication or parts replacement shown in the igure.
by other than authorized representative of • WARNING:
Yokogawa Electric Corporation and Yokogawa A SEAL SHALL BE INSTALLED WITHIN 50cm OF
Corporation of America is prohibited and will THE ENCLOSURE.
void Canadian Standards Intrinsically safe and UN SCELLEMENT DOIT ÊTRE INSTALLÉ À
nonincendive Certiication. MOINS DE 50cm DU BOÎTIER.
• WARNING:
[Intrinsically Safe]
WHEN INSTALLED IN CL.I, DIV 2, SEAL NOT
Hazardous Location Nonhazardous Location
REQUIRED.
Group IIC, Zone 0
UNE FOIS INSTALLÉ DANS CL I, DIV 2, AUCUN
Class I, II, III, Division 1,
General JOINT N'EST REQUIS.
Groups A, B, C, D, E, F, G
Purpose
Pressure Transmitters Safety Barrier Equipment Non-Hazardous Hazardous Locations Division 1
Locations
+ + + +
Non-hazardous
Supply – – – – Location Equipment 50 cm Max.
F0206.ai
42 V DC Max. Conduit
4 to 20 mA DC Sealing Fitting
[Nonincendive]
Signal
Hazardous Location Nonhazardous Location Transmitter
F0208.ai
Group IIC, Zone 2
Class I, II, Division 2, CSA Certified Non-Hazardous Hazardous Locations Division 2
Groups A, B, C, D, F, G Equipment Locations
Class III, Division 1. ([nL] or Non-hazardous
Pressure Transmitters nonincendive) Location Equipment
+ +
Supply – –
Not Use 42 V DC Max.
4 to 20 mA DC Sealing Fitting
Safety Barrier
Signal
F0207.ai Transmitter
F0209.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Handling Cautions
the electrical connection port. Uo = 30 V
• When the lightning protector option is speciied, Io = 95.4 mA
the apparatus is not capable of withstanding the Po= 468 mW
500V insulation test required by EN60079-11. This Co = 11 nF
must be taken into account when installing the Lo= 3.9 mH
apparatus. Note 3. Installation
• All wiring shall comply with local installation
requirements. (Refer to the installation diagram)
b. ATEX Intrinsically Safe Type for EJX910A
• When the analog and pulse circuits are connected
and EJX930A to separate barriers, it shall be assured that the
Caution for ATEX Intrinsically safe type. voltage difference between these output circuits is
not more than 30 V.
Note 1. Model EJX Series pressure transmitters with
• When used in a potentially explosive atmosphere,
optional code /KS2 for potentially explosive
Requiring the use of apparatus of equipment
atmospheres:
category 1D or 2D, certiied cable entry devices
• No. KEMA 06ATEX 0037X
shall be used that are suitable for the application
• Applicable Standard:
and correctly installed.
EN 50014:1997, EN 50020:2002,
EN 50284:1999, EN 50281-1-1:1998 Note 4. Maintenance and Repair
• Type of Protection and Marking code: • The instrument modiication or parts replacement
EEx ia IIC T4 by other than authorized representative of
• Group: II Yokogawa Electric Corporation is prohibited and
• Category: 1G, 1D will void KEMA Intrinsically safe Certiication.
• Ambient Temperature for gas-proof:
–50* to 60°C Note 5. Special Conditions for Safe Use
* –15°C when /HE is speciied. • In the case where the enclosure of the Pressure
• Process Temperature (Tp.): 120°C max. Transmitter is made of aluminium, if it is mounted
• Maximum Surface Temperature for dust-proof: in an area where the use of category 1 G
T85°C (Tamb.: –40* to 60°C, Tp.: 80°C) apparatus is required, it must be installed such,
T100°C (Tamb.: –40* to 60°C, Tp.: 100°C) that, even in the event of rare incidents, ignition
T120°C (Tamb.: –40* to 60°C, Tp.: 120°C) sources due to impact and friction sparks are
* –15°C when /HE is speciied.
excluded.
• Enclosure: IP66 and IP67
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
To satisfy IP66 or IP67, apply waterproof glands to the • In the case where the enclosure of the Pressure
electrical connection port. Transmitter is made of aluminium, if it is mounted
in an area where the use of category 2D apparatus
is required, it shall be installed in such a way
c. ATEX Flameproof Type that the risk from electrostatic discharges and
propagating brush discharges caused by rapid
Caution for ATEX lameproof type.
low of dust is avoided.
Note 1. Model EJX/EJA-E Series pressure transmitters • The instrument modiication or parts replacement
with optional code /KF22 for potentially by other than an authorized Representative of
explosive atmospheres: Yokogawa Electric Corporation is prohibited and
• No. KEMA 07ATEX0109 X will void the certiication.
• Applicable Standard: EN 60079-0:2009, • To satisfy IP66 or IP67, apply waterproof glands to
EN 60079-1:2007, EN 60079-31:2009 the electrical connection port.
• Type of Protection and Marking Code:
Ex d IIC T6...T4 Gb, Ex tb IIIC T85°C Db
• Group: II
• Category: 2G, 2D
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Handling Cautions
must be taken into account when installing the
Caution for ATEX intrinsically safe Ex ic apparatus.
• Applicable Standard:
EN 60079-0:2009/EN 60079-0:2012,
EN 60079-11:2012 (2) Electrical Connection
• Type of Protection and Marking Code: A mark indicating the electrical connection type is
II 3G Ex ic IIC T4 Gc stamped near the electrical connection port. These
• Ambient Temperature: –30* to +60°C marks are as followed.
* –15°C when /HE is speciied.
• Ambient Humidity: Screw Size Marking
0 to 100% (No condensation)
ISO M20 × 1.5 female M
• Maximum Process Temperature: 120°C
• IP Code: IP66 ANSI 1/2 NPT female N or W
• Ambient pollution degree: 2
• Overvoltage category: I
Note 1. Electrical Data
Ui = 30 V
Ci = 27.6 nF Location of the mark
Li = 0 µH
F0214.ai
Note 2. Installation
• All wiring shall comply with local installation (3) Installation
requirements. (refer to the control drawing)
• Cable glands, adapters and/or blanking elements
shall be of Ex “n”, Ex “e” or Ex “d” and shall be WARNING
installed so as to maintain the speciied degree of
protection (IP Code) of the transmitters. • All wiring shall comply with local installation
requirements and the local electrical code.
Note 3. Maintenance and Repair • There is no need for conduit seal in Division 1
• The instrument modiication or parts replacement and Division 2 hazardous locations because this
by other than authorized representative of product is sealed at the factory.
Yokogawa Electric Corporation is prohibited and
will void ATEX intrinsically safe.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
WARNING
(4) Operation Tag plate for intrinsically safe type No. KEMA 06ATEX0037 X
EEx ia IIC T4
(for EJX910A and EJX930A) IP66 and IP67
Tamb. -50(-15) to 60°C MIN Tamb.for DUST -40(-15°C)
MAX PROCESS TEMP.(Tp) 120°C
WARNING
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
Supply/Pulse circuit
Ui=30 V, Ii=200 mA, Pi=0.9 W, Ci=10 nF, Li=0 mH
Sensor circuit
Uo=30 V, Io=95.4 mA, Po=468 mW, Co=11 nF, Lo=3.9 mH
• Take care not to generate mechanical sparking MODEL: Speciied model code.
when access to the instrument and peripheral STYLE: Style code.
devices in a hazardous location. SUFFIX: Speciied sufix code.
