Typical Laboratory
Sales Rep
Antec Controls by Price
Consulting Engineer
Antec Controls by Price
Typical Laboratory
Schedule 2021/09/07
Enclosure Assembly
Actuator Response
Calibration Method
Connection Type
Actuator Control
Pressure Range
Control Type
Room Offset
VA Required
Accessories
Valve Model
Application
Orientation
Body Type
MAX Flow
Insulation
Valve Tag
MIN Flow
Unit Size
Controls
Quantity
Coating
Room
(CFM)
(CFM)
(CFM)
(CFM)
Notes
VFX SAV-LAB Laboratory SAV 114 2150 1280 1280 200 - - - IN SL - PACE - HSA FCP - - - 40.0 1 1, 2, 3
VFX GEV-LAB Laboratory GEV 114 2150 530 530 200 - - - SL - PACE - HSA FOP - - - 40.0 1 1, 2, 3
VFX FEV-LAB1 Laboratory FEV 108 400 100 0 200 - - - P1 SL - FVM - HSA FOP - - - 39.0 1 1, 2, 3
VFX FEV-LAB2 Laboratory FEV 108 400 100 0 200 - - - P1 SL - FVM - HSA FOP - - - 39.0 1 1, 2, 3
VFX OEV-LAB Laboratory OEV 108 150 80 0 200 - - - P1 SL - PACE - HSA FOP - - - 40.0 1 1, 2, 3
Nomenclature:
108 8" Diameter - Single Body 114 14" Diameter - Single Body FCP Fail Closed Position
FEV Fume Hood Exhaust Valve FOP Fail Open Position FVM Fume Hood Valve Module
GEV General Exhaust Valve HSA High Speed Actuator IN 3/4" External Foam Insulation
OEV Other Exhaust Valve (eg. Biosafety Cabinets/ Snorkels/ etc) P1 Phenolic Coating (Heresite Class 1) PACE PACE Controller
SAV Supply Air Valve SL Slip Connection VFX Venturi FX Valve
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
3. VA Draw for all valves in above schedule includes power requirement for Controls and Actuator.
Typical Laboratory
Schedule 2021/09/07
Controller Schedule
VA Required
Valve Type
Valve Tag
Quantity
Room
Notes
CAVA FEV-LAB1 Laboratory - - - 12.0 1 1, 2
CAVA FEV-LAB2 Laboratory - - - 12.0 1 1, 2
Nomenclature:
CAVA Cava Touchscreen Fume Hood Controller
Notes:
1. Installation and wiring of equipment by Others.
2. See ProdSubmittal for option details.
Typical Laboratory
Schedule 2021/09/07
VCT Schedule
Valve Accessories Model
Connection Type
Material Type
Quantity
Notes
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
Typical Laboratory
Schedule 2021/09/07
VIT Schedule
Valve Accessories Model
Quantity
Notes
VIT 1 1, 2, 3
Nomenclature:
VIT Valve Installation Tape
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
3. VIT to be used on coated valves only.
Typical Laboratory
Schedule 2021/09/07
ES Schedule
Room Control Accessories
Setpoint Adjustment
Relative Humidity
Carbon Dioxide
Display Type
Sensor Type
Room Name
Occupancy
Valve Tag
Quantity
Model
Notes
ES SAV-LAB Laboratory DT 1 1, 2
ES SAV-LAB Laboratory RM LCD BTN 1 1, 2
Nomenclature:
BTN Pushbutton Setpoint Adjustment
DT Duct Mounted Sensor
ES Environmental Sensor
LCD LCD Display
RM Room Temperature Sensor
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
Typical Laboratory
Schedule 2021/09/07
Retrofit Accessory
Mounting Config
Sash Length
VA Required
Valve Type
Valve Tag
Quantity
Room
Notes
SPS FEV-LAB1 Laboratory 50 - - - - 1 1, 2
SPS FEV-LAB2 Laboratory 50 - - - - 1 1, 2
SVS FEV-LAB1 Laboratory - - - - 17.0 1 1, 2
FPS FEV-LAB1 Laboratory - - - 10.0 1 1, 2
Nomenclature:
FPS Fume Hood Presence Sensor
SPS Sash Position Sensor
SVS Sidewall Velocity Sensor
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
Typical Laboratory
Schedule 2021/09/07
Coil Capacity
Heating Flow
Access Door
Fluid Type
Fluid Flow
Valve Tag
Coil Type
Unit Size
(in. w.g.)
Quantity
(ft. w.g.)
Glycol
(GPM)
(MBH)
(CFM)
Notes
(°F)
(°F)
(°F)
(°F)
(%)
VVHWC SAV-LAB 114 2150 SC 2R WTR 0.00 55.0 180.0 82.2 114.9 2.00 0.42 63.3 0.51 AD CSL 1 1, 2
Nomenclature:
2R Right Hand Two Row 114 14" Diameter - Single Body
AD Coil Access (upstream) Fastened w/ Screws CSL Heating Coil Shipped Loose
SC Standard Capacity Hot Water Coil VVHWC Hot Water Reheat Coil
Notes:
1. Installation and wiring of equipment by Others.
2. See Product Submittal for option details.
Typical Laboratory
Schedule 2021/09/07
Sound Performance
Pressure Drop
Valve Model
MAX Flow
Valve Tag
MIN Flow
Unit Size
(in. w.g.)
