You are on page 1of 8

KERJA-KERJA PEMASANGAN LAMPU LIMPAH SERTA KERJA-KERJA BERKAITAN DI PUSPEN SERI

ISKANDAR, PERAK DARUL RIDZUAN

NO. SEBUTHARGA : JKR(E) PK/SH(PY) 58 / 2022

BILL OF QUANTITIES (All quantities are Provisional And Will Be Subjected To Final Measurement)

RATE AMOUNT
ITEM DESCRIPTION UNIT QTY
(RM) (RM)

A PRELIMINARIES
1 Polisi Insuran merangkumi : - lot 1 3,500.00 3,500.00
i. Public Liabiliti / All Risk
ii. Workmen Compensation
iii. Nombor-nombor pendaftaran di bawah Skim
keselamatan Sosial Pekerja (PERKESO)
2 Menyediakan dan menyerahkan Lukisan Kerja Harga - 500.00 500.00
(Working Drawing) untuk kerja-kerja pemasangan pukal
elektrik kepada JKR(e) untuk diperiksa dan diluluskan
sebelum memulakan kerja ditapak dengan
mengunakan perisian AutoCad dalam bentuk hardcopy
A3

3 Membekal kertas A4 untuk tujuan dokumentasi (1 Box box 5 50.00 250.00


- 5 ream)
4 Membekal CD-R (50pcs) termasuk CD Sticker dan box 5 70.00 350.00
cover
5 Melaksanakan kerja-kerja pengujian bagi kerja-kerja Harga - 1,500.00 1,500.00
pendawaian yang dilaksanakan termasuk pukal
mengemukakan Sijil Penatahan Alat Ujian bagi setiap
ujian yang dilaksanakan seperti berikut:-
a) Line Continuity and Phase Sequence Test;
b) Continuity and Insulation Resistance Test;
c) Continuity and Insulation Resistance For Ring Final
Circuit Test;
d) Earth Electrode Resistance Test;
e) Insulation Resistance and Continuity Test;
f) Polarity Test;
g) RCCB Test.
**pengujian hendaklah disahkan oleh PW4

6 Menyediakan Laporan bergambar mengikut kemajuan Harga - 200.00 200.00


sebelum, semasa, selepas di Tapak secara hardcopy pukal
dan softcopy (pemacu USB 32G).
7 Kos berkaitan bagi penyediaan bon perlaksana dalam Harga - 36,515.25 36,515.25
bentuk jaminan bank/ jaminan insurans. pukal

SUB TOTAL A : RM 42,815.25


( CARRIED TO SUMMARY OF PRICES )
KERJA-KERJA PEMASANGAN LAMPU LIMPAH SERTA KERJA-KERJA BERKAITAN DI PUSPEN SERI ISKANDAR,
PERAK DARUL RIDZUAN

NO. SEBUTHARGA : JKR(E) PK/SH(PY) 58 / 2022

BILL OF QUANTITY (Quantities Are Provisional And Subjected to Remeasurement)

RATE AMOUNT BRAND'S NAME/


ITEM DESCRIPTION UNIT QTY
(RM) (RM) MODEL

PUSPEN SERI ISKANDAR

B LAMPU LIMPAH KESELAMATAN

1.0 LAMPU LUARAN

Supply And Install All stuff And Equipment According To


The Specifications And Requirements Of JKR. All prices
include labor, machinery and materials.

LAMPU LIMPAH KESELAMATAN JENIS LED

i) Wholesalers must examine the JKR specifications, namely


the Specification For Low Voltage Internal Electrical
Installation (LS-1).
ii) If the JKR officer (e) finds that any work carried out or any
equipment supplied, installed on the site does NOT
COMPLY with JKR specifications, JKR officer (e) is entitled
to issue instructions to the contractor to change
immediately without involving any additional cost.

1.1 10m mid-hinged type Hot-Dipped Galvanised Floodlight nos 33 5,800.00 191,400.00 mid-hinged type
Column two fibre service door, double slot hinge with door Hot-Dipped
stiffener and anti vandalism locking device c/w loop in loop Galvanised
out with hinged type cover concrete footing and other Column
necessary accessories.

( For 2 nos 220Watt LED Floodlight & For 1 nos 100Watt


LED Floodlight )

1.2 To supply and install range 220W LED IP66 floodlight with nos 62 1,980.00 122,760.00 220W LED IP66
high purity anodized polished aluminium deep draw floodlight
reflector, fix thermal resistant glass, IP65 die cast
aluminium body and 20kA-25kA range Surge Protection
Device.

