You are on page 1of 103

BACnet Map

Carlo Gavazzi

February 22, 2022


Index
Index ....................................................................................................................................................................................................................................................... 2
Functions .............................................................................................................................................................................................................................................. 13
(Fx) Analog comparator ................................................................................................................................................................................................................ 13
(Fx) Counter function..................................................................................................................................................................................................................... 13
(Fx) Car heating ............................................................................................................................................................................................................................. 13
(Fx) Main intruder alarm ............................................................................................................................................................................................................... 14
(Fx) Zone intruder alarm ............................................................................................................................................................................................................... 14
(Fx) Light function .......................................................................................................................................................................................................................... 14
(Fx) Dimmable light ....................................................................................................................................................................................................................... 15
(Fx) Multigate.................................................................................................................................................................................................................................. 15
(Fx) Simulated habitation .............................................................................................................................................................................................................. 15
(Fx) Rollerblinds ............................................................................................................................................................................................................................. 16
(Fx) Tilt rollerblinds ........................................................................................................................................................................................................................ 16
(Fx) Dimmer sequence ................................................................................................................................................................................................................. 17
(Fx) Sequence ................................................................................................................................................................................................................................ 17
(Fx) Siren......................................................................................................................................................................................................................................... 17
(Fx) Cooling temperature system ................................................................................................................................................................................................ 18
(Fx) Heating temperature system ................................................................................................................................................................................................ 18
(Fx) Smoke alarm .......................................................................................................................................................................................................................... 19
(Fx) Delay timer.............................................................................................................................................................................................................................. 19
(Fx) Zone temperature .................................................................................................................................................................................................................. 20
(Fx) Water alarm ............................................................................................................................................................................................................................ 21
(Fx) Open/close window ............................................................................................................................................................................................................... 21
(Fx) Light group function ............................................................................................................................................................................................................... 22
(Fx) Recycling timer....................................................................................................................................................................................................................... 22
(Fx) Interval timer ........................................................................................................................................................................................................................... 22
(Fx) Constant light ......................................................................................................................................................................................................................... 23
(Fx) Mathematical function ........................................................................................................................................................................................................... 24
(Fx) Analogue output ..................................................................................................................................................................................................................... 24
(Fx) Hour counter ........................................................................................................................................................................................................................... 24
(Fx) Dupline: Dimmer function ..................................................................................................................................................................................................... 25
(Fx) Dupline: Rollerblinds ............................................................................................................................................................................................................. 25
(Fx) Dupline: Digital Thermostat .................................................................................................................................................................................................. 25
(Fx) Dupline: Window control ....................................................................................................................................................................................................... 26
(Fx) Dupline: Temperature regulation ......................................................................................................................................................................................... 26
(Fx) DPO ......................................................................................................................................................................................................................................... 27
(Fx) Master zone counter ............................................................................................................................................................................................................. 27
(Fx) Switch function ....................................................................................................................................................................................................................... 28
(Fx) Program function ................................................................................................................................................................................................................... 28
(Fx) Smart light ............................................................................................................................................................................................................................... 29
Command fields description Smart Light function ....................................................................................................................................................................... 31
Modules ................................................................................................................................................................................................................................................ 33
B4X-LS4-U ...................................................................................................................................................................................................................................... 33
B4X-PIR90-U .................................................................................................................................................................................................................................. 33
B5X-LS4-U ...................................................................................................................................................................................................................................... 34
B5X-PIR90-U .................................................................................................................................................................................................................................. 34
BACC-KEYPAD-DC-U .................................................................................................................................................................................................................. 35
BDA-RE13A-U................................................................................................................................................................................................................................ 35
BDB-INCON4-U ............................................................................................................................................................................................................................. 35
BDB-INCON8-U ............................................................................................................................................................................................................................. 36
BDB-IOCP8-U ................................................................................................................................................................................................................................ 36
BDB-IOCP8A-U.............................................................................................................................................................................................................................. 37
BDD-INCON4-U ............................................................................................................................................................................................................................. 37
BEW-LS1-U .................................................................................................................................................................................................................................... 37
BEW-LS2-U .................................................................................................................................................................................................................................... 38
BEW-LS3-U .................................................................................................................................................................................................................................... 38
BEW-LS4-U .................................................................................................................................................................................................................................... 38
SH-8158 .......................................................................................................................................................................................................................................... 39
BH8-RE20A4-230 .......................................................................................................................................................................................................................... 39
BPC-INCON2 ................................................................................................................................................................................................................................. 39
BPC-INCON2A ............................................................................................................................................................................................................................... 39
BSB-PIR90-U ................................................................................................................................................................................................................................. 40
BSD-PIR90-U ................................................................................................................................................................................................................................. 40
BSF-WAT-U .................................................................................................................................................................................................................................... 40
BSG-SMO-U ................................................................................................................................................................................................................................... 41
BSG-SMOA-U ................................................................................................................................................................................................................................ 41
BSH-LUX-U..................................................................................................................................................................................................................................... 42
BSI-TEMANA-U ............................................................................................................................................................................................................................. 42
BSI-TEMANAB-U ........................................................................................................................................................................................................................... 42
BSN-ANE-U .................................................................................................................................................................................................................................... 42
BSP-PIR90-U ................................................................................................................................................................................................................................. 43
SH2D10V424 .................................................................................................................................................................................................................................. 43
SH2D500WE230 ............................................................................................................................................................................................................................ 44
SH2D500W1230 ............................................................................................................................................................................................................................ 44
SH2RE16A2E230 .......................................................................................................................................................................................................................... 45
SH2INDI424.................................................................................................................................................................................................................................... 45
SH2RE16A4 ................................................................................................................................................................................................................................... 46
SH2ROAC224 ................................................................................................................................................................................................................................ 46
SH2RODC224 ................................................................................................................................................................................................................................ 46
SH2SSTRI424 ................................................................................................................................................................................................................................ 46
SHA4XLS4TH................................................................................................................................................................................................................................. 47
SHA4XP90L .................................................................................................................................................................................................................................... 47
SHA4XTEMDIS .............................................................................................................................................................................................................................. 48
SHDRODC230 ............................................................................................................................................................................................................................... 48
SHE5XLS4TH................................................................................................................................................................................................................................. 48
SHE5XP90L .................................................................................................................................................................................................................................... 49
SHE5XTEMDIS .............................................................................................................................................................................................................................. 49
SHEKxTEMDIS .............................................................................................................................................................................................................................. 49
SHPOUTV224 ................................................................................................................................................................................................................................ 49
SHPINT1P1 .................................................................................................................................................................................................................................... 50
SHPINV2T1P124 ........................................................................................................................................................................................................................... 50
SHPINA224..................................................................................................................................................................................................................................... 50
SHPINV324..................................................................................................................................................................................................................................... 50
SHSBP90L ...................................................................................................................................................................................................................................... 51
SHSDP90L ...................................................................................................................................................................................................................................... 51
SHSPP90Lx .................................................................................................................................................................................................................................... 51
SHSQP360L ................................................................................................................................................................................................................................... 52
SBQP360L24M .............................................................................................................................................................................................................................. 52
SBQP360L24MF ............................................................................................................................................................................................................................ 53
SBQP360L24MFO ......................................................................................................................................................................................................................... 53
SHQP360L7M ................................................................................................................................................................................................................................ 54
SHQP360L7MF .............................................................................................................................................................................................................................. 54
SHQP360L7MFO ........................................................................................................................................................................................................................... 55
SHDWRE16AE230 ........................................................................................................................................................................................................................ 55
SHDWEM16A230 .......................................................................................................................................................................................................................... 55
SHE5XWLS4 .................................................................................................................................................................................................................................. 56
SHA4XWLS4 .................................................................................................................................................................................................................................. 56
BDA-INVOL-U ................................................................................................................................................................................................................................ 56
SHA4XLS4P90L............................................................................................................................................................................................................................. 57
SHE5XLS4P90L............................................................................................................................................................................................................................. 57
SH2RE1A424 ................................................................................................................................................................................................................................. 58
SHPINNI2........................................................................................................................................................................................................................................ 58
SHA4XP150 .................................................................................................................................................................................................................................... 58
SHA4XP150L ................................................................................................................................................................................................................................. 59
SHE5XP150 .................................................................................................................................................................................................................................... 59
SHE5XP150L ................................................................................................................................................................................................................................. 60
SHSUCOTL .................................................................................................................................................................................................................................... 60
SHSUCOTHL ................................................................................................................................................................................................................................. 60
SHSUT ............................................................................................................................................................................................................................................ 61
SHSUCOT....................................................................................................................................................................................................................................... 61
SHSUCOTH.................................................................................................................................................................................................................................... 61
SHSUTH.......................................................................................................................................................................................................................................... 62
SHSUCOTD.................................................................................................................................................................................................................................... 62
SHSUCOTHD ................................................................................................................................................................................................................................. 62
SHSUTD.......................................................................................................................................................................................................................................... 63
SHSUTHD ....................................................................................................................................................................................................................................... 63
SHG503WLS6 ................................................................................................................................................................................................................................ 63
SHG503BLS6 ................................................................................................................................................................................................................................. 64
SHG060WLS4 ................................................................................................................................................................................................................................ 64
SHG060BLS4 ................................................................................................................................................................................................................................. 65
SHG503WSLD ............................................................................................................................................................................................................................... 65
SHG503BSLD ................................................................................................................................................................................................................................ 66
SHG060WSLD ............................................................................................................................................................................................................................... 66
SHG060BSLD ................................................................................................................................................................................................................................ 67
SHG060BSLT ................................................................................................................................................................................................................................. 67
SHG060WSLT................................................................................................................................................................................................................................ 68
SHG503BSLT ................................................................................................................................................................................................................................. 68
SHG503WSLT................................................................................................................................................................................................................................ 69
SB2DALI230 ................................................................................................................................................................................................................................... 69
SHDWWISEN ................................................................................................................................................................................................................................. 69
SHDWWISENIN1........................................................................................................................................................................................................................... 69
SHPINCNT4 ................................................................................................................................................................................................................................... 70
SHPINCNTS04............................................................................................................................................................................................................................... 70
SH2EM16A230............................................................................................................................................................................................................................... 70
SB2REP230 .................................................................................................................................................................................................................................... 71
B4X-LS4 .......................................................................................................................................................................................................................................... 71
B5X-LS4 .......................................................................................................................................................................................................................................... 71
BEW-LS1......................................................................................................................................................................................................................................... 72
BEW-LS2......................................................................................................................................................................................................................................... 72
BEW-LS3......................................................................................................................................................................................................................................... 72
B4X-PIR90 ...................................................................................................................................................................................................................................... 72
BSF-WAT ........................................................................................................................................................................................................................................ 72
BDA-RE13A .................................................................................................................................................................................................................................... 73
BDD-INCON4 ................................................................................................................................................................................................................................. 73
BDB-INCON4 ................................................................................................................................................................................................................................. 73
BDB-INCON8 ................................................................................................................................................................................................................................. 73
BDB-IOCP8A .................................................................................................................................................................................................................................. 74
BDA-INVOL..................................................................................................................................................................................................................................... 74
BDB-IOCP8..................................................................................................................................................................................................................................... 74
BEW-LS4......................................................................................................................................................................................................................................... 75
BFW-LS4 ......................................................................................................................................................................................................................................... 75
BOW-LS4 ........................................................................................................................................................................................................................................ 75
BSB-PIR90...................................................................................................................................................................................................................................... 76
B5X-PIR90 ...................................................................................................................................................................................................................................... 76
BSD-PIR90 ..................................................................................................................................................................................................................................... 76
BSD-PIR90A ................................................................................................................................................................................................................................... 76
BSP-PIR90...................................................................................................................................................................................................................................... 76
BSP-PIR90A ................................................................................................................................................................................................................................... 77
BSN-ANE ........................................................................................................................................................................................................................................ 77
BACC-KEYPAD-DC ...................................................................................................................................................................................................................... 77
BSG-SMO ....................................................................................................................................................................................................................................... 77
BSG-SMOA..................................................................................................................................................................................................................................... 78
BSQ-PIR360 ................................................................................................................................................................................................................................... 78
BFW-PIR90 ..................................................................................................................................................................................................................................... 78
BOW-PIR90 .................................................................................................................................................................................................................................... 78
BOW-PIR90A ................................................................................................................................................................................................................................. 78
BSK-MAG........................................................................................................................................................................................................................................ 79
BEL-PIR90 ...................................................................................................................................................................................................................................... 79
BSA-IND .......................................................................................................................................................................................................................................... 79
BSA-INDA ....................................................................................................................................................................................................................................... 79
BSE-MAG........................................................................................................................................................................................................................................ 79
BSE-MAGA ..................................................................................................................................................................................................................................... 79
BDE-RE13A .................................................................................................................................................................................................................................... 79
BFW-HUM ....................................................................................................................................................................................................................................... 80
SHA4XLS2TEMDIS ....................................................................................................................................................................................................................... 80
SHE5XLS2TEMDIS ....................................................................................................................................................................................................................... 80
SHA4XLS2TEMDISU .................................................................................................................................................................................................................... 81
SHE5XLS2TEMDISU .................................................................................................................................................................................................................... 81
BOW-HUM ...................................................................................................................................................................................................................................... 81
BSH-LUX-A ..................................................................................................................................................................................................................................... 82
BSH-LUX-B ..................................................................................................................................................................................................................................... 82
G43111120 ..................................................................................................................................................................................................................................... 82
BFW-TEMANA ............................................................................................................................................................................................................................... 82
BOW-TEMANA............................................................................................................................................................................................................................... 82
BEL-TEMANA................................................................................................................................................................................................................................. 82
BSI-TEMANA.................................................................................................................................................................................................................................. 83
BDA-SSTRI1................................................................................................................................................................................................................................... 83
BSM-CAPSTD1 .............................................................................................................................................................................................................................. 83
BH4-RE16A8-230 .......................................................................................................................................................................................................................... 83
BH4-SSTRI8-230 ........................................................................................................................................................................................................................... 83
BH4-RE16A4-230 .......................................................................................................................................................................................................................... 84
BH2-SEP-230 ................................................................................................................................................................................................................................. 84
BFW-TEMTHE ............................................................................................................................................................................................................................... 84
BOW-TEMTHE ............................................................................................................................................................................................................................... 84
SHJWRE10AE230 ......................................................................................................................................................................................................................... 85
SHJWRE10AE115 ......................................................................................................................................................................................................................... 85
SHJWRE10AEBLS230 ................................................................................................................................................................................................................. 86
SHJWRE10AEWLS230 ................................................................................................................................................................................................................ 86
SHJWEM16A230 ........................................................................................................................................................................................................................... 87
SHJWEM16A115 ........................................................................................................................................................................................................................... 87
SHJWD200WE230 ........................................................................................................................................................................................................................ 88
SHJWD200WE115 ........................................................................................................................................................................................................................ 88
SHJWD200WEBLS230................................................................................................................................................................................................................. 89
SHJWD200WEWLS230 ............................................................................................................................................................................................................... 89
SBP2WREP230 ............................................................................................................................................................................................................................. 90
G34396470230............................................................................................................................................................................................................................... 90
SBP2DIW48524 ............................................................................................................................................................................................................................. 90
SHE5XWLS4WFT ......................................................................................................................................................................................................................... 90
SHE5XWLS4B ............................................................................................................................................................................................................................... 91
SHE5XWLS4WF ............................................................................................................................................................................................................................ 91
SHE5XWLS4BF ............................................................................................................................................................................................................................. 92
SBB4I2Oxxx ................................................................................................................................................................................................................................... 92
SBB4I ............................................................................................................................................................................................................................................... 93
SBP2DI48524 ................................................................................................................................................................................................................................. 93
SBPILED ......................................................................................................................................................................................................................................... 93
SBPSUSCNT .................................................................................................................................................................................................................................. 94
SBPSUSL ........................................................................................................................................................................................................................................ 94
SBPSUSL45 ................................................................................................................................................................................................................................... 95
SHJWINS04115 ............................................................................................................................................................................................................................. 96
SHJWINS04230 ............................................................................................................................................................................................................................. 96
SH2MCG24..................................................................................................................................................................................................................................... 96
SH2DUG24 ..................................................................................................................................................................................................................................... 96
SBP2MCG324 ................................................................................................................................................................................................................................ 97
UWPMM1UL1X .............................................................................................................................................................................................................................. 97
Definitions ............................................................................................................................................................................................................................................ 98
OBJECT_ANALOG_INPUT ......................................................................................................................................................................................................... 98
OBJECT_ANALOG_OUTPUT ..................................................................................................................................................................................................... 98
OBJECT_ANALOG_VALUE ........................................................................................................................................................................................................ 99
OBJECT_BINARY_INPUT ........................................................................................................................................................................................................... 99
OBJECT_BINARY_OUTPUT ..................................................................................................................................................................................................... 100
OBJECT_BINARY_VALUE ........................................................................................................................................................................................................ 100
OBJECT_CALENDAR ................................................................................................................................................................................................................ 101
OBJECT_COMMAND ................................................................................................................................................................................................................. 101
OBJECT_DEVICE ....................................................................................................................................................................................................................... 102
OBJECT_MULTI_STATE_INPUT ............................................................................................................................................................................................. 103
OBJECT_MULTI_STATE_OUTPUT ........................................................................................................................................................................................ 103
OBJECT_BITSTRING_VALUE.................................................................................................................................................................................................. 103
Functions

(Fx) Analog comparator


Function Parameter name BACnet object Data info Measure unit
name
State Binary Input 0 = Off, 1 = On; 0..1 -
InputValue Analog Input 0..100000 Number
Ref1 Analog value 0..100000 -
STATUS
Ref2 Analog value 0..100000 -
OnDelay Analog value 0..60 s
OffDelay Analog value 0..60 s

(Fx) Counter function


Function Parameter name BACnet object Data info Measure unit
name
STATUS State Analog Input 0..100000 Number
COMMANDS Cmd Analog Output 0..100000 -

(Fx) Car heating


Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = On, 2 = Off; 0..100000 -
STATUS
Temperature Analog Input -40..250 °C
COMMANDS Cmd Analog Output 1 = Start, 2 = Stop; 2 = default – no pending command; 0..100000
LowLimit Analog Value -40..250 °C
PARAMETER
HighLimit Analog Value -40..250 °C
(Fx) Main intruder alarm
Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = Deactivated with no sensors active, 2 = Deactivated with sensors active, 3 = Arming, 4 = All armed, -
STATUS 5 = Armed in at least one zone, 6 = Arming with sensor active, 7 = Disarming, 8 = Alarm, 9 = Waiting
acknowledgement; 0..100000
COMMANDS Cmd Multi State Output 1 = Start, 2 = Stop; 2 = default – no pending command; 0..100000 -
PARAMETER Delay Analog Value -40..250 Min

(Fx) Zone intruder alarm


Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = Deactivated with no sensors active, 2 = Deactivated with sensors active, 3 = Arming, 4 = Arming with sensor -
STATUS
active, 5 = Armed, 6 = Disarming, 7 = Alarm; 0..100000
COMMANDS Cmd Multi State Output 1 = Enable override disarmed, 2 = Disable override disarmed; 0..100000 -
ArmingDelay Analog Value 0..60 s
PARAMETER
DisarmingDelay Analog Value 0..60 s

(Fx) Light function


Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 =ON, 2 = OFF; 0..100000 -
STATUS
Diagnostic Bitstring value Bit1=DISABLE, bit2 = override OFF, bit3 override ON, bit4 PIR presence, bit 5 to bit6 = not used; 0..100000 -
Cmd Multi State Output When the present value us set to : 1 = Trigger output to ON, 2 = Trigger output to OFF; 2 = default – no pending -
COMMANDS
command; 0..100000
EnergySave Delay Analog Value Present value defines the energy save delay (read/write); 0..60 s
PARAMETER
Lux Threshold Analog Value Present value defines the Lux Threshold (read/write); 0..65535 Lux
(Fx) Dimmable light
Function Parameter name BACnet object Data info Measure unit
name
State Analog Input Dimmer %; 0..100000 -
STATUS
Diagnostic Bitstring value Bit1=DISABLE, bit2 = override OFF, bit3 override ON, bit4 PIR presence, bit 5 to bit6 = not used; 0..100000 -
COMMANDS Cmd Analog Output 0 = Dimmer OFF, 1 = SET S1, 2 = SET S2, 3 = SET S3, 4 = SET S4, 5 = SET S5, >=10 = SET Dimmer % ; 0..100000 -
EnergySave Delay Analog Value Present value defines the energy save delay (read/write); 0..60 s
Lux Threshold Analog Value Present value defines the lux threshold (read/write); 0..65535 Lux
S2 Analog Value Present value defines the S2 dim level; 0..100 %
S3 Analog Value Present value defines the S3 dim level; 0..100 %
S4 Analog Value Present value defines the S4 dim level; 0..100 %
PARAMETER
S5 Analog Value Present value defines the S5 dim level; 0..100 %
CorridorLightNightValue Analog Value 0..100 %
CorridorLightDayValue Analog Value 0..100 %
CorridorLightValue Analog Value 0..100 %
RestoreTimeout Analog Value 0..60 Min

