You are on page 1of 16

A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

STRUCTURAL DRAWINGS LIST 2

S.No. DWG. NO. TITLE


GENERAL DETAILS
3
1 S-000 STRUCTURAL DRAWINGS LIST 3

2 S-001 GENERAL NOTES - 1 OF 2

3 S-002 GENERAL NOTES - 2 OF 2

4 S-003 GENERAL DETAILS - 1 OF 5

5 S-004 GENERAL DETAILS - 2 OF 5


4 4

6 S-005 GENERAL DETAILS - 3 OF 5


7 S-006 GENERAL DETAILS - 4 OF 5
8 S-007 GENERAL DETAILS - 5 OF 5

COLUMNS & WALLS


5
9 S-101 COLUMN LAYOUT AT FOUNDATION LEVEL 5

10 S-102 COLUMN LAYOUT AT GROUND FLOOR


10 S-102 COLUMN LAYOUT AT FIRST FLOOR

FOUNDATIONS
12 S-201 FOUNDATION LAYOUT
6 6

SLAB LAYOUT
13 S-301 GROUND FLOOR FRAMING LAYOUT

14 S-302 FIRST FLOOR FRAMING LAYOUT


REV

15 S-303 ROOF FLOOR FRAMING LAYOUT No.


DATE

PROJECT:
REVISIONS BY CHK APP

RUKAN DEVELOPMENT
7
SECTIONS & DETAILS WADI AL SAFA 7
PLOT NO: 6654283 (TH-50)
7

OWNER OF TITLE:

16 S-401 SECTION DETAILS DUBAI LAND L.L.C.


PURCHASER :

Continental Investments

CONSULTANT:

8 8

DRAWING TITLE :

STRUCTURAL DRAWING
LIST FOR BLOCK 3
REV No. DATE SCALE

JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-000 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

GENERAL NOTES - 01
1.0 GENERAL: MINIMUM PERIOD BEFORE STRIKING
3.2 REINFORCEMENT : ALL REINFORCEMENT SHALL COMPLY WITH BS4449 AND AS FOLLOWS TYPE OF FORMWORK
OPC MSRC/GGBS
1.1 ALL STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH SPECIFICATIONS, LANDSCAPE, 3.2.1 HIGH YIELD DEFORMED TYPE 2 BARS (DENOTED BY 'T') HAVING FY IS 460 N/MM²
ARCHITECTURAL, MECHANICAL, PLUMBING & ELECTRICAL DRAWINGS, AND ANY OTHER WRITTEN INSTRUCTIONS THAT
VERTICAL SIDES OF BEAMS, WALLS, COLUMNS, LIFT NOT EXCEEDING 1.2M. 24 HOURS 36 HOURS
MAY BE ISSUED DURING THE COURSE OF THE CONTRACT. 3.2.2 REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY, IT IS NOT NECESSARILY SHOWN IN TRUE POSITION.

1.2 ALL DIMENSIONS SHALL BE VERIFIED BY THE CONTRACTOR BEFORE CONSTRUCTION AND ON SITE. ANY DISCREPANCY 3.2.3 SUPPORT ALL SLAB REINFORCEMENT AT THE CORRECT LEVELS ON APPROVED BAR CHAIRS SPACED AT MAX. 700MM VERTICAL SIDES OF BEAMS, WALLS, COLUMNS, LIFT EXCEEDING 1.2M. 36 HOURS 60 HOURS

SHALL BE REPORTED TO THE ENGINEER FOR REMEDIAL MEASURE BEFORE COMMENCEMENT OF RELATED WORK. CENTERS BOTH WAYS.
SOFFIT OF MAIN SLABS AND BEAMS, (PROPS LEFT UNDER) 9 DAYS* 10 DAYS*
1.3 ALL DIMENSIONS ARE IN MILLIMETERS AND ALL LEVELS ARE IN METERS UNLESS NOTED OTHERWISE.
3.2.4 PRIOR TO EXECUTION AND DURING THE PROGRESS OF WORK. IF REQUIRED BY THE ENGINEER, CONTRACTOR SHALL

TEST THE CONCRETE AND STEEL WITHOUT ANY EXTRA COST.