1.3 To supply and install range 50W LED IP66 floodlight with nos 1 980.00 980.00 50W LED IP66
high purity anodized polished aluminium deep draw floodlight
reflector, fix thermal resistant glass, IP65 die cast
aluminium body and 20kA-25kA range Surge Protection
Device.

1.4 To supply and install range 100W LED IP66 floodlight with nos 4 1,289.00 5,156.00 100W LED IP66
high purity anodized polished aluminium deep draw floodlight
reflector, fix thermal resistant glass, IP65 die cast
aluminium body and 20kA-25kA range Surge Protection
Device.

1.5 2 nos. SPD (Surge Protection Device) for columns, 1 nos. nos 33 250.00 8,250.00 Surge Protection
earth electrode 16mm g.p x3m, 2 nos. cut-out c/w 2 nos. Device
fuse 10A, 4 nos. neutral link, liner board HDG cable tray
10mm x 100mm x 450m, cable gland as well as
termination work inside the service door.
KERJA-KERJA PEMASANGAN LAMPU LIMPAH SERTA KERJA-KERJA BERKAITAN DI PUSPEN SERI ISKANDAR,
PERAK DARUL RIDZUAN

NO. SEBUTHARGA : JKR(E) PK/SH(PY) 58 / 2022

BILL OF QUANTITY (Quantities Are Provisional And Subjected to Remeasurement)

RATE AMOUNT BRAND'S NAME/


ITEM DESCRIPTION UNIT QTY
(RM) (RM) MODEL
1.6 Lighting points using 2 X 2.5mm sq PVC/PVC cables for nos 66 160.00 10,560.00 PVC/PVC cables
phase and neutral circuits and 1 X 2.5mm sq PVC CPC for
floodlight columns

1.7 Lighting point using 2 X 2.5 s.q mm PVC cable & nos 1 270.00 270.00 PVC cable
protective conductor in surface G.S conduit c/w 20A DP
metalclad switch with neon indicating light.

1.8 To supply and install concrete footing suitable to mount nos 33 550.00 18,150.00 concrete footing
lighting column as per approval from C&S Engineer. The
contractor shall confirm the size of concrete footing with
the flood lighting column manufacturer to suit the soil
condition.

2.0 UNDERGROUND CABLE

The price includes the work of supplying, installing,


connecting, soldering the ends of the cable, digging
trenches, sowing sand, laying bricks / uPVC cable
protective covers (uPVC cable protective covers), burying,
plowing, stretching nylon rope 6mm gp orange 300mm
from ground surface and compress in accordance with
PWD standard rules including the price of labor, machinery
and materials. COPPER type cable and comply with the
following:-

i) The cable price shall include cable gland terminations,


connections, cable markers etc. according to the relevant
drawings.

ii) All cables crossing roads, drains and covered walkways


etc. shall be covered with galvanized iron pipes.

2.1 4 core 10 sq. mm PVC/SWA/PVC underground cable c/w PVC/SWA/PVC


cable gland type cable termination from :- underground
cable
i. Feeder Pillar to Flood light columns mtr 1100 80.00 88,000.00

2.2 4 core 25 sq. mm XLPE/SWA/PVC underground cable c/w XLPE/SWA/PVC


cable gland type cable termination from :- underground
cable
i. Exsiting MSB to FP '1' mtr 20 110.00 2,200.00

ii. Exsiting SSB to FP '2' mtr 20 110.00 2,200.00

2.3 2 core 16 sq. mm PVC/SWA/PVC underground cable c/w


cable gland type cable termination from :-

i. Feeder Pillar ke DB 'P' mtr 56 64.00 3,584.00

2.4 2 core 10 sq. mm PVC/SWA/PVC underground cable c/w


cable gland type cable termination from :-

i. DB 'P' to Flood light columns mtr 65 64.00 4,160.00


KERJA-KERJA PEMASANGAN LAMPU LIMPAH SERTA KERJA-KERJA BERKAITAN DI PUSPEN SERI ISKANDAR,
PERAK DARUL RIDZUAN

NO. SEBUTHARGA : JKR(E) PK/SH(PY) 58 / 2022

BILL OF QUANTITY (Quantities Are Provisional And Subjected to Remeasurement)

RATE AMOUNT BRAND'S NAME/


ITEM DESCRIPTION UNIT QTY
(RM) (RM) MODEL
2.5 To supply 100mm dia. Double Wall Corrugated HDPE mtr 800 53.00 42,400.00 Double Wall
pipes for road crossing, paved areas, concrete areas, etc, Corrugated HDPE
digging trenches to a depth of 750mm, arrange the ducting pipes
and backfilling, making good of site surface.

2.6 Diamond saw cutting for roads work, repairing, mtr 100 38.00 3,800.00
compressing and paving tarmac roads with tar in their
original condition.

