Typical Laboratory Retrofit

Project Submittal Package 2021/09/07

Typical Laboratory Retrofit

Sales Rep
Antec Controls by Price

Consulting Engineer
Antec Controls by Price
Typical Laboratory Retrofit

Schedule 2021/09/07

Valve and Controller Schedule

MIN Unoccupied Flow

Actuator Fail Position

Enclosure Assembly
Actuator Response

Calibration Method
Connection Type

Actuator Control
Pressure Range

Control Type
Room Offset

VA Required
Accessories
Valve Model

Application

Orientation
Body Type
MAX Flow

Insulation
Valve Tag

MIN Flow
Unit Size

Controls

Quantity
Coating
Room

(CFM)

(CFM)

(CFM)

(CFM)

Notes
VVR SAV-R Laboratory SAV 114 2150 1280 1280 200 - M - - - - - PACE VDC HSA FLP - ENCL FLDC 41.0 1 1, 2, 3
VVR GEV-R Laboratory GEV 114 2150 530 530 200 - M - - - - - PACE VDC HSA FLP - ENCL FLDC 41.0 1 1, 2, 3
VVR FEV-R-1 Laboratory FEV 108 400 100 0 200 - M - - - - - FVM VDC HSA FLP - ENCL FLDC 40.0 1 1, 2, 3
VVR FEV-R-2 Laboratory FEV 108 400 100 0 200 - M - - - - - FVM VDC HSA FLP - ENCL FLDC 40.0 1 1, 2, 3
Nomenclature:
108 8" Diameter - Single Body 114 14" Diameter - Single Body ENCL Controller Enclosure Assembly
FEV Fume Hood Exhaust Valve FLDC Field Calibrated Curve FLP Fail Last Position
FVM Fume Hood Valve Module GEV General Exhaust Valve HSA High Speed Actuator
M Medium Pressure (0.6 to 3.0 in.w.c) PACE PACE Controller SAV Supply Air Valve
VDC Modulating (0-10 VDC) Actuator VVR Venturi Valve Retrofit

Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
3. VA Draw for all valves in above schedule includes power requirement for Controls and Actuator.
Typical Laboratory Retrofit

Schedule 2021/09/07

Controller Schedule

Valve Body Number


Mounting Config.
Controller Model

VA Required
Valve Type
Valve Tag

Quantity
Room

Notes
CAVA FEV-R-1 Laboratory - - - 12.0 1 1, 2
CAVA FEV-R-2 Laboratory - - - 12.0 1 1, 2
Nomenclature:
CAVA Cava Touchscreen Fume Hood Controller

Notes:
1. Installation and wiring of equipment by Others.
2. See ProdSubmittal for option details.
Typical Laboratory Retrofit

Schedule 2021/09/07

ES Schedule
Room Control Accessories

Setpoint Adjustment

Relative Humidity

Carbon Dioxide
Display Type
Sensor Type
Room Name

Occupancy
Valve Tag

Quantity
Model

Notes
ES SAV-R Laboratory RM LCD BTN 1 1, 2
ES SAV-R Laboratory DT 1 1, 2
Nomenclature:
BTN Pushbutton Setpoint Adjustment
DT Duct Mounted Sensor
ES Environmental Sensor
LCD LCD Display
RM Room Temperature Sensor

Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
Typical Laboratory Retrofit

Schedule 2021/09/07

POT Schedule
Retrofit Accessories Model

Quantity

Notes
Type

POT SPR 1 1, 2
Nomenclature:
POT Potentiometer
SPR Standard Potentiometer Replacement

Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
Typical Laboratory Retrofit

Schedule 2021/09/07

Fume Hood Accessories Schedule


Accessories Model

Retrofit Accessory

Mounting Config
Sash Length

VA Required
Valve Type
Valve Tag

Quantity
Room

Notes
SPS FEV-R-1 Laboratory 50 - - - - 1 1, 2
SPS FEV-R-2 Laboratory 50 - - - - 1 1, 2
SVS FEV-R-1 Laboratory - - - - 17.0 1 1, 2
FPS FEV-R-1 Laboratory - MP8 - - 10.0 1 1, 2
Nomenclature:
FPS Fume Hood Presence Sensor
MP8 Mounting Plate - 8.25" Hole Spacing
SPS Sash Position Sensor
SVS Sidewall Velocity Sensor

Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
VVR-1-X
Venturi Valve Retrofit Kit Sheet 1 of 2

270213
Rev.F
Product Submittal 2022/01/04

VVR SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)

.060in (2mm) GALV STEEL,


MOUNTING PLATE TO BE MOUNTED IN THE FIELD DIRECTLY ON RETROFIT VALVE,
NO MOUNTING HARDWARE INCLUDED

SINGLE VALVE DUAL VALVE

5.0" (127)

5.0" (127)

11.5" (292) 11.5" (292)

2.9" (74) 7.0" (178)

MOUNTING SPECIFICATIONS:

SINGLE VALVE DUAL VALVE TRIPLE VALVE*


*COMBINATION OF SINGLE VALVE AND
CONTROLLER ENCLOSURE, DUAL VALVE RETROFIT KITS.
OPTIONAL
3.0" (76) CONTROLLER CONTROLLER
13.5" (343) ENCLOSURE, ENCLOSURE,
OPTIONAL OPTIONAL

5.5" (140)

PRESSURE RANGE OPTIONS:


MEDIUM PRESSURE (M) - 0.6 to 3.0 in.w.c. (150-750 Pa), MEASURED ACROSS VALVE

LOW PRESSURE (L) - 0.3 to 3.0 in.w.c. (75-750 Pa), MEASURED ACROSS VALVE

ACTUATOR FAIL SAFE OPTIONS: ACTUATOR CONTROL OPTIONS:


FAIL IN PLACE (FLP) VDC CONTROL SIGNAL (VDC)
FAIL OPEN POSITION (FOP)
2-POSITION CONTROL SIGNAL (2P)
FAIL CLOSED POSITION (FCP)
CONTROLLER ENCLOSURE OPTIONS:
ACTUATOR SPEED OPTIONS:
CONTROLLER ENCLOSURE ASSEMBLY (ENCL),
STANDARD SPEED (SSA), FLP ONLY
PACE, FVM or LMX ENCLOSURE MOUNTED
HIGH SPEED (HSA)
Solid Edge

