Professional Documents
Culture Documents
G R A P H I C A L A B S T R A C T
A R T I C L E I N F O A B S T R A C T
Keywords: The district cooling system (DCS) is generally considered to be a key efficient cooling technology to
Multi-cold source cooling system cope with the increasing cooling demand. However, the energy consumption of pumps in DCS ac
TRNSYS counts for a large proportion. This work demonstrated a novel variable flow control strategy based on
Variable flow operation strategy measured operating parameters. An existing DCS in a subtropical climate zone was used as the
Cooling load baseline model, denoted as Case A. Furthermore, using TRNSYS software, the variable flow control of
the chilled water pumps and the cooling water pumps in Case A was performed in turn, and two
variable flow models were established, denoted as Case B and Case C, respectively. The operation
strategies capable of dealing with the diversified cooling loads were developed and simulated. The
results indicated that compared with Case A, the newly proposed models Case B and Case C reduced
the energy consumption by 9.50% and 14.15%, cut down CO2 emissions by 9.45% and 14.18%, saved
costs by 10.34% and 15.16%, respectively. Moreover, the efficiency of the two models was also
improved by 10.70% and 16.67%, respectively, compared with the Case A. Effective operation
strategies can further improve the performance of DCS, thereby providing energy-saving and efficient
cooling solutions.
* Corresponding author.
E-mail address: hwp@neepu.edu.cn (W. Hong).
https://doi.org/10.1016/j.csite.2023.102820
Received 9 November 2022; Received in revised form 20 January 2023; Accepted 13 February 2023
Available online 15 February 2023
2214-157X/© 2023 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license
(http://creativecommons.org/licenses/by-nc-nd/4.0/).
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
1. Introduction
Energy is the lifeblood and foundation of human development. With the continuous progress of society, the global energy demand
is increasing daily [1]. Buildings are the primary contributor to the total energy consumption [2], accounting for more than 20% in
China [3], and are also a substantial source of CO2 emissions [4]. With global warming and rising temperatures, cooling has become
increasingly indispensable and vital [5]. The energy consumption of air conditioning systems is almost half of the total consumption of
the building [6]. It is crucial for the building sector to conserve energy and reduce emissions while meeting the demand for cooling by
the residents to advance the “dual-carbon” goals announced by the Chinese government [7]. Therefore, it is vital to provide
low-energy, low-carbon, cost-effective, green and clean cooling options. Among these, the district cooling system (DCS) [8,9] over
comes the shortcomings of traditional cooling systems, also has the advantages of high efficiency and cleanliness. DCS technology is
that one or more cooling stations provide cooling energy for buildings in a district through the water supply and return pipe network
[10]. The typical DCS with various cold sources include not only the electric cooling technology, but also combined with the waste heat
technology [11] and the cold storage technology that utilizes the difference in peak and valley electricity tariffs [12]. The specific cold
source should be determined by the locally available resources. Overall, DCS transforms traditional cooling systems into sustainable
energy systems [13], resulting in emerging cooling systems being a subject of considerable interest. To explore the performance of DCS,
researchers have done extensive research.
Thakar et al. [14] used a campus cooling system in a hot and dry climate zone. Aiming at diversifying the cooling load, they
proposed a detailed design of a DCS with thermal energy storage and conducted a comprehensive lifecycle cost analysis. The results
demonstrated that the new design can save 0.34 million USD and reduce CO2 emissions by 50%. In Hong Kong, a distributed energy
system (DES) integrating DCS was applied in a typical university campus by Kang et al. [15]. Subsequently, they explored the energy
saving and economic performance of the new integrated cooling system. The results illustrated that the integrated system could save
energy and costs by 9.6% and 44%, respectively. In response to a series of challenges, such as high power consumption caused by the
standalone compression chiller-based cooling method, Jannatabadi et al. [16] proposed to implement a DCS in northern Iran and
performed a performance analysis. The application of the new cooling solution could reduce the current high power consumption, and
the payback period could be shortened to 6 years. Alajmi et al. [17] used simulation methods to study a low-rise building DCS in
Kuwait and analyzed its lifecycle cost. The results indicated that the peak electricity demand and CO2 emissions were cut by 50% and
53%, respectively. A DCS with different cooling sources in a subtropical climate zone was selected as the case study by Zhang et al.