(Fx) Multigate
Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = ON, 2 = OFF; 0..100000

(Fx) Simulated habitation


Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 0 = Not running, 2 = Running; 0..100000 -
COMMANDS Cmd Multi State Output 1 = Start, 2 = Stop; 2 =default – no pending command; 0..100000 -
(Fx) Rollerblinds
Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = Stop, 3 = Moving up, 4 = Moving down, 7 = Reset up, 8 = reset down; 0..100000 -
Position movement Analog Input 0..100 %
Wind Analog Input 0..35 m/s
STATUS Position Analog Input 0..100 %
Lux Analog Input 0..65535 Lux
ON_Position movement Binary Input 0..1 -
OFF_Position movement Binary Input 0..1 -
COMMANDS Cmd Analog Output 0 = 0%, 100 = 100%; 0..100000 -
WindStrong Analog Value 0..35 m/s
WindWeak Analog Value 0..35 m/s
PARAMETER WindStrongFilter Analog Value 0..60 s
WindWeakFilert Analog Value 0..60 s
CloudFilter Analog Value 0..60 s

(Fx) Tilt rollerblinds


Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = Stop, 2 = Moving 3 = Moving up, 4 = Moving down, 5 = Moving clockwise, 6 = moving anticlockwise, -
7 = Reset up, 8 = reset down; 0..100000
Wind Analog Input 0..35 m/s
Position movement Analog Input 0..100 %
STATUS Position Tilt Analog Input 0..100 %
Position Analog Input Aggregated Movement and Tilt position (16 bit integer); 0..25700 Number
Left Byte: Tilt position (%)
Right Byte: Movement position (%)
Lux Analog Input 0..65535 Lux
COMMANDS Cmd Analog Output XX,YY = XX = 0 to 100 and YY = 0 to 100; NO ANCTION FOR XX/YY > 100; 0..100000 -
WindStrong Analog Value 0..35 m/s
WindWeak Analog Value 0..35 m/s
PARAMETER WindStrongFilter Analog Value 0..60 s
WindWeakFilter Analog Value 0..60 s
CloudFilter Analog Value 0..60 s
(Fx) Dimmer sequence
Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = Not running, 2 = Running, 3 = Pause; 0..100000 -
STATUS
Step Analog Input 0..100000 Number
COMMANDS Cmd Multi State Output 1 = Start, 2 = Stop, 3= Pause/Play; 2 = default – no pending command; 0..100000 -

(Fx) Sequence
Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = Not running, 2 = Running, 3 = Pause; 0..100000 -
STATUS
Step Analog Input 0..100000 Number
COMMANDS Cmd Multi State Output 1 = Start, 2 = Stop, 3= Pause/Play; 2 = default – no pending command; 0..100000 -

(Fx) Siren
Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = Siren OFF, 2 = Siren ON; 0..100000 -
COMMANDS Cmd Multi State Output 1 = Siren start, 2 = Siren stop; 2 = default – no pending command; 0..100000 -
Delay Analog Value 0..60 s
PARAMETERS DelayON Analog Value 0..60 s
DelayOFF Analog Value 0..60 s
(Fx) Cooling temperature system
Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = ON, 2 = OFF; 0..100000 -
COMMANDS Cmd Multi State Output 1 = ON, 2 = OFF ; 2 = default; 0..100000 -

(Fx) Heating temperature system


Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = ON, 2 = OFF; 0..100000 -
COMMANDS Cmd Multi State Output 1 = ON, 2 = OFF ; 2 = default; 0..100000 -
(Fx) Smoke alarm
Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = No alarm, 2 = Alarm; 0..100000 -
COMMANDS Cmd Multi State Output 1 = Enable Alarm, 2 = Disable Alarm; 2 = default – no pending command; 0..100000 -
PARAMETERS ResetDelay Analog Value 0..60 Min

(Fx) Delay timer


Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = Not running, 2 = Running; 0..100000 -
COMMANDS Cmd Multi State Output 1 = Start, 2 = Stop; 2 = default – no pending command; 0..100000 -
OnDelay Analog Value 0..60 s
PARAMETERS
OffDelay Analog Value 0..60 s
(Fx) Zone temperature
Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = OFF, 2 = HeatOn, 3 = CoolOn, 4 = Heat&CoolOn; 0..100000 -
Heat selection Multi State Input 0 = OFF, 1 = T1, 2 = T2, 3 = T3; 0..100000 Number
Cool selection Multi State Input 0 = OFF, 1 = T1, 2 = T2, 3 = T3; 0..100000 Number
STATUS T Mode Multi State Input 0 = OFF, 1 = T1, 2 = T2, 3 = T3; 0..100000 Number
Temperature room Analog Input -40..250 °C
Temperature system Analog Input -40..250 °C
Temperature external Analog Input -40..250 °C
COMMANDS Cmd Multi State Output 0 = HeatTOff, 1 = HeatT1, 2 = HeatT2, 3 = HeatT3, 4 = CoolTOff, 5 = CoolT1, 6 = CoolT2, 7 = CoolT3; 0..100000 -
T1 Heating Analog Value -40..250 °C
T2 Heating Analog Value -40..250 °C
T3 Heating Analog Value -40..250 °C
T1 Cooling Analog Value -40..250 °C
T2 Cooling Analog Value -40..250 °C
T3 Cooling Analog Value -40..250 °C
T1 Heating Dead-band Analog Value -40..250 °C
T2 Heating Dead-band Analog Value -40..250 °C
PARAMETERS
T3 Heating Dead-band Analog Value -40..250 °C
T1 Cooling Dead-band Analog Value -40..250 °C
T2 Cooling Dead-band Analog Value -40..250 °C
T3 Cooling Dead-band Analog Value -40..250 °C
Manual Heating Analog Value -40..250 °C
Manual Cooling Analog Value -40..250 °C
Manual Heating Dead-band Analog Value -40..250 °C
Manual Cooling Dead-band Analog Value -40..250 °C
(Fx) Water alarm
Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = No alarm, 2 = Alarm; 0..100000 -
COMMANDS Cmd Multi State Output 1 = Enable Alarm, 2 = Disable Alarm; 2 = default – no pending command; 0..100000 -
PARAMETERS ResetDelay Analog Value 0..60 Min

(Fx) Open/close window


Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = Stop, 2 = Moving, 3 = Open, 4 = Close; 0..100000 -
Position movement Analog Input 0..100 %
STATUS Wind Analog Input 0..35 m/s
Position Analog Input 0..100 %
Temperature Analog Input -40..250 °C
COMMANDS Cmd Analog Output 0 = 0%, 100 = 100%; 0..100000 -
WindStrong Analog Value 0..35 m/s
WindWeak Analog Value 0..35 m/s
PARAMETER
WindStrongFilter Analog Value 0..60 s
WindWeakFilert Analog Value 0..60 s
(Fx) Light group function
Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 =ON, 2 = OFF, 3 = TOOGLE; 0..100000 -
Cmd Multi State Output When the present value us set to : 1 = Trigger output to ON, 2 = Trigger output to OFF; 3 = Trigger output to Toggle ; -
COMMANDS
0..100000

(Fx) Recycling timer


Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 =Not Running, 2 = Running; 0..100000 -
COMMANDS Cmd Multi State Output 1 = Start, 2 = Stop; 2 = default - no pending command 0..100000 -
OnDelay Analog Value 0..60 s
PARAMETERS
OffDelay Analog Value 0..60 s

(Fx) Interval timer


Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 =Not Running, 2 = Running; 0..100000 -
COMMANDS Cmd Multi State Output 1 = Start, 2 = Stop; 2 = default - no pending command 0..100000 -
PARAMETERS OffDelay Analog Value 0..60 s
(Fx) Constant light
Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = On, 2 = Off; 0..100000 -
COMMANDS Cmd Analog Output 0 = Off, 1 = On; 1 = Set S1 2 = Set S2, 3 = Set S3, 4 = Set S4, 5 = Set S5, >=10 = Set Lux; 0..100000 -
Diagnostic Bitstring Value 0..100000
AutomationEnableTimer Analog Input 0..60 s
EnergySave Timer Analog Input 0..60 s
LuxRead Analog Input 0..65535 Lux
Dimmer Percentage Analog Input 0..100 %
Dimmer Percentage Zone1 Analog Input 0..100 %
Dimmer Percentage Zone2 Analog Input 0..100 %
EnergySave Delay Analog Value 0..60 s
Lux Threshold Analog Value 0..65535 Lux
PARAMETERS DisableAutomation Delay Analog Value 0..60 Min
EnergySave Delay Analog Value 0..100000
Pir Action Analog Value 0..65535 Lux
PirRetriggersOnlyIfDimmerIsOff Binary Input 0..1
S2 Analog Value 0..65535 Lux
S3 Analog Value 0..65535 Lux
S4 Analog Value 0..65535 Lux
S5 Analog Value 0..65535 Lux
CorridorLightValue Analog Value 0..65535 Lux
RestoreTimeout Analog Value 0..60 Min
(Fx) Mathematical function
Function Parameter name BACnet object Data info Measure unit
name
State Analog Input 0..100000 -
STATUS Offset Analog Value 0..100000 Number
Output offset Analog Value 0..100000 Number

(Fx) Analogue output


Function Parameter name BACnet object Data info Measure unit
name
STATUS State Analog Input 0..100000 -
COMMANDS Cmd Analog Output 0..100000 -

(Fx) Hour counter


Function Parameter name BACnet object Data info Measure unit
name
State Analog Input 0..24 Hours
Diagnostic Bitstring Value 0..100000
STATUS
WarningLimit Analog Value 0..100000 Number
WorkHourLimit Analog Value 0..24 Hours
(Fx) Dupline: Dimmer function
Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = Off, 2 = ON; 0..100000 -
Cmd Multi State Output 1 = OFF, 2 = scenario-1, 3 = scenario-2, 4 = scenario-3, 5 = scenario-4, 6 = scenario-5, 7 = scenario-6, 8 = Toggle, 9 = -
COMMANDS
ON, 10 = Full-on; 0..100000
EnergySave Delay Analog Value 0..60 s
PARAMETER LuxLowLimit Analog Value 0..65535 Lux
LuxHighLimit Analog Value 0..65535 Lux

(Fx) Dupline: Rollerblinds


Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = Off, 2 = Reverse, 3 = Move UP, 4 = Move Down; 0..100000 -
STATUS Lux Analog Input 0..65535 Lux
Wind Analog Input 0..35 m/s
COMMANDS Cmd Analog Output 1 = Move UP, 2 = Move Down; 0..100000 -
WindStrong Analog Value 0..35 m/s
WindWeak Analog Value 0..35 m/s
WindStrongFilter Analog Value 0..60 Min
PARAMETER WindWeakFilert Analog Value 0..60 Min
LuxHighLimit Analog Value 0..65535 Lux
LuxLowLimit Analog Value 0..65535 Lux
CloudFilter Analog Value 0..60 s

(Fx) Dupline: Digital Thermostat


Function Parameter name BACnet object Data info Measure unit
name
STATUS State Multi State Input 1 = ON, 2 = OFF; 0..100000 -
(Fx) Dupline: Window control
Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = OFF, 2 = Reverse, 3 = Move UP, 4 = Move Down; 0..100000 -
STATUS Temperature Analog Input -40..250 °C
Wind Analog Input 0..35 m/s
COMMANDS Cmd Analog Output 1 = Move UP, 2 = Move Down; 0..100000 -
WindStrong Analog Value 0..35 m/s
WindWeak Analog Value 0..35 m/s
WindStrongFilter Analog Value 0..60 Min
PARAMETER WindWeakFilert Analog Value 0..60 Min
TempLowLimit Analog Value -40..250 °C
TempHighLimit Analog Value -40..250 °C
CloudFilter Analog Value 0..60 s

(Fx) Dupline: Temperature regulation


Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = OFF, 2 = On; 0..100000 -
STATUS Temperature room Analog Input -40..250 °C
Temperature floor Analog Input -40..250 °C
COMMANDS Cmd Multi State Output 1 = Setpoint heat, 2 = Setpoint cool, 3 = Energy save heat, 4 = Energy save cool, 5 = Antifreeze; 0..100000 -
Active temperature set Multi State Input 1 = Setpoint heat, 2 = Setpoint cool, 3 = Energy save heat, 4 = Energy save cool, 5 = Antifreeze; 0..100000 -
Heating status Multi State Input 1 = OFF, 2 = On; 0..100000 -
Cooling status Multi State Input 1 = OFF, 2 = On; 0..100000 -
PARAMETERS Cooling Setpoint Analog Value -40..250 °C
Cool Ensave Setpoint Analog Value -40..250 °C
Heating Setpoint Analog Value -40..250 °C
Heat Ensave Setpoint Analog Value -40..250 °C
(Fx) DPO
Function Parameter name BACnet object Data info Measure unit
name
STATUS State Analog Input 0..100000 -
COMMANDS Cmd Analog Output 0..100000 -
EntryExitCounter Analog Input 0..2147483648 CP Number
EntryCounter Analog Input 0..2147483648 CP Number
ExitCounter Analog Input 0..2147483648 CP Number
DPO Timeout Analog Value 0..60 s
Max EntryExitCounter Analog Value 0..2147483648 CP Number
PARAMETERS Max EntryCounter Analog Value 0..2147483648 CP Number
Max ExitCounter Analog Value 0..2147483648 CP Number
OverWrite Entry Exit Analog Value 0..2147483648 CP Number
Counter
OverWrite Entry Counter Analog Value 0..2147483648 CP Number
OverWrite Exit Counter Analog Value 0..2147483648 CP Number

(Fx) Master zone counter


Function Parameter name BACnet object Data info Measure unit
name
State Analog Value 0..100000 -
Car In Transit Analog Output 0..2147483648 CP Number
Surplus of available bays Analog Output 0..2147483648 CP Number
Available bays Analog Value 0..2147483648 CP Number
Car In Transit Analog Value 0..2147483648 CP Number
Surplus of available bays Analog Value 0..2147483648 CP Number
STATUS
Overwrite the number of Analog Value 0..2147483648 CP Number
available bays
Overwrite the number of Analog Value 0..2147483648 CP Number
car In Transit
Overwrite the number of Analog Value 0..2147483648 CP Number
surplus of available bays
(Fx) Program function
Function Parameter name BACnet object Data info Measure
name unit
State Bitstring Value Bit 0x00=AllDeactive, Bit 0x01 = Running, 0x02 = Pause, Bit 0x04 = OverrideOffActive, Bit 0x08 = OverrideOnActive; 0..2147483647 -
Step Time Analog Input 0..2147483647 s
STATUS StepRemaining Time Analog Input 0..2147483647 s
TotalExecution Time Analog Input 0..2147483647 s
Remaining Time Analog Input 0..2147483647 s
COMMANDS Cmd Multi State Output When the present value is set to: 1 = Start, 2 = Stop, 3 = Pause; 0..100000

(Fx) Switch function


Function Parameter name BACnet object Data info Measure unit
name
State Multi State Input 1 = OFF, 2 = ON; 0..100000 -
STATUS Disable Timer Analog Input 0..86399 s
Timer Off Analog Input 0..86399 s
Cmd Multi State Output When the present value is set to: 1 = Turn on, 2 = Turn off, 3= Toggle, 4 = Automation enable, 5 = Automation -
COMMANDS
disable, 6 = Automation toggle; 0..100000
(Fx) Smart light
Function Parameter name BACnet object Data info Measure unit
name
State Multi State input 1 = OFF, 2 = ON; 0..100000 -
Working Status Bitstring Value Working Status state; 0..2147483647 -
Automation Status Bitstring Value Automation Status bit array; 0..2147483647 -
Dimmer Set Analog Input Dimmer Set; 0..2147483647 %
Constant Set Analog Input Constant Set; 0..2147483647 Lux
Tc set Analog Input Tc set; 0..2147483647 MireK
Master Level Analog Input Master Level; 0..100 %
Slave1 Level Analog Input Slave1 Level; 0..100 %
Slave2 Level Analog Input Slave2 Level; 0..100 %
Tc Analog Input Tc output level; 0..65534 MireK
Lux Current Analog Input Lux current; 0..2147483647 Lux
Lux Estimated Analog Input Lux estimated; 0..2147483647 Lux
Lux Automation Analog Input Lux automation; 0..2147483647 Lux
EnergySave Timer Analog Input Energy save timer; 0..86400 s
Disable Timer Analog Input Disable automation timer; 0..86400 s
Constant Timer Analog Input Return to Tc auto mode timer; 0..86400 s
STATUS Colour Timer Analog Input Return to Tc auto mode timer; 0..86400 s
Refresh Timer Analog Input Refresh timer; 0..86400 s
TriggerS1 Action Multi State Output 1 = Trigger S1 Action, ..., 5 = Trigger S5 Action, 6 = OFF; 1..6 -
S1 Action
Level Analog Value -1..5018 -
Tc Analog Value -1..65534 -
Option Analog Value 0.. 134217727 -
Enable Analog Value 0.. 134217727 -
S2 Action
Level Analog Value -1..5018 -
Tc Analog Value -1..65534 -
Option Analog Value 0.. 134217727 -
Enable Analog Value 0.. 134217727 -
S3 Action
Level Analog Value -1..5018 -
Tc Analog Value -1..65534 -
Option Analog Value 0.. 134217727 -
Enable Analog Value 0.. 134217727 -
(Fx) Smart light
Function Parameter name BACnet object Data info Measure unit
name
S4Action
Level Analog Value -1..5018 -
Tc Analog Value -1..65534 -
Option Analog Value 0.. 134217727 -
Enable Analog Value 0.. 134217727 -
S5 Action
Level Analog Value -1..5018 -
Tc Analog Value -1..65534 -
Option Analog Value 0.. 134217727 -
Enable Analog Value 0.. 134217727 -
Sequence A
Step Enable Analog Value Enable step 1
Delay Analog Value Delay step 1; 0..86400 s
Level Analog Value Command step 1- Level
STATUS Tc Analog Value Command step 1-Tc
Option Analog Value Command step 1-Option
Enable Analog Value Command step 1-Enable
Sequence B
Step Enable Analog Value Enable step 1
Delay Analog Value Delay step 1; 0..86400 s
Level Analog Value Command step 1- Level
Tc Analog Value Command step 1-Tc
Option Analog Value Command step 1-Option
Enable Analog Value Command step 1-Enable