NOTE: PLEASE REFER TO PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

© Copyright Antec Controls by PRICE 2022


VVR-1-X
Venturi Valve Retrofit Kit Sheet 2 of 2

270213
Rev.F
Product Submittal 2022/01/04

ACTUATOR REFERENCE CHART

ACTUATOR
UNIT ACTUATOR ACTUATOR
FAIL PART # QTY
SIZE CONTROL RESPONSE
POSITION
SSA 019127-002 1
FLP
VDC 019127-001 1
HSA
FOP/FCP 019127-003 1
108
SSA 019128-001 1
FLP
2P 019128-003 1
HSA
FOP/FCP 019127-007 1
SSA 019127-002 1
FLP
VDC 019127-001 1
HSA
FOP/FCP 019127-003 1
110
SSA 019128-001 1
FLP
2P 019128-003 1
HSA
FOP/FCP 019127-007 1
SSA 019127-005 1
FLP
VDC 019127-004 1
HSA
FOP/FCP 019127-003 1
112
SSA 019128-002 1
FLP
2P 019128-009 1
HSA
FOP/FCP 019127-007 1
SSA 019127-005 1
FLP
VDC 019127-004 1
HSA
FOP/FCP 019127-003 1
114
SSA 019128-002 1
FLP
2P 019128-009 1
HSA
FOP/FCP 019127-007 1
SSA 019127-005 1
FLP
VDC 019127-004 1
HSA
FOP/FCP 019127-003 1
210
SSA 019128-002 1
FLP
2P 019128-009 1
HSA
FOP/FCP 019127-007 1
SSA 019127-005 1
FLP
VDC 019127-004 1
HSA
FOP/FCP 019127-003 1
212
SSA 019128-002 1
FLP
2P 019128-009 1
HSA
FOP/FCP 019127-007 1
SSA 019127-005 1
FLP
VDC 019127-006 1
HSA
FOP/FCP 019127-003 1
214
SSA 019128-002 1
FLP
2P 019128-009 1
HSA
FOP/FCP 019127-007 1

NOTE: SEE VALVE ACTUATOR PRODUCT SUBMITTAL FOR ACTUATOR SPECIFICATIONS.


Solid Edge

NOTE: PLEASE REFER TO PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 1 of 10

270117
Product Submittal Rev. O
2022/07/21

PACE SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)
24 VAC, 50/60 Hz SINGLE PHASE, 75 VA MAX (18 VA EXCLUDING EXTERNAL
INPUT POWER
LOADS), CLASS 2 or LPS PELV

2 BINARY INPUTS (CONTACT CLOSURE),


4 ANALOG INPUTS (0 to 10 VDC),
2 10K TYPE 2 THERMISTORS INPUTS,
INPUTS ROOM INFORMATION NETWORK,
2 POT INPUTS,
2 RS485 NETWORK (BACNET, SIN, FHN),
1 TRANSDUCER (VV: 0-4 in.w .c., VFX: 0-2 in.w .c.)

2 ACTIVE BINARY OUTPUTS (24 VAC, MAX: 500 mA),


OUTPUTS 4 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA),
1 SIN POWER OUTPUT (34 VDC, MAX: 300mA)

INDICATORS STATUS LED


HOUSING UL 94 V-0, PC-ABS PLASTIC
RATED IMPULSE VOLTAGE 330 V (AFTER TRANSFORMER)
COMMUNICATION PROTOCOL BACNET MS/TP
DEVICE TYPE B-AAC
COMMUNICATION TYPE MS/TP (RS-485)
COMMUNICATION SPEED 9600, 19200, 38400, 76800
BACNET CERTIFICATION BTL

1. ANTEC TOOLBOX
CONTROL PRIORITY ORDER 2. BACNET
3. NORMAL OPERATION

DIMENSIONS:
8.90 (226) 1.22 (31)

1.89 (48)

3.77 (114) 4.48 (114)

8.31 (211)
9.55 (243)

AIRFLOW DEVICE TYPE:

VENTURI VALVE (VV)


PRESSURE SENSOR 0 to 4.0 in.w.c. (0 to 1000 Pa)

VENTURI FX (VFX) OR TERMINAL (TU)


PRESSURE SENSOR 0 to 2.0 in.w.c. (0 to 500 Pa)
Solid Edge

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 2 of 10

270117
Product Submittal Rev. O
2022/07/21

TERMINATION:

+
-

COM
SIG

SIG

AO3

AO4
POT 2 POT 1

POWER RIN IN RIN OUT NET1 NET2 SIN


NETCOM

NETCOM
EARTH
24VAC

VCOM
VBUS
COM

COM

COM

COM

COM

COM
RX +

RX +
TX +

TX +

BO1

BO2

AO1

AO2
RX -

RX -
TX -

TX -

BI1

BI2

AI1

AI2

AI3

AI4

T1

T2
+

+
-

24VA C INP UT P OWER, HOT B I1 B INA RY INP UT 1


BINARY
P OWER COM INP UT P OWER, GROUND COM B INA RY INP UT GROUND
INP UTS
EA RTH INP UT P OWER, EARTH BI2 B INA RY INP UT 2

RX - A I1 A NALOG INPUT 1

RX + COM A NALOG INPUT GROUND


RIN IN ROOM INFORM ATION NETWORK IN
TX - A NA LOG AI2 A NALOG INPUT 2

TX + INP UTS AI3 A NALOG INPUT 3

RX - COM A NALOG INPUT GROUND

RX + AI4 A NALOG INPUT 4


RIN OUT ROOM INFORM ATION NETWORK OUT
TX - THERM ISTOR T1 THERM ISTOR INP UT 1

TX + INPUTS T2 THERM ISTOR INP UT 2

NETCOM BA CNET COM , SIN COM , FHN COM A O1 A NALOG OUTP UT 1


NET 1 + BA CNET +, SIN +, FHN + COM A NALOG OUTP UT GROUND

- BA CNET -, SIN -, FHN - A NA LOG AO2 A NALOG OUTP UT 2

NETCOM BA CNET COM , SIN COM , FHN COM OUTP UTS AO4 A NALOG OUTP UT 4
NET 2 + BA CNET +, SIN +, FHN + COM A NALOG OUTP UT GROUND

- BA CNET -, SIN -, FHN - AO3 A NALOG OUTP UT 3

VBUS SIN POWER - P OTENTIOM ETER FEEDB A CK GROUND


SIN
VCOM SIN GROUND P OT 1 SIG P OTENTIOM ETER FEEDB A CK SIGNA L

BO1 BINARY OUTP UT 1 + P OTENTIOM ETER FEEDB A CK P OWER


BINARY
COM BINARY OUTP UT GROUND - P OTENTIOM ETER FEEDB A CK GROUND
OUTP UTS
B O2 BINARY OUTP UT 2 POT 2 SIG P OTENTIOM ETER FEEDB A CK SIGNA L
+ P OTENTIOM ETER FEEDB A CK P OWER

MOUNT:

AIRFLOW DEVICE MOUNTED (DEFAULT)


Solid Edge

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 3 of 10

270117
Product Submittal Rev. O
2022/07/21

PANEL MOUNTED (PM)

SPECIFICATIONS:
MATERIAL 22 Ga GALV. STEEL
MOUNT WALL MOUNT
KNOCKOUTS 12 x .875in, FOR 0.5in TRADE SIZE CONDUIT

DIMENSIONS:

18.70 475
2.35 60 14.00 356

8.20 208 7.50 191

.350 9

O .875
(x12) 2.38 60

3.04 77

18.43 468 8.01 203

MOUNTING DETAILS:

16.00 406

6.51 165

O .164
(x4)
Solid Edge

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 4 of 10

270117
Product Submittal Rev. O
2022/07/21

BACNET POINTS LIST v2.0.0 OR NEWER

Write
Object Name Units Range Description
Setting

ANALOG INPUTS
Note: Analog input AI1 will display as AI11 for Controller 1, AI21 for Controller 2, etc.
Analog Input w ith multiple uses
AI#1 [Controller name] AI1 – [AI1 Device name] Dynamic Dynamic R
See Input section of the Antec Toolbox manual for options
Analog Input w ith multiple uses
AI#2 [Controller name] AI2 – [AI2 Device name] Dynamic Dynamic R
See Input section of the Antec Toolbox manual for options
Analog Input w ith multiple uses
AI#3 [Controller name] AI3 – [AI3 Device name] Dynamic Dynamic R
See Input section of the Antec Toolbox manual for options
Analog Input w ith multiple uses
AI#4 [Controller name] AI4 – [AI4 Device name] Dynamic Dynamic R
See Input section of the Antec Toolbox manual for options
-40 to 250 °F
AI#5 [Controller name] T1 – [T1 Device name] °F or °C Thermistor reading R
(-40 to 121 °C)
-40 to 250 °F
AI#6 [Controller name] T2 – [T2 Device name] °F or °C Thermistor reading R
(-40 to 121 °C)
BINARY INPUTS
Note: Binary input BI1 will display as BI11 for Controller 1, BI21 for Controller 2, etc.
Binary Input w ith multiple uses
BI#1 [Controller name] BI1 – [BI1 Device name] Open/Closed Open/Closed R
See Input section of the Antec Toolbox manual for options
Binary Input w ith multiple uses
BI#2 [Controller name] BI2 – [BI2 Device name] Open/Closed Open/Closed R
See Input section of the Antec Toolbox manual for options
Binary Input w ith multiple uses
BI#3 [Controller name] BI3 – [BI1 Device name] Open/Closed Open/Closed See Input section of the Antec Toolbox manual for options R
Hidden when controller is not a Cava™
Binary Input w ith multiple uses
BI#4 [Controller name] BI4 – [BI2 Device name] Open/Closed Open/Closed See Input section of the Antec Toolbox manual for options R
Hidden when controller is not a Cava™
ANALOG OUTPUTS
Note: Analog output AO1 will display as AO11 for Controller 1, AO21 for Controller 2, etc.
Analog Output w ith multiple uses
AO#1 [Controller name] AO1 – [AO1 Device name] VDC 0 to 10 R/W
See Output section of the Antec Toolbox manual for options
Analog Output w ith multiple uses
AO#2 [Controller name] AO2 – [AO2 Device name] VDC 0 to 10 R/W
See Output section of the Antec Toolbox manual for options
Analog Output w ith multiple uses
AO#3 [Controller name] AO3 – [AO3 Device name] VDC 0 to 10 R/W
See Output section of the Antec Toolbox manual for options
Analog Output w ith multiple uses
AO#4 [Controller name] AO4 – [AO4 Device name] VDC 0 to 10 R/W
See Output section of the Antec Toolbox manual for options
BINARY OUTPUTS
Note: Analog output BO1 will display as BO11 for Controller 1, BO21 for Controller 2, etc.
Binary Output w ith multiple uses
BO#1 [Controller name] BO1 – [BO1 Device name] Active/Inactive Active/Inactive R/W
See Output section of the Antec Toolbox manual for options
Binary Output w ith multiple uses
BO#2 [Controller name] BO2 – [BO2 Device name] Active/Inactive Active/Inactive R/W
See Output section of theAntec Toolbox manual for options
ANALOG VALUE
-5.0 to 5.0 in.w .c. Current room pressure setpoint
AV1 Room Pressure Setpoint in.w .c.; Pa R/W
(-1245 to 1245 Pa) Hidden when pressure control not used
-5.0 to 5.0 in.w .c.
AV2 Room Pressure in.w .c.; Pa Current room pressure R
(-1245 to 1245 Pa)
-5.0 to 5.0 in.w .c.
AV3 Room Pressure Low Alarm in.w .c.; Pa Low room pressure alarm setpoint (+/-) R/W
(-1245 to 1245 Pa)
-5.0 to 5.0 in.w .c.
AV4 Room Pressure High Alarm in.w .c.; Pa High room pressure alarm setpoint (+/-) R/W
(-1245 to 1245 Pa)
-50000 to 50000 CFM Current airflow offset setpoint
AV5 Airflow Offset Setpoint CFM; L/s R/W
(-23600 to 23600 L/s) Hidden when offset control not used
Solid Edge

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 5 of 10

270117
Product Submittal Rev. O
2022/07/21

BACNET POINTS LIST v2.0.0 OR NEWER (CONTINUED)

Write
Object Name Units Range Description
Setting

ANALOG VALUE
-50000 to 50000 CFM
AV6 Airflow Offset Actual CFM; L/s Current airflow offset (+/-) R
(-23600 to 23600 L/s)

0 to 50000 CFM
AV7 Total Exhaust Airflow Target CFM; L/s Total room exhaust airflow target R
(0 to 23600 L/s)

0 to 50000 CFM
AV8 Total Exhaust Airflow Actual CFM; L/s Total room exhaust airflow R
(0 to 23600 L/s)

0 to 50000 CFM
AV9 Total Supply Airflow Target CFM; L/s Total room supply airflow target R
(0 to 23600 L/s)

0 to 50000 CFM
AV10 Total Supply Airflow Actual CFM; L/s Total room supply airflow R
(0 to 23600 L/s)

0 to 50000 CFM Total fume hood exhaust airflow


AV11 Total Fume Hood Exhaust CFM; L/s R
(0 to 23600 L/s) Hidden if no fume hoods connected

0 to 100000000 ft^3
AV12 Room Volume ft3; m3 Room volume R/W
(0 to 2831685 m^3)

AV13 Current Air Change Rate # 0.0 to 100.0 Current air change rate R

-40 to 250 °F Temperature setpoint in zone 1


AV14 Temperature Setpoint - Zone 1 °F;°C R/W
(-40 to 121 °C) Hidden if there are no temperature zones

-40 to 250 °F
AV15 Temperature Reading - Zone 1 °F;°C Current temperature in zone 1 R
(-40 to 121 °C)

-40 to 250 °F Temperature setpoint in zone 2


AV16 Temperature Setpoint - Zone 2 °F;°C R/W
(-40 to 121 °C) Hidden if multiple zones have not been configured

-40 to 250 °F Current temperature in zone 2


AV17 Temperature Reading - Zone 2 °F;°C R
(-40 to 121 °C) Hidden if multiple zones have not been configured

-40 to 250 °F Temperature setpoint in Zone 3


AV18 Temperature Setpoint - Zone 3 °F;°C R/W
(-40 to 121 °C) Hidden if multiple zones have not been configured

-40 to 250 °F Current Temperature in zone 3


AV19 Temperature Reading - Zone 3 °F;°C R
(-40 to 121 °C) Hidden if multiple zones have not been configured

-40 to 250 °F
AV20 Room Temperature Setpoint - Low Limit °F;°C Low est user-adjustable temperature setpoint on the thermostat R/W
(-40 to 121 °C)

-40 to 250 °F
AV21 Room Temperature Setpoint - High Limit °F;°C Highest user-adjustable temperature setpoint on the thermostat R/W
(-40 to 121 °C)

-40 to 250 °F Discharge air temperature low temperature limit


AV22 DAT Low Limit °F;°C R/W
(-40 to 121 °C) Hidden if DAT limits are not enabled

-40 to 250 °F Discharge air temperature high temperature limit


AV23 DAT High Limit °F; °C R/W
(-40 to 121 °C) Hidden if DAT limits are not enabled