SUPPLY: Supply voltage.
OUTPUT: Output signal.
(5) Maintenance and Repair MWP: Maximum working pressure.
CAL RNG: Speciied calibration range.
WARNING NO.: Serial number and year of production*1.
TOKYO 180-8750 JAPAN:
The instrument modiication or parts replacement by The manufacturer name and the address*2.
other than an authorized Representative of Yokogawa *1: The irst number in the second block of “NO.” column
Electric Corporation is prohibited and will void the is the last one number of the production year.
certiication.
second block
(6) Name Plate
NO. 91K819857 132 7
Name plate
The year 2011
Tag plate for intrinsically safe Ex ia installation must be in accordance with the
No. DEKRA 11ATEX 0228 X
Ex ia IIC T4 Ga Ta: -50 TO 60°C
description about the type of protection in this
instruction manual.
Ex ia IIIC T85°C T100°C T120°C Db Ta:-30(-15) TO 60°C
IP66/IP67
MAX. PROCESS TEMP.(Tp.) 120°C
T85°C(Tp.:80°C), T100°C(Tp.:100°C), T120°C(Tp.:120°C)
Ui=30V, Ii=200mA , Pi=0.9W, Ci=27.6nF, Li=0µH
*3 D
F0215.ai
Downloaded from https://www.rsmanuals.com
Handling Cautions
• Unused apertures shall be closed with suitable
Note 3. Installation
lameproof certiied blanking elements.
• In any safety barrier used output current must be
limited by a resistor 'R' such that Io=Uo/R. Note 3. Operation
• The safety barrier must be IECEx certiied. • WARNING:
• Input voltage of the safety barrier must be less AFTER DE-ENERGIZING, DELAY 5 MINUTES
than 250 Vrms/Vdc. BEFORE OPENING.
• The instrument modiication or parts replacement • WARNING:
by other than authorized representative of WHEN AMBIENT TEMPERATURE ≥ 65°C, USE
Yokogawa Electric Corporation and will void IECEx THE HEAT-RESISTING CABLES ≥ 90°C.
Intrinsically safe and type n certiication. • Take care not to generate mechanical sparking
[Intrinsically Safe] when accessing to the instrument and peripheral
Hazardous Location Nonhazardous Location devices in a hazardous location.
Group IIC, Zone 0 Note 4. Maintenance and Repair
General
IECEx certified
• The instrument modiication or parts replacement
EJX Series Pressure Purpose
Transmitters Safety Barrier Equipment by other than authorized representative of
+ + + + Yokogawa Electric Corporation is prohibited and
Supply – – – – will void IECEx Certiication.
F0216.ai
2.5 EMC Conformity Standards
EN61326-1 Class A, Table 2 (for use in industrial
[type n]
Hazardous Location Nonhazardous Location
locations)
EN61326-2-3
Group IIC, Zone 2
IECEx Certified
EJX Series Pressure
Transmitters Equipment [nL] CAUTION
+ +
To meet EMC regulations, Yokogawa recommends
Supply – – that customers run signal wiring through metal
Not Use
Safety Barrier
conduits or use shielded twisted-pair cabling when
F0217.ai
installing EJX/EJA-E Series transmitters in a plant.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Handling Cautions
(interfaces) are provided.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<3. Installation> 18
3. Installation
Vertical pipe mounting Vertical pipe mounting
IMPORTANT (Process connector upside) (Process connector downside)
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<3. Installation> 19
3.2.1 EJ210 3.3 Diaphragm Seals Installation
The transmitter is mounted on a process using its Consideration
high pressure side lange as shown in Figure 3.5. The
customer should prepare the mating lange, gasket, stud IMPORTANT
bolts and nuts.
• When measuring the liquid level of the tank, the
minimum liquid level (zero point) must be set to a
Gasket level at least 50 mm above the center of the high
pressure side diaphragm seal (see Figure 3.7).
• Correctly install the diaphragm seals on the high
and low pressure sides of the process, checking
the label on each seal.
• To avoid measuring error duets temperature
Stud bolt
difference between the two diaphragm seals,
Nut F0305.ai capillary tube must be bound together. The
Figure 3.5 EJ210 Mounting capillary tube must be securely ixed to the tank
wall to prevent movement by wind or vibration.
If the capillary tube is too long, loosely coil the
3.2.2 EJ118 and EJ438 extra tube portion (coil diameter of 300 mm or
Mount the diaphragm seals using the langes as shown in more) and secure the coiled tube with a clamp.
Figure 3.6. The mating lange, gasket, bolts and nuts are
to be procured by the customer. Low 3
Flange
IMPORTANT pressure
side
Installation
Nut
Bolt Diaphragm Install the sealed diaphragm
so that the shank positions
downward.
ød Minimum
High liquid level
Gasket
pressure
The product is side 50 mm minimum
shipped with these Correctly install the diaphragm
parts assembled. seals on the high and low pressure
sides of the process (The label on
each diaphragm seal is marked
HIGH or LOW). F0306.ai The transmitter should
be installed as low as
Figure 3.6 Mounting the Diaphragm Seals
possible below the
position where the high
pressure side
diaphragm seal is
installed.
F0307.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<3. Installation> 20
(P–P0) (–)
h= × 0.102 [mm]
ds
h≤0: Install the transmitter at least h (mm) below the Figure 3.8 Example of Installation to Tank
HP process connection (Caution on Installation)
h>0: Install the transmitter at most h (mm) above the
HP process connection
P: Pressure in the tank (Pa abs)
3.4 Mounting the Flushing
P0: Minimum working pressure limit of the transmitter (Pa
abs) See below table. Connection Ring
[For ill luid code A, B, C, D, E]
Wetted parts Process connection size 3.4.1 Mounting to Pressure Detector
Capillary
material
length
code Section
code 2, 8 3 4,W
1 to 5m 6790 3190 The lushing connection ring is mounted to the pressure
SW
6 to 10m 10030 3520 detector section as shown in Figure 3.9.
1 to 5m 6790 3190 At the factory shipment, the lushing connection ring is
SE
6 to 10m 10030 3520
1 to 5m 3190 already assembled and attached to process detector
SY section.
6 to 10m 3520
1 to 5m 19150 6140
HW Pressure-detector section
6 to 10m 8290
1 to 5m 9620 3620
TW
6 to 10m 4210
1 to 5m 9540 4750 Ring
UW
6 to 10m 6050
[For ill luid code 1, 2, 4]
Wetted parts Process connection size Spiral gasket
Capillary
material code
length Groove for
code 2, 8 3 4,W installing Ring holder
1 to 5m 2570 320 spiral gasket
SW
6 to 10m 4680 530
1 to 5m 2570 320 View from pressure Vent/Drain plug
SE detector section
6 to 10m 4680 530
1 to 5m 320 F0309.ai
SY
6 to 10m 530 Figure 3.9 Mounting to Pressure Detector Section
1 to 5m 10220 2050
HW
6 to 10m 3450
1 to 5m 4270 570 (1) Mount the ring holder on the ring and loosely tighten
TW
6 to 10m 960 the mounting screws.
ds: Speciic gravity of ill luid (at 25°C). See below table. (2) Place the spiral gasket in the ring groove. With the
ring correctly aligned and lush with the face of the
Fill luid
A, 1, 4 B C, 2 D E pressure detector, securely tighten each ring holder’s
code
ds: Speciic 1.90 to mounting screws.