[18]. Furthermore, they explored the impact of ice thermal storage (ITS) on the entire cooling system. The results revealed that the
addition of ITS can provide 20% more cooling capacity. Although the integrated system increased energy consumption and carbon
emissions by a small percentage, but the system was more economical with an annual cost saving of 6.78%.
The above-mentioned previous studies have shown that DCS can bring considerable energy-saving performance and economic
benefits. However, the energy consumption of the pumps accounts for about 20%–30% of the entire cooling system [19], implying that
there is a large space for energy saving. Therefore, how to cut the energy consumption of the pumps has become a critical link to further
energy-saving and high-performance operation of this emerging cooling system [20]. This work aims to explore the energy-saving
performance of a DCS with variable flow pumps (VFPs). Through literature research, it was found that the current research on the
application of VFPs in DCS was insufficient; however, it had received extensive attention in the field of district heating (DH) [21,22]. In
North China, it was estimated that the heating and domestic hot water demand of more than 10 million m2 of building areas was
provided by DH systems with VFPs [23,24]. Sheng et al. [25] indicated that DH with VFPs can reduce electricity consumption by
49.41% per year compared with the previous constant flow system. Gu et al. [26] explored the energy saving potential of VFPs applied
in DH with a case in Shenyang, China. They found that the system using VFPs can save 28.52% of electricity per year compared to the
traditional system. To explore the hydraulic performance of the variable-flow DH, Yan et al. [27] implemented such a system in Kuerle,
China. Their results indicated that the new system saved more than 30% of the energy compared with the constant-flow system.
Simultaneously, the capacities of the pumps were reduced accordingly. Wang et al. [28] developed a novel method for application to
an actual DH with distributed VFPs and examined two scenarios to explore the performance. The results demonstrated that the
maximum energy savings of the two scenarios were 66.8% and 90.3%, respectively, compared with the constant flow system.
From the above studies, it can be concluded that the application of VFPs in DH systems can greatly promote energy conservation
and emission reductions. Integrating the VFPs with the DCS sounds to be also a potential energy efficient cooling solution. However,
after literature research we found that there were few reports about such a new cooling option. To address this gap, this work develops
appropriate control methods to explore the rationality of variable flow cooling based on the measured data. An existing DCS operating
at constant flow, located in Zhuhai, China, was selected as the case study. Then, based on this constant flow model, the TRNSYS
software [29] was used to perform variable flow control program and established the models, and set reasonable operation strategies to
deal with the diversified cooling loads. Additionally, the comprehensive evaluation of the three models was carried out. Finally, the
feasibility of variable flow DCS was explored.
The remainder of this study proceeds as follows. Section 2 explains the key variable flow methods used in this study, and forecasts
the user cooling load. In Section 3, an existing typical DCS in a subtropical climate zone is used as the case, and the detailed system
information is categorized. Moreover, the variable flow control logics of different pumps and the elaborate evaluation methods are
shown. Additionally, the constant flow and variable flow models are built. Section 4 presents the multi-objective discussion based on
the simulation results. The study is concluded in Section 5.
2
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
2. Methodology
The primary study object of this work is a multi-cold source DCS, located in Zhuhai, China, which has a subtropical climate. The
peak cooling load is 75,000 kW. To minimizing the energy consumption of the cooling system while meeting user cooling loads, this
study proposes the variable flow operation strategy.
where m, H, and ηp represent the flow rate (in m3/h), head (in m), and efficiency of the pump, respectively. ω and ω0 are the actual
speed (in r/min) and rated speed (in r/min) of the pump, respectively, and the ratio of the two is the speed ratio of the pump, rep
resented by I, calculated as:
ω
I= (2)
ω0
The relationship between the flow rate and head at the rated speed is as follows:
H = a0 I 2 + a1 mI + a2 m2 (5)
The relationship between the power supply frequency of the pump and speed ratio can be expressed as follows:
f = 50I (6)
3
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
temperature difference is reached as the expected flow rate, which is expressed as follows:
Qload
m0 = (7)
cΔt
where m0 is the expected flow rate of the pump, in m3/h, Qload is the current load of the users, in kW, c is the specific heat capacity of the
fluid, in kJ/(kg⋅◦ C), and Δt is the temperature difference between the supply and return water, in ◦ C.