Virtual Off Threshold Analog Value 100..30000 Lux


Virtual Off Hysteresis Analog Value 0..50 %
Virtual Off DelayOn Analog Value 0..60 s
Room Lux Fail State Analog Value 0..100 %
Energy Save Timer Analog Value 0..86400 s
Command fields description Smart Light function
Word + 0: Level (-1...5018)
Word + 1: Tc (-1...65534)
Word + 2: Option (0...7FFFh)
Word + 3: Enable (0...7FFFh)
Level -1 = null)
Level 0 = OFF
Level 1 = ON (dimmer or constant set)
Level 2 = apply S2 predefined command
Level 3 = apply S3 predefined command
Level 4 = apply S4 predefined command
Level 5 = apply S5 predefined command
Level 6 = dimmer mode, 100
Level 7 = dimmer mode, 10
Level 8 = dimmer mode, 50
Level 9 = dimmer mode, 75
Level 9 = dimmer mode, 75
Level 10...100 = dimmer mode, x %
Level 101...5000 = constant mode, x Lux
Level 5001 = Start A sequence
Level 5002 = Stop A sequence
Level 5003 = Start/Stop A sequence
Level 5004 = Start B sequence
Level 5005 = Stop B sequence
Level 5006 = Start/Stop B sequence
Level 5007 = Activate disable
Level 5008 = Deactivate disable
Level 5009 = Activate / deactivate disable
Level 5010 = Activate force 100
Level 5011 = Deactivate force 100
Level 5012 = Activate / deactivate force 100
Level 5013 = Activate force OFF
Level 5014 = Deactivate force OFF
Level 5015 = Activate / deactivate OFF
Level 5016 = Activate calibration mode
Level 5017 = Deactivate calibration mode
Level 5018 = Activate / deactivate calibration mode
Tc -1 = null
Tc 0 = activate auto Tc mode
Tc 1…65534 = activate manual Tc mode, x mireK
Option Bit0=Toggle ON/OFF
Option Bit1=Start energy save timer
Option Bit2=Toggle dimmer / constant mode
Option Bit3=Set dimmer mode
Option Bit4=Set constant mode
Option Bit5=Start return to constant mode timer
Option Bit6=Toggle auto / manual Tc mode
Option Bit7=Set auto Tc mode
Option Bit8=Set manual Tc mode
Option Bit9=Start return to auto Tc mode timer
Enable Bit0=Light ON
Enable Bit1=Light OFF
Enable Bit2=Room presence ON
Enable Bit3=Room presence OFF
Enable Bit4=Day time ON
Enable Bit5=Day time OFF
Enable Bit6=Night time ON
Enable Bit7=Night time OFF
Enable Bit8=Rtc ON
Enable Bit9=Rtc OFF
Modules

B4X-LS4-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K2 Push 1 0 1
Push Binary Input 2: General - Switches K2 Push 2 0 1
Push Binary Input 3: General - Switches K2 Push 3 0 1
Push Binary Input 4: General - Switches K2 Push 4 0 1
Led Binary Output 5: General - Switches K2 Led 1 0 1
Led Binary Output 6: General - Switches K2 Led 2 0 1
Led Binary Output 7: General - Switches K2 Led 3 0 1
Led Binary Output 8: General - Switches K2 Led 4 0 1
Presence Binary Input 9: General - Switches K2 Presence 1 0 1
Configuration ok Binary Input 10: General - Switches K2 Configuration OK 1 0 1
Quality index Analog input 11: General - Switches K2 Quality index 1 0 100

B4X-PIR90-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K3 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K3 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors K3 Alarm 1 0 1
Bus voltage Analog Input 8: General - Motion detectors K3 Bus voltage 1 0 400 V
Led Binary Output 4: General - Motion detectors K3 Led 1 0 1
Presence Binary Input 5: General - Motion detectors K3 Presence 1 0 1
Configuration OK Binary Input 6: General - Motion detectors K3 Configuration OK 1 0 1
Quality index Analog Input 7: General - Motion detectors K3 Quality index 1 0 100
B5X-LS4-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K2 Push 1 0 1
Push Binary Input 2: General - Switches K2 Push 2 0 1
Push Binary Input 3: General - Switches K2 Push 3 0 1
Push Binary Input 4: General - Switches K2 Push 4 0 1
Led Binary Output 5: General - Switches K2 Led 1 0 1
Led Binary Output 6: General - Switches K2 Led 2 0 1
Led Binary Output 7: General - Switches K2 Led 3 0 1
Led Binary Output 8: General - Switches K2 Led 4 0 1
Presence Binary Input 9: General - Switches K2 Presence 1 0 1
Configuration ok Binary Input 10: General - Switches K2 Configuration OK 1 0 1
Quality index Analog input 11: General - Switches K2 Quality index 1 0 100

B5X-PIR90-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K3 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K3 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors K3 Alarm 1 0 1
Bus voltage Analog Input 8: General - Motion detectors K3 Bus voltage 1 0 400 V
Led Binary Output 4: General - Motion detectors K3 Led 1 0 1
Presence Binary Input 5: General - Motion detectors K3 Presence 1 0 1
Configuration OK Binary Input 6: General - Motion detectors K3 Configuration OK 1 0 1
Quality index Analog Input 7: General - Motion detectors K3 Quality index 1 0 100
BACC-KEYPAD-DC-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Bell Binary Input 1: General - Keypad K6 Bell 1 0 1
Code accepted Binary Input 2: General - Keypad K6 Code accepted 1 0 1
Led Binary Output 3: General - Keypad K6 Led 1 0 1
Led Binary Output 4: General - Keypad K6 Led 2 0 1
Buzzer Binary Output 5: General - Keypad K6 Buzzer 1 0 1
Presence Binary Input 6: General - Keypad K6 Presence 1 0 1
Configuration OK Binary Input 7: General - Keypad K6 Configuration OK 1 0 1
Quality index Analog Input 8: General - Keypad K6 Quality index 1 0 100

BDA-RE13A-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary Output 1: General - Relay module K7 Re 1 0 1
Presence Binary Input 2: General - Relay module K7 Presence 1 0 1
Configuration OK Binary Input 3: General - Relay module K7 Configuration OK 1 0 1
Quality index Analog Input 4: General - Relay module K7 Quality index 1 0 100

BDB-INCON4-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K8 Push 1 0 1
Push Binary Input 2: General - I/O Modules K8 Push 2 0 1
Push Binary Input 3: General - I/O Modules K8 Push 3 0 1
Push Binary Input 4: General - I/O Modules K8 Push 4 0 1
Presence Binary Input 5: General - I/O Modules K8 Presence 1 0 1
Configuration ok Binary Input 6: General - I/O Modules K8 Configuration OK 1 0 1
Quality index Analog input 7: General - I/O Modules K8 Quality index 1 0 100
BDB-INCON8-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K9 Push 1 0 1
Push Binary Input 2: General - I/O Modules K9 Push 2 0 1
Push Binary Input 3: General - I/O Modules K9 Push 3 0 1
Push Binary Input 4: General - I/O Modules K9 Push 4 0 1
Push Binary Input 5: General - I/O Modules K9 Push 5 0 1
Push Binary Input 6: General - I/O Modules K9 Push 6 0 1
Push Binary Input 7: General - I/O Modules K9 Push 7 0 1
Push Binary Input 8: General - I/O Modules K9 Push 8 0 1
Presence Binary Input 9: General - I/O Modules K9 Presence 1 0 1
Configuration ok Binary Input 10: General - I/O Modules K9 Configuration OK 1 0 1
Quality index Analog input 11: General - I/O Modules K9 Quality index 1 0 100

BDB-IOCP8-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K10 Push 1 0 1
Push Binary Input 2: General - I/O Modules K10 Push 2 0 1
Push Binary Input 3: General - I/O Modules K10 Push 3 0 1
Push Binary Input 4: General - I/O Modules K10 Push 4 0 1
Led Binary Output 5: General - I/O Modules K10 Led 1 0 1
Led Binary Output 6: General - I/O Modules K10 Led 2 0 1
Led Binary Output 7: General - I/O Modules K10 Led 3 0 1
Led Binary Output 8: General - I/O Modules K10 Led 4 0 1
Presence Binary Input 9: General - I/O Modules K10 Presence 1 0 1
Configuration ok Binary Input 10: General - I/O Modules K10 Configuration OK 1 0 1
Quality index Analog input 11: General - I/O Modules K10 Quality index 1 0 100
BDB-IOCP8A-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K10 Push 1 0 1
Push Binary Input 2: General - I/O Modules K10 Push 2 0 1
Push Binary Input 3: General - I/O Modules K10 Push 3 0 1
Push Binary Input 4: General - I/O Modules K10 Push 4 0 1
Led Binary Output 5: General - I/O Modules K10 Led 1 0 1
Led Binary Output 6: General - I/O Modules K10 Led 2 0 1
Led Binary Output 7: General - I/O Modules K10 Led 3 0 1
Led Binary Output 8: General - I/O Modules K10 Led 4 0 1
Presence Binary Input 9: General - I/O Modules K10 Presence 1 0 1
Configuration ok Binary Input 10: General - I/O Modules K10 Configuration OK 1 0 1
Quality index Analog input 11: General - I/O Modules K10 Quality index 1 0 100

BDD-INCON4-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K10 Push 1 0 1
Push Binary Input 2: General - I/O Modules K10 Push 2 0 1
Push Binary Input 3: General - I/O Modules K10 Push 3 0 1
Push Binary Input 4: General - I/O Modules K10 Push 4 0 1
Led Binary Output 5: General - I/O Modules K10 Led 1 0 1
Presence Binary Input 6: General - I/O Modules K10 Presence 1 0 1
Configuration ok Binary Input 7: General - I/O Modules K10 Configuration OK 1 0 1
Quality index Analog input 8: General - I/O Modules K10 Quality index 1 0 100

BEW-LS1-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K13 Push 1 0 1
Led Binary Output 2: General - Switches K13 Led 1 0 1
Presence Binary Input 3: General - Switches K13 Presence 1 0 1
Configuration ok Binary Input 4: General - Switches K13 Configuration OK 1 0 1
Quality index Analog input 5: General - Switches K13 Quality index 1 0 100
BEW-LS2-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K14 Push 1 0 1
Push Binary Input 2: General - Switches K14 Push 2 0 1
Led Binary Output 3: General - Switches K14 Led 1 0 1
Led Binary Output 4: General - Switches K14 Led 2 0 1
Presence Binary Input 5: General - Switches K14 Presence 1 0 1
Configuration ok Binary Input 6: General - Switches K14 Configuration OK 1 0 1
Quality index Analog input 7: General - Switches K14 Quality index 1 0 100

BEW-LS3-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K15 Push 1 0 1
Push Binary Input 2: General - Switches K15 Push 2 0 1
Push Binary Input 3: General - Switches K15 Push 3 0 1
Led Binary Output 4: General - Switches K15 Led 1 0 1
Led Binary Output 5: General - Switches K15 Led 2 0 1
Led Binary Output 6: General - Switches K15 Led 3 0 1
Presence Binary Input 7: General - Switches K15 Presence 1 0 1
Configuration ok Binary Input 8: General - Switches K15 Configuration OK 1 0 1
Quality index Analog input 9: General - Switches K15 Quality index 1 0 100

BEW-LS4-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K16 Push 1 0 1
Push Binary Input 2: General - Switches K16 Push 2 0 1
Push Binary Input 3: General - Switches K16 Push 3 0 1
Push Binary Input 4: General - Switches K16 Push 4 0 1
Led Binary Output 5: General - Switches K16 Led 1 0 1
Led Binary Output 6: General - Switches K16 Led 2 0 1
Led Binary Output 7: General - Switches K16 Led 3 0 1
Led Binary Output 8: General - Switches K16 Led 4 0 1
Presence Binary Input 9: General - Switches K16 Presence 1 0 1
Configuration ok Binary Input 10: General - Switches K16 Configuration OK 1 0 1
Quality index Analog input 11: General - Switches K61 Quality index 1 0 100
SH-8158
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K17 Push 1 0 1
Push Binary Input 2: General - Switches K17 Push 2 0 1
Push Binary Input 3: General - Switches K17 Push 3 0 1
Push Binary Input 4: General - Switches K17 Push 4 0 1
Led Binary Output 5: General - Switches K17 Led 1 0 1
Led Binary Output 6: General - Switches K17 Led 2 0 1
Led Binary Output 7: General - Switches K17 Led 3 0 1
Led Binary Output 8: General - Switches K17 Led 4 0 1
Presence Binary Input 9: General - Switches K17 Presence 1 0 1
Configuration ok Binary Input 10: General - Switches K17 Configuration OK 1 0 1
Quality index Analog input 11: General - Switches K17 Quality index 1 0 100

BH8-RE20A4-230
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary Output 1: General - Relay module K18 Re 1 0 1
Re Binary Output 2: General - Relay module K18 Re 2 0 1
Re Binary Output 3: General - Relay module K18 Re 3 0 1
Re Binary Output 4: General - Relay module K18 Re 4 0 1

BPC-INCON2
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K19 Push 1 0 1
Led Binary Output 5: General - I/O Modules K19 Led 1 0 1
Push Binary Input 2: General - I/O Modules K19 Push 2 0 1
Led Binary Output 6: General - I/O Modules K19 Led 2 0 1

BPC-INCON2A
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K20 Push 1 0 1
Led Binary Output 5: General - I/O Modules K20 Led 1 0 1
Push Binary Input 2: General - I/O Modules K20 Push 2 0 1
Led Binary Output 6: General - I/O Modules K20 Led 2 0 1
Led Binary Output 7: General - I/O Modules K20 Led 3 0 1
BSB-PIR90-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K21 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K21 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors K21 Alarm 1 0 1
Bus voltage Analog Input 8: General - Motion detectors K21 Bus voltage 1 0 400 V
Led Binary Output 4: General - Motion detectors K21 Led 1 0 1
Presence Binary Input 5: General - Motion detectors K21 Presence 1 0 1
Configuration OK Binary Input 6: General - Motion detectors K21 Configuration OK 1 0 1
Quality index Analog Input 7: General - Motion detectors K21 Quality index 1 0 100

BSD-PIR90-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K22 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K22 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors K22 Alarm 1 0 1
Bus voltage Analog Input 8: General - Motion detectors K22 Bus voltage 1 0 400 V
Led Binary Output 4: General - Motion detectors K22 Led 1 0 1
Presence Binary Input 5: General - Motion detectors K22 Presence 1 0 1
Configuration OK Binary Input 6: General - Motion detectors K22 Configuration OK 1 0 1
Quality index Analog Input 7: General - Motion detectors K22 Quality index 1 0 100

BSF-WAT-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Water alarm Binary Input 1: General – Water detector K23 Water alarm 1 0 1
Presence Binary Input 2: General - Water detector K23 Presence 1 0 1
Configuration OK Binary Input 3: General - Water detector K23 Configuration OK 1 0 1
Quality index Analog Input 4: General - Water detector K23 Quality index 1 0 100
BSG-SMO-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Smoke alarm Binary Input 1: General – Smoke sensor K24 Smoke alarm 1 0 1
Bus voltage Analog Input 10: General – Smoke sensor K24 Bus voltage 1 0 400 V
Buzzer Binary Output 2: General – Smoke sensor K24 Buzzer 1 0 1
Presence Binary Input 3: General – Smoke sensor K24 Presence 1 0 1
Configuration OK Binary Input 4: General – Smoke sensor K24 Configuration OK 1 0 1
Quality index Analog Input 5: General – Smoke sensor K24 Quality index 1 0 100
Battery low Binary Input 6: General – Smoke sensor K24 Battery low 1 0 1
Missing battery Binary Input 7: General – Smoke sensor K24 Missing battery 1 0 1
Sensor dirty Binary Input 8: General – Smoke sensor K24 Sensor dirty 1 0 1
Hardware error Binary Input 9: General – Smoke sensor K24 Hardware error 1 0 1

BSG-SMOA-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Smoke alarm Binary Input 1: General – Smoke sensor K25 Smoke alarm 1 0 1
Bus voltage Analog Input 8: General – Smoke sensor K25 Bus voltage 1 0 400 V
Buzzer Binary Output 2: General – Smoke sensor K25 Buzzer 1 0 1
Presence Binary Input 3: General – Smoke sensor K25 Presence 1 0 1
Configuration OK Binary Input 4: General – Smoke sensor K25 Configuration OK 1 0 1
Quality index Analog Input 5: General – Smoke sensor K25 Quality index 1 0 100
Sensor dirty Binary Input 6: General – Smoke sensor K25 Sensor dirty 1 0 1
Hardware error Binary Input 7: General – Smoke sensor K25 Hardware error 1 0 1
BSH-LUX-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Luxmeter Analog Input 1: General – Lux sensor K26 Luxmeter 1 0 65535 Lux
Bus voltage Analog Input 5: General – Lux sensor K26 Bus voltage 1 0 400 V
Presence Binary Input 2: General – Lux sensor K26 Presence 1 0 1
Configuration OK Binary Input 3: General – Lux sensor K26 Configuration OK 1 0 1
Quality index Analog Input 4: General – Lux sensor K26 Quality index 1 0 100

BSI-TEMANA-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Temp sensor K27 Temperature 1 -40 250 °C
Presence Binary Input 2: General – Temp sensor K27 Presence 1 0 1
Configuration OK Binary Input 3: General – Temp sensor K27 Configuration OK 1 0 1
Quality index Analog Input 4: General – Temp sensor K27 Quality index 1 0 100

BSI-TEMANAB-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Temp sensor K28 Temperature 1 -40 250 °C
Presence Binary Input 2: General – Temp sensor K28 Presence 1 0 1
Configuration OK Binary Input 3: General – Temp sensor K28 Configuration OK 1 0 1
Quality index Analog Input 4: General – Temp sensor K28 Quality index 1 0 100

BSN-ANE-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Wind Analog Input 1: General – Wind sensor K29 Wind 1 0 35 m/s
Presence Binary Input 2: General – Wind sensor K29 Presence 1 0 1
Configuration OK Binary Input 3: General – Wind sensor K29 Configuration OK 1 0 1
Quality index Analog Input 4: General – Wind sensor K29 Quality index 1 0 100
BSP-PIR90-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K30 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K30 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors K30 Alarm 1 0 1
Bus voltage Analog Input 8: General - Motion detectors K30 Bus voltage 1 0 400 V
Led Binary Output 4: General - Motion detectors K30 Led 1 0 1
Presence Binary Input 5: General - Motion detectors K30 Presence 1 0 1
Configuration OK Binary Input 6: General - Motion detectors K30 Configuration OK 1 0 1
Quality index Analog Input 7: General - Motion detectors K30 Quality index 1 0 100

SH2D10V424
Name BACnet object BACnet name Min Value Max Value Measure unit
Presence Binary Input 5: General - Motion detectors K33 Presence 1 0 1
Configuration OK Binary Input 6: General - Motion detectors K33 Configuration OK 1 0 1
Quality index Analog Input 7: General - Motion detectors K33 Quality index 1 0 100
SH2D500WE230
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General - Dimmer module K34 KWh 1 0 1000000000 kWh
kWdmd Analog Input 2: General - Dimmer module K34 kWdmd 1 0 1000000000 kW
kW Analog Input 3: General - Dimmer module K34 kW 1 0 1000000000 kW
kVA Analog Input 4: General - Dimmer module K34 kVA 1 0 1000000000 kVA
kVAr Analog Input 5: General - Dimmer module K34 kVAr 1 0 1000000000 kVAR
Ampere Analog Input 6: General - Dimmer module K34 Ampere 1 0 1000 A
Volt Analog Input 7: General - Dimmer module K34 Volt 1 0 400 V
PF Analog Input 8: General - Dimmer module K34 PF 1 -0.99 0.99
Presence Binary Input 10: General – Dimmer module k34 Presence 1 0 1
Configuration OK Binary Input 11: General - Dimmer module k34 Configuration OK 1 0 1
Quality index Analog Input 12: General - Dimmer module k34 Quality index 1 0 100
Overload warning Binary Input 13: General - Dimmer module K34 Overload warning 1 0 1
Over voltage Binary Input 14: General - Dimmer module K34 Over voltage 1 0 1
Over temperature Binary Input 15: General - Dimmer module K34 Over temperature 1 0 1
Hardware error Binary Input 16: General - Dimmer module K34 Hardware error 1 0 1
Over current Binary Input 17: General - Dimmer module K34 Over current 1 0 1
Load not present Binary Input 18: General - Dimmer module K34 Load not present 1 0 1
Short circuit Binary Input 19: General - Dimmer module K34 Short circuit 1 0 1

SH2D500W1230
Name BACnet object BACnet name Min Value Max Value Measure unit
Presence Binary Input 10: General – Dimmer module k35 Presence 1 0 1
Configuration OK Binary Input 11: General - Dimmer module k35 Configuration OK 1 0 1
Quality index Analog Input 12: General - Dimmer module k35 Quality index 1 0 100
Overload warning Binary Input 13: General - Dimmer module K35 Overload warning 1 0 1
Over voltage Binary Input 14: General - Dimmer module K35 Over voltage 1 0 1
Over temperature Binary Input 15: General - Dimmer module K35 Over temperature 1 0 1
Hardware error Binary Input 16: General - Dimmer module K35 Hardware error 1 0 1
Over current Binary Input 17: General - Dimmer module K35 Over current 1 0 1
Load not present Binary Input 18: General - Dimmer module K35 Load not present 1 0 1
Short circuit Binary Input 19: General - Dimmer module K35 Short circuit 1 0 1
SH2INDI424
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Switches K36 Switch 1 0 1
Switch Binary Input 2: General - Switches K36 Switch 2 0 1
Switch Binary Input 3: General - Switches K36 Switch 3 0 1
Switch Binary Input 4: General - Switches K36 Switch 4 0 1
Presence Binary Input 5 General - Switches K36 Presence 1 0 1
Configuration ok Binary Input 6: General - Switches K36 Configuration OK 1 0 1
Quality index Analog input 7: General - Switches K36 Quality index 1 0 100