2.7 Cable marker with lettering and sign at straight path, every nos 37 65.00 2,405.00
cable change of direction and every cable connection.

3.0 FEEDER PILLAR AND ACCESSORIES

The price includes supplying and installing all materials


according to JKR specifications and complying with the
following:-

i) All MSB, SSB, DB, FP shall be from "EXPOXY BAKED"


metal covered finish.
ii) Supply, installation, testing and commissioning
Switchboards complete with copper busbar, MCCB,
RCCB, MCB, etc. according to the drawings.

iii) All distribution boards and user units shall be of the metal-
covered / insulated type complete with Moulded Case
Circuit Breaker (MCCB), Residual Current Circuit Breaker
(RCCB), Miniature Circuit Breaker (MCB), etc. for a
complete installation system.

iv) All cables shall be of copper type and cable prices shall
include connections etc. according to specifications.

v) The successful tenderer must submit the relevant MSB /


SSB / DB / FP 'shop drawing' to JKR (e) for approval
review before reservation.
KERJA-KERJA PEMASANGAN LAMPU LIMPAH SERTA KERJA-KERJA BERKAITAN DI PUSPEN SERI ISKANDAR,
PERAK DARUL RIDZUAN

NO. SEBUTHARGA : JKR(E) PK/SH(PY) 58 / 2022

BILL OF QUANTITY (Quantities Are Provisional And Subjected to Remeasurement)

RATE AMOUNT BRAND'S NAME/


ITEM DESCRIPTION UNIT QTY
(RM) (RM) MODEL
3.1 Supply, deliver, install, test and commission of outdoor lot 2 16,000.00 32,000.00
weatherproof (IP54) electrogalvanised sheet steel
Feeder Pillar (25kA@400V 1sec) with busbar
compartment, 2mm thickness feeder pillar complete with
60A TPN MCCB, MCCB, MCB, RCCB, ELR, contactors,
power meter & quality monitoring analyzer, digital time
switch (Theben TR610 top3), Surge Protection Device with
Imax ≥ 65kA, Isc ≥ 20kA, Up ≤ 2kV c/w Fuse ( Fuse rating
as recommended by the manufacturer ) mode of
proctection : Phase - to - neutral & Neutral - to - earth,
(housed in separate compartment), photo cell, 2 nos x 1 x
(≤ 11W), (T8 LED) fitting, bypass switch, external
padlocking facilities with anti-chemical padlock, 13A S/S/O,
heater, indicator light (LED type), extended busbar c/w bi
metal lug, maintenance log book, laminated schematic,
anti sticker paint and other related accessories as per
drawings, specifications, JKR Approved. Heat shrinkable
must be used for incoming cable termination and cable
gland must be used for outgoing cable termination as per
drawing.
All extended busbar and accessories shall be used same
brand as MCCB.

3.2 To supply and install in-situ pre-cast grade 25/20 concrete lot 2 3,000.00 6,000.00
foundation footing c/w 100mm dia. UPVC duct for cable
entry, 4R20 main bar, loops R6-200mm, 16mm diameter
steel wall plug, 3 ft' apron concrete slap for feeder pillar
side and others accessories for mounting compound
lighting feeder pillar. The height of plinth is varies to finish
ground level include apron concrete slap for plinth (width -
3ft x thickness - 3 inch) and other accessories and etc as
per drawing.

3.3 4-Ways SPN Double Layer Outdoor Weatherproof (IP54)


Metalclad Wall Mounted CP c/w 1 no. 40A DP MCCB, 1
no. 63A DP RCCB (sen. 100mA), 4 no. 20A MCB, 1 no.
40A DP contactor, 40A DP changeover switches, digital
time switch (Theben TR610 top3) with daily/ weekly
program, bypass switches, looping wire, etc. as per
drawing and specification.

i. DB 'P' lot 1 1,850.00 1,850.00

4.0 EARTHING PROTECTION SYSTEM Copper tape

4.1 3mm x 25mm copper tape earthing conductor mtr 40 42.00 1,680.00
Earth Chamber
4.2 16mm (gp) x 3.0m long copper-plated steel core earth nos 9 650.00 5,850.00
electrode, including connection using "exorthermic
welding" method, concrete inspection chamber with
removable "heavy duty" removable cover and connection
to earthing termination panel and other work related.