1.4 DO NOT SCALE. THE DRAWING, REFER WRITTEN DIMENSIONS. REMOVAL OF PROPS - BEAMS AND MAIN SLABS AND OTHER WORK 18 DAYS 19 DAYS

1.5 IT IS THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN THE STRUCTURE DURING CONSTRUCTION IN A STABLE
2 2
CANTILEVER BEAMS AND SLABS 21 DAYS 21 DAYS
CONDITION AT ALL TIMES AND ASSUME THAT NO PART SHALL BE OVERSTRESSED. 3.3 CONTRACTOR SHALL BE RESPONSIBLE FOR THE QUALITY OF CONCRETE AND STEEL

1.6 THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER SETTING OUT OF WORKS, FOR CORRECTNESS OF POSITION,
3.4 LAB TRAIL MIX AND PLANT TRIAL MIX SHALL BE CONDUCTED AND APPROVED BY ENGINEER * CONCRETE CUBE STRENGTH SHALL ATTAIN 100% OF DESIGN COMPRESSIVE STRENGTH.
LEVELS AND ALIGNMENTS OF ALL PARTS OF THE WORK, AND FOR QUALITY AND FINAL FINISHES AT ANY TIME

DURING THE PROGRESS OF WORKS.


3.5 AGGREGATES: 3.13.4 STRIKING OF FORMWORK SHALL BE DONE WITH WRITTEN APPROVAL FROM ENGINEER/CONSULTANT.
1.7 IF ANY ERROR IS DETECTED IN ANY PART, THE CONTRACTOR SHALL RECTIFY IT AT HIS OWN EXPENSE. THE
TO CONFORM TO B.S 5328 AND B.S 812 PART 101 & 102 AND SHALL BE TESTED IN APPROVED LABORATORY. 4.0 BLOCK WORKS:
CHECKING/APPROVAL DONE BY THE ENGINEER SHALL NOT IN ANY WAY RELIEVE THE CONTRACTOR FROM HIS

RESPONSIBILITIES.
3.6 WATER: 4.1 BLOCKS:
1.8 IN CASE OF DISCREPANCIES IN DETAILS OR MISSING DETAILS, THE ENGINEER SHALL BE APPROACHED FOR
DEWA WATER TO BE USED. ANY OTHER WATER TO BE SUBJECT TO TESTING AND SUBSEQUENT APPROVAL. WATER TO BE CLEAN, FREE FROM ORGANIC MATTER, ALKALI, SALTS AND OTHER DELETERIOUS ALL BLOCKS USED SHALL COMPLY WITH LOCAL GOVERNMENT ORDER AND ADMINISTRATIVE REGULATIONS.
DECISION PRIOR TO TAKING ANY ACTION. THE ENGINEERS DECISION SHALL BE FINAL WITHOUT ANY EXTRA CLAIMS. IMPURITIES AND TO THE REQUIREMENTS OF B.S 3148, TEST TO B.S 3148.
4.2 CONC. BLOCKS:
1.9 ANY DETAIL PROVIDED SHALL TAKE PRECEDENCE OVER GENERAL DRAWINGS
CONCRETE BLOCKS BELOW GROUND LEVEL SHALL BE MADE FROM MSRC TO B.S 4027 HAVING MIN. AVERAGE
3 3
1.10 DETAIL RCC SHOP DRAWINGS 3.7 WORKMANSHIP: COMPRESSIVE STRENGTH OF 10 N/mm2.
DETAIL R.C. SHOP DRAWINGS AND BAR BENDING SCHEDULES SHALL BE PREPARED BY THE CONTRACTOR AND SUBMITTED AS DEFINED IN THE CONTRACT. WORK SHALL NOT COMMENCING UNTIL
REVIEWED AND ACCEPTED. REVIEW OF THESE DRAWINGS DOES NOT ALLEVIATE THE CONTRACTOR'S RESPONSIBILITIES.
4.3 MORTAR:
THE CODE OF PRACTICE FOR CONCRETE WORK IS TO BE IN COMPLIANCE WITH THE REQUIREMENTS OF B.S 8110, SECTION-6.

3.8 TESTING AND ACCEPTABLE LIMITS: 4.3.1 FOR USE OF BELOW GROUND SHALL BE MADE WITH MSRC CEMENT IN PROPORTION OF ONE PART CEMENT TO THREE

PARTS SAND AND SHALL COMPLY WITH SPECIFICATION.