SH2RE16A2E230
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1 0 1000000000 kWh
kWdmd Analog Input 1 0 1000000000 kW
kW Analog Input 1 0 1000000000 kW
kVA Analog Input 1 0 1000000000 kVA
kVAr Analog Input 1 0 1000000000 kVAR
Ampere Analog Input 1 0 1000 A
Volt Analog Input 1 0 400 V
PF Analog Input 1 -0.99 0.99
Re Binary output 1 0 1
Re Binary output 1 0 1
Presence Binary Input 1 0 1
Configuration OK Binary Input 1 0 1
Quality index Analog Input 1 0 100
Overload warning Binary Input 1 0 1
Hardware error Binary Input 1 0 1
Load not present Binary Input 1 0 1
SH2RE16A4
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary output 1: General - Relay module k38 Re 1 0 1
Re Binary output 2: General - Relay module k38 Re 2 0 1
Re Binary output 3: General - Relay module k38 Re 3 0 1
Re Binary output 4: General - Relay module k38 Re 4 0 1
Bus voltage Analog input 8: General - Relay module k38 Bus voltage 1 0 400 V
Presence Binary Input 5: General - Relay module k38 Presence 1 0 1
Configuration OK Binary Input 6: General - Relay module k38 Configuration OK 1 0 1
Quality index Analog Input 7: General - Relay module k38 Quality index 1 0 100

SH2ROAC224
Name BACnet object BACnet name Min Value Max Value Measure unit
Presence Binary Input 5: General - Rollerblinds module k39 Presence 1 0 1
Configuration OK Binary Input 6: General - Rollerblinds module k39 Configuration OK 1 0 1
Quality index Analog Input 7: General - Rollerblinds module k39 Quality index 1 0 100

SH2RODC224
Name BACnet object BACnet name Min Value Max Value Measure unit
Presence Binary Input 5: General - Rollerblinds module k39 Presence 1 0 1
Configuration OK Binary Input 6: General - Rollerblinds module k39 Configuration OK 1 0 1
Quality index Analog Input 7: General - Rollerblinds module k39 Quality index 1 0 100

SH2SSTRI424
Name BACnet object BACnet name Min Value Max Value Measure unit
Tri Binary output 1: General - Triac k38 Tri 1 0 1
Tri Binary output 2: General - Triac k38 Tri 2 0 1
Tri Binary output 3: General - Triac k38 Tri 3 0 1
Tri Binary output 4: General - Triac k38 Tri 4 0 1
Presence Binary Input 5: General - Triac k38 Presence 1 0 1
Configuration OK Binary Input 6: General - Triac k38 Configuration OK 1 0 1
Quality index Analog Input 7: General - Triac k38 Quality index 1 0 100
SHA4XLS4TH
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K42 Push 1 0 1
Push Binary Input 2: General - Switches K42 Push 2 0 1
Push Binary Input 3: General - Switches K42 Push 3 0 1
Push Binary Input 4: General - Switches K42 Push 4 0 1
Humidity Analog input 5: General - Switches K42 Humidity 1 0 100 %
Temperature Analog input 6: General - Switches K42 Temperature 1 -40 250 °C
Led Binary Output 7: General - Switches K42 Led 1 0 1
Led Binary Output 8: General - Switches K42 Led 2 0 1
Led Binary Output 9: General - Switches K42 Led 3 0 1
Led Binary Output 10: General - Switches K42 Led 4 0 1
Presence Binary Input 11: General - Switches K42 Presence 1 0 1
Configuration ok Binary Input 12: General - Switches K42 Configuration OK 1 0 1
Quality index Analog input 13: General - Switches K42 Quality index 1 0 100

SHA4XP90L
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K43 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K43 Pir movement 1 0 1
Luxmeter Analog input 4: General - Motion detectors K43 Pir Luxmeter 1 0 65535 Lux
Alarm Binary Input 3: General - Motion detectors K43 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K43 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K43 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K43 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K43 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K43 Quality index 1 0 100
SHA4XTEMDIS
Name BACnet object BACnet name Min Value Max Value Measure unit
TRoom Analog Input 1: General - Temdis display k44 TRoom 1 -40 250 °C
TAuxiliary Analog Input 2: General - Temdis display k44 TAuxiliary 1 -40 250 °C
Presence Binary Input 5: General - Temdis display k44 Presence 1 0 1
Configuration OK Binary Input 6: General - Temdis display k44 Configuration OK 1 0 1
Quality index Analog Input 7: General - Temdis display k44 Quality index 1 0 100

SHDRODC230
Name BACnet object BACnet name Min Value Max Value Measure unit
Presence Binary Input 8: General - Rollerblinds module k45 Presence 1 0 1
Configuration OK Binary Input 9: General - Rollerblinds module k45 Configuration OK 1 0 1
Quality index Analog Input 10: General - Rollerblinds module k45 Quality index 1 0 100

SHE5XLS4TH
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K46 Push 1 0 1
Push Binary Input 2: General - Switches K46 Push 2 0 1
Push Binary Input 3: General - Switches K46 Push 3 0 1
Push Binary Input 4: General - Switches K46 Push 4 0 1
Humidity Analog input 5: General - Switches K46 Humidity 1 0 100 %
Temperature Analog input 6: General - Switches K46 Temperature 1 -40 250 °C
Led Binary Output 7: General - Switches K46 Led 1 0 1
Led Binary Output 8: General - Switches K46 Led 2 0 1
Led Binary Output 9: General - Switches K46 Led 3 0 1
Led Binary Output 10: General - Switches K46 Led 4 0 1
Presence Binary Input 11: General - Switches K46 Presence 1 0 1
Configuration ok Binary Input 12: General - Switches K46 Configuration OK 1 0 1
Quality index Analog input 13: General - Switches K46 Quality index 1 0 100
SHE5XP90L
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K43 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K43 Pir movement 1 0 1
Luxmeter Analog input 4: General - Motion detectors K43 Pir Luxmeter 1 0 65535 Lux
Alarm Binary Input 3: General - Motion detectors K43 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K43 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K43 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K43 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K43 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K43 Quality index 1 0 100

SHE5XTEMDIS
Name BACnet object BACnet name Min Value Max Value Measure unit
TRoom Analog Input 1: General - Temdis display k48 TRoom 1 -40 250 °C
TAuxiliary Analog Input 2: General - Temdis display k48 TAuxiliary 1 -40 250 °C
Presence Binary Input 3: General - Temdis display k48 Presence 1 0 1
Configuration OK Binary Input 4: General - Temdis display k48 Configuration OK 1 0 1
Quality index Analog Input 5: General - Temdis display k48 Quality index 1 0 100

SHEKxTEMDIS
Name BACnet object BACnet name Min Value Max Value Measure unit
TRoom Analog Input 1: General - Temdis display k49 TRoom 1 -40 250 °C
TAuxiliary Analog Input 2: General - Temdis display k49 TAuxiliary 1 -40 250 °C
Presence Binary Input 3: General - Temdis display k49 Presence 1 0 1
Configuration OK Binary Input 4: General - Temdis display k49 Configuration OK 1 0 1
Quality index Analog Input 5: General - Temdis display k49 Quality index 1 0 100

SHPOUTV224
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue 0-10 Analog Output 1: General - Analog output k50 Analogue 0-10 1 0 400 V
Analogue 0-10 Analog Output 2: General - Analog output k50 Analogue 0-10 2 0 400 V
Presence Binary Input 3: General - Analog output k50 Presence 1 0 1
Configuration OK Binary Input 4: General - Analog output k50 Configuration OK 1 0 1
Quality index Analog Input 5: General - Analog output k50 Quality index 1 0 100
SHPINT1P1
Name BACnet object BACnet name Min Value Max Value Measure unit
Thermistor Analog Input 1: General - Analog output k51 Thermistor 1 -40 250 °C
Analogue Analog Input 2: General - Analog output k51 Analogue 1 0 100 %
Presence Binary Input 3: General - Analog output k51 Presence 1 0 1
Configuration OK Binary Input 4: General - Analog output k51 Configuration OK 1 0 1
Quality index Analog Input 5: General - Analog output k51 Quality index 1 0 100

SHPINV2T1P124
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue Analog Input 1: General - Analog output k52 Analogue 1 0 400 V
Analogue Analog Input 2: General - Analog output k52 Analogue 2 0 400 V
Thermistor Analog Input 3: General - Analog output k52 Thermistor 1 -40 250 °C
Analogue Analog Input 4: General - Analog output k52 Analogue 1 0 100 %
Presence Binary Input 5: General - Analog output k52 Presence 1 0 1
Configuration OK Binary Input 6: General - Analog output k52 Configuration OK 1 0 1
Quality index Analog Input 7: General - Analog output k52 Quality index 1 0 100

SHPINA224
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue Analog Input 1: General - Analog output k53 Analogue 1 0 1000 A
Analogue Analog Input 2: General - Analog output k53 Analogue 2 0 1000 A
Presence Binary Input 3: General - Analog output k53 Presence 1 0 1
Configuration OK Binary Input 4: General - Analog output k53 Configuration OK 1 0 1
Quality index Analog Input 5: General - Analog output k53 Quality index 1 0 100

SHPINV324
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue Analog Input 1: General - Analog output k54 Analogue 1 0 400 V
Analogue Analog Input 2: General - Analog output k54 Analogue 2 0 400 V
Analogue Analog Input 3: General - Analog output k54 Analogue 3 0 400 V
Presence Binary Input 4: General - Analog output k54 Presence 1 0 1
Configuration OK Binary Input 5: General - Analog output k54 Configuration OK 1 0 1
Quality index Analog Input 6: General - Analog output k54 Quality index 1 0 100
SHSBP90L
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K55 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K55 Pir movement 1 0 1
Luxmeter Analog input 4: General - Motion detectors K55 Luxmeter 1 0 65535 Lux
Alarm Binary Input 3: General - Motion detectors K55 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K55 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K55 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K55 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K55 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K55 Quality index 1 0 100

SHSDP90L
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K56 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K56 Pir movement 1 0 1
Luxmeter Analog input 4: General - Motion detectors K56 Luxmeter 1 0 65535 Lux
Alarm Binary Input 3: General - Motion detectors K56 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K56 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K56 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K56 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K56 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K56 Quality index 1 0 100

SHSPP90Lx
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K57 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K57 Pir movement 1 0 1
Luxmeter Analog input 4: General - Motion detectors K57 Luxmeter 1 0 65535 Lux
Alarm Binary Input 3: General - Motion detectors K57 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K57 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K57 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K57 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K57 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K57 Quality index 1 0 100
SHSQP360L
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K58 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K58 Pir movement 1 0 1
Luxmeter Analog input 4: General - Motion detectors K58 Luxmeter 1 0 65535 Lux
Alarm Binary Input 3: General - Motion detectors K58 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K58 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K58 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K58 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K58 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K58 Quality index 1 0 100

SBQP360L24M
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K59 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K59 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors K59 Alarm 1 0 1
Luxmeter Analog input 4: General - Motion detectors K59 Luxmeter 1 0 65535 Lux
Bus voltage Analog Input 5: General - Motion detectors K59 Bus voltage 1 0 400 V
Presence Binary Input 8: General - Motion detectors K59 Presence 1 0 1
Configuration OK Binary Input 9: General - Motion detectors K59 Configuration OK 1 0 1
Quality index Analog Input 10: General - Motion detectors K59 Quality index 1 0 100
White led Binary Output 6 General - Motion detectors K59 Led 1 0 1
Blue led Binary Output 7: General - Motion detectors K59 Led 2 0 1
SBQP360L24MF
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors k60 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors k60 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors k60 Alarm 1 0 1
Luxmeter Analog input 4: General - Motion detectors K60 Luxmeter 1 0 65535 Lux
Bus voltage Analog Input 5: General - Motion detectors K60 Bus voltage 1 0 400 V
Presence Binary Input 8: General - Motion detectors K60 Presence 1 0 1
Configuration OK Binary Input 9: General - Motion detectors k60 Configuration OK 1 0 1
Quality index Analog Input 10: General - Motion detectors K60 Quality index 1 0 100
White led Binary Output 6: General - Motion detectors k60 Led 1 0 1
Blue led Binary Output 7: General - Motion detectors k60 Led 2 0 1

SBQP360L24MFO
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors k61 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors k61 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors k61 Alarm 1 0 1
Luxmeter Analog input 4: General - Motion detectors K61 Luxmeter 1 0 65535 Lux
Bus voltage Analog Input 5: General - Motion detectors K61 Bus voltage 1 0 400 V
Presence Binary Input 8: General - Motion detectors K61 Presence 1 0 1
Configuration OK Binary Input 9: General - Motion detectors k61 Configuration OK 1 0 1
Quality index Analog Input 10: General - Motion detectors K61 Quality index 1 0 100
White led Binary Output 6: General - Motion detectors k61 Led 1 0 1
Blue led Binary Output 7: General - Motion detectors k61 Led 2 0 1
SHQP360L7M
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors k62 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors k62 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors k62 Alarm 1 0 1
Luxmeter Analog input 4: General - Motion detectors K62 Luxmeter 1 0 65535 Lux
Bus voltage Analog Input 5: General - Motion detectors K62 Bus voltage 1 0 400 V
Presence Binary Input 8: General - Motion detectors K62 Presence 1 0 1
Configuration OK Binary Input 9: General - Motion detectors k62 Configuration OK 1 0 1
Quality index Analog Input 10: General - Motion detectors K62 Quality index 1 0 100
White led Binary Output 6: General - Motion detectors k62 Led 1 0 1
Blue led Binary Output 7: General - Motion detectors k62 Led 2 0 1

SHQP360L7MF
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors k63 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors k63 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors k63 Alarm 1 0 1
Luxmeter Analog input 4: General - Motion detectors K63 Luxmeter 1 0 65535 Lux
Bus voltage Analog Input 5: General - Motion detectors K63 Bus voltage 1 0 400 V
Presence Binary Input 8: General - Motion detectors K63 Presence 1 0 1
Configuration OK Binary Input 9: General - Motion detectors k63 Configuration OK 1 0 1
Quality index Analog Input 10: General - Motion detectors K63 Quality index 1 0 100
White led Binary Output 6: General - Motion detectors k63 Led 1 0 1
Blue led Binary Output 7: General - Motion detectors k63 Led 2 0 1
SHQP360L7MFO
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors k64 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors k64 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detectors k64 Alarm 1 0 1
Luxmeter Analog input 4: General - Motion detectors K64 Luxmeter 1 0 65535 Lux
Bus voltage Analog Input 5: General - Motion detectors K64 Bus voltage 1 0 400 V
Presence Binary Input 8: General - Motion detectors K64 Presence 1 0 1
Configuration OK Binary Input 9: General - Motion detectors k64 Configuration OK 1 0 1
Quality index Analog Input 10: General - Motion detectors K64 Quality index 1 0 100
White led Binary Output 6: General - Motion detectors k64 Led 1 0 1
Blue led Binary Output 7: General - Motion detectors k64 Led 2 0 1

SHDWRE16AE230
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General - Relay module K65 KWh 1 0 1000000000 kWh
Re Binary output 1: General - Relay module K65 Re 1 0 1
kWdmd Analog Input 2: General - Relay module K65 kWdmd 1 0 1000000000 kW
kW Analog Input 3: General - Relay module K65 kW 1 0 1000000000 kW
kVA Analog Input 4: General - Relay module K65 kVA 1 0 1000000000 kVA
kVAr Analog Input 5: General - Relay module K65 kVAr 1 0 1000000000 kVAR
Ampere Analog Input 6: General - Relay module K65 Ampere 1 0 1000 A
Volt Analog Input 7: General - Relay module K65 Volt 1 0 400 V
PF Analog Input 8: General - Relay module K65 PF 1 -0.99 0.99

SHDWEM16A230
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General - Relay module K66 KWh 1 0 1000000000 kWh
kWdmd Analog Input 2: General - Relay module K66 kWdmd 1 0 1000000000 kW
kW Analog Input 3: General - Relay module K66 kW 1 0 1000000000 kW
kVA Analog Input 4: General - Relay module K66 kVA 1 0 1000000000 kVA
Kvar Analog Input 5: General - Relay module K66 kVAr 1 0 1000000000 kVAR
Ampere Analog Input 6: General - Relay module K66 Ampere 1 0 1000 A
Volt Analog Input 7: General - Relay module K66 Volt 1 0 400 V
PF Analog Input 8: General - Relay module K66 PF 1 -0.99 0.99
SHE5XWLS4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Wireless K46 Push 1 0 1
Push Binary Input 2: General - Wireless K46 Push 2 0 1
Push Binary Input 3: General - Wireless K46 Push 3 0 1
Push Binary Input 4: General - Wireless K46 Push 4 0 1
Presence Binary Input 5: General - Wireless K46 Presence 1 0 1
Configuration ok Binary Input 6: General - Wireless K46 Configuration OK 1 0 1
Quality index Analog input 7: General - Wireless K46 Quality index 1 0 100
Quality index master generator Analog input 8: General - Wireless K46 Quality index master generator 1 0 100
Battery low Binary Input 9: General - Wireless K46 Battery low 1 0 1
Battery level Analog input 10: General - Wireless K46 Battery level 1 0 400 V

SHA4XWLS4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Wireless K69 Push 1 0 1
Push Binary Input 2: General - Wireless K69 Push 2 0 1
Push Binary Input 3: General - Wireless K69 Push 3 0 1
Push Binary Input 4: General - Wireless K69 Push 4 0 1
Presence Binary Input 5: General - Wireless K69 Presence 1 0 1
Configuration ok Binary Input 6: General - Wireless K69 Configuration OK 1 0 1
Quality index Analog input 7: General - Wireless K69 Quality index 1 0 100
Quality index master generator Analog input 8: General - Wireless K69 Quality index master generator 1 0 100
Battery low Binary Input 9: General - Wireless K69 Battery low 1 0 1
Battery level Analog input 10: General - Wireless K69 Battery level 1 0 400 V

BDA-INVOL-U
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General – I/O Modules K70 Switch 1 0 1
Presence Binary Input 2: General - I/O Modules K70 Presence 1 0 1
Configuration ok Binary Input 3: General - I/O Modules K70 Configuration OK 1 0 1
Quality index Analog input 4: General - I/O Modules K70 Quality index 1 0 100
SHA4XLS4P90L
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Motion detector K71 Push 1 0 1
Push Binary Input 2: General - Motion detector K71 Push 2 0 1
Push Binary Input 3: General - Motion detector K71 Push 3 0 1
Push Binary Input 4: General - Motion detector K71 Push 4 0 1
Luxmeter Analog input 5: General - Motion detector K71 Luxmeter 1 0 65535 Lux
Pir presence Binary input 6: General - Motion detector K71 Pir presence 1 0 1
Pir movement Binary input 7: General - Motion detector K71 Pir movement 1 0 1
Alarm Binary input 8: General - Motion detector K71 Alarm 1 0 1
Bus voltage Analog input 14: General - Motion detector K71 Bus voltage 1 0 400 V
Led Binary Output 10: General - Motion detector K71 Led 1 0 1
Presence Binary Input 11: General - Motion detector K71 Presence 1 0 1
Configuration OK Binary Input 12: General - Motion detector K71 Configuration OK 1 0 1
Quality index Analog input 13: General - Motion detector K71 Quality index 1 0 100