Table 1
The design parameters of the buildings.
Items Values
4
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
5
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
Table 2
The main basic information of the multi-cold source DCS.
6
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
include chillers(e), chillers(ab), and chillers(d), and the pumps include CHWPs and CLWPs.
The calculation process is presented in Eqs. 8–11:
Powerchillers = Powerchillers(e) + Powerchillers(d) + Powerchillers(ab) (8)
To discuss the energy consumption of the cooling system, the power of each energy-consuming equipment in the system should be
counted first. In Eqs. 8–10, the left side of the equation is the total power of the chillers, pumps and system, and the right side is the
single item, where Powerchillers(e) , Powerchillers(d) , Powerchillers(ab) , PowerCHWPs , PowerCLWPs and Powerc(tower)s are the powers (in kW) of
chillers(e), chillers(d), chillers(ab), CHWPs, CLWPs, and c(tower)s respectively. After the simulation by TRNSYS, the power of the above
equipment is calculated, and then the total power of the equipment is integrated during the cooling period by Eq. (11) to obtain the
system consumption, namely ECtotal (in kWh), Where t1 and t2 are the two end-point time values of the system cooling period, in h.
where PTOU is the electricity price corresponding to different periods. The product of the two is the OCs, in million RMB.
To more prominently compare the economics of the different systems, we defined the index of OC reduction ratio (OCRR), that is,
the difference between OC of the constant flow system (OCcon) and OC of the variable flow system (OCvar) divided by the OC of the
constant flow system. As demonstrated in Eq. (14), a positive value of the ratio indicates that the variable flow system is more
economical, and the larger the ratio, the better the economy of the system. Correspondingly, the OCRR of models Case B and Case C are
shown in Eqs. (15) and (16).
OCcon − OCvar
OCRR = × 100% (14)
OCcon
OCCaseA − OCCaseB
OCRRCaseB = × 100% (15)
OCCaseA
OCCaseA − OCCaseC
OCRRCaseC = × 100% (16)
OCCaseA
The well-known advantage of a DCS is its high efficiency. Therefore, system efficiency (η) is also a key item to evaluate the DCS
performance, as shown in Eq. (17), which is determined by the total cooling capacity (Qcooling,system , in kWh) and energy consumption of
the system. Therefore, system efficiency and energy consumption are inseparable.
/
η = Qcooling,system ECtotal (17)
7
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
∑
N
Qload > 0.80 · QSn− 1 + 3 · QPHEmelting · Si 3 · 0.90 (2 ≤ N ≤ 11) (19)
n=2
In the above equations, Qload (in kW) is the cooling capacity that the system needs to provide. QSn (in kW) refers to the cooling
capacity of the chiller currently associated with the signal Sn . QPHEmelting (in kW) means the rated heat exchange of the PHEmelting. Si 3 is
the signal to start the third PHEmelting, because when it is opening, it can be enough to prove that all the PHEmelting are running. N
represents the number of the control signal, and the figure ‘3’ in Eqs. (18) and (19) represents three PHEmelting. Additionally, referring
to the actual work of the chillers and the PHEs, combined with the compilation logic of cooling capacity superposition for the TRNSYS
model [35], the operating upper limit ratios of these two types of equipment are set to 0.80 and 0.90, respectively, as shown in Eq. (19).
The above settings can ensure that when the load rate is close to the working upper limit of the equipment, new equipment will be
started in sequence, so that the system can always run safely.