2.0 FOUNDATION:
3.8.1 CHLORIDE CONTENT IN CONCRETE FROM ALL SOURCES INCLUDING CEMENT, AGGREGATES, WATER, ADMIXTURES
4.3.2 FOR USE OF ABOVE GROUND SHALL BE MADE WITH O.P CEMENT IN PROPORTION OF 1 PART CEMENT TO 3 PARTS LIME
ETC. SHALL NOT EXCEED LESSER OF 0.02% BY WEIGHT OF COARSE AGGREGATE OR 0.03%BY WEIGHT OF FINE
AND 9 PARTS SAND AND SHALL COMPLY WITH SPECIFICATION.
AGGREGATE, OR 0.1%BY WEIGHT OF CEMENT IN THE MIX.
2.1 REFER RELEVANT FOUNDATION DRAWING FOR EXCAVATION
4.4 ALL BLOCKS USED FOR LOAD BEARING WALLS SHALL BE TOP CLOSED CONCRETE BLOCKS COMPLYING TO LOCAL ORDERS.
3.8.2 SULPHATE CONTENT IN CONCRETE MIX - IN FORM OF SO3 FROM ALL SOURCES SHALL NOT EXCEED LESSER OF 0.4% BY

2.2 THE FOUNDATION SHALL BE CONSTRUCTED ON PLAIN CONCRETE ( GRADE C20 ) LAYER OF 100 mm THICK BLINDING WEIGHT OF AGGREGATES OR 4.0% BY WEIGHT OF CEMENT IN THE MIX.
4.5 CONSTRUCT WALLS WITH MORTAR FULLY BONDED OR TIED TOGETHER TO ENSURE DESIGN REQUIREMENTS FOR
CONCRETE AND EXTENDING 100mm FROM BOTH SIDES. STABILITY, STRENGTH, FIRE RESISTANCE, THERMAL AND SOUND INSULATION.
3.8.3 CONCRETE TESTING:
2.3 ANY AREA IF OVER EXCAVATED OR POCKETS OF SOIL UNDER THE FOUNDATIONS ARE TO BE FILLED WITH PCC TO ATTAIN * TO BE IN ACCORDANCE TO BS 5328
4.6 BLOCK WORK SHALL BE ANCHORED TO R.C. COLUMNS, BASES AND SOFFITS OF R.C. MEMBERS BY APPROVED G.I. TIES
THE REQUIRED LEVEL. * TO BE CARRIED OUT BY APPROVED LABORATORY
AND ANCHORS TO ENGINEERS APPROVAL.
4 4
2.4 THE CONTRACTOR SHALL BE ENTIRELY RESPONSIBLE FOR ENSURING THAT THE EXCAVATIONS ARE SUITABLE,
3.9 PROTECTION OF STEEL WORK:
SAFE AND STABLE. (i.e. TEMPORARY WORKS) ALTHOUGH SUCH PRECAUTIONS MAY HAVE ALREADY BEEN REVIEWED IN 4.7 IN CASE OF PANEL WALLS EXCEEDING 14 SQ.MT. REINFORCED BLOCK COLUMNS SHALL BE INTRODUCED 200mm WIDE