Quantity
Levels
Levels
Levels
Levels
Levels
Levels
Room
(CFM)
(CFM)
Notes
VFX SAV-LAB Laboratory 114 2150 1280 - 0.14 53 48 49 46 43 38 35 28 32 29 30 22 63 53 50 44 39 35 59 53 53 50 47 42 33 34 38 34 34 31 71 60 55 48 43 39 1 1, 2, 3, 4
VFX GEV-LAB Laboratory 114 2150 530 - 0.14 41 40 42 39 36 31 33 -- 24 22 24 -- 49 43 41 36 32 28 59 53 53 50 47 42 33 34 38 34 34 31 71 60 55 48 43 39 1 1, 2, 3, 4
VFX FEV-LAB1 Laboratory 108 400 100 - 0.08 38 37 42 35 32 31 30 -- -- -- -- -- 45 38 37 32 29 30 59 46 46 41 40 38 34 26 27 28 28 27 65 49 46 42 38 38 1 1, 2, 3, 4
VFX FEV-LAB2 Laboratory 108 400 100 - 0.08 38 37 42 35 32 31 30 -- -- -- -- -- 45 38 37 32 29 30 59 46 46 41 40 38 34 26 27 28 28 27 65 49 46 42 38 38 1 1, 2, 3, 4
VFX OEV-LAB Laboratory 108 150 80 - 0.02 38 37 42 35 32 31 30 -- -- -- -- -- 45 38 37 32 29 30 44 40 43 37 34 33 31 21 20 22 22 21 51 42 39 35 31 32 1 1, 2, 3, 4
Nomenclature:
108 8" Diameter - Single Body 114 14" Diameter - Single Body VFX Venturi FX Valve
Notes:
1. Test obtained in accordance with AHRI Standard 880 and ASHRAE Standard 130.
2. See Product Submittal for option details.
3. Blanks (--) in schedule indicate values less than 20dB.
4. VFX pressure drop tested in accordance to ASHRAE 130:2016
VFX-1-X
Venturi FX Valve Sheet 1 of 4
270128
Rev. F
Product Submittal 2022/01/18
VFX SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)
VALVE BODY 14 Ga ALUMINUM
UNCOATED: TWO 24 Ga GALVANIZED STEEL PLATES AND TEFLON GASKET
MOUNTED ON A ZINC PLATED STEEL SHAFT.
DAMPER ASSEMBLY
COATED: TWO 22 Ga 316 STAINLESS STEEL PLATES AND A TEFLON
GASKET MOUNTED ON A 316 STAINLESS STEEL SHAFT.
PRESSURE SENSOR 316 STAINLESS STEEL TUBES
SINGLE VALVE
LOW PRESSURE TAP
HIGH PRESSURE TAP D -1/8" (3)
DUAL VALVE
1.50 (38)
L W
270128
Rev. F
Product Submittal 2022/01/18
CONTROL ENCLOSURE
6.26 (160)
6.26 (160) 6.15 (156)
16.00 (406)
GALVANIZED 6.15 (156)
CONTROLS
ENCLOSURE
16.00
(406)
INSULATION OPTION
COATING OPTION
PHENOLIC COATING - VALVE BODY (P1)
270128
Rev. F
Product Submittal 2022/01/18
UNIT X Y A B
SIZE in.(mm) in.(mm) in. (mm) in. (mm)
A 212 27.250 (692) 14.250 (362) 6.675(170) 6.850 (174)
214 31.250 (794) 16.250 (413) 7.675 (195) 7.850 (199)
Y
B .275 (7)
A
.275 (7)
X FLANGE CORNER
DETAIL A
270128
Rev. F
Product Submittal 2022/01/18
FLP 019127-002 1
SSA
FOP/FCP 019128-014 1
108
FLP 019127-001 1
HSA
FOP/FCP 019127-003 1
FLP 019127-002 1
SSA
FOP/FCP 019128-014 1
110
FLP 019127-001 1
HSA
FOP/FCP 019127-003 1
FLP 019127-002 1
SSA
FOP/FCP 019128-014 1
112
FLP 019127-001 1
HSA
FOP/FCP 019127-003 1
FLP 019127-002 1
SSA
FOP/FCP 019128-014 1
114
FLP 019127-001 1
HSA
FOP/FCP 019127-003 1
FLP 019127-002 2
SSA
FOP/FCP 019128-014 2
212
FLP 019127-001 2
HSA
FOP/FCP 019127-003 2
FLP 019127-002 2
SSA
FOP/FCP 019128-014 2
214
FLP 019127-001 2
HSA
FOP/FCP 019127-003 2
270117
Product Submittal Rev. O
2022/07/21
PACE SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)
24 VAC, 50/60 Hz SINGLE PHASE, 75 VA MAX (18 VA EXCLUDING EXTERNAL
INPUT POWER
LOADS), CLASS 2 or LPS PELV
1. ANTEC TOOLBOX
CONTROL PRIORITY ORDER 2. BACNET
3. NORMAL OPERATION
DIMENSIONS:
8.90 (226) 1.22 (31)
1.89 (48)
8.31 (211)
9.55 (243)
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270117
Product Submittal Rev. O
2022/07/21
TERMINATION:
+
-
COM
SIG
SIG
AO3
AO4
POT 2 POT 1
NETCOM
EARTH
24VAC
VCOM
VBUS
COM
COM
COM
COM
COM
COM
RX +
RX +
TX +
TX +
BO1
BO2
AO1
AO2
RX -
RX -
TX -
TX -
BI1
BI2
AI1
AI2
AI3
AI4
T1
T2
+
+
-
RX - A I1 A NALOG INPUT 1
NETCOM BA CNET COM , SIN COM , FHN COM OUTP UTS AO4 A NALOG OUTP UT 4
NET 2 + BA CNET +, SIN +, FHN + COM A NALOG OUTP UT GROUND
MOUNT:
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270117
Product Submittal Rev. O
2022/07/21
SPECIFICATIONS:
MATERIAL 22 Ga GALV. STEEL
MOUNT WALL MOUNT
KNOCKOUTS 12 x .875in, FOR 0.5in TRADE SIZE CONDUIT
DIMENSIONS:
18.70 475
2.35 60 14.00 356
.350 9
O .875
(x12) 2.38 60
3.04 77
MOUNTING DETAILS:
16.00 406
6.51 165
O .164
(x4)
Solid Edge
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270117
Product Submittal Rev. O
2022/07/21
Write
Object Name Units Range Description
Setting
ANALOG INPUTS
Note: Analog input AI1 will display as AI11 for Controller 1, AI21 for Controller 2, etc.