In order to maximize the economic benefits of the cold storage system, the three PHEmelting are first activated to release the cold
energy as much as possible. If the cooling capacity is not sufficient to supply current demand, the two chillers chiller(e) − 1 and
chiller(ab) − 1 arranged in series with smaller CAP are started first to cope with the smaller cooling load demand. As the cooling load
demand continues to increase, the other two series-connected chillers with slightly larger CAP controlled by signals S3 and S4 are
turned on in sequence. As the cooling continues, the chillers controlled by the signals S5 –S10 are operated according to the sequence in
Table 3, and the reasons are as follows. As presented in Fig. 4, the chilled water at 7.5 ◦ C produced by chiller(ab) − 3/4/5 will exchange
heat with glycol (1.5 ◦ C) from chiller(d) − 2/3/4. Therefore, before starting the chillers(ab) controlled by the signals S8 –S10 , the
chiller(d) − 2/3/4 should be started first in the descending order of CAP, so that the cooling capacity can be provided by as few chillers
as possible. Furthermore, considering that chiller(d) − 1 is a dual-evaporator-type chiller, it is started at the end to facilitate rapid
unloading during ice storage, so that it can be directly used for cooling or ice storage.
The detailed control principle for the Signals(var) is explained as follows. In the constant flow model illustrated in Fig. 4, the chillers
chiller(e) − 1 and chiller(ab) − 1 controlled by S1 and S2 are connected in series, and the pump CHWP(a) − 1 conveys the return water
to the two chillers. Therefore, in the variable flow system, signal S1− controls the pump CHWP(a) − 1 and the chillers chiller(e)− 1
′
2
and chiller(ab) − 1 simultaneously. The same rule applies to signal S3− 4 . Notably, the control of signals S5 –S7 are different. Taking S5
′ ′ ′ ′
as an example, its corresponding Signal(con) is S5 , and the controlled chiller is chiller(d) − 2. This chiller is connected in series with the
chiller(ab) − 5, so S5 controls the CHWPs in front of the two chillers at the same time, namely CHWP(d) − 2 and CHWP(a) − 5.
′
Similarly, signals S6 and S7 have the same control idea. Furthermore, the S8 , S9 , and S10 control the chillers chiller(ab) − 5, 4, 3, so the
′ ′
new Signals(var) also control the CHWPs connected to these chillers(ab). Next, we take the signals S5 and S8 as examples to illustrate
′ ′
the control process of the two signals on the same pump as follows.
Fig. 5 presents the variable flow calculation process of CHWPs. As mentioned above, CHWP(a) − 5 is controlled by signals S5 and
′
S8 at the same time, and the process can be integrated according to the process in Fig. 5. Where QSn ′ (in kW) in the first step represent
′
the load that the chiller controlled by signal Sn should bear. Si is the signal that controls the start of melting ice. In the second step, the
′
expected flow rate of CHWP mExp CHWP (in m3/h) is the theoretical flow value required to achieve the design temperature difference.
The cCHWP (in kJ/(kg⋅◦ C)) and Δt (in ◦ C) represent the specific heat capacity and design temperature difference of the fluid in the pump,
respectively. The ratio of mExp CHWP to the real flow rate (mCHWP ) when the pump is running is the speed ratio ICHWP . This value is used
Table 3
Control signals and equipment information of the Case B model.