PRINCIPLE BY THE ENGINEER. WITH T12 IN EACH CAVITY AND 6mm DIA. TIES AT 200 AND BLOCK CAVITY SHALL BE FILLED WITH CONCRETE.
REINFORCEMENT TO BE PROTECTED FROM CORROSIVE EFFECTS OF HUMID AIR, WATER & DUST AND KEPT CLEAR OF GROUND.
STARTER BARS AND EXPOSED REINFORCEMENT BARS TO BE SUITABLY PROTECTED BY APPLYING 'ZINKRICH' PRIMER OR
2.5 THE CONTRACTOR SHALL BE TAKE FULL ACCOUNT OF THE SOIL INVESTIGATION INFORMATION AND HIS OWN 4.8 ALL BLOCK WORK PANELS WITHOUT A TOP R.C.C MEMBER SHALL BE PROVIDED WITH 100 THK. R.C COPING BEAM WITH 2
EQUIVALENT TO APPROVAL.
EXPERIENCE TO DESIGN THE NECESSARY TEMPORARY WORKS. THE DESIGN TOGETHER WITH THE SHOP DRAWINGS T10 TOP & BTM. 6mm DIA. TIES AT 200.
SHALL BE SUBMITTED FOR THE ENGINEER'S APPROVAL PRIOR TO DEWATERING. ALL BACKFILLING SHALL BE COMPACTED 3.10 CURING AND PROTECTION OF CONCRETE:
4.9 LOAD BEARING WALLS TO BE DESIGNED AND CONSTRUCTED AS PER B.S 5628.
TO AT LEAST 98% OF THE MAXIMUM DENSITY AND IN ACCORDANCE WITH THE SPECIFICATION.
3.10.1 CURING:
4.10 MORTAR ADMIXTURE SHALL BE TO APPROVAL. USE OF ADMIXTURES CONTAINING CALCIUM CHLORIDE IS PROHIBITED.
2.6 IT SHALL REMAIN THE CONTRACTOR'S OBLIGATION TO PROVIDE DRY WORKING CONDITIONS BY ANY
FRESH CONCRETE SHALL BE IMMEDIATELY COVERED WITH IMPERVIOUS SHEET MATERIAL (POLYTHENE 500 G. OR SIMILAR)
PLASTICISERS CONFORMING TO B.S.4887 SHALL BE USED ON WRITTEN APPROVAL. PROLAPIN 431 OR EQUIVALENT SHALL
MEANS HE MIGHT SEE EFFECTIVE AND UTILIZING THE INSTALLED DEWATERING SYSTEM. EXCAVATION SHALL
AS SOON AS CONCRETE HAS SET OR UPON STRIKING THE FORM WORK, COVER THE SURFACE WITH ABSORBENT MATERIAL
BE USED THE PROPORTION SHALL BE AS RECOMMENDED BY THE MANUFACTURER.
BE AT ALL TIMES CARRIED OUT IN DRY CONDITIONS. GROUND WATER SHALL BE MAINTAINED AT LEAST 500mm
KEPT CONTINUOUSLY DAMP FOR A PERIOD OF 7 DAYS.
BELOW THE DEEPEST POINT IN THE EXCAVATION WHILE IT REMAINS OPEN. DEWATERING SHALL NOT BE DISCONTINUED
4.11 MIXING OF MORTAR:
WITHOUT THE WRITTEN AGREEMENT OF THE ENGINEER. 3.10.2 PROTECTION: MORTAR SHALL BE MIXED BY MECHANICAL MIXER. THE DRY COMPONENTS EXCLUDING WATER AND PLASTICISERS SHALL

2.7 ALL FOUNDATION AND SUB STRUCTURE CONCRETE SHALL BE PROTECTED WITH WATER-PROOFING SYSTEM AS PER BE MIXED JUST PRIOR TO USE. AVOID OVER MIXING, AFTER ADDING THE PLASTICISERS MORTAR SHALL BE USED WITHIN
THE SURFACE SHALL BE PROTECTED AGAINST RAIN, SUN, WIND, PHYSICAL DAMAGES, IMMATURE CONCRETE FROM
MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS AND SHALL COMPLIES WITH PROJECT SPECIFICATION 30 MINUTES OF MIXING SUBJECT TO INSPECTION TO ENSURE THAT THE INITIAL SET OF MORTAR HAS NOT TAKEN PLACE.
5 PHYSICAL SHOCK OR MOVEMENT AND THERMAL SHOCK FROM COLD WATER. 5

4.12 ACCESSORIES AND SUNDRY ITEMS FOR MASONRY:


3.11 DAMP PROOF MEMBRANES AND COATINGS:

4.12.1 TIES FOR BOUNDING WALLS TO CONCRETE SHALL CONFORM TO B.S.1243 AND SHALL BE STAINLESS STEEL BUTTERFLY
3.11.1 POLYTHENE SHEET : 1000 G. TO APPROVAL.
TYPE 1 OR STRIPS OF STAINLESS STEEL EXPANDED STEEL MESH.

3.11.2 COLD APPLIED ASPHALT COMPOUND : TO BE MODIFIED BITUMEN WITH 12% LATEX CONTENT N.P 120 FROM
4.12.2 MOVEMENT JOINT FILLERS SHALL BE BITUMEN IMPREGNATED FIBRE BOARD "HYDROCELL" OR EQUIVALENT T'O APPROVAL.
FOSROC OR EQUIVALENT TO APPROVAL. RATE OF APPLICATION TO MANUFACTURERS RECOMMENDATION TO BE APPLIED

TO ALL UNDERGROUND SURFACES AND SHALL COMPLY WITH SPECIFICATION. 4.13 CURING:

ALL BLOCK WORK SHALL BE CONTINUOUSLY CURED FOR 7 DAYS WITHOUT DRYING. THE NEWLY CONSTRUCTED WALLS
3.11.3 DAMP PROOF COURSE CONSISTING OF ONE LAYER OF TROPICAL QUALITY BITUMENISED FIBRE FELT COMPLYING
SHALL BE PROTECTED FROM EXTREME WEATHER CONDITIONS.
WITH TYPE B OF B.S 73, WEIGHING NOT LESS THAN 3.3kg PER SQ.MT SHALL BE PROVIDED AT THE GROUND LEVEL AND
PLINTH LEVEL AND SHALL COMPLY WITH SPECIFICATION.
5.0 REINFORCEMENT NOTES:
3.12 GENERAL NOTES FOR R.C.C. WORKS:
5.1 HOOKS AND BENDS:
3.12.1 REFER ARCHITECTURAL, LANDSCAPE, MECHANICAL, AND ELECTRICAL DRAWINGS FOR OPENINGS AND SLEEVES
a) STANDARD HOOKS:
6
IN CONCRETE SLABS AND WALLS NOT SHOWN ON STRUCTURAL DRAWINGS AND FOR SIZE & LOCATION OF OPENING NOT 6
DIMENSIONED. THE TERM "STANDARD HOOK" AS USED IN THIS DWG. SHALL MEAN ONE OF THE FOLLOWING:
1- 180-deg BEND PLUS (4 db) EXTENSION , BUT NOT LESS THAN 60 MM AT FREE END OF BAR.
3.0 REINFORCED CONCRETE WORKS: 3.12.2 ALL OPENINGS SHALL BE FORMED OR SLEEVED BEFORE PLACING CONCRETE.
2- 90-deg BEND PLUS (12 db) EXTENSION AT FREE END OF BAR.

3.12.3 NO OPENINGS OR SLEEVES MORE THAN 75 MM SHALL BE PLACED IN BEAMS OR COLUMNS EXCEPT AS INDICATED 3- FOR STIRRUPS AND TIE HOOKS (T16 BAR AND SMALLER), 90-deg BEND PLUS 6 db EXTENSION AT FREE END OF BAR.
3.1 CONCRETE GRADE AND CLEAR COVER 4- FOR HOOPS (T16 BAR AND SMALLER), 135-deg BEND PLUS AN EXTENSION AT LEAST (6 db), BUT NOT LESS THAN
MAX. WATER ON THE STRUCTURAL DRAWINGS. OPENINGS OR SLEEVES LESS THAN 75 MM SHALL BE EXACTLY LOCATED ON SHOP
ELEMENT SUBSTRUCTURE SUPERSTRUCTURE CEMENT MAX. SLUMP
DRAWINGS AND APPROVED BY THE ENGINEER. 75MM AT FREE END OF BAR.
RATIO
MIN. CLEAR MIN. CLEAR NOTE : HOOP IS A CLOSED TIE OR CONTINUOUSLY WOUND TIE.
MIN. CEMENT COVER MIN. CEMENT COVER
GRADE 3.12.4 PROVIDE ALL NECESSARY INSERTS, CLIPS, ANCHORS, TIES, REGLETS AND OTHER FASTENING DEVICES AS REQUIRED
GRADE
CAST INTO CONCRETE. b) MINIMUM BEND DIAMETERS:
TYPE KG/M³ MM TYPE KG/M³ MM MM