SHE5XLS4P90L
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Motion detector K72 Push 1 0 1
Push Binary Input 2: General - Motion detector K72 Push 2 0 1
Push Binary Input 3: General - Motion detector K72 Push 3 0 1
Push Binary Input 4: General - Motion detector K72 Push 4 0 1
Luxmeter Analog input 5: General - Motion detector K72 Luxmeter 1 0 65535 Lux
Pir presence Binary input 6: General - Motion detector K72 Pir presence 1 0 1
Pir movement Binary input 7: General - Motion detector K72 Pir movement 1 0 1
Alarm Binary input 8: General - Motion detector K72 Alarm 1 0 1
Bus voltage Analog input 14: General - Motion detector K72 Bus voltage 1 0 400 V
Led Binary Output 9: General - Motion detector K72 Led 1 0 1
Presence Binary Input 10: General - Motion detector K72 Presence 1 0 1
Configuration OK Binary Input 11: General - Motion detector K72 Configuration OK 1 0 1
Quality index Analog input 12: General - Motion detector K72 Quality index 1 0 100
SH2RE1A424
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary output 1: General - Relay module k73 Re 1 0 1
Re Binary output 2: General - Relay module k73 Re 2 0 1
Re Binary output 3: General - Relay module k73 Re 3 0 1
Re Binary output 4: General - Relay module k73 Re 4 0 1
Presence Binary Input 5: General - Relay module k73 Presence 1 0 1
Configuration OK Binary Input 6: General – Relay module k73 Configuration OK 1 0 1
Quality index Analog Input 7: General – Relay module k73 Quality index 1 0 100

SHPINNI2
Name BACnet object BACnet name Min Value Max Value Measure unit
Thermistor Analog Input 1: General - Analog input k74 Thermistor 1 -40 250 °C
Thermistor Analog Input 2: General - Analog input k74 Thermistor 2 -40 250 °C
Presence Binary Input 3: General - Analog input k74 Presence 1 0 1
Configuration OK Binary Input 4: General - Analog input k74 Configuration OK 1 0 1
Quality index Analog Input 5: General - Analog input k74 Quality index 1 0 100

SHA4XP150
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K75 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K75 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detector K75 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K75 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K75 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K75 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K75 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K75 Quality index 1 0 100
SHA4XP150L
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K76 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K76 Pir movement 1 0 1
Luxmeter Analog input 4: General - Motion detectors K76 Luxmeter 1 0 65535 Lux
Alarm Binary Input 3: General - Motion detectors K76 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K76 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K76 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K76 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K76 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K76 Quality index 1 0 100

SHE5XP150
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K77 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K77 Pir movement 1 0 1
Alarm Binary Input 3: General - Motion detector K77 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K77 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K77 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K77 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K77 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K77 Quality index 1 0 100
SHE5XP150L
Name BACnet object BACnet name Min Value Max Value Measure unit
Pir presence Binary Input 1: General - Motion detectors K76 Pir presence 1 0 1
Pir movement Binary Input 2: General - Motion detectors K76 Pir movement 1 0 1
Luxmeter Analog input 4: General - Motion detectors K76 Luxmeter 1 0 65535 Lux
Alarm Binary Input 3: General - Motion detectors K76 Alarm 1 0 1
Bus voltage Analog Input 9: General - Motion detectors K76 Bus voltage 1 0 400 V
Led Binary Output 5: General - Motion detectors K76 Led 1 0 1
Presence Binary Input 6: General - Motion detectors K76 Presence 1 0 1
Configuration OK Binary Input 7: General - Motion detectors K76 Configuration OK 1 0 1
Quality index Analog Input 8: General - Motion detectors K76 Quality index 1 0 100

SHSUCOTL
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue CO2 Analog Input 1: General – Environmental sensor K79 Analogue CO2 1 0 1000000 ppm
Temperature Analog Input 2: General – Environmental sensor K79 Temperature 2 -40 250 °C
Bus voltage Analog Input 6: General – Environmental sensor K79 Bus voltage 1 0 400 V
Presence Binary Input 3: General – Environmental sensor K79 Presence 1 0 1
Configuration OK Binary Input 4: General – Environmental sensor K79 Configuration OK 1 0 1
Quality index Analog Input 5: General – Environmental sensor K79 Quality index 1 0 100

SHSUCOTHL
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue CO2 Analog Input 1: General – Environmental sensor K80 Analogue CO2 1 0 1000000 ppm
Temperature Analog Input 2: General – Environmental sensor K80 Temperature 2 -40 250 °C
Humidity Analog Input 3: General – Environmental sensor K80 Humidity 3 0 100 %
Bus voltage Analog Input 6: General – Environmental sensor K80 Bus voltage 1 0 400 V
Presence Binary Input 3: General – Environmental sensor K80 Presence 1 0 1
Configuration OK Binary Input 4: General – Environmental sensor K80 Configuration OK 1 0 1
Quality index Analog Input 5: General – Environmental sensor K80 Quality index 1 0 100
SHSUT
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Environmental sensor K81 Temperature 1 -40 250 °C
Bus voltage Analog Input 5: General – Environmental sensor K81 Bus voltage 1 0 400 V
Presence Binary Input 2: General – Environmental sensor K81 Presence 1 0 1
Configuration OK Binary Input 3: General – Environmental sensor K81 Configuration OK 1 0 1
Quality index Analog Input 4: General – Environmental sensor K81 Quality index 1 0 100

SHSUCOT
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue CO2 Analog Input 1: General – Environmental sensor K82 Analogue CO2 1 0 1000000 ppm
Temperature Analog Input 2: General – Environmental sensor K82 Temperature 2 -40 250 °C
Bus voltage Analog Input 6: General – Environmental sensor K82 Bus voltage 1 0 400 V
Presence Binary Input 3: General – Environmental sensor K82 Presence 1 0 1
Configuration OK Binary Input 4: General – Environmental sensor K82 Configuration OK 1 0 1
Quality index Analog Input 5: General – Environmental sensor K82 Quality index 1 0 100

SHSUCOTH
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue CO2 Analog Input 1: General – Environmental sensor K83 Analogue CO2 1 0 1000000 ppm
Temperature Analog Input 2: General – Environmental sensor K83 Temperature 2 -40 250 °C
Humidity Analog Input 3: General – Environmental sensor K83 Humidity 3 0 100 %
Bus voltage Analog Input 6: General – Environmental sensor K83 Bus voltage 1 0 400 V
Presence Binary Input 3: General – Environmental sensor K83 Presence 1 0 1
Configuration OK Binary Input 4: General – Environmental sensor K83 Configuration OK 1 0 1
Quality index Analog Input 5: General – Environmental sensor K83 Quality index 1 0 100
SHSUTH
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Environmental sensor K84 Temperature 1 -40 250 °C
Humidity Analog Input 2: General – Environmental sensor K84 Humidity 2 0 100 %
Bus voltage Analog Input 6: General – Environmental sensor K84 Bus voltage 1 0 400 V
Presence Binary Input 3: General – Environmental sensor K84 Presence 1 0 1
Configuration OK Binary Input 4: General – Environmental sensor K84 Configuration OK 1 0 1
Quality index Analog Input 5: General – Environmental sensor K84 Quality index 1 0 100

SHSUCOTD
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue CO2 Analog Input 1: General – Environmental sensor K85 Analogue CO2 1 0 1000000 ppm
Temperature Analog Input 2: General – Environmental sensor K85 Temperature 2 -40 250 °C
Bus voltage Analog Input 6: General – Environmental sensor K85 Bus voltage 1 0 400 V
Presence Binary Input 3: General – Environmental sensor K85 Presence 1 0 1
Configuration OK Binary Input 4: General – Environmental sensor K85 Configuration OK 1 0 1
Quality index Analog Input 5: General – Environmental sensor K85 Quality index 1 0 100

SHSUCOTHD
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue CO2 Analog Input 1: General – Environmental sensor K86 Analogue CO2 1 0 1000000 ppm
Temperature Analog Input 2: General – Environmental sensor K86 Temperature 2 -40 250 °C
Humidity Analog Input 3: General – Environmental sensor K86 Humidity 3 0 100 %
Bus voltage Analog Input 6: General – Environmental sensor K86 Bus voltage 1 0 400 V
Presence Binary Input 3: General – Environmental sensor K86 Presence 1 0 1
Configuration OK Binary Input 4: General – Environmental sensor K86 Configuration OK 1 0 1
Quality index Analog Input 5: General – Environmental sensor K86 Quality index 1 0 100
SHSUTD
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Environmental sensor K87 Temperature 1 -40 250 °C
Bus voltage Analog Input 5: General – Environmental sensor K87 Bus voltage 1 0 400 V
Presence Binary Input 3: General – Environmental sensor K87 Presence 1 0 1
Configuration OK Binary Input 4: General – Environmental sensor K87 Configuration OK 1 0 1
Quality index Analog Input 6: General – Environmental sensor K87 Quality index 1 0 100

SHSUTHD
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Environmental sensor K88 Temperature 1 -40 250 °C
Humidity Analog Input 2: General – Environmental sensor K88 Humidity 2 0 100 %
Bus voltage Analog Input 6: General – Environmental sensor K88 Bus voltage 1 0 400 V
Presence Binary Input 3: General – Environmental sensor K88 Presence 1 0 1
Configuration OK Binary Input 4: General – Environmental sensor K88 Configuration OK 1 0 1
Quality index Analog Input 5: General – Environmental sensor K88 Quality index 1 0 100

SHG503WLS6
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K89 Push 1 0 1
Push Binary Input 2: General - Glass switches K89 Push 2 0 1
Push Binary Input 3: General - Glass switches K89 Push 3 0 1
Push Binary Input 4: General - Glass switches K89 Push 4 0 1
Push Binary Input 5: General - Glass switches K89 Push 4 0 1
Push Binary Input 6: General - Glass switches K89 Push 4 0 1
Temperature Analog input 13: General - Glass switches K89 Temperature 1 -40 250 °C
Led Binary Output 7: General - Glass switches K89 Led 1 0 1
Led Binary Output 8: General - Glass switches K89 Led 2 0 1
Led Binary Output 9: General - Glass switches K89 Led 3 0 1
Led Binary Output 10: General - Glass switches K89 Led 4 0 1
Led Binary Output 11: General - Glass switches K89 Led 5 0 1
Led Binary Output 12: General - Glass switches K89 Led 6 0 1
Presence Binary Input 14: General - Glass switches K89 Presence 1 0 1
Configuration ok Binary Input 15: General - Glass switches K89 Configuration OK 1 0 1
Quality index Analog input 16: General - Glass switches K89 Quality index 1 0 100
SHG503BLS6
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K90 Push 1 0 1
Push Binary Input 2: General - Glass switches K90 Push 2 0 1
Push Binary Input 3: General - Glass switches K90 Push 3 0 1
Push Binary Input 4: General - Glass switches K90 Push 4 0 1
Push Binary Input 5: General - Glass switches K90 Push 4 0 1
Push Binary Input 6: General - Glass switches K90 Push 4 0 1
Temperature Analog input 13: General - Glass switches K90 Temperature 1 -40 250 °C
Led Binary Output 7: General - Glass switches K90 Led 1 0 1
Led Binary Output 8: General - Glass switches K90 Led 2 0 1
Led Binary Output 9: General - Glass switches K90 Led 3 0 1
Led Binary Output 10: General - Glass switches K90 Led 4 0 1
Led Binary Output 11: General - Glass switches K90 Led 5 0 1
Led Binary Output 12: General - Glass switches K90 Led 6 0 1
Presence Binary Input 14: General - Glass switches K90 Presence 1 0 1
Configuration ok Binary Input 15: General - Glass switches K90 Configuration OK 1 0 1
Quality index Analog input 16: General - Glass switches K90 Quality index 1 0 100

SHG060WLS4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K91 Push 1 0 1
Push Binary Input 2: General - Glass switches K91 Push 2 0 1
Push Binary Input 3: General - Glass switches K91 Push 3 0 1
Push Binary Input 4: General - Glass switches K91 Push 4 0 1
Temperature Analog input 9: General - Glass switches K91 Temperature 1 -40 250 °C
Led Binary Output 5: General - Glass switches K91 Led 1 0 1
Led Binary Output 6: General - Glass switches K91 Led 2 0 1
Led Binary Output 7: General - Glass switches K91 Led 3 0 1
Led Binary Output 8: General - Glass switches K91 Led 4 0 1
Presence Binary Input 10: General - Glass switches K91 Presence 1 0 1
Configuration ok Binary Input 11: General - Glass switches K91 Configuration OK 1 0 1
Quality index Analog input 11: General - Glass switches K91 Quality index 1 0 100
SHG060BLS4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K92 Push 1 0 1
Push Binary Input 2: General - Glass switches K92 Push 2 0 1
Push Binary Input 3: General - Glass switches K92 Push 3 0 1
Push Binary Input 4: General - Glass switches K92 Push 4 0 1
Temperature Analog input 9: General - Glass switches K92 Temperature 1 -40 250 °C
Led Binary Output 5: General - Glass switches K92 Led 1 0 1
Led Binary Output 6: General - Glass switches K92 Led 2 0 1
Led Binary Output 7: General - Glass switches K92 Led 3 0 1
Led Binary Output 8: General - Glass switches K92 Led 4 0 1
Presence Binary Input 10: General - Glass switches K92 Presence 1 0 1
Configuration ok Binary Input 11: General - Glass switches K92 Configuration OK 1 0 1
Quality index Analog input 11: General - Glass switches K92 Quality index 1 0 100

SHG503WSLD
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K93 Button 1 0 1
Push Binary Input 2: General - Glass switches K93 Button 2 0 1
Push Binary Input 3: General - Glass switches K93 Button 3 0 1
Push Binary Input 4: General - Glass switches K93 Button 4 0 1
Led Binary Output 5: General - Glass switches K93 Led 1 0 1
Led Binary Output 6: General - Glass switches K93 Led 2 0 1
Led Binary Output 7: General - Glass switches K93 Led 3 0 1
Led Binary Output 8: General - Glass switches K93 Led 4 0 1
Presence Binary Input 9: General - Glass switches K93 Presence 1 0 1
Configuration ok Binary Input 10: General - Glass switches K93 Configuration OK 1 0 1
Quality index Analog input 11: General - Glass switches K93 Quality index 1 0 100
SHG503BSLD
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K94 Button 1 0 1
Push Binary Input 2: General - Glass switches K94 Button 2 0 1
Push Binary Input 3: General - Glass switches K94 Button 3 0 1
Push Binary Input 4: General - Glass switches K94 Button 4 0 1
Led Binary Output 5: General - Glass switches K94 Led 1 0 1
Led Binary Output 6: General - Glass switches K94 Led 2 0 1
Led Binary Output 7: General - Glass switches K94 Led 3 0 1
Led Binary Output 8: General - Glass switches K94 Led 4 0 1
Presence Binary Input 9: General - Glass switches K94 Presence 1 0 1
Configuration ok Binary Input 10: General - Glass switches K94 Configuration OK 1 0 1
Quality index Analog input 11: General - Glass switches K94 Quality index 1 0 100

SHG060WSLD
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K95 Button 1 0 1
Push Binary Input 2: General - Glass switches K95 Button 2 0 1
Push Binary Input 3: General - Glass switches K95 Button 3 0 1
Push Binary Input 4: General - Glass switches K95 Button 4 0 1
Led Binary Output 5: General - Glass switches K95 Led 1 0 1
Led Binary Output 6: General - Glass switches K95 Led 2 0 1
Led Binary Output 7: General - Glass switches K95 Led 3 0 1
Led Binary Output 8: General - Glass switches K95 Led 4 0 1
Presence Binary Input 9: General - Glass switches K95 Presence 1 0 1
Configuration ok Binary Input 10: General - Glass switches K95 Configuration OK 1 0 1
Quality index Analog input 11: General - Glass switches K95 Quality index 1 0 100
SHG060BSLD
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K96 button 1 0 1
Push Binary Input 2: General - Glass switches K96 Button 2 0 1
Push Binary Input 3: General - Glass switches K96 Button 3 0 1
Push Binary Input 4: General - Glass switches K96 Button 4 0 1
Led Binary Output 5: General - Glass switches K96 Led 1 0 1
Led Binary Output 6: General - Glass switches K96 Led 2 0 1
Led Binary Output 7: General - Glass switches K96 Led 3 0 1
Led Binary Output 8: General - Glass switches K96 Led 4 0 1
Presence Binary Input 9: General - Glass switches K96 Presence 1 0 1
Configuration ok Binary Input 10: General - Glass switches K96 Configuration OK 1 0 1
Quality index Analog input 11: General - Glass switches K96 Quality index 1 0 100

SHG060BSLT
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K97 button 1 0 1
Push Binary Input 2: General - Glass switches K97 Button 2 0 1
Push Binary Input 3: General - Glass switches K97 Button 3 0 1
Push Binary Input 4: General - Glass switches K97 Button 4 0 1
TRoom Analog Input 9: General - Glass switches K97 TRoom 1 -40 250 °C
Led Binary Output 5: General - Glass switches K97 Led 1 0 1
Led Binary Output 6: General - Glass switches K97 Led 2 0 1
Led Binary Output 7: General - Glass switches K97 Led 3 0 1
Led Binary Output 8: General - Glass switches K97 Led 4 0 1
Presence Binary Input 10: General - Glass switches K97 Presence 1 0 1
Configuration ok Binary Input 11: General - Glass switches K97 Configuration OK 1 0 1
Quality index Analog input 12: General - Glass switches K97 Quality index 1 0 100
SHG060WSLT
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K98 button 1 0 1
Push Binary Input 2: General - Glass switches K98 Button 2 0 1
Push Binary Input 3: General - Glass switches K98 Button 3 0 1
Push Binary Input 4: General - Glass switches K98 Button 4 0 1
TRoom Analog Input 9: General - Glass switches K98 TRoom 1 -40 250 °C
Led Binary Output 5: General - Glass switches K98 Led 1 0 1
Led Binary Output 6: General - Glass switches K98 Led 2 0 1
Led Binary Output 7: General - Glass switches K98 Led 3 0 1
Led Binary Output 8: General - Glass switches K98 Led 4 0 1
Presence Binary Input 10: General - Glass switches K98 Presence 1 0 1
Configuration ok Binary Input 11: General - Glass switches K98 Configuration OK 1 0 1
Quality index Analog input 12: General - Glass switches K98 Quality index 1 0 100

SHG503BSLT
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K99 button 1 0 1
Push Binary Input 2: General - Glass switches K99 Button 2 0 1
Push Binary Input 3: General - Glass switches K99 Button 3 0 1
Push Binary Input 4: General - Glass switches K99 Button 4 0 1
TRoom Analog Input 9: General - Glass switches K99 TRoom 1 -40 250 °C
Led Binary Output 5: General - Glass switches K99 Led 1 0 1
Led Binary Output 6: General - Glass switches K99 Led 2 0 1
Led Binary Output 7: General - Glass switches K99 Led 3 0 1
Led Binary Output 8: General - Glass switches K99 Led 4 0 1
Presence Binary Input 10: General - Glass switches K99 Presence 1 0 1
Configuration ok Binary Input 11: General - Glass switches K99 Configuration OK 1 0 1
Quality index Analog input 12: General - Glass switches K99 Quality index 1 0 100
SHG503WSLT
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Glass switches K100 button 1 0 1
Push Binary Input 2: General - Glass switches K100 Button 2 0 1
Push Binary Input 3: General - Glass switches K100 Button 3 0 1
Push Binary Input 4: General - Glass switches K100 Button 4 0 1
TRoom Analog Input 9: General - Glass switches K100 TRoom 1 -40 250 °C
Led Binary Output 5: General - Glass switches K100 Led 1 0 1
Led Binary Output 6: General - Glass switches K100 Led 2 0 1
Led Binary Output 7: General - Glass switches K100 Led 3 0 1
Led Binary Output 8: General - Glass switches K100 Led 4 0 1
Presence Binary Input 10: General - Glass switches K100 Presence 1 0 1
Configuration ok Binary Input 11: General - Glass switches K100 Configuration OK 1 0 1
Quality index Analog input 12: General - Glass switches K100 Quality index 1 0 100

SB2DALI230
Name BACnet object BACnet name Min Value Max Value Measure unit
Presence Binary Input 65: General – Dimmer module K101 Presence 1 0 1
Configuration ok Binary Input 66: General - Dimmer module K101 Configuration OK 1 0 1
Quality index Analog input 66: General - Dimmer module K101 Quality index 1 0 100
DALI lamp failure Binary Input 67: General - Dimmer module K101 DALI lamp failure 1 0 1
DALI bus short-circuit Binary Input 68: General - Dimmer module K101 DALI bus short-circuit 1 0 1
No answer from DALI ballast Binary Input 69: General - Dimmer module K101 No answer from DALI ballast 1 0 1

SHDWWISEN
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Wireless K102 Switch 1 0 1

