Professional Documents
Culture Documents
College of Engineering
Department of Petroleum
Prepared by :-
Ali Al Akbar Monther Salman
Supervised by :-
Mohammed A.Abdulnabi
Date :-
9 / 12 / 2022
Beggs and Brill Correlation (Beggs and Brill 1973)
Beggs and Brill developed correlations for liquid holdup and friction
factor. The correlations are based on experimental data from 90 ft
long acrylic pipes. Fluids used were air and water and 584 tests
were conducted. Gas rate, liquid rate and average system
pressure was varied. Pipes of 1 and 1.5 inch diameter were used.
First the pipe was horizontal, and the flow rates were varied in
such a way that all horizontal flow patterns were observed, see
figure 1. Afterwards the pipe inclination was changed, and liquid
holdup ( H L(θ)) and pressure drop was measured. By this the
effect of inclination on holdup and pressure drop could be studied.
Beggs and Brill proposed the following pressure-gradient equation,
2
Liquid holdup and friction factor should be found as described in
the following.
Beggs and Brill plotted liquid holdup versus angle of pipe from
horizontal, see figure 2. They found that holdup has a definite
dependency on angle. From the figure one can see that the curves
have maximum and minimum at +/- 50° from the horizontal. The
slippage and liquid holdup increase as the angle of the pipe
increase, from horizontal towards vertical (flow upwards). Gravity
forces act on the liquid, causing a decrease in the liquid velocity
and thereby slippage and holdup is increased. By further
3
increasing of the angle, liquid covers the entire cross section of the
pipe. The slippage between the phases is reduced and liquid
holdup reduces. Beggs and Brill observed that degree of holdup
with angle varied with flow rates. To include effects of pipe
inclination, it was decided to normalize liquid holdup. The following
equation was proposed,
The liquid holdup for horizontal flow should be calculated first, and
corrected for inclination afterwards. The equations used for
calculating liquid holdup is the same for all flow patterns, but there
4
are different empirical coefficients for each flow pattern. The
equation for calculating liquid holdup for horizontal flow is:
5
where θ is actual angle of pipe from the horizontal, and C is liquid
holdup parameter. The liquid holdup parameter is defined as