C40 TYPE - 1 420 50 C40 TYPE - 2 420 40 0.35 150±25 1- DIAMETER OF BEND MEASURED ON THE INSIDE OF THE BAR, OTHER THAN FOR STIRRUPS AND TIES IN SIZES T10
BEAMS 3.12.5 PROVIDE CONCRETE PADS, CURBS AND OTHER SUPPORTING CONCRETE FOR ARCHITECTURAL, LANDSCAPING,
THROUGH T16, SHALL NOT BE LESS THAN THE VALUES IN TABLE (1). REV
420 C40 MECHANICAL, AND ELECTRICAL EQUIPMENT AND INSTALLATIONS AS REQUIRED. REFER ARCHITECTURAL, LANDSCAPING, DATE REVISIONS BY CHK APP
SLABS / STAIRS C40 TYPE - 1 50 TYPE - 2 420 25 0.35 150±25 No.
MECHANICAL AND ELECTRICAL DWG. FOR SIZE & LOCATION OF PADS, CURBS AND OTHER NON-STRUCTURAL CONCRETE PROJECT:
2- INSIDE DIAMETER OF BEND FOR STIRRUPS AND TIES SHALL NOT BE LESS THAN (4 dp) FOR T16 BAR AND SMALLER.
SLAB ON GRADE C20 TYPE - 1 370 50 0.35 150±25
- - - - ELEMENTS. REFER TYPICAL DETAILS ON STRUCTURAL DRAWINGS FOR REINFORCING AND OTHER CONSTRUCTION DETAILS.
FOR BARS LARGER THAN T16, DIAMETER OF BEND SHALL BE IN ACCORDANCE WITH TABLE (1). RUKAN DEVELOPMENT
COLUMNS C40 TYPE - 1 420 50 C40 TYPE - 2 450 40 0.35 150±25
7 3.12.6 SURFACE OF CONCRETE CONSTRUCTION JOINTS SHALL BE CLEANED AND LAITANCE REMOVED.
TABLE(1)-MINIMUM DIAMETER OF BEND WADI AL SAFA 7 7

C40 TYPE - 1 420 50 C40 TYPE - 2 450 50 0.35 150±25


WALLS AT WATER FACE # PLOT NO: 6654283 (TH-50)
3.12.7 CONSTRUCTION JOINTS SHALL BE SO MADE AND LOCATED AS NOT TO IMPAIR THE STRENGTH OF THE STRUCTURE. BAR SIZE MINIMUM DIAMETER OF BEND
RETAINING WALLS C40 TYPE - 1 420 50 C40 TYPE - 2 450 50 0.35 150±25 OWNER OF TITLE:

3.12.8 THE MAXIMUM PERMISSIBLE TEMPERATURE OF ANY CONCRETE MIX AT POINT OF PLACEMENT SHALL BE 32 DEGREES T10 THROUGH T25
C40 TYPE - 1 420 50 C40 TYPE - 2 450 25 0.35 150±25 6 db
WALLS / CORE WALL

C40 TYPE - 1 420 C40 TYPE - 2 450 25 0.35 150±25


AS SAID IN ITEM 3.1. DUBAI LAND L.L.C.
FOOTING 50 T28 THROUGH T32 8 db
3.12.9 A 1000 GAUGE POLYTHENE SHEET SHALL BE PROVIDED BELOW PCC.
BLINDING C20 TYPE - 1 280 - - - - - 0.52 150±25 BAR DIA. db BAR DIA. db PURCHASER :
135
3.12.10 LINTEL TO BE ADDED FOR WALLS AT A HEIGHT EQUAL TO DOOR HEIGHT. FOR LINTEL DIMENSIONS AND REINFORCEMENT,
LIGHT WEIGHT FOAM CONCRETE (MAX. DENSITY - 8KN/M³) - FOR ROOF BEDDING AS PER SPEC.
REFER TO STANDARD DETAILS.
CONCRETE SCREED (MAX. DENSITY-18KN/M³)-FOR ALL OTHER WORKS C35 TYPE - 2 375 -
3.12.11 ALL EXPOSED EDGES AND EXPOSED INTERNAL ANGLES OF CONCRETE STRUCTURES SHALL HAVE CHAMFERS OF
BEND DIA.
BEND DIA.
Continental Investments
BAR DIA. db
MINIMUM 20MMX20MM.
12 db 6 db
# THE CONCRETE SHALL BE WATER TIGHT CONCRETE BY ADDING PUDLO ADMIXTURES OR EQUIVALENT IF NOT AVAILABLE / CONSULTANT:
3.13 FORM WORKS BEND DIA.
PLASTICISERS TO APPROVAL
3.13.1 ALL FORMS SHALL BE REMOVED WITHOUT DAMAGE TO THE CONCRETE. 6 db
- MAXIMUM TEMPERATURE OF FRESH CONCRETE AT SITE SHALL BE 30° ± 2°C AND MINIMUM TEMPERATURE SHALL BE 9° ± 2°
8 8
AND SHALL COMPLY WITH SPECIFICATION. (75MM MIN. FOR HOOPS)
3.13.2 BEFORE SOFFIT FORMS AND PROPS ARE REMOVED, THE CONCRETE SHALL BE EXPOSED BY REMOVAL OF THE SIDE 4 db (60MM MIN)
- TYPE - 1 MIX SHALL BE OPC (46%) + GGBS (50%) + MICRO SILICA (4%) AS PER SPEC, CEMENT TYPE SHALL BE AS PER FORMS OR OTHERWISE AS REQUIRED BY THE ENGINEER, IN ORDER TO ENSURE THAT IT HAS SUFFICIENTLY HARDENED. STANDARD HOOKS FOR REINFORCEMENT STANDARD HOOKS FOR STIRRUPS, TIES, DRAWING TITLE :
SOIL INVESTIGATION REPORT RECOMMENDATION. 3.13.3 MINIMUM PERIOD BEFORE STRIKING FORMWORK. OTHER THAN STIRRUPS, TIES, AND HOOPS. AND HOOPS.