0 to 50000 CFM Supply airflow setpoint


AV24 Supply Airflow Setpoint CFM; L/s R/W
(0 to 23600 L/s) Hidden if Supply airflow control not used

0 to 50000 CFM Supply airflow


AV25 Supply Airflow Actual CFM; L/s R
(0 to 23600 L/s) Hidden if Supply airflow control not used

Temperature load in Zone 1


AV26 Temperature Load - Zone 1 % -100% to 100% R
Hidden if there are no temperature zones

Temperature load in Zone 2


AV27 Temperature Load - Zone 2 % -100% to 100% R
Hidden if multiple zones have not been configured

Temperature load in Zone 3


AV28 Temperature Load - Zone 3 % -100% to 100% R
Hidden if multiple zones have not been configured
Solid Edge

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 6 of 10

270117
Product Submittal Rev. O
2022/07/21
BACNET POINTS LIST v2.0.0 OR NEWER (CONTINUED)

Write
Object Name Units Range Description
Setting

0 to 50000 CFM Exhaust airflow setpoint


AV29 Exhaust Airflow Setpoint CFM; L/s R/W
(0 to 23600 L/s) Hidden if Exhaust airflow control not used

0 to 50000 CFM Exhaust airflow


AV30 Exhaust Airflow Actual CFM; L/s R
(0 to 23600 L/s) Hidden if Exhaust airflow control not used

0 to 50000 CFM
AV81 [Mode name #1] - Room Min CFM; L/s Room flow minimum for the default room mode R/W
(0 to 23600 L/s)

0 to 50000 CFM
AV82 [Mode name #1] - Room Heating Max CFM; L/s Room flow heating maximum for the default room mode R/W
(0 to 23600 L/s)

0 to 50000 CFM
AV83 [Mode name #1] - Room Cooling Max CFM; L/s Room flow cooling maximum for the default room mode R/W
(0 to 23600 L/s)

0 to 50000 CFM Room flow minimum for the second room mode
AV84 [Mode name #2] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 2 room modes

0 to 50000 CFM Room flow heating maximum for the second room mode
AV85 [Mode name #2] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 2 room modes

0 to 50000 CFM Room flow cooling maximum for the second room mode
AV86 [Mode name #2] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 2 room modes

0 to 50000 CFM Room flow minimum for the third room mode
AV87 [Mode name #3] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 3 room modes

0 to 50000 CFM Room flow heating maximum for the third room mode
AV88 [Mode name #3] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 3 room modes

0 to 50000 CFM Room flow cooling maximum for the third room mode
AV89 [Mode name #3] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 3 room modes

0 to 50000 CFM Room flow minimum for the fourth room mode
AV90 [Mode name #4] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 4 room modes

0 to 50000 CFM Room flow heating maximum for the fourth room mode
AV91 [Mode name #4] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 4 room modes

0 to 50000 CFM Room flow cooling maximum for the fourth room mode
AV92 [Mode name #4] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 4 room modes

0 to 50000 CFM Room flow minimum for the fifth room mode
AV93 [Mode name #5] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 5 room modes

0 to 50000 CFM Room flow heating maximum for the fifth room mode
AV94 [Mode name #5] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 5 room modes

0 to 50000 CFM Room flow cooling maximum for the fifth room mode
AV95 [Mode name #5] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 5 room modes

0 to 50000 CFM Room flow minimum for the sixth room mode
AV96 [Mode name #6] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 6 room modes

0 to 50000 CFM Room flow heating maximum for the sixth room mode
AV97 [Mode name #6] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 6 room modes

0 to 50000 CFM Room flow cooling maximum for the sixth room mode
AV98 [Mode name #6] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 6 room modes
Solid Edge

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 7 of 10

270117
Product Submittal Rev. O
2022/07/21
BACNET POINTS LIST v2.0.0 OR NEWER (CONTINUED)

Write
Object Name Units Range Description
Setting

Note: Analog value AV#01 will display as AV101 for Controller 1, AV201 for Controller 2, etc.

0 to 50000 CFM POT1 airflow reading


AV#01 [Controller name] Flow - [POT1 Device name] CFM; L/s R
(0 to 23600 L/s) Hidden when POT1 is not used

0 to 50000 CFM POT2 airflow reading


AV#02 [Controller name] Flow - [POT2 Device name] CFM; L/s R
(0 to 23600 L/s) Hidden when POT2 is not used

-5.0 to 5.0 in.w .c. Valve Pressure


AV#03 [Controller name] - Valve Pressure in.w .c.; Pa R
(-1245 to 1245 Pa) Hidden when device type is not VV

[Controller name] Flow - [Transducer Device 0 to 50000 CFM Transducer airflow reading
AV#04 CFM; L/s R
name] (0 to 23600 L/s) Hidden when airflow source is not transducer

-40 to 250 °F Discharge Air Temperature Setpoint for AI1


AV#05 [Controller name] AI1 - DAT Setpoint °F;°C R/W
(-40 to 121 °C) Hidden when DAT control is not enabled

-40 to 250 °F Discharge Air Temperature Setpoint for AI2


AV#06 [Controller name] AI2 - DAT Setpoint °F;°C R/W
(-40 to 121 °C) Hidden when DAT control is not enabled

-40 to 250 °F Discharge Air Temperature Setpoint for AI3


AV#07 [Controller name] AI3 - DAT Setpoint °F;°C R/W
(-40 to 121 °C) Hidden when DAT control is not enabled

-40 to 250 °F Discharge Air Temperature Setpoint for AI4


AV#08 [Controller name] AI4 - DAT Setpoint °F;°C R/W
(-40 to 121 °C) Hidden when DAT control is not enabled

-40 to 250 °F Discharge Air Temperature Setpoint for T1


AV#09 [Controller name] T1 - DAT Setpoint °F;°C R/W
(-40 to 121 °C) Hidden when DAT control is not enabled

-40 to 250 °F Discharge Air Temperature Setpoint for T2


AV#10 [Controller name] T2 - DAT Setpoint °F;°C R/W
(-40 to 121 °C) Hidden when DAT control is not enabled

0 to 1000 FPM Displays the current face velocity across the fume hood
AV#15 [Controller name] Face Velocity FPM; m/s R
(0 to 5.08 m/s) Hidden when controller is not a Cava™
MULTISTATE VALUE
Displays the current airflow control sequence
1 - Constant Flow Control
MV1 Airflow Control Sequence Text 3 states R
2 - Pressure Control
3 - Offset Control
Displays the current room pressure mode
MV2 Room Pressure Mode Text 2 states 1 - Positive R
2 - Negative

Solid Edge

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 8 of 10

270117
Product Submittal Rev. O
2022/07/21

BACNET POINTS LIST v2.0.0 OR NEWER (CONTINUED)