1.07 0.94 1.09 1.09 (3) Position the ring so that the vent/drain plugs are
gravity 1.92
aligned straight up and down.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<3. Installation> 21
3.4.2 Mounting to Process Flange 3.5 Afixing the Telon Film
Tighten the bolts to completely close the gap between the
ring and the pressure detector section. IMPORTANT
The mating lange, gasket, stud bolts and nuts are to
procured by the customer. The FEP Teflon option includes a teflon film and
fluorinated oil. Before mounting the transmitter to the
process lange, afix the telon ilm as follows:
Installation
F0310.ai
Teflon film
Figure 3.10 Mounting to Process Flange PART No.
EJ210 F9347YD
2 inch EJ118
F9347YA
IMPORTANT EJ438
3 inch F9347XA
Fluorinated oil
• Conirm that there is no gap between the ring [PART No. : F9145YN]
and the process-detector section after they are Diaphragm
mounted on the process lange. A gap can lead to
a sudden, explosive release of process luids. Gasket area
• When mounting or removing the ring, take care not F0311.ai
to tilt the pressure detector downward as the ring Figure 3.11 Afixing the Telon Film
can slip off and cause injury.
• When re-mounting the ring, use the new spiral
gasket as shown in below table.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<3. Installation> 22
3.6 Rotating Transmitter Section 3.7 Changing the Direction of
The transmitter section can be rotated approximately Integral Indicator
360° (180° to either direction or 360° to one direction
from the original position at shipment, depending on the IMPORTANT
coniguration of the instrument.) It can be ixed at any
angle within above range. Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area before
1) Remove the two setscrews that fasten the transmitter
disassembling and reassmbling an indicator.
section and capsule assembly, using the Allen
wrench.
An integral indicator can be installed in the following
2) Rotate the transmitter section slowly and stop it at
three directions.
designated position.
3) Tighten the two setscrews to a torque of 1.5 N·m.
IMPORTANT
Do not rotate the transmitter section more than the
F0313.ai
above limit.
Figure 3.13 Integral Indicator Direction
Vertical impulse piping type
IMPORTANT
Pressure-detector section
Stopper
The terminal box cover is locked by an Allen head
bolt (a shrouding bolt) on ATEX lameproof type
Rotate 0 to ±180° segments
transmitters. When the shrouding bolt is driven
clockwise by an Allen wrench, it is going in and cover
lock is released, and then the cover can be opened.
When a cover is closed it should be locked by a
shrouding bolt without fail. Tighten the shrouding bolt
Conduit connection to a torque of 0.7 N·m.
Integral 90°
Pressure-detector section indicator 90°
F0312.ai
Amplifier cover
F0314.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
57 mm 54 mm 51 mm
F0402.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Drain plug
Pipe (opened to atmosphere
at low pressure side) F0407.ai
The transmitter is shipped with the process connector Note the following points when referring to these piping
mounting bolts only loosely tightened. After connecting examples.
the process piping, tighten these bolts uniformly to
• The process piping material used must be compatible
prevent leaks with a torque of 39 to 49 N·m {4 to 5 kgf·m}.
with the process pressure, temperature, and other
conditions.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Stop valve
Manifold
Process piping
Union or flange
Stop valve
Process piping
F0410.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<5. Wiring> 28
5. Wiring
5.2 Connections of External
NOTE
Wiring to Terminal Box
For FOUNDATION Fieldbus and PROFIBUS PA
communication types, please refer to manuals in the 5.2.1 Power Supply Wiring Connection
attached CD-ROM.
IMPORTANT
5.1 Wiring Precautions Connecting with the commercial AC power supply
will damage the device. Be sure to use the DC power
supply in the predetermined range.
IMPORTANT
Connect the power supply wiring to the SUPPLY + and –
• Lay wiring as far as possible from electrical noise
terminals.
sources such as large capacity transformers,
motors, and power supplies. Transmitter terminal box
• Remove electrical connection dust cap before +
Power supply
wiring.
–
• All threaded parts must be treated with
waterprooing sealant. (A non-hardening silicone F0502.ai
group sealant is recommended.)
Figure 5.2 Power Supply Wiring Connection
• To prevent noise pickup, do not pass signal and
power cables through the same ducts.
• Explosion-protected instruments must be wired 5.2.2 Coniguration Tool Connection
in accordance with speciic requirements (and, Connect the coniguration tool to the SUPPLY + and –
in certain countries, legal regulations) in order terminals. (Use hooks.)
to preserve the effectiveness of their explosion-
protected features. Transmitter terminal box Power supply
• The terminal box cover is locked by an Allen head +
bolt (a shrouding bolt) on ATEX lameproof type USB –
transmitters. When the shrouding bolt is driven FieldMate Modem
Ignore the polarity since
clockwise using an Allen wrench, it gose in. The the configuration tool is
AC-coupled to the
cover lock can then be released and the cover can terminal box.
PC/FieldMate F0503.ai
be opened by hand.
When a cover is closed it should be locked by a Figure 5.3 Coniguration Tool Connection
shrouding bolt without fail. Tighten the shrouding
bolt to a torque of 0.7 N·m. 5.2.3 Status Output Connection
When option code /AL is speciied, connect the external
wiring as shown in Figure 5.4.
Shrouding Bolt
To conigure and activate the process alarm function and
Shrouding Bolt
F0501.ai status output, it is necessary to set some parameters.
Refer to each communication manual for procedures.
Figure 5.1 Shrouding Bolt
Transmitter
24V DC
terminal box Shielded cable
• Plug and seal an unused conduit connection. +
Distributor
– 250Ω
Magnetic
valve
External power
supply 30V DC,
120mA max
Use two-wire separately shielded cables. AC power supply
F0504.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<5. Wiring> 29
5.2.4 Connection Example for EJX910A and EJX930A
Table 5.1 The connection example for simultaneous analog and pulse and alarm, status output. (For HART
protocol type)
Connection Description
Analog Output Transmitter Electrical Terminal
Distributor
In this case, + 24V DC
Communication is SUPPLY +
possible (up to a distance – 250Ω
of 2km when a CEV cable –
*
is used.) PULSE B * Either B or +
Pulse Output Transmitter Electrical Terminal Use the Three-wire shielded cable.
Shielded Cable
In this case,
No communication is SUPPLY + E
possible.
–
* *1
PULSE B *2 R Electric counter
* Either B or +
Simultaneous
When analog and pulse output are used, the length of communication line is subjected to wiring conditions. Refer to 5
example 1 to 3.
Distributor (or communication medium : ex. EP card)
Analog
Wiring
Shielded Cable For the shielded cables in this example of
-Pulse Output *3 24V DC
flowmeter installation, use two-wire separately
Example 1 SUPPLY + shielded cables.
In this case, Communica – *2 R 250Ω
-tion is possible(up to a * E(10.5 to 30V DC) This supply voltage requires a power sourse
distance of 2km when a
PULSE B Counting input with a maximum output current of no less than
CEV cable is used). * Either B or + Common E/R.
Electric counter *1 (or communication medium : ex. EP card)
Transmitter Electrical Terminal
For the shielded cables in this
Example 2 Recorder or
example of flowmeter installation,
In this case, Communica Shielded Cable other instrument
use two-wire separately shielded
-tion is possible (up to a 250Ω cables.
distance of 200m when a
SUPPLY + *2
E(16.4 to 30V DC)
This supply voltage requires a power
CEV cable is used) and R
= 1kΩ). – R
Counting input sourse with a maximum output current
PULSE * of no less than E/R+25mA.