- TYPE - 2 MIX SHALL BE OPC (40%) + GGBS (60%) AS PER SPEC, CEMENT TYPE SHALL BE AS PER GENERAL NOTES -
SOIL INVESTIGATION REPORT RECOMMENDATION.
1 OF 2 FOR BLOCK 3
REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-001 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

GENERAL NOTES - 02
5.2 DEVELOPMENT LENGTH, Ld: 7.0 ABBREVIATIONS:

UNLESS NOTED OTHERWISE ON THE DRAWINGS, DEVELOPMENT LENGTH (Ld) 7.1 GENERAL: FINISH SYMBOL
SHALL BE AS FOLLOWS : GROOVE ANGLE, INCLUDED ANGLE OF COUNTERSUNK FOR PLUG WELDS
CONTOUR SYMBOL
TABLE-2 : DEVELOPMENT LENGTH OF DEFORMED BARS AND DEFORMED WIRE IN TENSION, Ld
ARCH ARCHITECTURAL MM MILLIMETRE
ROOF OPENING, DEPTH OF FILLING FOR PLUG AND SLOT
2 BAR DIAMETER, db (MM). 6 8 10 12 16 18 20 25 28 32 @ AT MIN MINIMUM WELDS 2
LENGTH OF WELDS
B.O.F. BOTTOM OF FOOTING MPA MEGA PASCAL
CLEAR SPACING OF BARS BEING EFFECTIVE THROAT
B/W BOTH WAYS M METRE F PITCH (CENTER TO CENTER SPACING) OF WELDS
DEVELOPED OR SPLICED NOT
CL DEPTH OF PREPARATION, SIZE OR STRENGTH FOR CERTAIN WELDS
LESS THAN db, CLEAR COVER CENTER LINE N.T.S. NOT TO SCALE
A
300 360 450 540 720 810 910 1140 1270 1460
NOT LESS THAN db, STIRRUPS C/C CENTER TO CENTER NO NUMBER ) FIELD WELD SYMBOL
R
OR TIES THROUGHOUT Ld NOT
DWG DRAWING OC ON CENTERS ARROW CONNECTING REFERENCE LINE TO ARROW SIDE MEMBER
LESS THAN THE CODE MINIMUM SPECIFICATION PROCESS, OR OTHER REFERENCES { }
SIDE OF JOINT
DIA DIAMETER PVT LVL PAVEMENT LEVEL S (E) OTHER L-P
OR SIDES) (
T
CLEAR SPACING OF BARS BEING DMD DM DATUM R RADIUS
{ )
DEVELOPED OR SPLICED NOT DN DOWN RL ROAD LEVEL }
LESS THAN 2db AND CLEAR TAIL (TAIL OMITTED WHEN REFERENCE IS NOT USED) (BOTH
ELEC ELECTRICAL RC RIENFORCED CONCRETE SIDE
COVER NOT LESS THAN db ARROW
(
ELEV ELEVATION RW RETAINING WALL (N)
3 NUMBER OF SPOT OR PROJECTION WELDS WELD ALL AROUND SYMBOL 3
OTHER CASES 330 440 550 660 880 980 1370 1710 1910 2180 EQ EQUAL STIRR STIRRUPS

EGL / NGL EXISTING / NATURAL GROUND LEVEL SCHED SCHEDULES REFERENCE LINE

EXT EXTERNAL SEC SECTION BASIC WELD SYMBOL OF DETAIL REFERENCE


TABLE-3 : DEVELOPMENT LENGTH OF DEFORMED BARS IN COMPRESSION, Ld
FGL FINISHED GROUND LEVEL SMD SM DATUM ELEMENTS IN THIS AREA REMAIN AS SHOWN
WHEN TAIL AND ARROW ARE REVERSED
BAR DIAMETER, db (MM) 6 8 10 12 16 18 20 25 28 32 FIG FIGURE SWL SIDE WALK LEVEL