S1 S1− 2
′
chiller(e) − 1 3165 chiller(e) − 1, chiller(ab) − 1, CHWP(a) − 1
S2 chiller(ab) − 1 3165
S3 S3− 4
′
chiller(e) − 2 7034 chiller(e) − 2, chiller(ab) − 2, CHWP(a) − 2
S4 chiller(ab) − 2 7034
S5 S5
′
chiller(d) − 2 8441 chiller(d) − 2, CHWP(d) − 2, CHWP(a) − 5
S6 S6
′
chiller(d) − 4 8441 chiller(d) − 4, CHWP(d) − 4, CHWP(a) − 4
S7 S7
′
chiller(d) − 3 5627 chiller(d) − 3, CHWP(d) − 3, CHWP(a) − 3
S8 S8
′
chiller(ab) − 5 8441 chiller(ab) − 5, CHWP(a) − 5
S9 S9
′
chiller(ab) − 4 8441 chiller(ab) − 4, CHWP(a) − 4
S10 S10
′
chiller(ab) − 3 5627 chiller(ab) − 3, CHWP(a) − 3
S11 S11
′
chiller(d) − 1 8441 chiller(d) − 1, CHWP(d) − 1
8
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
to calculate the speed ratio of pump under the control of signal Sn , as shown in step 4, where ICon CHWP is the control speed ratio of the
′
pump. gt and le represent “greater than” and “less than or equal to”, respectively. The logic for controlling the speed ratio is that under
the premise that the signal Sn is greater than zero, when the operating speed ratio of pump is greater than or equal to 1, the value is 1;
′
when the speed ratio is less than or equal to 0.5, the value is 0.5; when the speed ratio is between 0.5 and 1, the input value is the
current true speed ratio. In step 5, ITru CHWP indicates the true speed ratio of pump in variable flow system. When ice melting occurs, the
pump runs at full flow, which is controlled by the Si . When it is controlled by the signal Sn , the pump speed ratio obeys the calculation
′
process of ICon CHWP . According to the above calculation process, the true speed ratio of CHWP(d) − 2 and CHWP(a) − 5 controlled by
signals S5 and S8 can be obtained as follows:
′ ′
(20)
′ ′
ITru CHWP(d)− 2 = Si · (1 − S5 ) + ICon CHWP(d)− 2 · S5
(21)
′ ′ ′
ITru CHWP(a)− 5 = ICon S5
′
CHWP(a)− 5 · S5 · (1 − S8 ) + ICon S8
′
CHWP(a)− 5 · S8
The integrated speed ratio is the true speed ratio (ITru CHWP(a)− 5 ) when CHWP(a) − 5 is running. The control procedures for signal
groups S6 and S9 , S7 and S10 are based the same process.
′ ′ ′ ′
speed ratios of the CLWP(a) ∼ 3 − 5 must be switched and integrated according to the calculation process shown in Fig. 5. Moreover,
Fig. 5. Calculation process of signal coupling control with S5’ and S8’ as examples.
9
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
Table 4
The CLWP variable flow control program of Case C model.
3
CLWP(a) − S6 ·(1 − S9 ) · ICon
′ ′
+ S9 · ICon
′
S6 CHWP(a)− 4 S9 CHWP(a)− 4
′ ′
4
CLWP(a) − S5 ·(1 − S8 ) · ICon
′ ′
+ S8 · ICon
′
S5 CHWP(a)− 5 S8 CHWP(a)− 5
′ ′
5
CLWP(e) − gt(S1 , 0) ·(gt(ICHWP(a)− 1 , 1) · 1 + le(ICHWP(a)− 1 , 1) · gt(ICHWP(a)− 1 , 0.5) · ICHWP(a)− 1 + le(ICHWP(a)− 1 , 0.5) · 0.5)
1
CLWP(e) − gt(S3 , 0) ·(gt(ICHWP(a)− 2 , 1) · 1 + le(ICHWP(a)− 2 , 1) · gt(ICHWP(a)− 2 , 0.5) · ICHWP(a)− 2 + le(ICHWP(a)− 2 , 0.5) · 0.5)
2
CLWP(a) − 1/2 and CLWP(e) − 1/2 only need to satisfy their own control process.
10
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
In Fig. 6, the blue lines refer to the chilled water cycle, which are the loops for the chilled water supply and return. The red lines
connect the loops between the chillers and the c(tower)s. The pink lines are the glycol circulation that occurs between the chillers(d)
and the ice storage tank. To highlight the loops of the water supply and return pipelines in the system, the control and output lines are
uniformly represented by light gray dashed lines. Additionally, the work flow of all the equipment in the model is as detailed in the
corresponding explanation in Fig. 4. The collected real weather data is converted into the TMY2 format commonly used by TRNSYS
software and used as the input data of the c(tower)s to calculate the cooling water return temperature. The VFPs used in the system are
Type 110 from the TRNSYS component library, which is compatible with any flow rate between 0 and nominal. The ice storage
component is established based on the mathematical model of ice storage, and the exhaustive description and accuracy verification of
this component have been discussed in our previous work [18].
11
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
Table 5
The result statistics of the three models.