Analog Input w ith multiple uses
AI#1 [Controller name] AI1 – [AI1 Device name] Dynamic Dynamic R
See Input section of the Antec Toolbox manual for options
Analog Input w ith multiple uses
AI#2 [Controller name] AI2 – [AI2 Device name] Dynamic Dynamic R
See Input section of the Antec Toolbox manual for options
Analog Input w ith multiple uses
AI#3 [Controller name] AI3 – [AI3 Device name] Dynamic Dynamic R
See Input section of the Antec Toolbox manual for options
Analog Input w ith multiple uses
AI#4 [Controller name] AI4 – [AI4 Device name] Dynamic Dynamic R
See Input section of the Antec Toolbox manual for options
-40 to 250 °F
AI#5 [Controller name] T1 – [T1 Device name] °F or °C Thermistor reading R
(-40 to 121 °C)
-40 to 250 °F
AI#6 [Controller name] T2 – [T2 Device name] °F or °C Thermistor reading R
(-40 to 121 °C)
BINARY INPUTS
Note: Binary input BI1 will display as BI11 for Controller 1, BI21 for Controller 2, etc.
Binary Input w ith multiple uses
BI#1 [Controller name] BI1 – [BI1 Device name] Open/Closed Open/Closed R
See Input section of the Antec Toolbox manual for options
Binary Input w ith multiple uses
BI#2 [Controller name] BI2 – [BI2 Device name] Open/Closed Open/Closed R
See Input section of the Antec Toolbox manual for options
Binary Input w ith multiple uses
BI#3 [Controller name] BI3 – [BI1 Device name] Open/Closed Open/Closed See Input section of the Antec Toolbox manual for options R
Hidden when controller is not a Cava™
Binary Input w ith multiple uses
BI#4 [Controller name] BI4 – [BI2 Device name] Open/Closed Open/Closed See Input section of the Antec Toolbox manual for options R
Hidden when controller is not a Cava™
ANALOG OUTPUTS
Note: Analog output AO1 will display as AO11 for Controller 1, AO21 for Controller 2, etc.
Analog Output w ith multiple uses
AO#1 [Controller name] AO1 – [AO1 Device name] VDC 0 to 10 R/W
See Output section of the Antec Toolbox manual for options
Analog Output w ith multiple uses
AO#2 [Controller name] AO2 – [AO2 Device name] VDC 0 to 10 R/W
See Output section of the Antec Toolbox manual for options
Analog Output w ith multiple uses
AO#3 [Controller name] AO3 – [AO3 Device name] VDC 0 to 10 R/W
See Output section of the Antec Toolbox manual for options
Analog Output w ith multiple uses
AO#4 [Controller name] AO4 – [AO4 Device name] VDC 0 to 10 R/W
See Output section of the Antec Toolbox manual for options
BINARY OUTPUTS
Note: Analog output BO1 will display as BO11 for Controller 1, BO21 for Controller 2, etc.
Binary Output w ith multiple uses
BO#1 [Controller name] BO1 – [BO1 Device name] Active/Inactive Active/Inactive R/W
See Output section of the Antec Toolbox manual for options
Binary Output w ith multiple uses
BO#2 [Controller name] BO2 – [BO2 Device name] Active/Inactive Active/Inactive R/W
See Output section of theAntec Toolbox manual for options
ANALOG VALUE
-5.0 to 5.0 in.w .c. Current room pressure setpoint
AV1 Room Pressure Setpoint in.w .c.; Pa R/W
(-1245 to 1245 Pa) Hidden when pressure control not used
-5.0 to 5.0 in.w .c.
AV2 Room Pressure in.w .c.; Pa Current room pressure R
(-1245 to 1245 Pa)
-5.0 to 5.0 in.w .c.
AV3 Room Pressure Low Alarm in.w .c.; Pa Low room pressure alarm setpoint (+/-) R/W
(-1245 to 1245 Pa)
-5.0 to 5.0 in.w .c.