B Common
The supply voltage requires output
* Either B or +
Electric counter *1 impedance no more than 1/1000 of R
Transmitter Electrical Terminal (load resistance).
Recorder or
other instrument
Example 3 250Ω
In this case, No communi
-cation is possible (when SUPPLY + E(16.4 to 30V DC) This supply voltage requires
R*2 a power sourse with a
shielded cable is not used). – Counting input maximum output current of
* no less than E/R+25mA.
PULSE B Common
* Either B or + Electric counter *1
Transmitter Electrical Terminal
*1: To avoid the inluence of external noise, use an electric counter which its to the pulse frequency.
*2: Resistor is not necessary in case of an electric counter which can receive contact pulse signal directly.
*3: When using analog and pulse output simultaneously, the HART communication may be inluenced by noise comparing analog output only. Take
countermeasure for noise shown above, e.g. use shield cable etc.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<5. Wiring> 30
5.2.5 External Temperature Connection (2) Intrinsically Safe Type
(for EJX910A and EJX930A) With the intrinsically safe type, a safety barrier must be
Connect the RTD cable assembly to the Juck Terminal. included in the loop.
F0505.ai
Receiver
Figure 5.5 External Temperature Connection instrument
5.3 Wiring
Safety barrier F0508.ai
For details of the power supply voltage and load • Analog Output
resistance, see Section 5.6.
Hazardous Location Nonhazardous Location
(1) General-use Type and Flameproof Type
Transmitter terminal box Receiver instrument
• Analog Output Safety barreir (and power supply)
(Isolation type)
Hazardous Location Nonhazardous Location Power
supply
Transmitter terminal box Anaolg input
Distributor
(Power supply unit)
F0509.ai
Receiver
instrument • Simultaneous Analog-Pulse Output
Hazardous Location Nonhazardous Location
F0506.ai
Transmitter terminal box I/O module
Figure 5.6 Connection between Transmitter and Safety barrier
Distributor (Isolated type)
Power
• Pulse output and Alarm, Status Output or supply
Simultaneous Analog-Pulse Output
(for EJX910A and EJX930A)
Analog input
Hazardous Location Nonhazardous Location
Transmitter terminal box
Distributor Power
(Power supply unit) supply
F0507.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<5. Wiring> 31
5.3.2 Wiring Installation Gas sealing device
Non-hazardous area
(1) General-use Type and Intrinsically Safe
Type Flameproof flexible
metal conduit
With the cable wiring, use a metallic conduit or waterproof Hazardous area
glands. Flameproof Apply a non-hardening
heavy-gauge sealant to the threads of
• Apply a non-hardening sealant to the terminal box steel conduit these fittings for
connection port and to the threads on the lexible waterproofing
metal conduit for waterprooing.
Tee Seal fitting
Drain plug After wiring, impregnate the fitting
with a compound to seal tubing.
F0513.ai
Wiring
connection port and to the threads on the lameproof Two cable glands are attached.
packing adapter for waterprooing. Electrical connection
Cable gland
Flameproof packing
adapter
RTD cable
Flexible metal conduit with connector
F0515.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<5. Wiring> 32
• Components for the cable gland (4) Insert the RTD cable and irmly plug its connector into
The cable gland assembly consists of an entry, seal, the connecting port in the transmitter's terminal box.
running coupler, and backnut. Conirm that the seal is
attached inside the entry and that the thread size of the
cable gland is the same as that for the RTD electrical
connection.
1/2NPT Type
Running
Entry with Seal Coupler Backnut
F0519.ai
M20 Type
Running
Gasket Entry with Seal Coupler Backnut
F0520.ai
F0516.ai
(6) Turn the running coupler until the seal in the entry
comes into contact with the RTD cable.
CAUTION
Input/output signal is non-isolated.
Do not turn on power supply until you complete all the
wiring work.
Procedure
(1) Disassemble the cable gland: loosen the running
F0521.ai
coupler to separate the backnut from the entry.
(2) Remove the protection cap over the transmitter (7) Rotate the running coupler another half turn to
electrical connection and install the entry on the securely tighten the seal on the RTD cable.
electrical connection. Note that a non-hardening (8) Use a protection conduit, if necessary.
sealant should be applied to the threads for a 1/2 NPT In this case, insert the cable through the conduit and
connection and a gasket should be used for an M20 attach it to the Backnut.
connection.
CAUTION
After the cable is secured as explained above, do not
tighten the running coupler any further; to do so could
damage the RTD connection.
Do not pull the cable or subject it to excessive
mechanical shock.
F0517.ai
(3) Pass the RTD cable through the running coupler and
backnut assembly.
F0518.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<5. Wiring> 33
5.4.2 Connecting Shielded Cable for 5.4.3 Cable Connection RTD Terminal Box
Conduit Use (External temperature Side
input code: -B, -C, and -D) EJX multivariable transmitter RTD I/F is for 3-wire Type
• RTD connection components: EJX multivariable RTD, Pt100.
transmitter and RTD cable Heed the following when wiring an RTD of the 2- or 4-wire
type.
NOTE
Please note that a temperature error will occur when
you use a 2-wire RTD because of wiring resistance.
Please do not ground the shield on the RTD side of
F0522.ai the cable.
Procedure
(1) Remove the protection cap protecting the RTD CAUTION
electrical connection and insert the RTD cable.
Please use only the cables provided with this
instrument.
When wiring, be sure not to damage the cable's
insulation or its core.
All the cable cores must have suficient insulation
around them.
Do not let the signal line contact the shield line.
Do not allow the shield line or the signal line to come
F0523.ai the earth potential voltage.
(2) Remove the cap protecting the connecting port. Then
insert the RTD cable and irmly plug the connector
into the connecting port in the transmitter's terminal
2-Wire 3-Wire 4-Wire 5
box.
Wiring
(3) Insert the cable through the conduit and attach it to
the RTD electrical connection.
CAUTION A B A B b Aa B b
F0524.ai
Do not pull the cable or subject it to excessive Figure 5.13 The Method of Wiring for the RTD Side
mechanical shock.
Table 5.2 The Method of Wiring for the RTD Side
RTD Terminal
RTD Terminal A a B b
2-Wire White - Blue1 and Blue2 -
3-Wire White - Blue1 Blue2
4-Wire White open Blue1 Blue2
NOTE
The color display in the table shows the white line of
the cable.
The cable color could change depending on the cable
type.
Blue 1 and blue 2 allow changing places.
For 2-wire Type, connect either which is blue1 or
blue2, and give other side as OPEN.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<5. Wiring> 34
5.5 Grounding
Grounding is always required for the proper operation of
transmitters. Follow the domestic electrical requirements
as regulated in each country. For a transmitter with a
built-in lightning protector, grounding should satisfy
ground resistance of 10Ω or less.
Ground terminals are located on the inside and outside of
the terminal box. Either of these terminals may be used.
Ground terminal
(inside)
Ground terminal
(outside)
F0525.ai
600
External E–10.5
R= Communication
load 0.0244
applicable range
resistance BRAIN and HART
R (Ω)
250
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<6. Operation> 35
6. Operation
Verify and Change Transmitter
NOTE Parameter Setting and Values
For FOUNDATION Fieldbus and PROFIBUS PA The parameters related to the following items are set at
communication types and for the transmitter operating factory as speciied in order.
conirmation and zeroing by any communication • Calibration range
method, refer to manuals in the attached CD-ROM for • Integral indicator display
further information. • Output mode
• Software damping (optional)
Other parameters like following are shipped with the
default setting.