5. Conclusions
An excellent solution for transitioning from a traditional cooling system to a sustainable system is the district cooling system (DCS),
the subject of this study. For this system, pumps account for a large proportion of energy consumption and have great potential for
energy saving. This study discussed the applicability of variable flow pumps (VFPs) in DCS and set corresponding variable flow
operation strategies to explore the performance of the new system. Based on the measured data and using the TRNSYS to establish
12
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
13
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
three models, namely the constant flow baseline model, variable flow model of chilled water pumps (CHWPs), and variable flow model
of CHWPs and cooling water pumps (CLWPs), and indicated by Case A, Case B and Case C, respectively. Then we developed the
complete control programs applicable to the above three models that can deal with the cooling load fluctuations in real time.
Moreover, the simulation results were further discussed and summarized as the following points.
1) A DCS located in the subtropics was selected as the case study. The cooling load pattern of the users is obtained by TRNSYS, and the
simulated value of the peak load is compared with the investigated value, and the error is 0.27%.
2) An in-depth analysis of the results illustrated that the Case B and Case C saved 9.50% and 14.15% energy of the system, respectively,
compared to constant flow model. Regarding pump energy consumption statistics, the two variable flow models were 10.20% and
28.35% more energy-efficient than the baseline model. Environmentally, the two newly built models reduced emissions by 9.45%
and 14.18% than that of previous model, respectively.
3) About the economy, Case B and Case C reduced the annual OCs by 10.34% and 15.16%, respectively, compared with the Case A, and
the monthly savings of Case C were better than that of Case B. Furthermore, the efficiency of the three models in months with low
cooling load was slightly higher than that in months with large cooling load, and the monthly efficiency of Case C was the highest
among the three models. Additionally, Case B and Case C improved annual efficiency by 10.70% and 16.67%, respectively. This
further demonstrated that the Case C model performed better in all of the above criteria. Additionally, the feasibility of variable
flow DCS was demonstrated.
Funding
This work was supported by the National Natural Science Foundation of China (51976027); the Project Supported by Science and
Technology Development Plan of Jilin Province (20210203200SF), China.
Author statement
Wei Zhang: Data collection, System modeling, Analysis, Writing - Original Draft.
Xu Jin: Language polishing.
Ling Zhang: Data curation.
Wenpeng Hong: Supervision and Writing.
Data availability
Acknowledgments
The authors would like to acknowledge the Zhuhai Hengqin Energy Development Co., Ltd. for the system parameter support.
References
[1] S. Shi, Y. Wang, Y. Wang, X. Feng, A new optimization method for cooling systems considering low-temperature waste heat utilization in a polysilicon industry,
Energy 238 (2022), 121800, https://doi.org/10.1016/j.energy.2021.121800.
[2] X.J. Luo, L.O. Oyedele, O.O. Olugbenga, A.O. Ajayi, 3D pattern identification approach for cooling load profiles in different buildings, J. Build. Eng. 31 (2020),
101339, https://doi.org/10.1016/j.jobe.2020.101339.
[3] China building energy consumption annual report, Member of Energy Consumption Statistics Committee of China Association of Building Energy Efficiency,
2020 (in Chinese).
[4] P. Jafarpur, U. Berardi, Effects of climate changes on building energy demand and thermal comfort in Canadian office buildings adopting different temperature
setpoints, J. Build. Eng. 42 (2021), 102725, https://doi.org/10.1016/j.jobe.2021.102725.
[5] T. Novosel, M. Grozdek, J. Domac, N. Duić, Spatial assessment of cooling demand and district cooling potential utilizing public data, Sustain. Cities Soc. 75
(2021), 103409, https://doi.org/10.1016/j.scs.2021.103409.
[6] Z. Zhuang, C.M. Hsieh, B. Wang, Evaluation of exhaust performance of cooling towers in a super high-rise building: a case study, Build. Simulat. 8 (2015)
179–188, https://doi.org/10.1007/s12273-014-0201-8.