AV4 Room Pressure High Alarm in.w .c.; Pa High room pressure alarm setpoint (+/-) R/W
(-1245 to 1245 Pa)
-50000 to 50000 CFM Current airflow offset setpoint
AV5 Airflow Offset Setpoint CFM; L/s R/W
(-23600 to 23600 L/s) Hidden when offset control not used
Solid Edge
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270117
Product Submittal Rev. O
2022/07/21
Write
Object Name Units Range Description
Setting
ANALOG VALUE
-50000 to 50000 CFM
AV6 Airflow Offset Actual CFM; L/s Current airflow offset (+/-) R
(-23600 to 23600 L/s)
0 to 50000 CFM
AV7 Total Exhaust Airflow Target CFM; L/s Total room exhaust airflow target R
(0 to 23600 L/s)
0 to 50000 CFM
AV8 Total Exhaust Airflow Actual CFM; L/s Total room exhaust airflow R
(0 to 23600 L/s)
0 to 50000 CFM
AV9 Total Supply Airflow Target CFM; L/s Total room supply airflow target R
(0 to 23600 L/s)
0 to 50000 CFM
AV10 Total Supply Airflow Actual CFM; L/s Total room supply airflow R
(0 to 23600 L/s)
0 to 100000000 ft^3
AV12 Room Volume ft3; m3 Room volume R/W
(0 to 2831685 m^3)
AV13 Current Air Change Rate # 0.0 to 100.0 Current air change rate R
-40 to 250 °F
AV15 Temperature Reading - Zone 1 °F;°C Current temperature in zone 1 R
(-40 to 121 °C)
-40 to 250 °F
AV20 Room Temperature Setpoint - Low Limit °F;°C Low est user-adjustable temperature setpoint on the thermostat R/W
(-40 to 121 °C)
-40 to 250 °F
AV21 Room Temperature Setpoint - High Limit °F;°C Highest user-adjustable temperature setpoint on the thermostat R/W
(-40 to 121 °C)
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270117
Product Submittal Rev. O
2022/07/21
BACNET POINTS LIST v2.0.0 OR NEWER (CONTINUED)
Write
Object Name Units Range Description
Setting
0 to 50000 CFM
AV81 [Mode name #1] - Room Min CFM; L/s Room flow minimum for the default room mode R/W
(0 to 23600 L/s)
0 to 50000 CFM
AV82 [Mode name #1] - Room Heating Max CFM; L/s Room flow heating maximum for the default room mode R/W
(0 to 23600 L/s)
0 to 50000 CFM
AV83 [Mode name #1] - Room Cooling Max CFM; L/s Room flow cooling maximum for the default room mode R/W
(0 to 23600 L/s)
0 to 50000 CFM Room flow minimum for the second room mode
AV84 [Mode name #2] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 2 room modes
0 to 50000 CFM Room flow heating maximum for the second room mode
AV85 [Mode name #2] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 2 room modes
0 to 50000 CFM Room flow cooling maximum for the second room mode
AV86 [Mode name #2] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 2 room modes
0 to 50000 CFM Room flow minimum for the third room mode
AV87 [Mode name #3] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 3 room modes
0 to 50000 CFM Room flow heating maximum for the third room mode
AV88 [Mode name #3] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 3 room modes
0 to 50000 CFM Room flow cooling maximum for the third room mode
AV89 [Mode name #3] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 3 room modes
0 to 50000 CFM Room flow minimum for the fourth room mode
AV90 [Mode name #4] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 4 room modes
0 to 50000 CFM Room flow heating maximum for the fourth room mode
AV91 [Mode name #4] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 4 room modes
0 to 50000 CFM Room flow cooling maximum for the fourth room mode
AV92 [Mode name #4] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 4 room modes
0 to 50000 CFM Room flow minimum for the fifth room mode
AV93 [Mode name #5] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 5 room modes
0 to 50000 CFM Room flow heating maximum for the fifth room mode
AV94 [Mode name #5] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 5 room modes
0 to 50000 CFM Room flow cooling maximum for the fifth room mode
AV95 [Mode name #5] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 5 room modes
0 to 50000 CFM Room flow minimum for the sixth room mode
AV96 [Mode name #6] - Room Min CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 6 room modes
0 to 50000 CFM Room flow heating maximum for the sixth room mode
AV97 [Mode name #6] - Room Heating Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 6 room modes
0 to 50000 CFM Room flow cooling maximum for the sixth room mode
AV98 [Mode name #6] - Room Cooling Max CFM; L/s R/W
(0 to 23600 L/s) Hidden if using using less than 6 room modes
Solid Edge
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270117
Product Submittal Rev. O
2022/07/21
BACNET POINTS LIST v2.0.0 OR NEWER (CONTINUED)
Write
Object Name Units Range Description
Setting
Note: Analog value AV#01 will display as AV101 for Controller 1, AV201 for Controller 2, etc.