6.1 Preparation for Starting • Low-cut
Operation • Process alarm setting
• Static pressure range
• Signal characterizer
Conirming that Transmitter is Operating • Write protection
Properly To conirm or change the values, please refer to manuals
in the attached CD-ROM.
On the integral indicator
• If the wiring system is faulty, the display stays blank. Output Status Setting at CPU Failure and
• If the transmitter is faulty, an error code is displayed. Hardware Write Protection
Set the switches as shown in the igure below to set the
burn-out direction and write protection. The Burnout
switch is set to the H side for delivery (unless option code
/C1 or /C2 is speciied in the order), and the hardware
write protection switch is set to E side except EJX910A
and EJX930A. The setting of the switches can be
conirmed via communication.
6
Self-diagnostic error on the integral indicator
Slide switch
Operation
(Faulty transmitter) F0601.ai
Burnout Direction H L H L
Switch Position
Write Protection H L H L
Switch Position
E D E D
NO YES
Write Protection (Write enabled) (Write disabled)
F0602.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<6. Operation> 36
6.2 Zero Point Adjustment 6.2.2 Adjusting Zero Point for Gauge/
Absolute Pressure Transmitters
After completing preparations for operating the
transmitter, adjust the zero point.
(1) When you can obtain the Low Range Value
Zero point adjustment can be done by turning the from the actual measured value of 0%
transmitter’s zero-adjustment screw or by using the (0 kPa, atmospheric pressure);
communicator. This section describes the procedure
for the zero-adjustment screw. For the communicator For pressure measurement using gauge pressure
procedure, please refer to manuals in the attached transmitters, follow the steps below before performing
CD-ROM. zero point adjustment.
1) Close the tap valve (main valve).
IMPORTANT 2) Loosen the ill plug so that the pressure applied to the
transmitter is only the head of the seal liquid.
Do not turn off the power to the transmitter 3) Adjust the zero point at this status.
immediately after performing a zero point adjustment. 4) After the adjustment, close the ill plug and then
Powering off within 30 seconds of performing this gradually open the tap valve.
procedure will return the zero point to its previous
Use a slotted screwdriver to turn the zero-adjustment
setting.
screw. Turn the screw clockwise to increase the output or
counterclockwise to decrease the output. The zero point
6.2.1 Adjusting Zero Point for Differential adjustment can be made with a resolution of 0.01% of the
Pressure Transmitters setting range. Since the degree of the zero adjustment
varies with the screw turning speed, turn the screw slowly
Before adjusting zero point, make sure that the equalizing to make a ine adjustment and quickly to make a rough
valve is open. adjustment.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<6. Operation> 37
6.3 Local Parameter Setting 6.3.1 Local Parameter Setting (LPS)
Overview
WARNING Parameter coniguration by the external adjustment
screw and push button (integral indicator code E) offers
The local push button on the integral indicator must easy and quick setup for parameters of Tag number, Unit,
not be used in a hazardous area. When it is necessary LRV, URV, Damping,Output mode (linear/square root),
to use the push button, operate it in a non- hazardous Display out 1, and Re-range by applying actual pressure
location. (LRV/URV). There is no effect on measurement signal
(analog output or communication signal) when Local
Parameter Setting is carried out.
IMPORTANT
• Do not turn off the power to the transmitter
immediately after performing parameter setting.
Powering off within 30 seconds of performing this
procedure will return the parameter to its previous
setting. External adjustment
• The parameter of Ext SW must be“Enabled” screw cover
to perform this configuration. See the user’s
manual IM 01C25T (HART/BRAIN) for the setting F0604.ai
procedure.
Figure 6.3 External Adjustment Screw
• The Local Parameter Setting function is available
with HART or BRAIN communication type.
Integral indicator
Push-button
F0605.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<6. Operation> 38
screw
push
Process
Measurement Zero adjustment
Display
*
2. Press Unit Edit Press unit Save/Cancel the value
push *
3. Press LRV Edit Press LRV Save/Cancel the value
*
4. Press URV Edit Press URV Save/Cancel the value
push *
5. Damping Time Edit Damping time Save/Cancel the value
*
6. Output Mode Edit Output mode Save/Cancel the value
push *
7. Display Out1 Edit Display Out1 Save/Cancel the value
push
9. URV-Apply Press Set URV Save/Cancel the value
Process
Measurement
Display F0606.ai
*Note that the above 1 to 7 parameter conigurations are available with the software revision (SOFT REV)2.03 or later.
Software revision can be checked via a ield communicator (HART/BRAIN) or DTM. Please refer to IM 01C25T01 for HART parameter
“Software rev” and IM 01C25T03 for BRAIN “SOFT REV”.
Figure 6.5
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<6. Operation> 39
6.3.2 Activating Local Parameter Setting 6.3.3 Parameter Setting Review
Press the push button on the integral indicator to activate Current setting value for the below parameters are shown
the Local Parameter Setting mode. The transmitter will sequentially by each press of the push button.
exit automatically from the Local Parameter Setting mode Tag number, Unit, LRV, URV, Damping,Output mode
if no operation is carried out for 10 minutes. (linear/square root), Display out 1.
Process
Measurement
Display
push
push
push
push
push
push
push
push
push Process
Measurement
Display
F0607.ai
To conigure each parameter value, turn the external adjustment screw on each parameter screen after activating the Local
Parameter Setting mode.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<6. Operation> 40
6.3.4 Tag Number Coniguration
Tag Number is edited by turning the external adjustment screw. Up to 8 alphanumeric characters for HART or 16
alphanumeric characters for BRAIN can be set.
Save ?/
Cancel ?
Blinking Blinking
Set all other
characters in the
Go to the next Character same way
Change the first Character
screw
push
F0608.ai
Save ?/
Cancel ?
Blinking Blinking
[Available pressure units]
Select by the push button
kPa bar inH2O@4degC(39.2degF)
Torr mbar inH2O@20degC(68degF)
atm g/cm2 inHg
MPa kg/cm2 ftH2O@4degC(39.2degF)
screw hPa Pa ftH2O@20degC(68degF)
push mmHg mmH2O@4degC(39.2degF)
psi mmH2O@20degC(68degF)
In addition to the above units, mmAq@4degC,
mmAq@20degC, mmWG@4degC and mmWG@20degC
are available for BRAIN communication type.
F0609.ai
Save ?/
Cancel ?
push
F0610.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<6. Operation> 41
6.3.7 Re-range by applying actual 6.3.8 Save or Cancel
pressure (LRV/URV). At the end of each parameter setting, select “Save” or
This feature allows the lower and upper range values to “Cancel” by the external adjustment screw and press the
be setup with the actual input applied. push button to save or cancel the coniguration.
Save or Cancel
Follow the procedure below to change the LRV and URV After push
parameter screw
settings. setting
[Example]
Rerange LRV to 0 and URV to 3 MPa.
1) Connect the transmitter and apparatus and warm it up
for at least ive minutes. Cancel? Canceled
2) Press the push-button. The integral indicator then
push
displays “LRV.SET.”
3) Apply a pressure of 0 kPa (atmospheric pressure) to F0612.ai
F0613.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
<6. Operation> 42
6.3.9.2 Abort Coniguration (Parameter)
To exit the coniguration while editing the value, hold
down the button for over 2 seconds and select “Save” or
“Cancel”.