SHDWWISENIN1
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Wireless K103 Switch 1 0 1
Switch Binary Input 2: General - Wireless K103 Switch 2 0 1
SHPINCNT4
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - I/O Modules K104 Switch 1 0 1
Switch Binary Input 2: General - I/O Modules K104 Switch 2 0 1
Switch Binary Input 3: General - I/O Modules K104 Switch 3 0 1
Switch Binary Input 4: General - I/O Modules K104 Switch 4 0 1
Bus voltage Analog Input 8: General - I/O Modules K104 Bus voltage 1 0 400 V
Presence Binary Input 5: General - I/O Modules K104 Presence 1 0 1
Configuration ok Binary Input 6: General - I/O Modules K104 Configuration OK 1 0 1
Quality index Analog input 7: General - I/O Modules K104 Quality index 1 0 100

SHPINCNTS04
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - I/O Modules K105 Switch 1 0 1
Switch Binary Input 2: General - I/O Modules K105 Switch 2 0 1
Switch Binary Input 3: General - I/O Modules K105 Switch 3 0 1
Switch Binary Input 4: General - I/O Modules K105 Switch 4 0 1
Bus voltage Analog Input 8: General - I/O Modules K105 Bus voltage 1 0 400 V
Presence Binary Input 5: General - I/O Modules K105 Presence 1 0 1
Configuration ok Binary Input 6: General - I/O Modules K105 Configuration OK 1 0 1
Quality index Analog input 7: General - I/O Modules K105 Quality index 1 0 100

SH2EM16A230
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General – Energy meter K106 KWh 1 0 1000000000 kWh
kWdmd Analog Input 2: General - Energy meter K106 kWdmd 1 0 1000000000 kW
kW Analog Input 3: General - Energy meter K106 kW 1 0 1000000000 kW
kVA Analog Input 4: General - Energy meter K106 kVA 1 0 1000000000 kVA
Kvar Analog Input 5: General - Energy meter K106 kVAr 1 0 1000000000 kVAR
Ampere Analog Input 6: General - Energy meter K106 Ampere 1 0 1000 A
Volt Analog Input 7: General - Energy meter K106 Volt 1 0 400 V
PF Analog Input 8: General - Energy meter K106 PF 1 -0.99 0.99
Presence Binary Input 9: General - Energy meter K106 Presence 1 0 1
Configuration OK Binary Input 10: General - Energy meter K106 Configuration OK 1 0 1
Quality index Analog Input 11: General - Energy meter K106 Quality index 1 0 100
Overload warning Binary Input 12: General - Energy meter K106 Overload warning 1 0 1
Hardware error Binary Input 13: General - Energy meter K106 Hardware error 1 0 1
SB2REP230
Name BACnet object BACnet name Min Value Max Value Measure unit
Secondary-bus current Analog Input 2: General – Cabinet module K107 KWh 1 0 1000 A
Secondary-bus voltage Analog Input 3: General - Cabinet module K107 kWdmd 1 0 400 V
Presence Binary Input 4: General - Cabinet module K107 Presence 1 0 1
Configuration OK Binary Input 5: General - Cabinet module K107 Configuration OK 1 0 1
Quality index Analog Input 6: General - Cabinet module K107 Quality index 1 0 100
Wrong connection Binary Input 7: General - Cabinet module K107 Wrong connection 1 0 1
Short circuit Binary Input 8: General - Cabinet module K107 Short circuit 1 0 1
Overload warning Binary Input 9: General - Cabinet module K107 Overload warning 1 0 1
Overload protection active Binary Input 10: General - Cabinet module K107 Overload protection active 1 0 1
Power supply spike Binary Input 11: General - Cabinet module K107 Power supply spike 1 0 1

B4X-LS4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K108 Push 1 0 1
Led Binary Output 5: General - Switches K108 Led 1 0 1
Push Binary Input 2: General - Switches K108 Push 2 0 1
Led Binary Output 6: General - Switches K108 Led 2 0 1
Push Binary Input 3: General - Switches K108 Push 3 0 1
Led Binary Output 7: General - Switches K108 Led 3 0 1
Push Binary Input 4: General - Switches K108 Push 4 0 1
Led Binary Output 8: General - Switches K108 Led 4 0 1

B5X-LS4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K109 Push 1 0 1
Led Binary Output 5: General - Switches K109 Led 1 0 1
Push Binary Input 2: General - Switches K109 Push 2 0 1
Led Binary Output 6: General - Switches K109 Led 2 0 1
Push Binary Input 3: General - Switches K109 Push 3 0 1
Led Binary Output 7: General - Switches K109 Led 3 0 1
Push Binary Input 4: General - Switches K109 Push 4 0 1
Led Binary Output 8: General - Switches K109 Led 4 0 1
BEW-LS1
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K110 Push 1 0 1
Led Binary Output 5: General - Switches K110 Led 1 0 1

BEW-LS2
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K111 Push 1 0 1
Push Binary Input 2: General - Switches K111 Push 2 0 1
Led Binary Output 5: General - Switches K111 Led 1 0 1
Led Binary Output 6: General - Switches K111 Led 2 0 1

BEW-LS3
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K112 Push 1 0 1
Push Binary Input 2: General - Switches K112 Push 2 0 1
Push Binary Input 3: General - Switches K112 Push 3 0 1
Led Binary Output 5: General - Switches K112 Led 1 0 1
Led Binary Output 6: General - Switches K112 Led 2 0 1
Led Binary Output 7: General - Switches K112 Led 3 0 1

B4X-PIR90
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K113 PIR 1 0 1
LED Binary Output 5: General - Motion detectors K113 LED 1 0 1
LED Binary Output 6: General - Motion detectors K113 LED 2 0 1

BSF-WAT
Name BACnet object BACnet name Min Value Max Value Measure unit
Water alarm Binary Input 1: General – Water detector K114 Water alarm 1 0 1
Alarm Binary Input 2: General - Water detector K114 Alarm 1 0 1
BDA-RE13A
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary Output 1: General - Relay module K115 Re 1 0 1

BDD-INCON4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K116 Push 1 0 1
Led Binary Output 5: General - I/O Modules K116 Led 1 0 1
Push Binary Input 2: General - I/O Modules K116 Push 2 0 1
Push Binary Input 3: General - I/O Modules K116 Push 3 0 1
Push Binary Input 4: General - I/O Modules K116 Push 4 0 1

BDB-INCON4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K117 Push 1 0 1
Push Binary Input 2: General - I/O Modules K117 Push 2 0 1
Push Binary Input 3: General - I/O Modules K117 Push 3 0 1
Push Binary Input 4: General - I/O Modules K117 Push 4 0 1

BDB-INCON8
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Output 1: General - I/O Modules K118 Push 1 0 1
Push Binary Output 2: General - I/O Modules K118 Push 2 0 1
Push Binary Output 3: General - I/O Modules K118 Push 3 0 1
Push Binary Output 4: General - I/O Modules K118 Push 4 0 1
Push Binary Output 5: General - I/O Modules K118 Push 5 0 1
Push Binary Output 6: General - I/O Modules K118 Push 6 0 1
Push Binary Output 7: General - I/O Modules K118 Push 7 0 1
Push Binary Output 8: General - I/O Modules K118 Push 8 0 1
BDB-IOCP8
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K119 Push 1 0 1
Led Binary Output 5: General - I/O Modules K119 Led 1 0 1
Push Binary Input 2: General - I/O Modules K119 Push 2 0 1
Led Binary Output 6: General - I/O Modules K119 Led 2 0 1
Push Binary Input 3: General - I/O Modules K119 Push 3 0 1
Led Binary Output 7: General - I/O Modules K119 Led 3 0 1
Push Binary Input 4: General - I/O Modules K119 Push 4 0 1
Led Binary Output 8: General - I/O Modules K119 Led 4 0 1

BDB-IOCP8A
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - I/O Modules K120 Push 1 0 1
Led Binary Output 5: General - I/O Modules K120 Led 1 0 1
Push Binary Input 2: General - I/O Modules K120 Push 2 0 1
Led Binary Output 6: General - I/O Modules K120 Led 2 0 1
Push Binary Input 3: General - I/O Modules K120 Push 3 0 1
Led Binary Output 7: General - I/O Modules K120 Led 3 0 1
Push Binary Input 4: General - I/O Modules K120 Push 4 0 1
Led Binary Output 8: General - I/O Modules K120 Led 4 0 1

BDA-INVOL
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - I/O Modules K121 Switch 1 0 1
BEW-LS4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K122 Push 1 0 1
Push Binary Input 2: General - Switches K122 Push 2 0 1
Push Binary Input 3: General - Switches K122 Push 3 0 1
Push Binary Input 4: General - Switches K122 Push 4 0 1
Led Binary Output 5: General - Switches K122 Led 1 0 1
Led Binary Output 6: General - Switches K122 Led 2 0 1
Led Binary Output 7: General - Switches K122 Led 3 0 1
Led Binary Output 8: General - Switches K122 Led 4 0 1

BFW-LS4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K123 Push 1 0 1
Push Binary Input 2: General - Switches K123 Push 2 0 1
Push Binary Input 3: General - Switches K123 Push 3 0 1
Push Binary Input 4: General - Switches K123 Push 4 0 1
Led Binary Output 5: General - Switches K123 Led 1 0 1
Led Binary Output 6: General - Switches K123 Led 2 0 1
Led Binary Output 7: General - Switches K123 Led 3 0 1
Led Binary Output 8: General - Switches K123 Led 4 0 1

BOW-LS4
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches K124 Push 1 0 1
Led Binary Output 5: General - Switches K124 Led 1 0 1
Push Binary Input 2: General - Switches K124 Push 2 0 1
Led Binary Output 6: General - Switches K124 Led 2 0 1
Push Binary Input 3: General - Switches K124 Push 3 0 1
Led Binary Output 7: General - Switches K124 Led 3 0 1
Push Binary Input 4: General - Switches K124 Push 4 0 1
Led Binary Output 8: General - Switches K124 Led 4 0 1
B5X-PIR90
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K125 PIR 1 0 1
LED Binary Output 5: General - Motion detectors K125 LED 1 0 1
LED Binary Output 6: General - Motion detectors K125 LED 2 0 1

BSB-PIR90
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K126 PIR 1 0 1
LED Binary Output 2: General - Motion detectors K126 LED 1 0 1

BSD-PIR90
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K127 PIR 1 0 1
Led Binary Output 2: General - Motion detectors K127 Led 1 0 1
Alarm Binary Input 3: General - Motion detectors K127 Alarm 1 0 1

BSD-PIR90A
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K128 PIR 1 0 1
Led Binary Output 5: General - Motion detectors K128 Led 1 0 1
Alarm Binary Input 2: General - Motion detectors K128 Alarm 1 0 1

BSP-PIR90
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K129 PIR 1 0 1
Led Binary Output 5: General - Motion detectors K129 Led 1 0 1
BSP-PIR90A
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K130 PIR 1 0 1
Led Binary Output 5: General - Motion detectors K130 Led 1 0 1

BSN-ANE
Name BACnet object BACnet name Min Value Max Value Measure unit
Wind Analog Input 1: General – Wind sensor K131 Wind 1 0 35 m/s
Strong wind alarm Binary Input 2: General – Wind sensor K131 Strong wind alarm 1 0 1
Strong wind alarm Binary Input 3: General – Wind sensor K131 Strong wind alarm 2 0 1
Strong wind alarm Binary Input 4: General – Wind sensor K131 Strong wind alarm 3 0 1
Strong wind alarm Binary Input 5: General – Wind sensor K131 Strong wind alarm 4 0 1
Strong wind alarm Binary Input 6: General – Wind sensor K131 Strong wind alarm 5 0 1
Strong wind alarm Binary Input 7: General – Wind sensor K131 Strong wind alarm 6 0 1
Strong wind alarm Binary Input 8: General – Wind sensor K131 Strong wind alarm 7 0 1

BACC-KEYPAD-DC
Name BACnet object BACnet name Min Value Max Value Measure unit
Bell Binary Input 1: General - Keypad K6 Bell 1 0 1
Led Binary Output 3: General - Keypad K6 Led 1 0 1
Code accepted Binary Input 2: General - Keypad K6 Code accepted 1 0 1
Led Binary Output 4: General - Keypad K6 Led 2 0 1
Buzzer Binary Output 5: General - Keypad K6 Buzzer 1 0 1

BSG-SMO
Name BACnet object BACnet name Min Value Max Value Measure unit
Smoke alarm Binary Input 1: General – Smoke sensor K133 Smoke alarm 1 0 1
Buzzer Binary Output 5: General – Smoke sensor K133 Buzzer 1 0 1
Alarm Binary Input 2: General – Smoke sensor K133 Alarm 2 0 1
Alarm Binary Input 3: General – Smoke sensor K133 Alarm 3 0 1
Alarm Binary Input 4: General – Smoke sensor K133 Alarm 4 0 1
BSG-SMOA
Name BACnet object BACnet name Min Value Max Value Measure unit
Smoke alarm Binary Input 1: General – Smoke sensor K134 Smoke alarm 1 0 1
Buzzer Binary Output 5: General – Smoke sensor K134 Buzzer 1 0 1
Alarm Binary Input 2: General – Smoke sensor K134 Alarm 2 0 1
Alarm Binary Input 3: General – Smoke sensor K134 Alarm 3 0 1
Alarm Binary Input 4: General – Smoke sensor K134 Alarm 4 0 1

BSQ-PIR360
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K135 PIR 1 0 1
Led Binary Output 5: General - Motion detectors K135 Led 1 0 1

BFW-PIR90
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K136 PIR 1 0 1
Led Binary Output 2: General - Motion detectors K136 Led 1 0 1

BOW-PIR90
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K137 PIR 1 0 1
Led Binary Output 2: General - Motion detectors K137 Led 1 0 1

BOW-PIR90A
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K138 PIR 1 0 1
Led Binary Output 2: General - Motion detectors K138 Led 1 0 1
BEL-PIR90
Name BACnet object BACnet name Min Value Max Value Measure unit
PIR Binary Input 1: General - Motion detectors K139 PIR 1 0 1
Led Binary Output 5: General - Motion detectors K139 Led 1 0 1
Alarm Binary input 2: General - Motion detectors K139 Alarm 1 0 1

BSK-MAG
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Alarms K140 Switch 1 0 1

BSA-IND
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Alarms K141 Switch 1 0 1

BSA-INDA
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Alarms K142 Switch 1 0 1

BSE-MAG
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Alarms K143 Switch 1 0 1

BSE-MAGA
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Alarms K144 Switch 1 0 1

BDE-RE13A
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary Input 1: General – Relay module K145 Re 1 0 1
BFW-HUM
Name BACnet object BACnet name Min Value Max Value Measure unit
Humidity Analog Input 1: General - Environmental sensor K146 Humidity 1 0 100 %
Led Binary Output 3: General - Environmental sensor K146 Led 1 0 1
Temperature Analog input 2: General - Environmental sensor K146 Temperature 1 -40 250 °C

SHA4XLS2TEMDIS
Name BACnet object BACnet name Min Value Max Value Measure unit
TRoom Analog Input 1: General - Temdis display k148 TRoom 1 -40 250 °C
TAuxiliary Analog Input 2: General - Temdis display k148 TAuxiliary 1 -40 250 °C
Presence Binary Input 9: General - Temdis display k148 Presence 1 0 1
Configuration OK Binary Input 10: General - Temdis display k148 Configuration OK 1 0 1
Quality index Analog Input 11: General - Temdis display k148 Quality index 1 0 100
Push Binary Input 3: General - Temdis display k148 Push 1 0 1
Push Binary Input 4: General - Temdis display k148 Push 2 0 1
Led Binary Output 5: General - Temdis display k148 Led 1 0 1
Led Binary Output 6: General - Temdis display k148 Led 2 0 1
Led Binary Output 7: General - Temdis display k148 Led 3 0 1
Led Binary Output 8: General - Temdis display k148 Led 4 0 1

SHE5XLS2TEMDIS
Name BACnet object BACnet name Min Value Max Value Measure unit
TRoom Analog Input 1: General - Temdis display k149 TRoom 1 -40 250 °C
TAuxiliary Analog Input 2: General - Temdis display k149 TAuxiliary 1 -40 250 °C
Presence Binary Input 9: General - Temdis display k149 Presence 1 0 1
Configuration OK Binary Input 10: General - Temdis display k149 Configuration OK 1 0 1
Quality index Analog Input 11: General - Temdis display k149 Quality index 1 0 100
Push Binary Input 3: General - Temdis display k149 Push 1 0 1
Push Binary Input 4: General - Temdis display k149 Push 2 0 1
Led Binary Output 5: General - Temdis display k149 Led 1 0 1
Led Binary Output 6: General - Temdis display k149 Led 2 0 1
Led Binary Output 7: General - Temdis display k149 Led 3 0 1
Led Binary Output 8: General - Temdis display k149 Led 4 0 1
SHA4XLS2TEMDISU
Name BACnet object BACnet name Min Value Max Value Measure unit
TRoom Analog Input 1: General - Temdis display k150 TRoom 1 -40 250 °C
TAuxiliary Analog Input 2: General - Temdis display k150 TAuxiliary 1 -40 250 °C
Presence Binary Input 9: General - Temdis display k150 Presence 1 0 1
Configuration OK Binary Input 10: General - Temdis display k150 Configuration OK 1 0 1
Quality index Analog Input 11: General - Temdis display k150 Quality index 1 0 100
Push Binary Input 3: General - Temdis display k150 Push 1 0 1
Push Binary Input 4: General - Temdis display k150 Push 2 0 1
Led Binary Output 5: General - Temdis display k150 Led 1 0 1
Led Binary Output 6: General - Temdis display k150 Led 2 0 1
Led Binary Output 7: General - Temdis display k150 Led 3 0 1
Led Binary Output 8: General - Temdis display k150 Led 4 0 1

SHE5XLS2TEMDISU
Name BACnet object BACnet name Min Value Max Value Measure unit
TRoom Analog Input 1: General - Temdis display k151 TRoom 1 -40 250 °C
TAuxiliary Analog Input 2: General - Temdis display k151 TAuxiliary 1 -40 250 °C
Presence Binary Input 9: General - Temdis display k151 Presence 1 0 1
Configuration OK Binary Input 10: General - Temdis display k151 Configuration OK 1 0 1
Quality index Analog Input 11: General - Temdis display k151 Quality index 1 0 100
Push Binary Input 3: General - Temdis display k151 Push 1 0 1
Push Binary Input 4: General - Temdis display k151 Push 2 0 1
Led Binary Output 5: General - Temdis display k151 Led 1 0 1
Led Binary Output 6: General - Temdis display k151 Led 2 0 1
Led Binary Output 7: General - Temdis display k151 Led 3 0 1
Led Binary Output 8: General - Temdis display k151 Led 4 0 1

BOW-HUM
Name BACnet object BACnet name Min Value Max Value Measure unit
Humidity Analog Input 1: General - Environmental sensor K152 Humidity 1 0 100 %
Temperature Analog input 2: General - Environmental sensor K152 Temperature 1 -40 250 °C
Led Binary Output 3: General - Environmental sensor K152 Led 1 0 1
BSH-LUX-A
Name BACnet object BACnet name Min Value Max Value Measure unit
Luxmeter Binary Input 1: General – Lux sensor K153 Luxmeter 1 0 65535 Lux

BSH-LUX-B
Name BACnet object BACnet name Min Value Max Value Measure unit
Luxmeter Analog Input 1: General – Lux sensor K154 Luxmeter 1 0 65535 Lux

G43111120
Name BACnet object BACnet name Min Value Max Value Measure unit
Luxmeter Analog Input 1: General – Lux sensor K155 Luxmeter 1 0 65535 Lux

BFW-TEMANA
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Temp sensor K156 Temperature 1 -40 250 °C
Led Binary Output 5: General – Temp sensor K156 Led 1 0 1

BOW-TEMANA
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Temp sensor K157 Temperature 1 -40 250 °C
Led Binary Output 5: General – Temp sensor K157 Led 1 0 1

BEL-TEMANA
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Temp sensor K158 Temperature 1 -40 250 °C
BSI-TEMANA
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General – Temp sensor K159 Temperature 1 -40 250 °C

BDA-SSTRI1
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary Output 1: General - Relay module K160 Re 1 0 1

BSM-CAPSTD1
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Switches k161 Push 1 0 1