[Controller name] Flow - [Transducer Device 0 to 50000 CFM Transducer airflow reading
AV#04 CFM; L/s R
name] (0 to 23600 L/s) Hidden when airflow source is not transducer
0 to 1000 FPM Displays the current face velocity across the fume hood
AV#15 [Controller name] Face Velocity FPM; m/s R
(0 to 5.08 m/s) Hidden when controller is not a Cava™
MULTISTATE VALUE
Displays the current airflow control sequence
1 - Constant Flow Control
MV1 Airflow Control Sequence Text 3 states R
2 - Pressure Control
3 - Offset Control
Displays the current room pressure mode
MV2 Room Pressure Mode Text 2 states 1 - Positive R
2 - Negative
Solid Edge
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270117
Product Submittal Rev. O
2022/07/21
Write
Object Name Units Range Description
Setting
MULTISTATE VALUE
Displays the current room alarm status
1 - Controller Not Responding
2 - Missing Room Pressure Sensor
3 - Diversity
4 - Binary Input
5 - Mode Alarm
6 - Door Open
MV3 Room Alarm Status Text 13 states R
7 - Room Low Pressure
8 - Room High Pressure
9 - Low Airflow
10 - Low Valve Pressure
11 - High Airflow
12 - High Valve Pressure
13 - No Alarm
Displays the current room mode
1 - [Default Room Mode Name]
2 - [Custom Room Mode 1 Name]
MV4 Room Mode Text 6 states 3 - [Custom Room Mode 2 Name] R/W
4 - [Custom Room Mode 3 Name]
5 - [Custom Room Mode 4 Name]
6 - [Custom Room Mode 5 Name]
Displays the current room mode override
1 - [Default Room Mode Name]
2 - [Custom Room Mode 1 Name]
MV5 Room Mode Override Text 6 states 3 - [Custom Room Mode 2 Name] R/W
4 - [Custom Room Mode 3 Name]
5 - [Custom Room Mode 4 Name]
6 - [Custom Room Mode 5 Name]
Displays the current firmw are update status
1 - Idle
MV99 Firmw are Update Status Text 4 states 2 - Start Firmw are Update R/W
3 - Updating Firmw are
4 - Firmw are Update Failed
Note: Multistate value MV#3 will display as MV13 for Controller 1, MV23 for Controller 2, etc…
270117
Product Submittal Rev. O
2022/07/21
Write
Object Name Units Range Description
Setting
FILE
The file object used for firmw are upgrades -
FIL1 Firmw are - - W
feature only available if supported by BAS
CALENDAR
CAL1 Calendar Object - - The calendar object used for scheduling R/W
NOTIFICATION CLASS
EVC1 Notification Class object - - The notification class object for alarming R/W
SCHEDULE
SCH1 Room Mode Schedule - - The scheduling object for scheduling room mode changes R/W
NOTE: THE BACNET POINT NAMES CAN BE OVERRIDDEN USING ANTEC TOOLBOX AND MAY NOT MATCH THE NAMES LISTED IN THIS TABLE. THE INSTANCE NUMBERS
CAN BE USED IN THIS CASE TO IDENTIFY THE POINTS.
Solid Edge
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270117
Product Submittal Rev. O
2022/07/21
Write
Object Name Units Range Description
Setting
ANALOG VALUE
Note: Analog value AV#11 will display as AV111 for Fume Hood Controller (FHC) 1, AV211 for Fume Hood Controller (FHC) 2, etc.
0 to 50000 CFM
AV#11 Fume Hood # Airflow CFM; L/s Displays the current airflow being exhausted from the fume hood R
(0 to 23600 L/s)
0 to 1000 FPM
AV#12 Fume Hood # Face Velocity FPM; m/s Displays the current face velocity across the fume hood R
(0 to 5.08 m/s)
AV#13 Fume Hood # Sash Position % 0 to 100 Displays the current position of the sash on the fume hood R
Note: Multistate value MV#1 will display as MV11 for Fume Hood Controller (FHC) 1, MV21 for Fume Hood Controller (FHC) 2, etc…
NOTE: PLEASE REFER TO PACE MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST VALUE.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
272815
Product Submittal Rev. B
2021/08/09
FVM SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC, 50/60 Hz, 17 VA MAX, CLASS 2 or LPS PELV
CANbus,
INPUTS
1 TRANSDUCER, 0-4 in.w .c. (0-1000 Pa)
DIMENSIONS:
5.27 (134) 1.22 (31)
1.90 (48)
4.74 (120)
5.95 (151)
