Combox-P Profibus address mapping for Mk5 controller

EVOL75_18A gen. 1 , API596554 Mk5 controller must be in Mk4 CAN profil


1900526417 - G/Z VSD - Touch 2.68.20. VSD
13.10.2022 12:24:25 Register Address Bytes = B2B3

Analog Inputs Data Record


Name Type Unit B2B3 (reg) B4B5 (W1) B6B7 (W2) Value Interpretation
Wylot ze sprężarki Pressure (mBamBar 0
Wylot ze stopnia Temperature 0.1 °C 1
Value StatusValues are S16. 32767 = Sensor error.
Temperatura otoczenia Temperature 0.1 °C 2
Kontrola temperatury Temperature 0.1 °C 3

Digital Inputs Data Record


Name B2B3 (reg) B4B5 (W1) B6B7 (W2) Functional Interpretation 0/1
Zatrzymanie awaryjne 200 Otwarty / Zamknięty
Przeciążenie silnika wentylatora 201 Otwarty / Zamknięty
Value Status
Zdalny start/stop 202 Otwarty / Zamknięty
Wybór nastawy ciśnienia 203 Nastawa 1 / Nastawa 2
Bit Description (1/0)
0 PreWarning
1 Warning
2 ShutdownWarning
3 Shutdown
4 Service
5 Permissive
6 Sensor Error
7 Set/Not set
8 SPM valid measurement
13 PrePermissive

Counters Data Record


Name Unit B2B3 (reg) B4B5B6B7 (W1W2) Reference counters for % calculation
Godziny pracy s 300
Godziny dociążenia s 301
Startów silnika Count 302
Przekaźnik dociążenia Count 305
VSD 1-20% obr/min s 306 Running Hours
VSD 20-40% obr/min s 307 Running Hours
VSD 40-60% obr/min s 308 Running Hours
VSD 60-80% obr/min s 309 Running Hours
VSD 80-100% obr/min s 310 Running Hours
Starty wentylatora Count 314
Value
Value
Zsumowany wydatek _1000_m3 304
Czas pracy modułu s 303
Zatrzymania awaryjne Count 315
Zatrzymania bezpośrednie Count 316
Czas dostepności maszyny s 317
Czas niedostępności maszyny s 318
Czas na wyłączeniu awaryjnym s 319
Godz. pracy przy obniżonym obciąż. s 320
Licz. startów przy obniż. obciążeniu Count 321
Liczba spadków ociążenia Count 322

Special Alarms Data Record


Name B2B3 (reg) B6B7 (W2)
Nie wybrana nastawa ciśnień 604
Alarm falownika silnika 1 605
Status
Zewnętrzny moduł komunikacyjny 606
Awaria systemu. 607
Bit Description (1/0)
2 Warning
6 Shutdown
10 Permissive

Main Motor Speed


Name B2B3 (reg) B4B5B6B7 (W1W2)
Required Speed 800 rpm
Actual Speed 801 rpm

Machine Control Mode


Register 400 - B2B3
Name Value - B5
2a - Local Start/Stop & Pressure Sensing 0
3a - Remote Start/Stop, Local Pressure S 1
4a - Communication Start/stop, Local Pr 2
2b - Local Start/Stop, Digital Contact Pr 16
3b - Remote Start/Stop, Digital Contact 17
4b - Communication Start/Stop & SPS Co 18
4c - Communication Start/Stop & Speed 34
4d - ECO Controlled 50
2e - Local Start/Stop & 4-20mA Speed Co 64
3e - Remote Start/Stop & 4-20mA Speed 65

Machine Mechanical State


Register 400 - B2B3
Name Value - B6
Stop 1
Unload 2
Loaded 4

General Status
Register 401 - B2B3
Name Bit - B6B7(W2)
PreWarning 0
General Warning 1
General Shutdown Warning 2
General Shutdown 3
General Service 4
General Start Failure 5
Emergency Stop 6
Manual/Automatic 7
Local/Remote 8
Week Timer 9
PreWarning Service Running Hours 10
PreWarning Service Accumulated Volume 11
PreWarning Service Analog Input 12
PrePermissive 13
Test Mode 14
Normal or Special Test Sequence 15

ECOi Status
B2B3 : reg 401 ==> B4
Name Value - B4
PowerUp ECO 22
Local Operation ECO 1
Central Stop ECO 3
Shutdown ECO 14
Automatic Operation ECO 2

ECOi Counters Data Record


Name Unit B2B3 (reg)
B4B5B6B7 (W1W2)
Compressor 1: Running Hours s 500 Value

Regulation Parameters B4B5B6B7-W1W2-


Name B2B3 (reg) Value Read Value Write Info
Use VSD Setpoint 1 1050 1 1
used in local pressure sensing mode
used in local pressure sensing mode
Use VSD Setpoint 2 1050 2 2
VSD Setpoint 1 1051 mBar n/a
VSD Setpoint 2 1052 mBar n/a

Use ECO(i) Pressure Band 1 1080 0 1


Use ECO(i) Pressure Band 2 1080 1 2
ECO(i) Pressure Band 1 - Load 1081 mBar n/a
ECO(i) Pressure Band 1 - Unload 1082 mBar n/a
ECO(i) Pressure Band 2 - Load 1083 mBar n/a
ECO(i) Pressure Band 2 - Unload 1084 mBar n/a

Commands - LAN mode B4B5B6B7-W1W2-


Name Register Value Read Value Write Info
Start 2000 n/a 1 Start the main machine
Stop 2000 n/a 2 Stop the main machine
Load 2000 n/a 3
Unload 2000 n/a 4

Switch to LAN A - local Setpoint Control Accepted


2001 in LAN Bn/a
or LAN C. Use2of this command is not mandatory (auto isolation after 20s).
Switch to LAN C - external
Accepted
Speed Control
in LAN A or2001
LAN B. Command
n/a to be repeated
3 at least every 20s (typ. 10s), if not compressor will isolate automatically.
rs for % calculation
sor will isolate automatically.