Write
Object Name Units Range Description
Setting

MULTISTATE VALUE
Displays the current room alarm status
1 - Controller Not Responding
2 - Missing Room Pressure Sensor
3 - Diversity
4 - Binary Input
5 - Mode Alarm
6 - Door Open
MV3 Room Alarm Status Text 13 states R
7 - Room Low Pressure
8 - Room High Pressure
9 - Low Airflow
10 - Low Valve Pressure
11 - High Airflow
12 - High Valve Pressure
13 - No Alarm
Displays the current room mode
1 - [Default Room Mode Name]
2 - [Custom Room Mode 1 Name]
MV4 Room Mode Text 6 states 3 - [Custom Room Mode 2 Name] R/W
4 - [Custom Room Mode 3 Name]
5 - [Custom Room Mode 4 Name]
6 - [Custom Room Mode 5 Name]
Displays the current room mode override
1 - [Default Room Mode Name]
2 - [Custom Room Mode 1 Name]
MV5 Room Mode Override Text 6 states 3 - [Custom Room Mode 2 Name] R/W
4 - [Custom Room Mode 3 Name]
5 - [Custom Room Mode 4 Name]
6 - [Custom Room Mode 5 Name]
Displays the current firmw are update status
1 - Idle
MV99 Firmw are Update Status Text 4 states 2 - Start Firmw are Update R/W
3 - Updating Firmw are
4 - Firmw are Update Failed
Note: Multistate value MV#3 will display as MV13 for Controller 1, MV23 for Controller 2, etc…

Displays the current room alarm status


1 - CANbus Device Not Responding
2 - Sash Missing/Broken
3 - Sash Height Low
4 - Sash Height High
5 - Face Velocity Low
6 - Face Velocity High
MV#3 [Controller Name] Status Text 12 States R
7 - Valve Pressure Low
8 - Valve Pressure High
9 - Valve Airflow Low
10 - Valve Aiflow High
11 - Fume Hood Mode
12 - No Alarm
Hidden when controller is not a Cava™
Displays the current hood mode
1 - [Hood Mode 1 Name]
2 - [Hood Mode 2 Name]
MV#4 [Controller Name] Hood Mode Text 4 States R/W
3 - [Hood Mode 3 Name]
4 - [Hood Mode 4 Name]
Hidden when controller is not a Cava™
Displays the current hood mode override
1 - [Hood Mode 1 Name]
2 - [Hood Mode 2 Name]
MV#5 [Controller Name] Hood Mode Override Text 4 States R/W
3 - [Hood Mode 3 Name]
4 - [Hood Mode 4 Name]
Solid Edge

Hidden when controller is not a Cava™


NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 9 of 10

270117
Product Submittal Rev. O
2022/07/21

BACNET POINTS LIST v2.0.0 OR NEWER (CONTINUED)

Write
Object Name Units Range Description
Setting

FILE
The file object used for firmw are upgrades -
FIL1 Firmw are - - W
feature only available if supported by BAS
CALENDAR
CAL1 Calendar Object - - The calendar object used for scheduling R/W
NOTIFICATION CLASS
EVC1 Notification Class object - - The notification class object for alarming R/W
SCHEDULE
SCH1 Room Mode Schedule - - The scheduling object for scheduling room mode changes R/W

NOTE: THE BACNET POINT NAMES CAN BE OVERRIDDEN USING ANTEC TOOLBOX AND MAY NOT MATCH THE NAMES LISTED IN THIS TABLE. THE INSTANCE NUMBERS
CAN BE USED IN THIS CASE TO IDENTIFY THE POINTS.

DEFAULT CHANGE OF VALUE (COV) INCREMENTS


VARIABLE DEFAULT COV INCREMENT UNITS DEFAULT COV INCREMENT UNITS
- IMPERIAL METRIC

Airflow 50 CFM 24 L/s


Of fset 20 CFM 9 L/s
Actuator 0.001 V 0.001 V
Heating 0.001 V 0.001 V
Pressure 0.001 in.w .c. 0.25 Pa
Valve Pressure 0.2 in.w .c. 49.8 Pa
ACH 1 ACH 1 ACH
CO2 100 ppm 100 ppm
Face Velocity 10 FPM 0.51 m/s
Humidity 1 % 1 %
Position 1 % 1 %
Room Volume 100 ft³ 2.83 m³
Temperature 0.5 °F 0.3 °C
Temperature Load 0.1 % 0.1 %
VOC 100 ppm 100 ppm
Voltage 0.05 V 0.05 V

Solid Edge

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


PACE-1-X
Pace™ - Critical Space Controller Sheet 10 of 10

270117
Product Submittal Rev. O
2022/07/21

BACNET POINTS LIST v2.0.0 OR NEWER (CONTINUED)

Write
Object Name Units Range Description
Setting

Fume Hood Controller (FHC) BACnet points - Legacy Controls

ANALOG VALUE

Note: Analog value AV#11 will display as AV111 for Fume Hood Controller (FHC) 1, AV211 for Fume Hood Controller (FHC) 2, etc.

0 to 50000 CFM
AV#11 Fume Hood # Airflow CFM; L/s Displays the current airflow being exhausted from the fume hood R
(0 to 23600 L/s)

0 to 1000 FPM
AV#12 Fume Hood # Face Velocity FPM; m/s Displays the current face velocity across the fume hood R
(0 to 5.08 m/s)

AV#13 Fume Hood # Sash Position % 0 to 100 Displays the current position of the sash on the fume hood R

-5.0 to 5.0 in.w .c.


AV#14 Fume Hood # Valve Pressure in.w .c.; Pa Displays the current pressure across the valve on the fume hood R
(-1245 to 1245 Pa)
MULTISTATE VALUE

Note: Multistate value MV#1 will display as MV11 for Fume Hood Controller (FHC) 1, MV21 for Fume Hood Controller (FHC) 2, etc…

Displays the status of the fume hoods


1 - Missing FHC
2 - Normal
MV#1 Fume Hood # Status Text 6 states 3 - Caution R
4 - Alarm
5 - Setback
6 - Off

Displays the cause of any alarms or cautions on the fume hoods


1 - No Error
2 - Emergency
3 - Netw ork
4 - Contact Input
5 - No Primary Sensor
6 - No Sec. Sensor
7 - No Sash1
8 - No Sash2
9 - No Sash 3
10 - Low Velocity
MV#2 Fume Hood # Error Type Text 21 states R
11 - High Velocity
12 - Low Pressure
13 - High Pressure
14 - Venturi Out of Range
15 - Sash Height
16 - Low Airflow
17 - High Airflow
18 - Sash Broken
19 - BI1
20 - BI2
21 - Setback Sash Height
Solid Edge

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


FVM-1-X
Fume Hood Valve Module Sheet 1 of 3

272815
Product Submittal Rev. B
2021/08/09

VENTURI VALVE (VV)


PRESSURE SENSOR 0 to 4.0 in.w.c. (0 to 1000 Pa)

FVM SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC, 50/60 Hz, 17 VA MAX, CLASS 2 or LPS PELV
CANbus,
INPUTS 2 POT INPUTS,
1 TRANSDUCER, 0-4 in.w .c. (0-1000 Pa)

OUTPUTS 4 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA)