SUB TOTAL B : RM 553,655.00


( CARRIED TO SUMMARY OF PRICES )
KERJA-KERJA PEMASANGAN LAMPU LIMPAH SERTA KERJA-KERJA BERKAITAN DI PUSPEN
SERI ISKANDAR, PERAK DARUL RIDZUAN

NO. SEBUTHARGA : JKR(E) PK/SH(PY) 58 / 2022

BILL OF QUANTITY (Quantities Are Provisional And Subjected to Remeasurement)

RATE AMOUNT
ITEM DESCRIPTION UNIT QTY
(RM) (RM)

C MISCELLANEOUS

1 FLOOD LIGHTING LED INSTALLATION TESTING


REPORT.

i. Allow here or in the rates for the cost of carrying out lot 1 2,500.00 2,500.00
inspection and test at works, testing and commisioning of the
installation and the equipment of the Contractor Works as
required in the relevant Specifications including providing all
necessary labour, materials, transportation, appliance or
equipment, electricity and fuels, and paying all fees and
charges for tests carried out by others. traffic management
to be included.

a. Testing and commisioning of the whole road lighting


installation using calibrated and appropriate equipment must
include:-

i) Luminance (cd/m2) and illuminance (lux) test in accordance


with the computer plot.

ii) Insulation resistance, polarity and continuity test for all


cables, Insulation resistance test for pole to pole shall be
included.

iii) Earth resistance test at all Feeder Pillars

b. All testing report shall be complied and submitted to the


S.O.'s Representative for approval.

2 UPON COMPLETION

As-Fitted Drawings (using AUTOCAD R14 or above) - lump 500.00 500.00


including 3 sets of A3 size drawings, (photostat) printed sum
together with catalog, results of electrical installation tests,
Inventory etc. according to JKR (E) Perak requirements in
hardcopy and softcopy.

3 SERVICE AND MAINTENANCE


KERJA-KERJA PEMASANGAN LAMPU LIMPAH SERTA KERJA-KERJA BERKAITAN DI PUSPEN
SERI ISKANDAR, PERAK DARUL RIDZUAN

NO. SEBUTHARGA : JKR(E) PK/SH(PY) 58 / 2022

BILL OF QUANTITY (Quantities Are Provisional And Subjected to Remeasurement)

RATE AMOUNT
ITEM DESCRIPTION UNIT QTY
(RM) (RM)
The Electrical Contractor shall make good of any defects, - lump 2,500.00 2,500.00
shrinkage and any other faults which may appear within the sum
Defect Liability Period and comprehensive service and
maintennance Schedule/breakdown during the Defects
Liability Period as provided in the contract, commencing from
Practical Completion of the contract Works as certified by the
S.O.'s (Refer to Appendix G of L-S20) excluding defective
components replacement.

4 Testing, calibration and resetting, all earth fault and overcurrent bil. 5 560.00 2,800.00
relays (Protection Relays Overcurrent and Earth Fault Relay by the
Electrical Services Engineer) inclusive of current transformers,
voltage transformers etc.

HACKING AND MAKING GOOD

5 Breaking, hacking, cutting holes and making good, - lump 1,000.00 1,000.00
restoration, backfilling and permanent reinstatements of sum
damage brickwall, road, drains, hardstandings, tarmac area,
other civil work, etc. necessary for the installation of the
system.

PROTECTION OF EXISTING SERVICES (If necessary)

6 Protect, uphold and maintain all existing and in use pipes, - lump 2,500.00 2,500.00
ducts, sewers, sevices mains, underground cables, etc. sum
during the execution of the Contract Works, unless otherwise
directed.
The Electrical Contractor shall be responsible for making
good all damages to the cables, pipes, etc. and shall
indemnify the Government against any claims as a results of
such damage.

INSPECTION, TESTING AND COMMISSIONING

7 Testing and commissioning as well as all matters related to - lump 1,500.00 1,500.00
the installation until perfect. sum

SUB TOTAL C : RM 13,300.00


( CARRIED TO SUMMARY OF PRICES )
KERJA-KERJA PEMASANGAN LAMPU LIMPAH SERTA KERJA-KERJA BERKAITAN DI PUSPEN SERI
ISKANDAR, PERAK DARUL RIDZUAN

NO. SEBUTHARGA : JKR(E) PK/SH(PY) 58 / 2022

SUMMARY OF PRICES

ITEM DESCRIPTION OF WORKS TOTAL (RM)

A PRELIMINARIES 42,815.25

B LAMPU LIMPAH KESELAMATAN 553,655.00

C MISCELLANEOUS 13,300.00

GRAND TOTAL (RM) 609,770.25

RINGGIT ENAM RATUS SEMBILAN RIBU TUJUH RATUS TUJUH PULUH DAN DUA PULUH
MALAYSIA : LIMA SEN SAHAJA

Notes: This total must agree with the total lump sum quoted in the form of tender
otherwise the tender may not be considered.

Signature :

Name: LIYANA SYAZWANI BINTI ABD RAZAK

Designation: MANAGER

Company's
Chop:

Date: 09.06.2022

You might also like