6.3.11 Others
• Difference between BRAIN and HART
HART BRAIN
Up to 8 Up to 16
Tag Number characters can characters can
be set be set
“TRNS.FC” “OUT.MOD”
Output Mode
shown on the shown on the
(Linear/Sq root)
integral indicator integral indicator
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
The table below shows a summary of error messages for BRAIN and HART (protocol revision 5) protocols.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
8. Parameter Summary
NOTE IMPORTANT
For HART protocol revision 7, FOUNDATION Fieldbus If the transmitter is turned off within 30 seconds after
and PROFIBUS PA communication types, and parameters have been set, the set data will not be
EJX910A/EJX930A, please refer to manuals in the stored and the terminal returns to previous settings.
attached CD-ROM.
Menu Tree for HART Protocol Revision 5 (Except EJX910A and EJX930A)
(Device setup) (Process variables) (Diag/Service)
1 Process variables 1 Pres 1 Test device 1 Status 1 Status group 1
2 Pres % 2 Self test 2 Status group 2
3 AO 3 Status group 3
4 SP 4 Status group 4
5 SP % 5 Status group 5
6 Snsr temp 6 Status group 6
7 Engr Disp 7 Status group 7
8 Engr exp 8 Status group 8
9 Engr Unit 9 Status group 9
2 Loop test
2 Diag/Service 1 Keypad input
1 Re-range 2 Apply values
(Basic setup)
3 Calibration 1 D/A trim
1 Tag 2 Analog output trim
3 Basic setup 2 Scaled D/A trim
2 Unit 3 Clear D/A trim
1 Keypad input
3 Re-range 2 Apply values 1 Pres Zero trim
2 Pres trim
4 Device information 1 Date 3 Pres sensor trim 3 P LTP
2 Descriptor
4 P UTP
3 Message
4 Write Protect 5 Pres trim info.
1 Keypad input
2 Re-range 2 Apply values
3 Unit
4 Xfer fnctn 1 T.Z. Cmp mode
5 Pres Damp 2 Temp Zero
6 Low cut
7 Low cut mode
8 H/L Swap
1 Pres
9 Bi-dir mode
2 Pres %
Quick resp
3 AO
T.Z. Cmp menu
4 SP
S.C. menu
5 SP %
1 S.C. 6 Snsr temp 1 Loop test
5. Review
2 Num of points 7 Engr Disp 2 D/A trim
3 Point setting 8 Engr exp 3 Scaled D/A trim
9 Engr Unit 4 Clear D/A trim
1 Process variables Digital Output 5 AO alm typ
3 Output condition
6 Auto recover
Hot Key 2 Analog output 7 AO lower limit
8 AO upper limit
1 Keypad Input 1 LRV 1 Poll addr
2 URV 3 HART output 2 Num req preams 1 Pres Alert mode
3 Unit 3 Burst mode 2 Config Pres Alerts
4 LSL 4 Burst option 3 SP Alart mode
5 USL 4 Config SP Alerts 1 Digital Output
6 Min Span 4 Process Alerts 5 Temp Alert mode 2 DO Select
6 Config Temp Alerts 3 DO Signal type
1 Write protect 1 Disp Out 1 7 DO Config 4 DO Test
1 Disp select
2 Enable wrt 10min 4 Display condition 2 Disp Out 2
2 Wrt protect menu
3 New password 3 Disp Out 3
4 Software seal 4 Disp Out 4
1 Disp Pres % fnctn
2 Disp Pres % Reso 1 Tag
2 P disp condition 2 Date
3 Pres disp point
3 Descriptor
3 SP disp condition 1 Engr LRV 4 Message
2 Engr URV 5 Model 1
4 Engr disp range 3 Engr exp 6 Model 2
4 Engr Unit 7 Model 3
5 Bar Indicator 5 Engr point 8 Write Protect 1 Universal rev
6 Set Engr Unit 9 Ext SW 2 Fld dev rev
1 Field device info
5 Device information 7 Modify Engr Unit 3 Software rev
2 Sensor information Revision #s
6 Test Key 3 Self test Additional Info
F0801-1.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
A
4 Diag Parameters
1 Lim fDPmax
2 Lim fDPmin
2 Configuration 1 Set Diag Mode
3 Lim fSPlmax
2 Diag Period
4 Lim fSPlmin
3 Diag Lim
5 Lim fSPhmax
6 Lim fSPhmin
7 Lim BlkFmax
8 Lim BlkFmin
9 Lim DPAvgmax
a Lim DPAvgmin
1 Diag Description
4 Diag Reference
2 Ref fDP
5 Diag Supp Count
3 Ref fSPl
4 Ref fSPh
5 Ref BlkF
6 Ref BlkF
Parameter Summary
1 Diag Out Option
5 Diag Output
2 Diag Fixed Out Val
F0801-2.ai
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Upload
data
No. Parameter name Item R/W*1 Content Default value
F P L
01 MODEL Model R EJX (for EJX series) —
EJA (for EJA series)
02 TAG No. Tag number R As speciied —
03 SELF CHECK Self-diagnostics R GOOD —
A DISPLAY Measured data display
A10 OUTPUT Output (in %) R -2.5 to 110% —
A11 PRES Measured pressure R Unit speciied in C20 —
after zero adjustment
A15 OUTPUT mA Output current R 3.6000 to 21.600 mA —
A16 ENGR. OUTPUT User scaled value R Unit speciied in I30 —
A17 ENGR. EXP Exponents R Unit speciied in I32 —
A20 SP % Static pressure (in %) R -10 to 110% — —
A21 SP Static pressure after R Unit speciied in D30 — —
zero adjustment
A30 CAPSULE TEMP Capsule temperature R Unit speciied in D40 —
A60 SELF CHECK Self-diagnostics R Refer to Table 4.1 Alarm —
Message Summary
B SENSOR TYPE Sensor type
B10 MODEL Model and capsule type R Model and capsule type —
B11 STYLE NO. Style number R Style number of product —
B20 PRES LRL Lower range limit R Unit speciied in C20 —
B21 PRES URL Upper range limit R Unit speciied in C20 —
B22 P MIN SPAN Minimum span R Unit speciied in C20 —
B30 SP LRL Lower range limit for R Unit speciied in D30 — —
static pressure
B31 SP URL Upper range limit for R Unit speciied in D30 — —
static pressure
B32 SP MIN SPAN Minimum span for static R Unit speciied in D30 — —
pressure
B60 SELF CHECK Self-diagnostics R See A60 —
C BASIC SETUP Setting data
C10 TAG NO. Tag number W 16 alphanumeric characters As speciied
C20 PRES UNIT Measurement range W mmH2O, mmAq, mmWG, kPa
unit mmHg, Torr, kPa, MPa,
mbar, bar, gf/cm2, kgf/cm2,
inH2O, inHg, ftH2O, psi,
atm, Pa, hPa
C21 PRES LRV Lower range value W -32000 to 32000 within As speciied
measurement range
C22 PRES URV Upper range value W -32000 to 32000 within As speciied
measurement range
C23 PRES POINT Decimal place W 0 to 4 2
C30 AMP DAMPING Damping time constant W 0.50 (0.00) to 100.00 sec, 2.00 sec or as
at ampliier see D50 speciied
C40 OUTPUT MODE Output mode W LINEAR or SUQARE ROOT LINEAR or as
speciied
C60 SELF CHECK Self-diagnostics R See A60 —
*1: R/W: R = Read only, W = Read & Write
*2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Speciications section in each user’s manual.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Upload