INDICATORS STATUS LED
HOUSING UL 94 V-0, PC-ABS PLASTIC

DIMENSIONS:
5.27 134 1.22 31

1.90 48

3.81 97 4.48 114

4.74 120

5.95 151

24VA C INP UT P OWER, HOT


TERMINATION: P OWER
COM INP UT P OWER, GROUND

COM CA Nbus GROUND


CA Nbus CA NH CA Nbus HIGH
COM
+

AO3

AO4
SIG

SIG
-

CA NL CA Nbus LOW

POT 2 POT 1 A O1 A NA LOG OUTP UT 1

COM A NA LOG OUTP UT GROUND

A NA LOG A O2 A NA LOG OUTP UT 2


H

OUTP UTS A O3 A NA LOG OUTP UT 3


PT

COM A NA LOG OUTP UT GROUND


L

A O4 A NA LOG OUTP UT 4

+ P OTENTIOM ETER FEEDB A CK P OWER


POWER CANbus
P OT 1 SIG P OTENTIOM ETER FEEDB A CK SIGNA L
24VAC

CANH
CANL
COM

COM

COM
AO1

AO2

- P OTENTIOM ETER FEEDB A CK GROUND

+ P OTENTIOM ETER FEEDB A CK P OWER


P OT 2 SIG P OTENTIOM ETER FEEDB A CK SIGNA L

- P OTENTIOM ETER FEEDB A CK GROUND


MOUNT:
AIRFLOW DEVICE MOUNTED (DEFAULT)
Solid Edge

NOTE: PLEASE REFER TO CAVA MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
© Copyright Antec Controls by PRICE 2021
CAVA-1-X
Cava™ - Touchscreen Fume Hood Controller Sheet 1 of 4

Product Submittal 272814


Rev. B
2021/08/20

CAVA SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 10%, 50/60 Hz, 12 VA MAX (EXCLUDING EXTERNAL LOADS), CLASS 2

BINARY INPUT (CONTACT CLOSURE or ACTIVE),


4 UNIVERSAL INPUTS ANALOG INPUT (0 to 10 VDC),
INPUTS RESISTANCE INPUT - SASH POSITION (0-50 kOhm)

CANbus
ROOM INFORMATION NETWORK

OUTPUTS 2 BINARY OUTPUTS (MAX: 24 VAC, 500 mA)


INDICATORS TOUCHSCREEN DISPLAY, 4.3" TFT
HOUSING UL 94 V - 0, PC-ABS PLASTIC
COMMUNICATION PROTOCOL BACNET
DEVICE TYPE B-AAC
COMMUNICATION TYPE MS/TP (RS-485)
COMMUNICATION SPEED 9600, 19200, 38400, 76800
BACNET
CERTIFICATION BTL
CONTROL 1. BACNET
PRIORITY ORDER 2. NORMAL OPERATION

2.96 75 .83 21 1.48 38


DIMENSIONS:
.49 12

3.65 93 3.30 84
5.76 146 3.74 95
5.71 145
2.18 (55)

.92 23 1.12 29

TERMINATION:
VA C INP UT P OWER, HOT

COM INP UT P OWER, GROUND

COM B A CNET NET COM

+ B A CNET +
BO1
COM COM VAC

- B A CNET -
BO2

COM

CA NH CA Nbus NETWORK
UI4

CA NL
UI3 COM
+

B O1 B INA RY OUTP UT
-

B O2 B INA RY OUTP UT
CANL CANH COM

UI1 COM UI2

UI4 UNIVERSA L INP UT

COM UNIVERSA L INP UT GROUND

UI3 UNIVERSA L INP UT

UI2 UNIVERSA L INP UT

COM UNIVERSA L INP UT GROUND

RIN RIN RIN UI1 UNIVERSA L INP UT

RIN ROOM INFORM A TION NETWORK IN/OUT

RIN ROOM INFORM A TION NETWORK IN/OUT

RIN ROOM INFORM A TION NETWORK IN/OUT


Solid Edge

NOTE: PLEASE REFER TO CAVA MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2021


Valve Actuator Sheet 2 of 15

Product Submittal 270736


Rev. F
2022/01/04

ACTUATOR - 35 in-lbs (4 Nm), VDC, HSA, FLP

SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -40⁰F to 176⁰F (-40⁰C to 80⁰C), 5% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 20%, 50/60 Hz, 23 VA, CLASS 2
CONTROL SIGNAL RANGE 2 to 10 VDC
MIN 30°, MAX 95°, ADJUSTABLE WITH MECHANICAL STOP
ANGLE OF ROTATION
ELECTRONICALLY VARIABLE (POWER ADAPTION)

DIRECTION OF ROTATION REVERSIBLE WITH BUILT-IN SWITCH (FACTORY SET TO 0)


TORQUE 35 in-lb (4 Nm)
MANUAL OVERRIDE EXTERNAL PUSH BUTTON
RUNNING TIME 2.5 sec
HOUSING NEMA 2, IP54, UL ENCLOSURE TYPE 2
HOUSING MATERIAL UL94 -5VA
WEIGHT 1.8 lbs (0.85 kg)
PART # (BELIMO MODEL) 019127-001 (LMQB24-MFT)

7.35 (187)
DIMENSIONS:
POWER ADAPTION BUTTON
1
0

DIRECTION OF ROTATION SWITCH


3.15 (80)

MANUAL OVERRIDE BUTTON


.98 (25) NOTE: DO NOT PRESS WHEN AIRFLOW IS PRESENT

2.95 (75)
1.97 (50)

4.88 (124)
TERMINATION:

BLACK
RED RED INP UT P OWER, HOT
WHITE
ORANGE B LA CK INP UT P OWER, COM M ON
WHITE CONTROL SIGNA L

ORA NGE NOT USED


Solid Edge

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


Valve Actuator Sheet 5 of 15

Product Submittal 270736


Rev. F
2022/01/04

ACTUATOR - 70 in-lbs (8 Nm), VDC, HSA, FLP

SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -40⁰F to 176⁰F (-40⁰C to 80⁰C), 5% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 20%, 50/60 Hz, 23 VA, CLASS 2
CONTROL SIGNAL RANGE 2 to 10 VDC

MIN 30°, MAX 95°, ADJUSTABLE WITH MECHANICAL STOP


ANGLE OF ROTATION
ELECTRONICALLY VARIABLE (POWER ADAPTION)

DIRECTION OF ROTATION REVERSIBLE WITH BUILT-IN SWITCH (FACTORY SET TO 0)


TORQUE 70 in-lbs (8 Nm)
MANUAL OVERRIDE EXTERNAL PUSH BUTTON
RUNNING TIME 4 sec
HOUSING NEMA 2, IP54, UL ENCLOSURE TYPE 2
HOUSING MATERIAL UL94 -5VA
WEIGHT 1.8 lbs (0.85 kg)
PART # (BELIMO MODEL) 019127-004 (NMQB24-MFT)

8.30 211
DIMENSIONS: 5.20 132
DIRECTION OF ROTATION SWITCH
0
1

POWER ADAPTION BUTTON


3.46 88

MANUAL OVERRIDE BUTTON


1.18 30 NOTE: DO NOT PRESS WHEN AIRFLOW IS PRESENT

2.49 63
1.69 43

4.06 103
5.24 133.1
TERMINATION:

BLACK
RED RED INP UT P OWER, HOT
WHITE
ORANGE B LA CK INP UT P OWER, COM M ON

WHITE CONTROL SIGNA L

ORA NGE NOT USED


Solid Edge

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2022


ES-1-X
Environmental Sensor Sheet 4 of 11

270215
Rev. G
Product Submittal 2020/06/09

ROOM TEMPERATURE SENSOR (RM) WITH DISPLAY (LCD) AND


PUSHBUTTON SETPOINT ADJUSTMENT (BTN)