TERMINATION:
AO4
P OWER
COM INP UT P OWER, GROUND
CA NL CA Nbus LOW
PT
A O1 A NA LOG OUTP UT 1
L
CANH
CANL
COM
COM
COM
AO1
AO2
A O4 A NA LOG OUTP UT 4
MOUNT:
AIRFLOW DEVICE MOUNTED (DEFAULT)
Solid Edge
NOTE: PLEASE REFER TO CAVA MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
© Copyright Antec Controls by PRICE 2021
CAVA-1-X
Cava™ - Touchscreen Fume Hood Controller Sheet 1 of 4
CAVA SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 10%, 50/60 Hz, 12 VA MAX (EXCLUDING EXTERNAL LOADS), CLASS 2
CANbus
ROOM INFORMATION NETWORK
3.65 93 3.30 84
5.76 146 3.74 95
5.71 145
2.18 (55)
.92 23 1.12 29
TERMINATION:
VA C INP UT P OWER, HOT
+ B A CNET +
BO1
COM COM VAC
- B A CNET -
BO2
COM
CA NH CA Nbus NETWORK
UI4
CA NL
UI3 COM
+
B O1 B INA RY OUTP UT
-
B O2 B INA RY OUTP UT
CANL CANH COM
NOTE: PLEASE REFER TO CAVA MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -40⁰F to 176⁰F (-40⁰C to 80⁰C), 5% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 20%, 50/60 Hz, 22 VA, CLASS 2
CONTROL SIGNAL RANGE 2 to 10 VDC
6.30 160
DIMENSIONS:
DIRECTION OF ROTATION SWITCH
3.20 81
2.05 52
5.47 139
9.09 231
TERMINATION:
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270214
Rev. D
Product Submittal 2019/12/16
DBC SPECIFICATIONS:
BAND 3.5in. WIDTH
FOAM 0.25in., UL 94, ELASTOMERIC
HARDWARE BOLT AND LOCK NUTS
VALVE COMPANION SIZES 108, 110, 112, 114
VALVE COMPANION TYPE SLIP
CFL SPECIFICATIONS:
MATERIAL SEE MATERIAL OPTIONS BELOW
HARDWARE NOT INCLUDED
VALVE COMPANION SIZES 108, 110, 112, 114
VALVE COMPANION TYPE SLIP
DIMENSIONS:
A/2
ID
BC NUMBER BC OD A
ID UNIT (MAX DUCT OD)
OF BOLT
SIZE
HOLES in. (mm) in. (mm) Degrees in. (mm)
O .438 (11) 8 6 Ø 9.25" (235) Ø 10" (254) 60 Ø 8.25" (210)
10 6 Ø 11.25" (286) Ø 12" (305) 60 Ø 10.25" (260)
12 6 Ø 13.25" (337) Ø 15" (381) 60 Ø 12.25" (311)
OD 14 8 Ø 15.75" (400) Ø 17" (432) 45 Ø 14.25" (362)
ALUMINUM (AL)
316 STAINLESS STEEL (SS)
270216
Product Submittal Rev.A
2019/04/26
VIT SPECIFICATIONS:
MATERIAL: PTFE ADHESIVE TAPE
LENGTH: 108ft.
WIDTH: 2.0in.
Solid Edge
270215
Rev. G
Product Submittal 2020/06/09
ES-RM-LCD-BTN SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 122⁰F (0⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
STANDARD 2in. x 4in. (51mm x 102mm) J-BOX or
MOUNT
DRYWALL MOUNT
DISPLAY LCD SCREEN
15 to 40 VDC or 15 to 28 VAC. (DO NOT RUN AC POWER IN THE
INPUT POWER
SAME CONDUIT AS SIGNAL WIRES)
1 ANALOG (0 to 10 VDC):
OUTPUT
TEMPERATURE SETPOINT - RANGE: 50⁰F to 90⁰F (10⁰C to 32⁰C)
INPUT TYPE KEYPAD
TEMPERATURE READING 10K-2 THERMISTOR, ±0.36⁰F, 32⁰ to 158⁰F (±0.2⁰C, 0 to 70⁰C)
HOUSING UL 94 V-0, ABS PLASTIC
COMMUNICATION PORT RJ-45
.7 (18)
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270215
Rev. G
Product Submittal 2020/06/09
ES-DT SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) -40⁰F to 185⁰F (-4⁰C to 85⁰C), 0 to 95% R.H.(NON-CONDENSING)
TEMPERATURE READING 10K-2 THERMISTOR, ±0.36⁰F, 32⁰ to 158⁰F (±0.2⁰C, 0 to 70⁰C)
PROBE 304 STAINLESS STEEL PROBE, 0.25in. (7mm) DIAMETER, 6in. (152mm) LENGTH
HOUSING PC PLASTIC, UL 94 V-0, IP10, NEMA1
DIMENSIONS:
2.1 (53)
.25 6
3.0 (76) 2.67 (68)
6.0 152
8.0 202
1.78 (45)
TERMINATION:
YELLOW
YELLOW
YELLOW
THERM ISTOR RESISTA NCE OUTP UT
YELLOW
270115
Product Submittal Rev. D
2021/07/13
FPS SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 50⁰F to 122⁰F (10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 10%, 10 VA, CLASS 2
DETECTION DOPPLER SHIFT RADAR
DETECTION PATTERN SELECTABLE, WIDE OR NARROW
OUTPUTS 1 BINARY OUTPUT (DRY CONTACT FORM C, MAX: 1A)
MAX. MOUNTING HEIGHT 15ft (4.6m)
PLASTIC HOUSING ABS COVER AND BASE
5.75 (146)
6.50 (165)
O 2.75 (70)
TERMINATION:
BLACK
RED
BROWN
WHITE B LA CK INP UT P OWER, GROUND
GREEN
RED INP UT P OWER, HOT
B ROWN RELA Y, N/O
NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS.
SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Solid Edge
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
270123
Product Submittal Rev. C
2019/04/26
SPS SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) -50⁰F to 120⁰F (-10⁰C to 50⁰C), 5% to 95% R.H.(NON-CONDENSING)
OUTPUT SIGNAL VOLTAGE DIVIDER UTILIZING 10K POT
CONNECTION TYPE 2-WIRE
MEASURING CABLE NYLON COATED STAINLESS STEEL
STROKE RANGE 0 to 50in. (0 to 1270mm)
HOUSING IP 50 PLASTIC
ACCURACY ±0.25% FS
DIMENSIONS:
O.14 (4)
(2x)
3.5 (90)
1.4 (36)
1.8 (46)
1.45 (37)
2.0 (51)
O.19 (5)
2.0 (51)
3.6 (91)
TERMINATION:
BLACK
GREEN
SA SH P OSITION FEEDB A CK
GREEN RED
RED
B LA CK NOT REQUIRED
NOTE: PLEASE REFER TO FHC MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS
SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
Solid Edge
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
273420
Product Submittal Rev. A
2021/06/28
SVS SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 32⁰F to 130⁰F (0⁰C to 55⁰C), 5% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 158⁰F (-30⁰C to 70⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC, 50/60 Hz, 17 VA MAX, CLASS 2 or LPS PELV
CANbus,
INPUTS
1 TRANSDUCER, -0.5 to 0.5 in.w .c. (-125 to 125 Pa)
DIMENSIONS:
5.27 134 1.22 31
1.90 48
4.74 120
5.95 151
TERMINATION:
CA NL CA Nbus LOW
PT
A O1 A NA LOG OUTP UT 1
L
A NA LOG
COM A NA LOG OUTP UT GROUND
OUTP UTS
POWER CANbus A O2 A NA LOG OUTP UT 2
24VAC
CANH
CANL
COM
COM
COM
AO1
AO2
MOUNT:
SHIPPED LOOSE
Solid Edge
NOTE: PLEASE REFER TO CAVA MANUAL FOR INSTALLATION INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
© Copyright Antec Controls by PRICE 2021
VVHWC-1-X
Valve Hot Water Coil Sheet 1 of 4
270129
Rev. G
Product Submittal 2022/01/18
D C OA
NOTE: CONFIGURATION WITH SINGLE ADAPTER SHOWN.
ADD 10 7/8"(276) LENGTH OF SECOND ADAPTER
FOR TOTAL LENGTH OF UNIT WITH
SEE NOTE #7 8"(203) UPSTREAM AND DOWNSTREAM ADAPTERS.
O1/2"(13) @ 3"(76)
O7/8"(22) @ 4 1/4(108) 10 7/8"(276)
BEAD-IN VVHWC, B x C
INLET, ØA
TOP & BOTTOM ACCESS DOOR
4" x 6 3/4" (102 x 171)
NOTES: 1. FABRICATED FROM 22 GA. GALVANIZED STEEL, MECHANICALLY SEALED, LEAK RESISTANT CONSTRUCTION.
2. HOT WATER COILS HAVE COPPER TUBES AND ALUMINUM FINS WITH O.D. SWEAT CONNECTIONS.
3. REFER TO SUBMITTED TERMINAL UNIT SCHEDULE FOR AIR VOLUMES AND HOT WATER COIL CAPACITIES.
4. METHOD OF VENTING HOT WATER COIL IS TO BE PROVIDED BY INSTALLING CONTRACTOR.
5. ACCESS DOORS WITH GASKETED PERIMETER FOR INSPECTION AND MAINTENANCE OF COIL, TOP & BOTTOM.
6. HAND OF HOT WATER COIL CONNECTIONS IS DETERMINED WHEN VIEWED FROM AIR INLET SIDE.
7. ALLOW 1 1/2 " (38) MINIMUM CLEARANCE FOR INSTALLATION AT THIS END.
8. CONFIGURATION OF COIL CONNECTION VARIES WITH SIZE & CIRCUITRY OF COIL.
9. PERFORMANCE RATED AND CERTIFIED IN ACCORDANCE WITH THE CURRENT EDITION OF AHRI STANDARD 410.
10. IT IS NOT RECOMENDED TO REVERSE 3 & 4 ROW COILS. INDICATE HANDING WHILE ORDERING.
11. STANDARD COILS SUPPLIED WITH 10 FINS PER INCH / HIGH CAPACITY COILS SUPPLIED WITH 12 FINS PER INCH.
12. HIGH CAPACITY ONLY AVAILABLE FOR 1 AND 2 ROW COILS.
13. LEAK TESTED TO A MINIMUM OF 390 POUNDS PER SQUARE INCH WITH A MINIMUM BURST PRESSURE OF 1800 POUNDS PER SQUARE INCH.
NOTE: PLEASE REFER TO VV MANUAL FOR INSTALLATION INSTRUCTIONS.
Solid Edge
270129
Rev. G
Product Submittal 2022/01/18
VENTURI VALVE WITH OVERSIZED HIGH CAPACITY (OHC) HWC. ONLY 1 & 2 ROW HC COILS AVAILABLE
NOTE: OVERSIZED WATER COIL OPTION UTILIZES AN ADAPTER ONE SIZE LARGER THAN STANDARD VENTURI UNIT.