data
No. Parameter name Item R/W*1 Content Default value
F P L
D AUX SET 1 Auxiliary setting data 1
D10 LOW CUT Low cut W 0.00 to 20.00% 10.00%
D11 LOW CUT MODE Low cut mode W LINEAR or ZERO LINEAR
D15 H/L SWAP Impulse piping W NORMAL or REVERSE NORMAL —
accessing direction
D16 H2O UNIT SEL H2O unit select W @4degC or @20degC @4degC
(68.0F)
D20 OUT LIMIT (L) Low side output limiter W -2.50 to 110.00% -2.50%
D21 OUT LIMIT (H) High side output limiter W -2.50 to 110.00% 110%
D22 REV OUTPUT Output reversal W NORMAL or REVERSE NORMAL
D25 BURNOUT CPU error R HIGH or LOW —
D26 ERROR OUT Hardware error W BURNOUT DIR or HOLD BURNOUT DIR
D30 SP UNIT Static pressure unit W See C20 MPa —
D31 SP A/G SLCT Gauge/Abs select for W GAUGE or ABSOLUTE ABSOLUTE —
static pressure
D32 ATM. PRESS Coeficient for given W Unit speciied in D30 0.10133 MPa —
gauge pressure
D33 SP LRV Lower limit of static W -32000 to 32000 within 0.0 MPa —
pressure measurement range
D34 SP URV Upper limit of static W -32000 to 32000 within —
pressure*2 measurement range
D35 SP POINT Decimal place of static W 0 to 4 1 —
pressure
D36 SP DAMPING Damping time constant W 0.00 to 100.00 sec 2.00 sec —
of SP
D37 SP SELECT H/L select for static W HIGH or LOW HIGH —
pressure
D40 TEMP UNIT Temperature setting W degC, degF, or K degC
unit
D50 QUICK RESP Quick response W OFF or ON (enable 0.00 to OFF
0.50 sec at C30)
D55 WRT PROTECT Write protect indicator R NO or YES NO —
D56 WRT ENABLE Write protect release W 8 alphanumeric characters None —
D57 NEW PASSWORD User set password for W 8 alphanumeric characters None —
write protect
D58 SOFTWR SEAL Software seal R BREAK or KEEP KEEP —
D60 SELF CHECK Self-diagnostics R See A60 —
E AUX SET 2 Auxiliary setting data 2
E10 T. ZERO CMP Temperature W OFF or ON OFF —
8
compensation mode
Parameter Summary
E11 TEMP ZERO Zero shift compensation W -99.999 to 99.999%/degC 0.000%/degC —
E30 BI DIRE MODE Bidirectional mode W OFF or ON OFF —
E50 DO SELECT Contact output select W INHIBIT, PRES, SP, TEMP, INHIBIT —
PRES/SP, PRES/TEMP,
SP/TEMP, or PRES/SP/
TEMP
E51 DO SIG. TYPE Signal type select W OFF WHEN ALARM or ON ON WHEN ALARM —
WHEN ALARM
E52 D OUTPUT Contact output R OFF or ON OFF —
E60 SELF CHECK Self-diagnostics R See A60 —
*1: R/W: R = Read only, W = Read & Write
*2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Speciications section in each user’s manual.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Upload
data
No. Parameter name Item R/W*1 Content Default value
F P L
G ALARM SET Alarm setting
G10 P AL MODE Alert mode W INHIBIT, HI. AL DETECT, INHIBIT —
LO. AL DETECT, or HI/LO.
AL DETECT
G11 P HI. AL VAL High side alert value W -32000 to 32000, unit 100.000 kPa —
speciied in C20
G12 P LO. AL VAL Low side alert value W -32000 to 32000, unit -100.000 kPa —
speciied in C20
G20 SP AL MODE Static pressure alert W INHIBIT, HI. AL DETECT, INHIBIT — —
mode LO. AL DETECT, or HI/LO.
AL DETECT
G21 SP HI. AL VAL High side alert value of W -32000 to 32000, unit — —
SP*2 speciied in D30
G22 SP LO. AL VAL Low side alert value W -32000 to 32000, unit 0.00000 MPa — —
of SP speciied in D30
G30 T AL MODE Temperature alert mode W INHIBIT, HI. AL DETECT, INHIBIT —
LO. AL DETECT, or HI/LO.
AL DETECT
G31 T HI. AL VAL High side alert value of W -50 to 130 120 degC —
temperature
G32 T LO. AL VAL Low side alert value of W -50 to 130 -40 degC —
temperature
G50 AUTO RECOVER Auto-recover from W OFF or ON ON —
sensor error
G60 SELF CHECK Self-diagnostics R See A60 —
H AUTO SET Automatic setup
H10 AUTO P LRV Lower range value auto W -32000 to 32000, unit As speciied —
setup speciied in C20
H11 AUTO P URV Upper range value auto W -32000 to 32000, unit As speciied —
setup speciied in C20
H20 AUTO SP LRV SP lower range value W -32000 to 32000, unit 0.00000 MPa — —
auto setup speciied in D30
H21 AUTO SP URV SP upper range value W -32000 to 32000, unit — —
auto setup*2 speciied in D30
H60 SELF CHECK Self-diagnostics R See A60 —
I DISP SET Display setting
I10 DISP OUT1 LCD output 1 W PRES, PRES %, ENGR. PRES %
PRES, SP, or SP %
I11 DISP OUT2 LCD output 2 W PRES, PRES %, ENGR. ---
PRES, SP, SP %, or ---
I12 DISP OUT3 LCD output 3 W See I11 ---
I13 DISP OUT4 LCD output 4 W See I11 ---
I20 P DISP MODE % display mode W LINEAR or SQUARE ROOT LINEAR
I21 PRES % RESO % display resolution W NORMAL or HIGH NORMAL
RESOLUTION
I30 ENGR. UNIT User set engineering W 8 alphanumeric characters
unit
I31 EASY EU SET Engineering unit select W —
I32 ENGR. EXP Exponents W ---, ×10, ×100, ×1000 ---
I33 ENGR. LRV User set lower range W -32000 to 32000, unit 0.00
limit speciied in I30
I34 ENGR. URV User set upper range W -32000 to 32000, unit 100.00
limit speciied in I30
I35 ENGR. POINT Decimal place of user W 0 to 4 1
set
I40 BAR INDICATR Bar indicator W OFF or ON ON
I41 POWER ON INF Display when powering W OFF or ON ON —
on
I60 SELF CHECK Self-diagnostics R See A60 —
*1: R/W: R = Read only, W = Read & Write
*2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Speciications section in each user’s manual.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Upload
data
No. Parameter name Item R/W*1 Content Default value
F P L
J ADJUST Adjusting data
J09 ADJ UNIT Pressure adjusting unit W % or PRES UNIT PRES UNIT —
select
J10 ADJ PRES Adjustment reference R Unit speciied in J09 —
pressure
J11 P ZERO ADJ Automatic zero W -32000 to 32000, unit 0.00000 kPa —
adjustment speciied in J09
J12 P SPAN ADJ Automatic span W -32000 to 32000, unit 100.000 kPa —
adjustment speciied in J09
J15 P ZERO DEV Manual zero adjustment W -32000 to 32000, unit 100.000 kPa —
speciied in J09
J16 P SPAN DEV Manual span W -32000 to 32000, unit 100.000 kPa —
adjustment speciied in J09
J20 ADJ SP Adjustment reference R Unit speciied in J09 — —
pressure of SP