ES-RM-LCD-BTN SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 122⁰F (0⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
STANDARD 2in. x 4in. (51mm x 102mm) J-BOX or
MOUNT
DRYWALL MOUNT
DISPLAY LCD SCREEN
15 to 40 VDC or 15 to 28 VAC. (DO NOT RUN AC POWER IN THE
INPUT POWER
SAME CONDUIT AS SIGNAL WIRES)

1 ANALOG (0 to 10 VDC):
OUTPUT
TEMPERATURE SETPOINT - RANGE: 50⁰F to 90⁰F (10⁰C to 32⁰C)
INPUT TYPE KEYPAD
TEMPERATURE READING 10K-2 THERMISTOR, ±0.36⁰F, 32⁰ to 158⁰F (±0.2⁰C, 0 to 70⁰C)
HOUSING UL 94 V-0, ABS PLASTIC
COMMUNICATION PORT RJ-45

DIMENSIONS: CLOSED CELL FOAM


3.0 (76) 1.0 (28)

.7 (18)

4.4 (112) 3.28 (83)

FACE PLATE WALLMOUNT PLATE


COMMUNICATION PORT:

CKJ-B - PUSHDOWN CONNECTION


RJ-45 TO PACE CONTROLLER
WHERE APPLICABLE
WALLMOUNT PLATE
TERMINATION:

V+ INP UT P OWER, HOT


OVR1
OVR2 GND INP UT P OWER, GROUND
EXT-TEMP
EXT-GND SEN1
SEN1 OCCUPY THERM ISTOR RESISTA NCE OUTP UT
SEN2 W1 SEN2
SET1 GND
SET2 V+ SET1 TEM P ERA TURE SETP OINT OUTP UT
°F/C

DISPLAY SWITCH v( F or vC)

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.


SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Solid Edge

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2020


ES-1-X
Environmental Sensor Sheet 10 of 11

270215
Rev. G
Product Submittal 2020/06/09

DUCT MOUNTED SENSOR (DT)

ES-DT SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) -40⁰F to 185⁰F (-4⁰C to 85⁰C), 0 to 95% R.H.(NON-CONDENSING)
TEMPERATURE READING 10K-2 THERMISTOR, ±0.36⁰F, 32⁰ to 158⁰F (±0.2⁰C, 0 to 70⁰C)
PROBE 304 STAINLESS STEEL PROBE, 0.25in. (7mm) DIAMETER, 6in. (152mm) LENGTH
HOUSING PC PLASTIC, UL 94 V-0, IP10, NEMA1

DIMENSIONS:

2.1 (53)

.25 6
3.0 (76) 2.67 (68)

6.0 152

8.0 202
1.78 (45)

TERMINATION:

YELLOW
YELLOW

YELLOW
THERM ISTOR RESISTA NCE OUTP UT
YELLOW

NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS.


Solid Edge

SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.


ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2020


POT-1-X
Retrofit Potentiometer Replacement Sheet 1 of 2

272002
Rev. 0
Product Submittal 2020/03/26

STANDARD POTENTIOMETER REPLACEMENT (SPR)

POT SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) -67⁰F to 221⁰F (-50⁰C to 105⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -67⁰F to 221⁰F (-50⁰C to 105⁰C), 5% to 95% R.H.(NON-CONDENSING)
OUTPUT SIGNAL VOLTAGE DIVIDER UTILIZING 10K POT
POTENTIOMETER RANGE SINGLE TURN ROTATION
CONNECTION TYPE 3-WIRE
HOUSING MATERIAL HIGH TEMP. THERMOPLASTIC
SHAFT MATERIAL STAINLESS STEEL
MATERIAL ALUMINUM
SHAFT COUPLER
HEX SIZE 3/32"
MOUNTING BRACKETS MATERIAL 16 Ga GALVANIZED STEEL
EXTENSION PIN MATERIAL STAINLESS STEEL

DIMENSIONS:

1.1 29

1.6 42

24.0 ( 61 ) 1.5 ( 38 )

TERMINATION:

P A CE FHC/LM X
P OT
(P OT 1OR P OT 2) (RGB TERM INA L B LOCK)
RED
RED + R
GREEN
GREEN SIG G
BLACK
B LA CK - B

NOTE: PLEASE REFER TO VVR MANUAL FOR INSTALLATION INSTRUCTIONS.


Solid Edge

SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.


ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2020


FPS-1-X
Fume Hood Presence Sensor Sheet 1 of 2

270115
Product Submittal Rev. D
2021/07/13

FPS SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 10%, 10 VA, CLASS 2
DETECTION DOPPLER SHIFT RADAR
DETECTION PATTERN SELECTABLE, WIDE OR NARROW
OUTPUTS 1 BINARY OUTPUT (DRY CONTACT FORM C, MAX: 1A)
MAX. MOUNTING HEIGHT 15ft (4.6m)
PLASTIC HOUSING ABS COVER AND BASE

DIMENSIONS: 1.13 (29)

5.75 (146)

6.50 (165)

1.75 (44) 2.00 (51)

O 2.75 (70)

TERMINATION:

BLACK
RED
BROWN
WHITE B LA CK INP UT P OWER, GROUND
GREEN
RED INP UT P OWER, HOT
B ROWN RELA Y, N/O

WHITE RELA Y, COM M ON

GREEN RELA Y, N/C

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS.
SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Solid Edge

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2021


FPS-1-X
Fume Hood Presence Sensor Sheet 2 of 2

270115
Product Submittal Rev. D
2021/07/13

RETROFIT ACCESSORY:

ACCESSORY SPECIFICATIONS:
MOUNTING PLATE MATERIAL 16ga STAINLESS STEEL, BRUSHED
SCREW #10 x .5", STAINLESS STEEL

MOUNTING PLATE - 8.25" HOLE SPACING (MP8)


MOUNTING PLATE - 17.50" HOLE SPACING (MP18)

MP8 PLATE SHOWN

DIMENSIONS:

9.50 241

3.00 76

O .19 5 8.25 210

MP8 PLATE

18.50 470

3.00 76

O .19 5 17.50 444

MP18 PLATE

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS.
SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Solid Edge

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2021


SPS-1-X
Sash Position Sensor Sheet 1 of 2

270123
Product Submittal Rev. C
2019/04/26

SASH POSITION SENSOR - 50in. (1270mm) STROKE RANGE

SPS SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) -50⁰F to 120⁰F (-10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
OUTPUT SIGNAL VOLTAGE DIVIDER UTILIZING 10K POT
CONNECTION TYPE 2-WIRE
MEASURING CABLE NYLON COATED STAINLESS STEEL
STROKE RANGE 0 to 50in. (0 to 1270mm)
HOUSING IP 50 PLASTIC
ACCURACY ±0.25% FS

DIMENSIONS:

O.14 (4)
(2x)
3.5 (90)
1.4 (36)
1.8 (46)
1.45 (37)

2.0 (51)
O.19 (5)

2.0 (51)

3.6 (91)

TERMINATION:
BLACK

GREEN
SA SH P OSITION FEEDB A CK
GREEN RED
RED
B LA CK NOT REQUIRED

NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS
SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Solid Edge

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2019


SVS-1-X
Sidewall Velocity Sensor Sheet 1 of 1

273420
Product Submittal Rev. A
2021/06/28

SIDEWALL VELOCITY SENSOR (SVS)