BH4-RE16A8-230
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary Output 1: General - Relay module K162 Re 1 0 1
Re Binary Output 2: General - Relay module K162 Re 2 0 1
Re Binary Output 3: General - Relay module K162 Re 3 0 1
Re Binary Output 4: General - Relay module K162 Re 4 0 1
Re Binary Output 5: General - Relay module K162 Re 5 0 1
Re Binary Output 6: General - Relay module K162 Re 6 0 1
Re Binary Output 7: General - Relay module K162 Re 7 0 1
Re Binary Output 8: General - Relay module K162 Re 8 0 1

BH4-SSTRI8-230
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary Output 1: General - Relay module K164 Re 1 0 1
Re Binary Output 2: General - Relay module K164 Re 2 0 1
Re Binary Output 3: General - Relay module K164 Re 3 0 1
Re Binary Output 4: General - Relay module K164 Re 4 0 1
Re Binary Output 5: General - Relay module K164 Re 5 0 1
Re Binary Output 6: General - Relay module K164 Re 6 0 1
Re Binary Output 7: General - Relay module K164 Re 7 0 1
Re Binary Output 8: General - Relay module K164 Re 8 0 1
BH4-RE16A4-230
Name BACnet object BACnet name Min Value Max Value Measure unit
Re Binary Output 1: General - Relay module K166 Re 1 0 1
Re Binary Output 2: General - Relay module K166 Re 2 0 1
Re Binary Output 3: General - Relay module K166 Re 3 0 1
Re Binary Output 4: General - Relay module K166 Re 4 0 1

BH2-SEP-230
Name BACnet object BACnet name Min Value Max Value Measure unit
Alarm Binary Input 1: General - Alarms K168 Alarm 1 0 1
Led Binary Output 5: General - Alarms K168 Led 2 0 1

BFW-TEMTHE
Name BACnet object BACnet name Min Value Max Value Measure unit
Thermostat Analog Input 1: General - Temperatures K169 Thermostat 1 -40 250 °C
Night Set Back Binary Output 5: General - Temperatures K169 Night Set Back 1 0 1
Led Binary Output 6: General - Temperatures K169 Led 2 0 1

BOW-TEMTHE
Name BACnet object BACnet name Min Value Max Value Measure unit
Thermostat Analog Input 1: General - Temperatures K170 Thermostat 1 -40 250 °C
Night Set Back Binary Output 5: General - Temperatures K170 Night Set Back 1 0 1
Led Binary Output 6: General - Temperatures K170 Led 2 0 1
SHJWRE10AE230
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General - Relay module K179 KWh 1 0 1000000000 kWh
Volt Analog Input 2: General - Relay module K179 Volt 1 0 400 V
Ampere Analog Input 3: General - Relay module K179 Ampere 1 0 1000 A
KW Analog Input 4: General - Relay module K179 kW 1 0 1000000000 kW
KWdmd Analog Input 5: General - Relay module K179 kWdmd 1 0 1000000000 kW
PF Analog Input 6: General - Relay module K179 PF 1 -0.99 0.99
KVA Analog Input 7: General - Relay module K179 kVA 1 0 1000000000 kVA
Kvar Analog Input 8: General - Relay module K179 kVAr 1 0 1000000000 kVAR
Re Binary output 9: General - Relay module K179 Re 2 0 1
Presence Binary Input 10: General - Relay module k179 Presence 1 0 1
Configuration OK Binary Input 11: General - Relay module k179 Configuration OK 1 0 1
Quality index Analog Input 12: General - Relay module k179 Quality index 1 0 100
Quality index master generator Analog Input 13: General - Relay module k179 Quality index master generator 1 0 100
Overload warning Binary Input 14: General - Relay module K179 Overload warning 1 0 1
Load not present Binary Input 15: General - Relay module K179 Load not present 1 0 1

SHJWRE10AE115
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General - Relay module K180 KWh 1 0 1000000000 kWh
Volt Analog Input 2: General - Relay module K180 Volt 1 0 400 V
Ampere Analog Input 3: General - Relay module K180 Ampere 1 0 1000 A
KW Analog Input 4: General - Relay module K180 kW 1 0 1000000000 kW
KWdmd Analog Input 5: General - Relay module K180 kWdmd 1 0 1000000000 kW
PF Analog Input 6: General - Relay module K180 PF 1 -0.99 0.99
KVA Analog Input 7: General - Relay module K180 kVA 1 0 1000000000 kVA
Kvar Analog Input 8: General - Relay module K180 kVAr 1 0 1000000000 kVAR
Re Binary output 9: General - Relay module K180 Re 2 0 1
Presence Binary Input 10: General - Relay module k180 Presence 1 0 1
Configuration OK Binary Input 11: General - Relay module k180 Configuration OK 1 0 1
Quality index Analog Input 12: General - Relay module k180 Quality index 1 0 100
Quality index master generator Analog Input 13: General - Relay module k180 Quality index master generator 1 0 100
Overload warning Binary Input 14: General - Relay module K180 Overload warning 1 0 1
Load not present Binary Input 15: General - Relay module K180 Load not present 1 0 1
SHJWRE10AEBLS230
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Relay module K181 Push 1 0 1
Push Binary Input 2: General - Relay module K181 Push 2 0 1
KWh Analog Input 3: General - Relay module K181 KWh 1 0 1000000000 kWh
Volt Analog Input 4: General - Relay module K181 Volt 1 0 400 V
Ampere Analog Input 5: General - Relay module K181 Ampere 1 0 1000 A
KW Analog Input 6: General - Relay module K181 kW 1 0 1000000000 kW
KWdmd Analog Input 7: General - Relay module K181 kWdmd 1 0 1000000000 kW
PF Analog Input 8: General - Relay module K181 PF 1 -0.99 0.99
KVA Analog Input 9: General - Relay module K181 kVA 1 0 1000000000 kVA
Kvar Analog Input 11: General - Relay module K181 kVAr 1 0 1000000000 kVAR
Re Binary output 13: General - Relay module K181 Re 2 0 1
Presence Binary Input 10: General - Relay module k181 Presence 1 0 1
Configuration OK Binary Input 11: General - Relay module k181 Configuration OK 1 0 1
Quality index Analog Input 12: General - Relay module k181 Quality index 1 0 100
Quality index master generator Analog Input 13: General - Relay module k181 Quality index master generator 1 0 100
Overload warning Binary Input 14: General - Relay module K181 Overload warning 1 0 1
Load not present Binary Input 15: General - Relay module K181 Load not present 1 0 1

SHJWRE10AEWLS230
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Relay module K182 Push 1 0 1
Push Binary Input 2: General - Relay module K182 Push 2 0 1
KWh Analog Input 3: General - Relay module K182 KWh 1 0 1000000000 kWh
Volt Analog Input 4: General - Relay module K182 Volt 1 0 400 V
Ampere Analog Input 5: General - Relay module K182 Ampere 1 0 1000 A
KW Analog Input 6: General - Relay module K182 kW 1 0 1000000000 kW
KWdmd Analog Input 7: General - Relay module K182 kWdmd 1 0 1000000000 kW
PF Analog Input 8: General - Relay module K182 PF 1 -0.99 0.99
KVA Analog Input 9: General - Relay module K182 kVA 1 0 1000000000 kVA
Kvar Analog Input 11: General - Relay module K182 kVAr 1 0 1000000000 kVAR
Re Binary output 13: General - Relay module K182 Re 2 0 1
Presence Binary Input 10: General - Relay module K 182 Presence 1 0 1
Configuration OK Binary Input 11: General - Relay module k182 Configuration OK 1 0 1
Quality index Analog Input 12: General - Relay module k182 Quality index 1 0 100
Quality index master generator Analog Input 13: General - Relay module k182 Quality index master generator 1 0 100
Overload warning Binary Input 14: General - Relay module K182 Overload warning 1 0 1
Load not present Binary Input 15: General - Relay module K182 Load not present 1 0 1
SHJWEM16A230
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General - Relay module K183 KWh 1 0 1000000000 kWh
Volt Analog Input 2: General - Relay module K183 Volt 1 0 400 V
Ampere Analog Input 3: General - Relay module K183 Ampere 1 0 1000 A
kW Analog Input 4: General - Relay module K183 kW 1 0 1000000000 kW
kWdmd Analog Input 5: General - Relay module K183 kWdmd 1 0 1000000000 kW
PF Analog Input 6: General - Relay module K183 PF 1 -0.99 0.99
kVA Analog Input 7: General - Relay module K183 kVA 1 0 1000000000 kVA
kVAr Analog Input 8: General - Relay module K183 kVAr 1 0 1000000000 kVAR
Presence Binary Input 9: General - Relay module K 183 Presence 1 0 1
Configuration OK Binary Input 10: General - Relay module k183 Configuration OK 1 0 1
Quality index Analog Input 11: General - Relay module k183 Quality index 1 0 100
Quality index master generator Analog Input 12: General - Relay module k183 Quality index master generator 1 0 100

SHJWEM16A115
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General - Relay module K183 KWh 1 0 1000000000 kWh
Volt Analog Input 2: General - Relay module K183 Volt 1 0 400 V
Ampere Analog Input 3: General - Relay module K183 Ampere 1 0 1000 A
kW Analog Input 4: General - Relay module K183 kW 1 0 1000000000 kW
kWdmd Analog Input 5: General - Relay module K183 kWdmd 1 0 1000000000 kW
PF Analog Input 6: General - Relay module K183 PF 1 -0.99 0.99
kVA Analog Input 7: General - Relay module K183 kVA 1 0 1000000000 kVA
kVAr Analog Input 8: General - Relay module K183 kVAr 1 0 1000000000 kVAR
Presence Binary Input 9: General - Relay module K 183 Presence 1 0 1
Configuration OK Binary Input 10: General - Relay module k183 Configuration OK 1 0 1
Quality index Analog Input 11: General - Relay module k183 Quality index 1 0 100
Quality index master generator Analog Input 12: General - Relay module k183 Quality index master generator 1 0 100
SHJWD200WE230
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General - Relay module K185 KWh 1 0 1000000000 kWh
Volt Analog Input 2: General - Relay module K185 Volt 1 0 400 V
Ampere Analog Input 3: General - Relay module K185 Ampere 1 0 1000 A
kW Analog Input 4: General - Relay module K185 kW 1 0 1000000000 kW
kWdmd Analog Input 5: General - Relay module K185 kWdmd 1 0 1000000000 kW
Presence Binary Input 13: General - Relay module k185 Presence 1 0 1
Configuration OK Binary Input 14: General - Relay module k185 Configuration OK 1 0 1
Quality index Analog Input 15: General - Relay module k185 Quality index 1 0 100
Quality index master generator Analog Input 16: General - Relay module k185 Quality index master generator 1 0 100
Overload warning Binary Input 17: General - Relay module K185 Overload warning 1 0 1
Over voltage Binary Input 18: General - Relay module k185 Over voltage 1 0 1
Over temperature Binary Input 19: General - Relay module k185 Over temperature 1 0 1
Hardware error Binary Input 20: General - Relay module k185 Hardware error 1 0 1
Over current Binary Input 21: General - Relay module k185 Over current 1 0 1
Load not present Binary Input 22: General - Relay module K185 Load not present 1 0 1
Short circuit Binary Input 23: General - Relay module k185 Short circuit 1 0 1

SHJWD200WE115
Name BACnet object BACnet name Min Value Max Value Measure unit
KWh Analog Input 1: General - Relay module K186 KWh 1 0 1000000000 kWh
Volt Analog Input 2: General - Relay module K186 Volt 1 0 400 V
Ampere Analog Input 3: General - Relay module K186 Ampere 1 0 1000 A
kW Analog Input 4: General - Relay module K186 kW 1 0 1000000000 kW
kWdmd Analog Input 5: General - Relay module K186 kWdmd 1 0 1000000000 kW
Presence Binary Input 13: General - Relay module k186 Presence 1 0 1
Configuration OK Binary Input 14: General - Relay module k186 Configuration OK 1 0 1
Quality index Analog Input 15: General - Relay module k186 Quality index 1 0 100
Quality index master generator Analog Input 16: General - Relay module k186 Quality index master generator 1 0 100
Overload warning Binary Input 17: General - Relay module K186 Overload warning 1 0 1
Over voltage Binary Input 18: General - Relay module k186 Over voltage 1 0 1
Over temperature Binary Input 19: General - Relay module k186 Over temperature 1 0 1
Hardware error Binary Input 20: General - Relay module k186 Hardware error 1 0 1
Over current Binary Input 21: General - Relay module k186 Over current 1 0 1
Load not present Binary Input 22: General - Relay module K186 Load not present 1 0 1
Short circuit Binary Input 23: General - Relay module k186 Short circuit 1 0 1
SHJWD200WEBLS230
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Relay module K187 Push 1 0 1
Push Binary Input 2: General - Relay module K187 Push 2 0 1
KWh Analog Input 3: General - Relay module K187 KWh 1 0 1000000000 kWh
Volt Analog Input 4: General - Relay module K187 Volt 1 0 400 V
Ampere Analog Input 5: General - Relay module K187 Ampere 1 0 1000 A
kW Analog Input 6: General - Relay module K187 kW 1 0 1000000000 kW
kWdmd Analog Input 7: General - Relay module K187 kWdmd 1 0 1000000000 kW
Presence Binary Input 16: General - Relay module k187 Presence 1 0 1
Configuration OK Binary Input 17: General - Relay module k187 Configuration OK 1 0 1
Quality index Analog Input 18: General - Relay module k187 Quality index 1 0 100
Quality index master generator Analog Input 19: General - Relay module k187 Quality index master generator 1 0 100
Overload warning Binary Input 20: General - Relay module K187 Overload warning 1 0 1
Over voltage Binary Input 21: General - Relay module k187 Over voltage 1 0 1
Over temperature Binary Input 22: General - Relay module k187 Over temperature 1 0 1
Hardware error Binary Input 23: General - Relay module k187 Hardware error 1 0 1
Over current Binary Input 24: General - Relay module k187 Over current 1 0 1
Load not present Binary Input 25: General - Relay module K187 Load not present 1 0 1
Short circuit Binary Input 26: General - Relay module k187 Short circuit 1 0 1

SHJWD200WEWLS230
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Relay module K187 Push 1 0 1
Push Binary Input 2: General - Relay module K187 Push 2 0 1
KWh Analog Input 3: General - Relay module K187 KWh 1 0 1000000000 kWh
Volt Analog Input 4: General - Relay module K187 Volt 1 0 400 V
Ampere Analog Input 5: General - Relay module K187 Ampere 1 0 1000 A
kW Analog Input 6: General - Relay module K187 kW 1 0 1000000000 kW
kWdmd Analog Input 7: General - Relay module K187 kWdmd 1 0 1000000000 kW
Presence Binary Input 16: General - Relay module k187 Presence 1 0 1
Configuration OK Binary Input 17: General - Relay module k187 Configuration OK 1 0 1
Quality index Analog Input 18: General - Relay module k187 Quality index 1 0 100
Quality index master generator Analog Input 19: General - Relay module k187 Quality index master generator 1 0 100
Overload warning Binary Input 20: General - Relay module K187 Overload warning 1 0 1
Over voltage Binary Input 21: General - Relay module k187 Over voltage 1 0 1
Over temperature Binary Input 22: General - Relay module k187 Over temperature 1 0 1
Hardware error Binary Input 23: General - Relay module k187 Hardware error 1 0 1
Over current Binary Input 24: General - Relay module k187 Over current 1 0 1
Load not present Binary Input 25: General - Relay module K187 Load not present 1 0 1
Short circuit Binary Input 26: General - Relay module k187 Short circuit 1 0 1
SBP2WREP230
Name BACnet object BACnet name Min Value Max Value Measure unit
Presence Binary Input 1: General - Relay module k189 Presence 1 0 1
Configuration OK Binary Input 2: General - Relay module k189 Configuration OK 1 0 1
Quality index Analog Input 3: General - Relay module k189 Quality index 1 0 100
Quality index master generator Analog Input 4: General - Relay module k189 Quality index master generator 1 0 100

G34396470230
Name BACnet object BACnet name Min Value Max Value Measure unit
Analogue output Analog Output 1: General - Analog output k190 Analogue output 1 0 400 V
Analogue output Analog Output 2: General - Analog output k190 Analogue output 2 0 400 V
Analogue output Analog Output 3: General - Analog output k190 Analogue output 3 0 400 V
Analogue output Analog Output 4: General - Analog output k190 Analogue output 4 0 400 V

SBP2DIW48524
Name BACnet object BACnet name Min Value Max Value Measure unit
Display disconnected Binary Input 1: General - Carpark k191 Display disconnected 1 0 1
Display not correct Binary Input 2: General - Carpark k191 Display not correct 1 0 1
Configuration OK Binary Input 3: General - Carpark k191 Configuration OK 1 0 1
Quality index Analog Input 4: General - Carpark k191 Quality index 1 0 100
Quality index master generator Analog Input 5: General - Carpark k191 Quality index master generator 1 0 100

SHE5XWLS4WFT
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Wireless K192 Push 1 0 1
Push Binary Input 2: General - Wireless K192 Push 2 0 1
Push Binary Input 3: General - Wireless K192 Push 3 0 1
Push Binary Input 4: General - Wireless K192 Push 4 0 1
Temperature Analog Input 5: General - Wireless K192 Temperature 1 -40 250 °C
Presence Binary Input 6: General - Wireless K192 Presence 1 0 1
Configuration ok Binary Input 7: General - Wireless K192 Configuration OK 1 0 1
Quality index Analog input 8: General - Wireless K192 Quality index 1 0 100
Quality index master generator Analog input 9: General - Wireless K192 Quality index master generator 1 0 100
Battery low Binary Input 10: General - Wireless K192 Battery low 1 0 1
Battery level Analog input 11: General - Wireless K192 Battery level 1 0 400 V
SHE5XWLS4B
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Wireless K193 Push 1 0 1
Push Binary Input 2: General - Wireless K193 Push 2 0 1
Push Binary Input 3: General - Wireless K193 Push 3 0 1
Push Binary Input 4: General - Wireless K193 Push 4 0 1
Temperature Analog Input 5: General - Wireless K193 Temperature 1 -40 250 °C
Presence Binary Input 6: General - Wireless K193 Presence 1 0 1
Configuration ok Binary Input 7: General - Wireless K193 Configuration OK 1 0 1
Quality index Analog input 8: General - Wireless K193 Quality index 1 0 100
Quality index master generator Analog input 9: General - Wireless K193 Quality index master generator 1 0 100
Battery low Binary Input 10: General - Wireless K193 Battery low 1 0 1
Battery level Analog input 11: General - Wireless K193 Battery level 1 0 400 V

SHE5XWLS4WF
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Wireless K194 Push 1 0 1
Push Binary Input 2: General - Wireless K194 Push 2 0 1
Push Binary Input 3: General - Wireless K194 Push 3 0 1
Push Binary Input 4: General - Wireless K194 Push 4 0 1
Presence Binary Input 5: General - Wireless K194 Presence 1 0 1
Configuration ok Binary Input 6: General - Wireless K194 Configuration OK 1 0 1
Quality index Analog input 7: General - Wireless K194 Quality index 1 0 100
Quality index master generator Analog input 8: General - Wireless K194 Quality index master generator 1 0 100
Battery low Binary Input 9: General - Wireless K194 Battery low 1 0 1
Battery level Analog input 10: General - Wireless K194 Battery level 1 0 400 V
SHE5XWLS4BF
Name BACnet object BACnet name Min Value Max Value Measure unit
Push Binary Input 1: General - Wireless K195 Push 1 0 1
Push Binary Input 2: General - Wireless K195 Push 2 0 1
Push Binary Input 3: General - Wireless K195 Push 3 0 1
Push Binary Input 4: General - Wireless K195 Push 4 0 1
Presence Binary Input 5: General - Wireless K195 Presence 1 0 1
Configuration ok Binary Input 6: General - Wireless K195 Configuration OK 1 0 1
Quality index Analog input 7: General - Wireless K195 Quality index 1 0 100
Quality index master generator Analog input 8: General - Wireless K195 Quality index master generator 1 0 100
Battery low Binary Input 9: General - Wireless K195 Battery low 1 0 1
Battery level Analog input 10: General - Wireless K195 Battery level 1 0 400 V

