ESP CALCULATION SHEET

EWPS-10 - RESIDENTIAL BUILDING 1&2

Location FIRST FLOOR


Unit Ref FCU-09

Air Flow (L/S) 82


Specified ESP (Pa) 125 (As per IFC)

Calculated ESP (Pa) 13


SIZE OF THE DUCT DUCT VELOCITY REMARKS
VELOCITY COEFFICIENT Pressure
Air Flow Eq. Dia FRICTION
PRESSURE LOSS Drop
SR. No. DESCRIPTION WIDTH HEIGHT LENGTH LENGTH Actual Round
ASHRAE FITTING REF
mm mm mm m L/S m/s m/s Pa mm Pa/m Pa

1 Straight Duct 400 100 150 0.15 82 2.1 2.4 2.5 211 0.43 0.10 CR11-1
400 100 82 2.1 2.4 2.52 211 0.43 0.45
2 Transition 350 0.35 1.00 SR4-2
300 200 82 1.4 1.4 1.12 269 0.13 0.20

3 Supply Register (SR-2) 300 200 - 82 1.4 1.4 1.1 269 0.13 3.00 From catalogue
4 Return Register (RR-1) 200 150 - 57 1.9 2.0 2.2 190 0.36 8.00 From catalogue
5 Straight Duct 200 150 100 0.10 57 1.9 2.0 2.2 190 0.36 0.00 CR11-1
6 Plenum Box 460 200 540 0.54 57 0.6 0.7 0.2 328 0.03 0.10

ESP Calculated (Pa) 12.200

10% Margin 1.22

Total ESP (Pa) 13.42