PRESSURE SENSOR -0.5 to 0.5 in.w.c. (-125 to 125 Pa)

SVS SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC, 50/60 Hz, 17 VA MAX, CLASS 2 or LPS PELV

CANbus,
INPUTS
1 TRANSDUCER, -0.5 to 0.5 in.w .c. (-125 to 125 Pa)

OUTPUTS 2 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA)


INDICATORS STATUS LED
HOUSING UL 94 V-0, PC-ABS PLASTIC

DIMENSIONS:
5.27 134 1.22 31

1.90 48

3.81 97 4.48 114

4.74 120
5.95 151

TERMINATION:

24VA C INP UT P OWER, HOT


P OWER
COM INP UT P OWER, GROUND

COM CA Nbus GROUND


CA Nbus CA NH CA Nbus HIGH
H

CA NL CA Nbus LOW
PT

A O1 A NA LOG OUTP UT 1
L

A NA LOG
COM A NA LOG OUTP UT GROUND
OUTP UTS
POWER CANbus A O2 A NA LOG OUTP UT 2
24VAC

CANH
CANL
COM

COM

COM
AO1

AO2

MOUNT:
SHIPPED LOOSE
Solid Edge

NOTE: PLEASE REFER TO CAVA MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.

ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
© Copyright Antec Controls by PRICE 2021
Typical Laboratory Retrofit

Sequence of Operations 2021/09/07

Sequence Number: 1
Sequence Type: Flow Offset Control
Room(s): Laboratory

Flow Offset Control:


Supply and General Exhaust with Fume Hoods: The Airflow Control System (ACS) will modulate the supply and general exhaust to maintain
the scheduled flow offset target. The ACS will sum the total exhaust airflow from all sources, including fume hoods and will modulate the
general exhaust air device to maintain the flow offset target. With no thermal demand, the supply will maintain the minimum scheduled value.
As airflow demand increases (see section: Temperature Control) the supply and general exhaust will be increased to maintain the scheduled
flow offset. With additional control sequences, the sequence with the highest demand for airflow will take priority.

Modes of Operation:
Occupied Mode (Default): Occupied Mode is the default room mode. While in Occupied Mode, the Airflow Control System (ACS) will target
the scheduled occupied airflows.

Emergency Mode: The Airflow Control System (ACS) will activate Emergency Mode by contact input.

While in Emergency Mode, the room air change rate will increase to the scheduled emergency room flow value. The ACS will maintain the
scheduled flow offset.

Fume Hood Control:


Hybrid Control: The Fume Hood Control System (FCS) uses a sash position sensor and a sidewall velocity sensor together to control the face
velocity of the fume hood. When a user moves the fume hood sash, the sash position sensor measures the height of the vertical fume hood
sash. The FCS will calculate the correct airflow to result in the target face velocity and will modulate the air device to the airflow target. The
FCS will then use the sidewall velocity sensor to adjust the airflow until the measured face velocity meets the target face velocity. The FCS will
maintain a minimum airflow at all times when the sash is closed to ensure the proper fume hood air change rate.
Occupied Mode (Default): Occupied Mode is the default fume hood mode. While in Occupied Mode, the Fume Hood Control System (FCS)
will target the scheduled occupied face velocity while maintaining the scheduled occupied airflows.

Unoccupied Mode: The Fume Hood Control System (FCS) will activate Unoccupied Mode by contact input. While in Unoccupied Mode, the
FCS will target the scheduled unoccupied face velocity while maintaining the scheduled unoccupied airflows.

Emergency Mode: The Fume Hood Control System (FCS) will active Emergency Mode when the "Emergency" button on the touchscreen
fume hood interface is pressed. The air device will modulate to its maximum airflow to purge the fume hood. A visual and audible alarm will
activate to indicate that the fume hood is being purged. Emergency Mode can be deactivated by pressing and holding the "Emergency" button
for 5 seconds.

Fume Hood Alarms:


While the unit is in alarm, the audible alarm can be silenced but will re-engage after an adjustable time delay. Audible and visual alarms are
available for face velocity, low/high valve pressure, sash height, and emergency.
Typical Laboratory Retrofit

Sequence of Operations 2021/09/07

Face Velocity: The Fume Hood Control System (FCS) will alarm if the measured face velocity drops below the adjustable low alarm limit or
rises above the adjustable high alarm limit.

Valve Pressure Alarms: The Fume Hood Control System (FCS) will alarm if the pressure across the Venturi Valve drops below the minimum
or rises above the maximum operating pressure for the valve.

Sash Alarm: The Fume Hood Control System (FCS) will alarm if the sash height is above the sash height alarm limit. The FCS will also alarm
if the sash position sensor cable fails or reports a value outside of the initially calibrated range.

Room Temperature Monitoring:


A room temperature sensor will measure the room temperature. Room temperature is available to the building management system (BMS).

The ES will display room temperature locally on the LCD display.

Duct Temperature Monitoring:


A duct temperature sensor will measure the duct temperature. Duct temperature is available to the building management system (BMS).

Valve Pressure Monitoring:


The PACE will monitor valve pressure. Valve pressure is available to the building management system (BMS).

The CAVA will monitor valve pressure. Valve pressure is available to the building management system (BMS).

Local/Room Level Communication:


All valves and controllers in the Airflow Control System (ACS) within the room will communicate via an independent high-speed room level
network called the Room Information Network (RIN).

Building Network Communication:


The Airflow Control System (ACS) will communicate over a native BACnet MS/TP trunk to the building automation network. All points are
available to the building management system (BMS) with no network gateway required.
Space Temperature Control:
Single Stage Reheat: Stage I: Modulating Reheat Coil: The Airflow Control System (ACS) will monitor room temperature from a wall
mounted room temperature sensor. In the first heating stage, the reheat coil will modulate to maintain space temperature.
If there are multiple reheat coils, all coils will modulate together to maintain space temperature.

Second Fume Hood Control:


Sash Position Control: The Fume Hood Control System (FCS) uses a sash position sensor to control the face velocity of the fume hood. When
a user moves the fume hood sash, the sash position sensor measures the height of the vertical fume hood sash. The FCS will calculate the
correct airflow to result in the target face velocity and will modulate the air device to the airflow target. The FCS will maintain a minimum airflow
at all times when the sash is closed to ensure the proper fume hood air change rate.
Typical Laboratory Retrofit

Sequence of Operations 2021/09/07

Second Fume Hood Alarms:


Fume Hood Alarms: While the unit is in alarm, the audible alarm can be silenced but will re-engage after an adjustable time delay. Audible and
visual alarms are available for face velocity, low/high valve pressure, sash height, and emergency.

Face Velocity: The Fume Hood Control System (FCS) will alarm if the measured face velocity drops below the adjustable low alarm limit or
rises above the adjustable high alarm limit.

Valve Pressure Alarms: The Fume Hood Control System (FCS) will alarm if the pressure across the Venturi Valve drops below the minimum or
rises above the maximum operating pressure for the valve.

Sash Alarm: The Fume Hood Control System (FCS) will alarm if the sash height is above the sash height alarm limit. The FCS will also alarm if
the sash position sensor cable fails or reports a value outside of the initially calibrated range.