Professional Documents
Culture Documents
NOTICE: The Type of Change and Recommended Compliance specified reflects Solar’s best judgment regarding the
Service Bulletin. All questions should be directed to your Solar Field Service Representative. Solar, Saturn,
Centaur, Taurus, Mercury, Mars, Titan, SoLoNOx, and Turbotronic are trademarks of Solar Turbines Incorporated.
Cat and Caterpillar are trademarks of Caterpillar Inc. Specifications subject to change without notice.
NUMBER: 22.0/100
ISSUED: April 1996
REVISED:
PRODUCT: All
MODEL(S): All
Specifics:
PRODUCT SAFETY
Purpose:
To recommend inspection of all package vents and drains to assure compliance with
Mechanical Installation Drawing instructions.
GENERAL INFORMATION:
Several instances have occurred where excessive back pressure in a package vent or drain
connected to a gas turbine skid connection point has resulted in, 1) continued operation of
Solar packages use atmospheric vents and drains to allow for momentary or controlled escape of
gas and pneumatic pressure or liquids from a system. This allows actuation of solenoid and shutoff
valves, provides venting for pneumatically powered motors and starters, and purging or draining of
unwanted liquids. Correct operation of valves and the mechanical integrity of certain parts depend
on maintaining back pressure in these vents below the working pressures for which these compo-
nents are designed.
Ideally, all package vent connections are separate atmospheric vents and lead directly to the atmos-
phere with no other restriction in the line except a flame arrestor. Solar realizes that increasingly
our customers are required to manifold these vents together for environmental or safety reasons
(e.g., platform operation, fuel gas containing H2S). The vented gas then must be piped to a flare or
common blow-down stack. Block and/or check valves are sometimes installed into the vent con-
nections to prevent back flow and to isolate the package for maintenance purposes.
NOTE
The Mechanical Installation Drawing provided during original shipment of
equipment contains important notes and instructions regarding the connec-
tions for vents and drains on the package skid. These notes must be followed
to insure safe and proper operation of the turbine equipment during startup,
operation, and shutdown.
Should blockages occur in a vent or drain, one or more of the following conditions can result
(refer to 1 for maximum allowable back pressure):
1. Combustor and Exhaust Collector Drain - These are provided to drain away any
liquids from the combustor or exhaust collector. The liquids most likely to be present
in this drain are water, liquid fuel, or lube oil. Any liquids collected in this drain must
be properly disposed of. Any back pressure at this connection may result in an
accumulation of combustible liquids in the engine or exhaust ducting and could
result in a fire.
2. Gas Compressor Case Vent - This has always been an atmospheric vent. If the
compressor case is vented to a flare line or pressurized vent system, the compressor
case will remain pressurized at that pressure. If the pressure is higher than the case
pressure switch (S360) set point, (4 psig typically), the auxiliary seal oil pump will
always run. If the gas compressor case pressure is lower than the compressor case
pressure switch set point (switch S360), the auxiliary seal oil pump will not run
and there is a potential of gas flowing over the oil seals and into the lube oil system.
NOTE
Although commonly called "pneumatic," this starter often operates on com-
pressed natural gas that is flammable. It is mandatory to always contain
natural gas.
NOTE
Most pneumatic motors start upon loss of electrical power and therefore
cannot be electrically interlocked. It is recommended that supply gas be
disconnected and blocked off for a positive shut off.
13. Water Injection Purge - When the package is shut down or the water injection system
is shut off, the fuel injectors and the water injection lines are cleared of water by use of
a back purge. The purged liquids and gases are mostly water and air, but as the purge
originates at the injector tip some natural gas and/or liquid fuel may also be carried out
with the air and water. Any back pressure at this port may not allow the water to
drain sufficiently from the injectors and manifold during shutdown or may allow
previously purged water to flow back into a hot engine.
ACTION REQUIRED:
Insure for each vent and drain that the maximum allowable back pressure is not
exceeded.Compare the package vent and drain connections to the Mechanical Installation
Drawing and 1. Inspect all package vents and drains for obstructions, blockage, or installation of
valves. If found, remove any blockage from vent or drain. If valving is installed and is otherwise
acceptable, it should be instrumented with limit switches connected to the turbine package
electrical controls to prevent operation of equipment with improper valve position.
Vents and drains have to be large enough to handle any flow given in the Mechanical
Installation Drawing without exceeding the maximum allowable back pressure. The
given size of each skid connection is a minimum size and cannot be reduced under any
circumstances. For longer pipe runs, line sizes have to be appropriately increased.
If a block valve is installed in any vent connection, it is mandatory to interlock the package
fuel and start gas supplies in such a way that all supply lines to the package (fuel, pilot and
start gas, air or pneumatic motors, liquid fuel) are disconnected, blocked off and vented before
The installation of any interlock is the customer’s responsibility.Solar always recommends the
installation of a manual shutoff valve in any supply line. These valves may be used in the design of
this interlock system. Mechanical or electrical interlocks may be used as described below:
Common vent lines experience periodic increases in back pressure (during a blow down of
other equipment). This back pressure must not exceed the pressures listed in 1 even for short
periods, regardless if the package is running or not. Additional precautions are required if this
condition cannot be met. The addition of a check valve is not sufficient. To prevent pressure build
up between the package and check valve, properly sized relief valves and rupture disks should be
installed with a bypass vent directly to atmosphere. This bypass vent should be sized to handle the
complete system flow.