RH WATER COIL
RIGHT HAND (R) HWC / CONTROL UP (CVT) AIRFLOW
CONTROL UP
SHOWN
RIGHT HAND (R) HWC / CONTROL DOWN (CVB)
RIGHT HAND (R) HWC / CONTROL LH (CVL)
RIGHT HAND (R) HWC / CONTROL RH (CVR)
SLIP & DRIVE
LEFT HAND (L) HWC / CONTROL UP (CVT) OPTIONAL CONNECTION
CONTROLS ENCLOSURE TOP VIEW
LEFT HAND (L) HWC / CONTROL DOWN (CVB)
RH WATER COIL
LEFT HAND (L) HWC / CONTROL LH (CVL)
AIRFLOW OPTIONAL
LEFT HAND (L) HWC / CONTROL RH (CVR) CONTROL UP SILENCER
SHOWN
TOP VIEW
CONTROLS ENCLOSURE
LEFT HAND (L) HWC / CONTROL UP (CVT) SLIP&DRIVE
CONNECTION
TOP VIEW
LEFT HAND (L) HWC / CONTROL DOWN (CVB)
RH WATER COIL
CONTROL UP
SHOWN
OPTIONAL
CONTROLS ENCLOSURE
270129
Rev. G
Product Submittal 2022/01/18
OPTIONAL OPTIONAL
COIL ACCESS DOOR COIL ACCESS DOOR
4" x 6 3/4" (102 x 171), 4" x 6 3/4" (102 x 171),
TOP & BOTTOM, TOP & BOTTOM,
UPSTREAM NOT INSULATED UPSTREAM NOT INSULATED
ADAPTOR ADAPTOR DOWNSTREAM
ADAPTOR
WATER COIL
WATER COIL
AIRFLOW AIRFLOW
OPTIONAL
UPSTREAM COIL ACCESS DOOR
TRANSITION 4" x 6 3/4" (102 x 171), OPTIONAL
TOP & BOTTOM,
COIL ACCESS DOOR
NOT INSULATED
UPSTREAM 4" x 6 3/4" (102 x 171),
TOP & BOTTOM,
TRANSITION
NOT INSULATED
WATER COIL
WATER COIL
AIRFLOW AIRFLOW
DOWNSTREAM
WATER COIL
TRANSITION
CONNECTIONS
SLIP & DRIVE
WATER COIL
CONNECTIONS CONNECTION
Sequence Number: 1
Sequence Type: Flow Offset Control
Room(s): Laboratory
Single Stage Cooling - Stage I: Added Airflow: The Airflow Control System (ACS) will monitor room temperature from a wall mounted room
temperature sensor. In the first cooling stage, the airflow will increase (between the Room Mode Minimum Airflow and the Room Mode
Maximum Airflow) to maintain space temperature.
Modes of Operation:
Occupied Mode (Default): Occupied Mode is the default room mode. While in Occupied Mode, the Airflow Control System (ACS) will target
the scheduled occupied airflows.
Unoccupied Mode: The Airflow Control System (ACS) will activate Unoccupied Mode by contact input.
While in Unoccupied Mode, the ACS will target the scheduled unoccupied airflows.
Occupied Mode (Default): Occupied Mode is the default fume hood mode. While in Occupied Mode, the Fume Hood Control System (FCS)
will target the scheduled occupied face velocity while maintaining the scheduled occupied airflows.
Unoccupied Mode: The Fume Hood Control System (FCS) will activate Unoccupied Mode by contact input. While in Unoccupied Mode, the
FCS will target the scheduled unoccupied face velocity while maintaining the scheduled unoccupied airflows.
Emergency Mode: The Fume Hood Control System (FCS) will active Emergency Mode when the "Emergency" button on the touchscreen
fume hood interface is pressed. The air device will modulate to its maximum airflow to purge the fume hood. A visual and audible alarm will
activate to indicate that the fume hood is being purged. Emergency Mode can be deactivated by pressing and holding the "Emergency" button
for 5 seconds.
Face Velocity: The Fume Hood Control System (FCS) will alarm if the measured face velocity drops below the adjustable low alarm limit or
rises above the adjustable high alarm limit.
Sash Alarm: The Fume Hood Control System (FCS) will alarm if the sash height is above the sash height alarm limit. The FCS will also alarm
if the sash position sensor cable fails or reports a value outside of the initially calibrated range.
Equipment Exhaust:
Dual-flow Set Point (PACE controlled): A two-position switch (provided by others) will provide the binary state to the Airflow Control System
(ACS). The ACS will update the airflow set point to either the active set point (when binary is in active state) or the inactive set point (when the
binary is in inactive state).
Occupied Mode (Default): Occupied Mode is the default fume hood mode. While in Occupied Mode, the Fume Hood Control System (FCS) will
target the scheduled occupied face velocity while maintaining the scheduled occupied airflows.
Unoccupied Mode: The Fume Hood Control System (FCS) will activate Unoccupied Mode by:
O Contact input O Building Management System
While in Unoccupied Mode, the FCS will target the scheduled unoccupied face velocity while maintaining the scheduled unoccupied airflows.
Emergency Mode: The Fume Hood Control System (FCS) will active Emergency Mode when the "Emergency" button on the touchscreen fume
hood interface is pressed. The air device will modulate to a specific or maximum airflow to purge the fume hood. A visual and audible alarm will
activate to indicate that the fume hood is being purged. Emergency Mode can be deactivated by pressing the "Emergency" button.
Face Velocity: The Fume Hood Control System (FCS) will alarm if the measured face velocity drops below the adjustable low alarm limit or
rises above the adjustable high alarm limit.
Sash Alarm: The Fume Hood Control System (FCS) will alarm if the sash height is above the sash height alarm limit. The FCS will also alarm if
the sash position sensor cable fails or reports a value outside of the initially calibrated range.