LN2 BULK
STORAGE TANK
TEST MEASUREMENTS 54
Christy
November 5, 2003
650612963.xls
ENGINEERING with the SPREADSHEET
Copyright 2006 American Society of Civil Engineers
The soils engineer predicted less than 1/4" settlement under working loads for
individual piles. It appears that our greatest settlement is on the order of 1/8".
Targets were glued to foundation columns on Friday, October 24, 2003. The water fill process
began on Thursday the 29th and was finished on Sunday, November 2nd.
row 20
North tilt of about 1/16"
4 6 8
δ = 3/16 δ = 1/16 δ = 3/16
15 17 19 21 23
δ = 2/16 δ = 2/16
row 30
35 37 39 41 43
δ = 1/16 δ = 1/16 δ = 3/16
55 57 59 61 63
δ = 1/16 δ = 1/16 δ = 2/16 δ = 2/16
70 72 74 row 40
δ = 1/16 δ = 1/16 δ = 1/16
row 50
Page 54 - 2
LN2 BULK
STORAGE TANK
TEST MEASUREMENTS 54
Christy
November 5, 2003
650612963.xls
ENGINEERING with the SPREADSHEET
Copyright 2006 American Society of Civil Engineers
row 60
targets on columns
laser level
COLUMN SHORTENING
5 and 3 Lb. lead weights were hung on monel line from the bottom of the deck.
row 110
4 6 8
15 17 19 21 23
1/16"
a 0.052, 0.005
2/16" 2/16"
1/16" 2/16"
35 37 39 41 43 row 120
b 0.026, 0.005
1/16" 2/16"
55 57 59 61 63
70 72 74
row 130
Note: The symbol indicates a < painted on the concrete and the
laser's position on that <. Laser measurements were made with a Hilti PD25.
Page 54 - 4
LN2 BULK
STORAGE TANK
TEST MEASUREMENTS 54
Christy
November 5, 2003
650612963.xls
ENGINEERING with the SPREADSHEET
Copyright 2006 American Society of Civil Engineers
The average design values for columns 39 to 139 Figure 54-7. Mechanical Dial Gage
and 41 to141 is 470k. Telltale with 5-pound Lead Weight
The mechanical dial gage c indicates +0.001" (down) is also in row 200
keeping with the inner tank shell uplift.
Sincerely,