[7] L. Zhang, Y. Li, H. Zhang, X. Xu, Z. Yang, W. Xu, A review of the potential of district heating system in Northern China, Appl. Therm. Eng. 188 (2021), 116605,
https://doi.org/10.1016/j.applthermaleng.2021.116605.
[8] M. Jangsten, T. Lindholm, J.O. Dalenbäck, Analysis of operational data from a district cooling system and its connected buildings, Energy 203 (2020), 117844,
https://doi.org/10.1016/j.energy.2020.117844.
[9] A. Inayat, H.H. Ang, M. Raza, B.A.A. Yousef, C. Ghenai, M. Ayoub, S.I.U.H. Gilani, Integration and simulation of solar energy with hot flue gas system for the
district cooling application, Case Stud. Therm. Eng. 19 (2020), 100620, https://doi.org/10.1016/j.csite.2020.100620.
[10] L. Zhang, J. Jing, M. Duan, M. Qian, D. Yan, X. Zhang, Analysis of district cooling system with chilled water thermal storage in hot summer and cold winter area
of China, Build. Simulat. 13 (2020) 349–361, https://doi.org/10.1007/s12273-019-0581-x.
[11] Z. He, T. Ding, Y. Liu, Z. Li, Analysis of a district heating system using waste heat in a distributed cooling data center, Appl. Therm. Eng. 141 (2018) 1131–1140,
https://doi.org/10.1016/j.applthermaleng.2018.06.036.
[12] K. Faraj, M. Khaled, J. Faraj, F. Hachem, C. Castelain, Phase change material thermal energy storage systems for cooling applications in buildings: a review,
Renew. Sustain. Energy Rev. 119 (2020), 109579, https://doi.org/10.1016/j.rser.2019.109579.
14
W. Zhang et al. Case Studies in Thermal Engineering 43 (2023) 102820
[13] H. Lund, F. Arler, P.A. Østergaard, F. Hvelplund, D. Connolly, B.V. Mathiesen, P. Karnøe, Simulation versus optimisation: theoretical positions in energy system
modelling, Energies 10 (2017) 1–17, https://doi.org/10.3390/en10070840.
[14] K. Thakar, R. Patel, G. Patel, Techno-economic analysis of district cooling system: a case study, J. Clean. Prod. 313 (2021), 127812, https://doi.org/10.1016/j.
jclepro.2021.127812.
[15] J. Kang, S. Wang, C. Yan, A new distributed energy system configuration for cooling dominated districts and the performance assessment based on real site
measurements, Renew. Energy 131 (2019) 390–403, https://doi.org/10.1016/j.renene.2018.07.052.
[16] M. Jannatabadi, H.R. Rahbari, A. Arabkoohsar, District cooling systems in Iranian energy matrix, a techno-economic analysis of a reliable solution for a serious
challenge, Energy 214 (2021), 118914, https://doi.org/10.1016/j.energy.2020.118914.
[17] A. Alajmi, M. Zedan, Energy, cost, and environmental analysis of individuals and district cooling systems for a new residential city, Sustain. Cities Soc. 54
(2020), 101976, https://doi.org/10.1016/j.scs.2019.101976.
[18] W. Zhang, W. Hong, X. Jin, Research on performance and control strategy of multi-cold source district cooling system, Energy 239 (2022), 122057, https://doi.
org/10.1016/j.energy.2021.122057.
[19] Y. Wang, Z. Wang, Z. Wang, A stochastic load demand-oriented synergetic optimal control strategy for variable-speed pumps in residential district heating or
cooling systems, Energy Build. 238 (2021), 110853, https://doi.org/10.1016/j.enbuild.2021.110853.
[20] T. Zhao, J. Zhang, L. Ma, On-line optimization control method based on extreme value analysis for parallel variable-frequency hydraulic pumps in central air-
conditioning systems, Build. Environ. 47 (2012) 330–338, https://doi.org/10.1016/j.buildenv.2011.07.007.
[21] D. Lee, H.J. Jeong, H.Y. Ji, S.Y. Park, D.Y. Chung, C. Kang, K.M. Kim, D. Park, Peak load shifting control on hot water supplied from district heating using latent
heat storage system in apartment complex, Case Stud. Therm. Eng. 34 (2022), 101993, https://doi.org/10.1016/j.csite.2022.101993.