SBB4I2Oxxx
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General – I/O Modules K196 Switch 1 0 1
Switch Binary Input 2: General – I/O Modules K196 Switch 2 0 1
Switch Binary Input 3: General – I/O Modules K196 Switch 3 0 1
Switch Binary Input 4: General – I/O Modules K196 Switch 4 0 1
Re Binary Output 5: General – I/O Modules K196 Re 1 0 1
Re Binary Output 6: General – I/O Modules K196 Re 2 0 1
Presence Binary Input 7: General - I/O Modules K196 Presence 1 0 1
Configuration ok Binary Input 8: General - I/O Modules K196 Configuration OK 1 0 1
Quality index Analog input 9: General - I/O Modules K196 Quality index 1 0 100
SBB4I
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General – I/O Modules K197 Switch 1 0 1
Switch Binary Input 2: General – I/O Modules K197 Switch 2 0 1
Switch Binary Input 3: General – I/O Modules K197 Switch 3 0 1
Switch Binary Input 4: General – I/O Modules K197 Switch 4 0 1
Presence Binary Input 5: General - I/O Modules K197 Presence 1 0 1
Configuration ok Binary Input 6: General - I/O Modules K197 Configuration OK 1 0 1
Quality index Analog input 7: General - I/O Modules K197 Quality index 1 0 100

SBP2DI48524
Name BACnet object BACnet name Min Value Max Value Measure unit
Display disconnected Binary Input 1: General - Carpark k198 Display disconnected 1 0 1
Display not correct Binary Input 2: General - Carpark k198 Display not correct 1 0 1
Configuration OK Binary Input 3: General - Carpark k198 Configuration OK 1 0 1
Quality index Analog Input 4: General - Carpark k198 Quality index 1 0 100

SBPILED
Name BACnet object BACnet name Min Value Max Value Measure unit
Indicator Binary Input 1: General - Carpark k199 Indicator 1 0 1
Presence Binary Input 2: General - Carpark k199 Presence 1 0 1
Configuration OK Binary Input 3: General - Carpark k199 Configuration OK 1 0 1
Quality index Analog Input 4: General - Carpark k199 Quality index 1 0 100
POW voltage drop Binary Input 5: General - Carpark k199 POW voltage drop 1 0 1
D+ voltage drop Binary Input 6: General - Carpark k199 D+ voltage drop 1 0 1
Base holder fault Binary Input 7: General - Carpark k199 Base holder fault 1 0 1
Local button fault Binary Input 8: General - Carpark k199 Local button fault 1 0 1
POW voltage Analog Input 9: General - Carpark k199 POW voltage 1 0 400 V
Dupline voltage Analog Input 10: General - Carpark k199 Dupline voltage 1 0 400 V
SBPSUSCNT
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General - Carpark k200 Temperature 1 0 250 °C
Presence Binary Input 2: General - Carpark k200 Presence 1 0 1
Configuration OK Binary Input 3: General - Carpark k200 Configuration OK 1 0 1
Quality index Analog Input 4: General - Carpark k200 Quality index 1 0 100
POW voltage drop Binary Input 5: General - Carpark k200 POW voltage drop 1 0 1
D+ voltage drop Binary Input 6: General - Carpark k200 D+ voltage drop 1 0 1
Base holder fault Binary Input 7: General - Carpark k200 Base holder fault 1 0 1
Local button fault Binary Input 8: General - Carpark k200 Local button fault 1 0 1
Calibration warning Binary Input 9: General - Carpark k200 Calibration warning 1 0 1
Sensor error Binary Input 10: General - Carpark k200 Sensor error 1 0 1
POW voltage Analog Input 11: General - Carpark k200 POW voltage 1 0 400 V
Dupline voltage Analog Input 12: General - Carpark k200 Dupline voltage 1 0 400 V

SBPSUSL
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General - Carpark k201 Temperature 1 0 250 °C
Carpark Binary Input 2: General - Carpark k201 Carpark 1 0 1
Presence Binary Input 3: General - Carpark k201 Presence 1 0 1
Configuration OK Binary Input 4: General - Carpark k201 Configuration OK 1 0 1
Quality index Analog Input 5: General - Carpark k201 Quality index 1 0 100
POW voltage drop Binary Input 6: General - Carpark k201 POW voltage drop 1 0 1
D+ voltage drop Binary Input 7: General - Carpark k201 D+ voltage drop 1 0 1
Base holder fault Binary Input 8: General - Carpark k201 Base holder fault 1 0 1
Local button fault Binary Input 9: General - Carpark k201 Local button fault 1 0 1
Calibration warning Binary Input 10: General - Carpark k201 Calibration warning 1 0 1
Sensor error Binary Input 11: General - Carpark k201 Sensor error 1 0 1
Crosstalk Binary Input 12: General - Carpark k201 Crosstalk 1 0 1
POW voltage Analog Input 13: General - Carpark k201 POW voltage 1 0 400 V
Dupline voltage Analog Input 14: General - Carpark k201 Dupline voltage 1 0 400 V
SBPSUSL45
Name BACnet object BACnet name Min Value Max Value Measure unit
Temperature Analog Input 1: General - Carpark k202 Temperature 1 0 250 °C
Carpark Binary Input 2: General - Carpark k202 Carpark 1 0 1
Presence Binary Input 3: General - Carpark k202 Presence 1 0 1
Configuration OK Binary Input 4: General - Carpark k202 Configuration OK 1 0 1
Quality index Analog Input 5: General - Carpark k202 Quality index 1 0 100
POW voltage drop Binary Input 6: General - Carpark k202 POW voltage drop 1 0 1
D+ voltage drop Binary Input 7: General - Carpark k202 D+ voltage drop 1 0 1
Base holder fault Binary Input 8: General - Carpark k202 Base holder fault 1 0 1
Local button fault Binary Input 9: General - Carpark k202 Local button fault 1 0 1
Calibration warning Binary Input 10: General - Carpark k202 Calibration warning 1 0 1
Sensor error Binary Input 11: General - Carpark k202 Sensor error 1 0 1
Crosstalk Binary Input 12: General - Carpark k202 Crosstalk 1 0 1
POW voltage Analog Input 12: General - Carpark k202 POW voltage 1 0 400 V
Dupline voltage Analog Input 13: General - Carpark k202 Dupline voltage 1 0 400 V
SHJWINS04115
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Wireless K203 Switch 1 0 1
Switch Binary Input 2: General - Wireless K203 Switch 2 0 1
Switch Binary Input 3: General - Wireless K203 Switch 3 0 1
Switch Binary Input 4: General - Wireless K203 Switch 4 0 1
Presence Binary Input 1: General - Wireless K203 Presence 1 0 1
Configuration ok Binary Input 2: General - Wireless K203 Configuration OK 1 0 1
Quality index Analog input 3: General - Wireless K203 Quality index 1 0 100
Quality index master generator Analog input 4: General - Wireless K203 Quality index master generator 1 0 100

SHJWINS04230
Name BACnet object BACnet name Min Value Max Value Measure unit
Switch Binary Input 1: General - Wireless K204 Switch 1 0 1
Switch Binary Input 2: General - Wireless K204 Switch 2 0 1
Switch Binary Input 3: General - Wireless K204 Switch 3 0 1
Switch Binary Input 4: General - Wireless K204 Switch 4 0 1
Presence Binary Input 1: General - Wireless K204 Presence 1 0 1
Configuration ok Binary Input 2: General - Wireless K204 Configuration OK 1 0 1
Quality index Analog input 3: General - Wireless K204 Quality index 1 0 100
Quality index master generator Analog input 4: General - Wireless K204 Quality index master generator 1 0 100

SH2MCG24
Name BACnet object BACnet name Min Value Max Value Measure unit
Current Analog Input 1: General - Master Generator K205 Current 1 0 10000 mA
Voltage Analog Input 2: General - Master Generator K205 Voltage 1 0 400 V
Quality index Analog input 3: General - Master Generator K205 Quality index 1 0 100

SH2DUG24
Name BACnet object BACnet name Min Value Max Value Measure unit
Current Analog Input 1: General - Master Generator K206 Current 1 0 10000 mA
Voltage Analog Input 2: General - Master Generator K206 Voltage 1 0 400 V
Quality index Analog input 3: General - Master Generator K206 Quality index 1 0 100
SBP2MCG324
Name BACnet object BACnet name Min Value Max Value Measure unit
Current Analog Input 1: General - Master Generator K207 Current 1 0 10000 mA
Voltage Analog Input 2: General - Master Generator K207 Voltage 1 0 400 V
Quality index Analog input 3: General - Master Generator K207 Quality index 1 0 100

UWPMM1UL1X
Name BACnet object BACnet name Min Value Max Value Measure unit
Presence Binary Input 1: General - Master Generator K208 Presence 1 0 1
Configuration ok Binary Input 2: General - Master Generator K208 Configuration OK 1 0 1
Definitions
OBJECT_ANALOG_INPUT
Name Description
Object_identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_ANALOG_INPUT
Present_Value Indicates the current value of the input being measured
Description Assigned automatically by the tool
Device_Type Home part number by the tool
Represents the general health of analogue input; Three of the flags are associated with the values of other properties; Flag IN_ALARM: False if communication OK, True if
Status_Flag communication error; Flag FAULT: False (fixed value); Flag OVERRIDDEN: False (fixed value); Flag OUT_OF_SERVICE: depends on OUT_OF_SERVICE property
Event_State NORMAL
Out_Of_Service Indication whether (TRUE) or not (FALSE) the physical input that the object represents is not in service
Units Measure unit set by tool
MinPresValue Min value of PRESENT_VALUE
MaxPresValue Max value of PRESENT_VALUE
Resolution Depends on measure unit
COV_Increment Minimum change in PRESENT_VALUE that will cause a COVNotification

OBJECT_ANALOG_OUTPUT
Name Description
Object_identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_ANALOG_OUTPUT
Present_Value The current value of the analog output
Description Assigned automatically by the tool
Device_Type Home part number by the tool
Represents the general health of analogue ouput; Three of the flags are associated with the values of other properties; Flag IN_ALARM: False if communication OK, True if
Status_Flag communication error; Flag FAULT: False (fixed value); Flag OVERRIDDEN: False (fixed value); Flag OUT_OF_SERVICE: depends on OUT_OF_SERVICE property
Event_State NORMAL
Out_Of_Service Indication whether (TRUE) or not (FALSE) the physical output that the object represents is not in service
Units Measure unit set by tool
MinPresValue Min value of PRESENT_VALUE
MaxPresValue Max value of PRESENT_VALUE
Resolution Depends on measure unit
Priority_Array Array of prioritized values
Relinquish_Default Is the default value to be used for the PRESENT_VALUE property when all command property values in the PRIORITY_ARRAY have a null value
COV_Increment Minimum change in PRESENT_VALUE that will cause a COVNotification
OBJECT_ANALOG_VALUE
Name Description
Object_identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_ANALOG_VALUE
Present_Value the current value of the analog value
Description Assigned automatically by the tool
Represents the general health of analogue value; Three of the flags are associated with the values of other properties; Flag IN_ALARM: False if communication OK, True if
Status_Flag communication error; Flag FAULT: False (fixed value); Flag OVERRIDDEN: False (fixed value); Flag OUT_OF_SERVICE: depends on OUT_OF_SERVICE property
Event_State NORMAL
Out_Of_Service Always FALSE
Units Measure unit set by tool
Priority_Array Array of prioritized values
Relinquish_Default Is the default value to be used for the PRESENT_VALUE property when all command property values in the PRIORITY_ARRAY have a null value
COV_Increment Minimum change in PRESENT_VALUE that will cause a COVNotification

OBJECT_BINARY_INPUT
Name Description
Object_identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_BINARY_INPUT
Present_Value Indicates the current value of the binary input being measured
Description Assigned automatically by the tool
Device_Type Home part number by the tool
Represents the general health of binary input; Three of the flags are associated with the values of other properties; Flag IN_ALARM: False if communication OK, True if
Status_Flag communication error; Flag FAULT: False (fixed value); Flag OVERRIDDEN: False (fixed value); Flag OUT_OF_SERVICE: depends on OUT_OF_SERVICE property
Event_State NORMAL
Out_Of_Service Indication whether (TRUE) or not (FALSE) the physical input that the object represents is not in service
Polarity Indicates the relationship between the physical state of the Input and the logical state represented by the PRESENT_VALUE property
Elapsed_Active_Time Indicates the accumulated number of seconds that the PRESENT_VALUE property has had the value ACTIVE
Time_Of_Active_Time_Reset Represents the actual datetime at which the ELAPSED_ACTIVE_TIME was set to 0
OBJECT_BINARY_OUTPUT
Name Description
Object_Identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_BINARY_OUTPUT
Present_Value Indicates the current value of the binary output
Description Assigned automatically by the tool
Device_Type Assigned automatically by the tool
Represents the general health of output; Three of the flags are associated with the values of other properties; Flag IN_ALARM: False if communication OK, True if
Status_Flag communication error; Flag FAULT: False (fixed value); Flag OVERRIDDEN: False (fixed value); Flag OUT_OF_SERVICE: depends on OUT_OF_SERVICE property
Event_State NORMAL
Out_Of_Service Indication whether (TRUE) or not (FALSE) the physical output that the object represents is not in service
Polarity Indicates the relationship between the physical state of the output and the logical state represented by the PRESENT_VALUE property
Elapsed_Active_Time Indicates the accumulated number of seconds that the PRESENT_VALUE property has had the value ACTIVE
Time_Of_Active_Time_Reset Represents the actual datetime at which the ELAPSED_ACTIVE_TIME was set to 0
Priority_Array Array of prioritized values
Relinquish_Default Is the default value to be used for the PRESENT_VALUE property when all command property values in the PRIORITY_ARRAY have a null value
COV_Increment Minimum change in PRESENT_VALUE that will cause a COVNotification

OBJECT_BINARY_VALUE
Name Description
Object_Identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_BINARY_VALUE
Present_Value Indicates the current value of the binary value
Description Assigned automatically by the tool
Device_Type Home part number by the tool
Represents the general health of input; Three of the flags are associated with the values of other properties; Flag IN_ALARM: False if communication OK, True if communication
Status_Flag error; Flag FAULT: False (fixed value); Flag OVERRIDDEN: False (fixed value); Flag OUT_OF_SERVICE: depends on OUT_OF_SERVICE property
Event_State NORMAL
Out_Of_Service Always FALSE
Elapsed_Active_Time Indicates the accumulated number of seconds that the PRESENT_VALUE property has had the value ACTIVE
Time_Of_Active_Time_Reset Represents the actual datetime at which the ELAPSED_ACTIVE_TIME was set to 0
Priority_Array Array of prioritized values
Relinquish_Default Is the default value to be used for the PRESENT_VALUE property when all command property values in the PRIORITY_ARRAY have a null value
COV_Increment Minimum change in PRESENT_VALUE that will cause a COVNotification
OBJECT_CALENDAR
Name Description
Object_Identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_CALENDAR
Indicates the current value of the calendar. TRUE if the current date is in the Date_List
Present_Value and FALSE if it is not
Description Assigned automatically by the tool
This property is a List of BACnetCalendarEntry, each of which is either a specific date or date pattern (Date), range of dates
(BACnetDateRange), or month/week-of-month/day-of-week specification (BACnetWeekNDay). If the current date matches the calendar entry criteria,
Date_List the present value of the Calendar object is TRUE.

OBJECT_COMMAND
Name Description
Object_Identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_COMMAND
The Present_Value may be written to with any value from 0 to the maximum number of actions supported by the Action
Present_Value property
Description Assigned automatically by the tool
In_Process This property, of type BOOLEAN, is set to TRUE when a value is written to the Present_Value property
This property, of type BOOLEAN, indicates the success or failure of the sequence of actions that are triggered when the
All_Writes_Successful Present_Value property is written to
This property, of type BACnetARRAY of BACnetActionList, specifies an array of "action lists". These action lists are
Action indexed by the value that is written to the Present_Value property
OBJECT_DEVICE
Name Description
Object_Identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_DEVICE
System_Status Reflects the current physical and logical status of the Device
Vendor_Name Carlo Gavazzi Controls SPA
Vendor_Identifier 388
Model_Name UWP30RSExxx
Firmware_Version Rev 0.1.0
Application_Software_Version SW000H00 Rxyz BACnet
Description UWP30RSExxx Smart Building Web
Protocol_Version Fixed 1
Protocol_Revision Fixed 10
READ_PROP; READ_MULTIPLE_PROP; WRITE_PROP; WRITE_MULTIPLE_PROP; I-AM; I-HAVE; UNCONF_COV_NOTIFICATION; WHO-HAS;
Protocol_Services_Supported WHO-IS; CONF_CONV_NOTIFICATION; SUBSCRIBE_COV_PROP;DEVICE_COMMUNICATION_CONTROL
OBJECT_ANALOG_INPUT OBJECT_ANALOG_OUTPUT OBJECT_BINARY_INPUT OBJECT_BINARY_OUTPUT OBJECT_BINARY_VALUE
Protocol_Object_Types_Supported OBJECT_ANALOG_VALUE OBJECT_MULTI_STATE_INPUT OBJECT_MULTI_STATE_OUTPUT OBJECT_BITSTRING_VALUE OBJECT_DEVICE
Object_List Is the List of all object in the System
Max_ADPU_Length_Accepted Is the maximum number of octets that may be contained in a single, indivisible application layer protocol data unit
Segmentation_Supported Segmented-both
Max_Segments_Accepted 1476
Local_Time Time of day
Local_Date Date
ADPU_Segment_Timeout 2000 ms
ADPU_Timeout 3000 ms
Number_Of_ADPU_Retries 5
Device_Address_Binding Always empty in this product version
Database_Revision Revision 0
Is a list of BACnetCOVSubscription, each of which consists of a Recipient, a Monitored Property 2 Issue Confirmed Notifications flag, a Time Remaining value and an
Active_COV_Subscriptions optional COV Increment
OBJECT_MULTI_STATE_INPUT
Name Description
Object_Identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_MULTI_STATE_INPUT
Present_Value Indicates the current value of the input being measured
Description Assigned automatically by the tool
Device_Type Home part number by the tool
Represents the general health of the input; Three of the flags are associated with the values of other properties; Flag IN_ALARM: False if communication OK, True if
Status_Flag communication error; Flag FAULT: False (fixed value); Flag OVERRIDDEN: False (fixed value); Flag OUT_OF_SERVICE: depends on OUT_OF_SERVICE property
Event_State NORMAL
Out_Of_Service Indication whether (TRUE) or not (FALSE) the physical input that the object represents is not in service
Number_Of_States Defines the number of states that the PRESENT_VALUE may have
State_Text This property is a BACnetARRAY of character strings representing descriptions of all possible states of the Present_Value

OBJECT_MULTI_STATE_OUTPUT
Name Description
Object_Identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_MULTI_STATE_OUTPUT
Present_Value Indicates the current value of the output
Description Assigned automatically by the tool
Device_Type Home part number by the tool
Represents the general health of analogue input; Three of the flags are associated with the values of other properties; Flag IN_ALARM: False if communication OK, True if
Status_Flag communication error; Flag FAULT: False (fixed value); Flag OVERRIDDEN: False (fixed value); Flag OUT_OF_SERVICE: depends on OUT_OF_SERVICE property
Event_State NORMAL
Out_Of_Service Indication whether (TRUE) or not (FALSE) the physical output that the object represents is not in service
Number_Of_States Defines the number of states that the PRESENT_VALUE may have
State_Text This property is a BACnetARRAY of character strings representing descriptions of all possible states of the Present_Value
Priority_Array Array of prioritized values
Relinquish_Default Is the default value to be used for the PRESENT_VALUE property when all command property values in the PRIORITY_ARRAY have a null value

OBJECT_BITSTRING_VALUE
Name Description
Object_Identifier Assigned automatically by the tool
Object_Name Assigned automatically by the tool
Object_Type OBJECT_BITSTRING_VALUE
Present_Value Indicates the current value of the object
Description Assigned automatically by the tool
Device_Type Home part number by the tool
Represents the general health of analogue input; Three of the flags are associated with the values of other properties; Flag IN_ALARM: False if communication OK, True if
Status_Flag communication error; Flag FAULT: False (fixed value); Flag OVERRIDDEN: False (fixed value); Flag OUT_OF_SERVICE: depends on OUT_OF_SERVICE property
Event_State NORMAL

You might also like