J21 SP ZERO ADJ Automatic SP zero W -32000 to 32000, unit 0.00000 MPa — —
adjustment speciied in J09
J22 SP SPAN ADJ Automatic SP span W -32000 to 32000, unit — —
adjustment*2 speciied in J09
J25 SP ZERO DEV Manual SP zero W -32000 to 32000, unit 0.00000 MPa — —
adjustment speciied in J09
J26 SP SPAN DEV Manual SP span W -32000 to 32000, unit 0.00000 MPa — —
adjustment speciied in J09
J40 OUTPUT 4mA 4 mA adjustment W -10.000 to 10.000% 0.000% —
J41 OUTPUT 20mA 20 mA adjustment W -10.000 to 10.000% 0.000% —
J45 AMP TEMP Ampliier temperature R Unit speciied D40 0 degC —
J50 ADJ WHO Adjustment information W 8 alphanumeric characters —
J51 ADJ DATE Adjustment information W 16 alphanumeric characters —
J52 ADJ LOC Adjustment information W 8 alphanumeric characters —
J53 ADJ DESC Adjustment information W 16 alphanumeric characters —
J55 EXT ZERO ADJ External zeroing W INHIBIT or ENABLE ENABLE —
permission
J56 CLEAR ADJ Clear adjustment W ---, PRES, SP, 4-20mA, or --- —
ALL
J60 SELF CHECK Self-diagnostics R See A60 —
K TEST Test parameters
K10 OUTPUT X % Test output % setting W Within a range between 0.00% —
D20 and D21
K40 DO TEST Test contact output W OFF or ON OFF — 8
K45 TEST TIME “OUTPUT X %” and W 10 min, 30 min, 60 min, 10 min —
“DO TEST” duration 3 hour, 6 hour, 12 hour
Parameter Summary
time selection
K50 TEST KEY1 Special maintenance W —
parameter
K51 TEST KEY2 Special maintenance W —
parameter
K52 TEST KEY3 Special maintenance W —
parameter
K53 TEST KEY4 Special maintenance W —
parameter
K60 SELF CHECK Self-diagnostics R See A60 —
M DEVICE INFO Device information
M10 SERIAL NO. Serial number R —
M11 MFTR. DATE Manufactured date R —
M12 EXTRA NO. Customization number R —
M15 SOFT REV Software revision R —
M16 BRAIN REV BRAIN protocol revision R —
M17 MEMO1 Memo W 16 alphanumeric characters —
M18 MEMO2 Memo W 16 alphanumeric characters —
M19 MEMO3 Memo W 16 alphanumeric characters —
*1: R/W: R = Read only, W = Read & Write
*2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Speciications section in each user’s manual.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Upload
data
No. Parameter name Item R/W*1 Content Default value
F P L
M20 ISOL MATL Capsule material W —
M21 FILL FLUID Fill luid W —
M22 GASKET MATL Gasket material W —
M23 PRO CON MATL Flange material W —
M24 D-VENT MATL Vent plug material W —
M25 PRO CON TYPE Process connection W —
type
M26 RS ISOL MATL Remote seal material W —
M27 PRO CON SIZE Flange size W —
M28 NUM RS Number of remote seal W —
M29 RS FILL FLUID Fill luid of remote seal W —
M30 RS TYPE Remote seal type W —
M50 MS CODE 1 Model and sufix code 1 W —
M51 MS CODE 2 Model and sufix code 2 W —
M52 MS CODE 3 Model and sufix code 3 W —
M53 MS CODE 4 Model and sufix code 4 W —
M54 MS CODE 5 Model and sufix code 5 W —
M55 MS CODE 6 Model and sufix code 6 W —
M60 SELF CHECK Self-diagnostics R See A60 —
P Record History of errors
P10 ERROR REC 1 Last error W See A60 GOOD —
P12 ERROR REC 2 Second recent error W See A60 GOOD —
P14 ERROR REC 3 Third recent error W See A60 GOOD —
P16 ERROR REC 4 Forth recent error W See A60 GOOD —
P60 SELF CHECK Self-diagnostics R See A60 —
T CHARACTERIZR Signal characterizer
setting
T10 S. C. ENABLE Signal characterizer W INHIBIT or ENABLE INHIBIT —
permission
T11 NUM OF POINT Number of coordinates W 0 to 9 0 —
T20 X START (FIX) Start point of X R 0.00% —
T21 Y START (FIX) Start point of Y R 0.00% —
T22 X1 Coordinate 1 of X W 0.00 to 100.00% 10.00 —
T23 Y1 Coordinate 1 of Y W 0.00 to 100.00% 10.00 —
T24 X2 Coordinate 2 of X W 0.00 to 100.00% 20.00 —
T25 Y2 Coordinate 2 of Y W 0.00 to 100.00% 20.00 —
T26 X3 Coordinate 3 of X W 0.00 to 100.00% 30.00 —
T27 Y3 Coordinate 3 of Y W 0.00 to 100.00% 30.00 —
T28 X4 Coordinate 4 of X W 0.00 to 100.00% 40.00 —
T29 Y4 Coordinate 4 of Y W 0.00 to 100.00% 40.00 —
T30 X5 Coordinate 5 of X W 0.00 to 100.00% 50.00 —
T31 Y5 Coordinate 5 of Y W 0.00 to 100.00% 50.00 —
T32 X6 Coordinate 6 of X W 0.00 to 100.00% 60.00 —
T33 Y6 Coordinate 6 of Y W 0.00 to 100.00% 60.00 —
T34 X7 Coordinate 7 of X W 0.00 to 100.00% 70.00 —
T35 Y7 Coordinate 7 of Y W 0.00 to 100.00% 70.00 —
T36 X8 Coordinate 8 of X W 0.00 to 100.00% 80.00 —
T37 Y8 Coordinate 8 of Y W 0.00 to 100.00% 80.00 —
T38 X9 Coordinate 9 of X W 0.00 to 100.00% 90.00 —
T39 Y9 Coordinate 9 of Y W 0.00 to 100.00% 90.00 —
T40 X END (FIX) End point of X R 100.00% —
T41 Y END (FIX) End point of Y R 100.00% —
T60 SELF CHECK Self-diagnostics R See A60 —
*1: R/W: R = Read only, W = Read & Write
*2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Speciications section in each user’s manual.
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
53
Revision Information
Title : EJX and EJA-E Series
Differential Pressure and Pressure Transmitters Installation Manual
Manual No. : IM 01C25A01-01E
IM 01C25A01-01E
Downloaded from https://www.rsmanuals.com
Blank Page
Downloaded from https://www.rsmanuals.com
[System Requirements]
for Windows
OS : Microsoft Windows XP (Professional), Microsoft Windows 7
CPU : Pentium 300 MHz or higher
RAM : 128 MB or more
Display : 800 × 600 SVGA or higher, 256 colors
[Contents]
This CD-R contains information in PDF format that is necessary for safe and effective operation of the product.
[Trademarks]
Microsoft, MS-DOS, Windows and Windows NT are either registered trademarks or trademarks of Microsoft
Corporation in the United States and/or other countries.
Other company and product names are trademarks or registered trademarks of their respective holders.
WARNING: This CD contains software, and is for use in a computer only. Do not play this on
an audio CD player, as the high volume may damage your hearing or audio speakers.
YOKOGAWA EUROPE B. V.
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
Phone : 31-88-4641000 Fax : 31-88-4641111
Oct. '13
Printed in Japan