[22] A.K.S. Al-Sayyab, J. Navarro-Esbrí, A. Mota-Babiloni, Energy, exergy, and environmental (3E) analysis of a compound ejector-heat pump with low GWP
refrigerants for simultaneous data center cooling and district heating, Int. J. Refrig. 133 (2022) 61–72, https://doi.org/10.1016/j.ijrefrig.2021.09.036.
[23] X. Xu, S. You, X. Zheng, H. Li, A survey of district heating systems in the heating regions of northern China, Energy 77 (2014) 909–925, https://doi.org/
10.1016/j.energy.2014.09.078.
[24] H. Wang, H. Wang, Z. Haijian, T. Zhu, Optimization modeling for smart operation of multi-source district heating with distributed variable-speed pumps, Energy
138 (2017) 1247–1262, https://doi.org/10.1016/j.energy.2017.08.009.
[25] X. Sheng, D. Lin, Energy saving analyses on the reconstruction project in district heating system with distributed variable speed pumps, Appl. Therm. Eng. 101
(2016) 432–445, https://doi.org/10.1016/j.applthermaleng.2016.01.059.
[26] J. Gu, J. Wang, C. Qi, X. Yu, B. Sundén, Analysis of a hybrid control scheme in the district heating system with distributed variable speed pumps, Sustain. Cities
Soc. 48 (2019), 101591, https://doi.org/10.1016/j.scs.2019.101591.
[27] A. Yan, J. Zhao, Q. An, Y. Zhao, H. Li, Y.J. Huang, Hydraulic performance of a new district heating systems with distributed variable speed pumps, Appl. Energy
112 (2013) 876–885, https://doi.org/10.1016/j.apenergy.2013.06.031.
[28] H. Wang, H. Wang, T. Zhu, A new hydraulic regulation method on district heating system with distributed variable-speed pumps, Energy Convers. Manag. 147
(2017) 174–189, https://doi.org/10.1016/j.enconman.2017.03.059.
[29] S.A. Klein, et al., TRNSYS 18: A Transient System Simulation Program, Solar Energy Laboratory, University of Wisconsin, Madison, USA, 2017. Retrieved on
9.11.2022 from, http://sel.me.wisc.edu/trnsys.
[30] X.Z. Fu, Y.M. Xiao, Fluid Network for Transportation and Distribution [M], China Architecture & Building Press, Beijing, 2018, pp. 183–189.
[31] Ministry of Housing and Urban-Rural Development of the People’s Republic of China, Design Standard for Energy Efficiency of Public Buildings: GB 50189-2015
[S], China Architecture & Building Press, Beijing, 2015. Retrieved on 9.11.2022 from, http://www.jianbiaoku.com/webarbs/book/73810/1628137.shtml.
[32] Ministry of Housing and Urban-Rural Development of the People’s Republic of China, Design Standard for Energy Efficiency of Residential Buildings in Hot
Summer and Warm Winter Zone: JGJ 75-2012[S], China Architecture & Building Press, Beijing, 2012. Retrieved on 9.11.2022 from, http://www.jianbiaoku.
com/webarbs/book/66/595561.shtml.
[33] W. Gang, S. Wang, F. Xiao, D.C. Gao, District cooling systems: technology integration, system optimization, challenges and opportunities for applications,
Renew. Sustain. Energy Rev. 53 (2016) 253–264, https://doi.org/10.1016/j.rser.2015.08.051.
[34] Ministry of Housing and Urban-Rural Development of the People’s Republic of China, Standard for Building Carbon Emission Calculation: GB/T 51366-2019
(Article description-basic rules) [S], China Architecture & Building Press, Beijing, 2019, p. 48. Retrieved on 9.11.2022 from, http://www.jianbiaoku.com/
webarbs/book/135082/3995319.shtml.
[35] TRNSYS 18 Documentation, Mathematical Reference, 4, Solar Energy Laboratory, University of Wisconsin-Madison, 2017, pp. 337–340.
15