HOR. HORIZONTAL TYP TYPICAL


DEVELOPMENT LENGTH, Ld (MM) 200 200 250 300 400 450 500 625 700 800
INT INTERNAL T.O.F. TOP OF FOOTING
KPA KILO PASCAL T.O.W TOP OF WALL
NOTES : KN KILO NEWTON THK. THICK

1- IN TENSION SPLICE, FOR HORIZONTAL REINFORCEMENT SO PLACED THAT MORE THAN 300MM OF FRESH CONCRETE IS LONGL LONGITUDINAL T&B TOP AND BOTTOM
CAST IN THE MEMBER BELOW, VALUES OF Ld SHALL BE MULTIPLIED BY 1.3. MECH MECHANICAL U.N.O. UNLESS NOTED OTHERWISE

2- WELDED WIRE FABRIC MESH SHOULD BE LAPPED OVER ADJACENT SHEETS BY 300MM. MWP MEMBRANE WATERPROOFING. VAR VARIES, VARIABLE
MAX MAXIMUM VER VERTICAL
3- BARS SHALL BE SPLICED ONLY WHERE INDICATED, EXCEPT THAT BARS INDICATED CONTINUOUS MAY BE SPLICED AT

4 CONTRACTOR CONVENIENCE AND ACCORDING TO SPECIFICATIONS. SPLICE LOCATIONS FOR CONTINUOUS BARS SHALL 4
BE TENSION SPLICED U.N.O. 7.2 CONCRETE: OCT OCTAGONAL

PCC PLAIN CEMENT CONCRETE


4- FOR COLUMN AND SHEAR WALL TO FOOTING JUNCTION, TENSION LAP SPLICE SHALL BE USED B FLOOR OR ROOF BEAM
RECT RECTANGULAR
5- ALL PROVISIONS FOR BUNDLED BARS SHALL BE APPLIED TO BUNDLES BOC BOTTOM OF CONCRETE
S SLAB
6- WALL REINFORCEMENT SHALL NOT BE CUT WITHOUT APPROVAL OF ENGINEER/CONSULTANT. CONC CONCRETE
SW SHEAR WALL
C, COL COLUMN
6.0 STRUCTURAL STEEL (USING HOT ROLLED SECTIONS UNO): SSL STRUCTURAL SLAB LEVEL
CS CANTILEVER SLAB
SQ SQUARE
CB CANTILEVER BEAM
6.1 FABRICATION DRAWINGS: TOC TOP OF CONCRETE
CJ CONSTRUCTION JOINT
TB TIE BEAM
6.1.1 DETAILED STRUCTURAL STEEL SHOP DRAWINGS, CONNECTION DETAILS AND CALCULATIONS SHALL BE PREPARED BY
F FOOTING
TSSL TOP OF STRUCTURAL SLAB LEVEL
THE CONTRACTOR IN ACCORDANCE WITH BS5950-1:2000 AND SUBMITTED AS DEFINED IN THE CONTRACT. FABRICATION
FFL FINISHED FLOOR LEVEL
OR INSTALLATION SHALL NOT COMMENCE UNTIL REVIEWED AND ACCEPTED. REVIEW OF THESE DRAWINGS DOES NOT TOB TOP OF BEAM
Fcu CUBE STRENGTH
ALLEVIATE THE CONTRACTORS RESPONSIBILITIES. COORDINATE THE INPUT OF ALL TRADES ON THE SHOP DRAWINGS W WALL
FDN FOUNDATION
WF WALL FOOTING
6.2 DESIGN: GGBS GROUND GRANULATED BLAST FURNACE SLAG
5 5
6.2.1 ALL DESIGN O F STEEL WORKS SHALL BE IN ACCORDANCE WITH BS 5950-1:2000. ALL STEEL SHALL BE GRADE S275 TO MSRC MODERATE SULFATE RESISTING CEMENT

BS 5950-2 UNLESS NOTED OTHERWISE. MJ MOVEMENT JOINT

6.3 MATERIAL: 7.3 REINFORCEMENT:

LP LAP SPLICE LENGTH


6.3.1 ALL STRUCTURAL STEEL WORKS SHALL BE IN ACCORDANCE WITH BS 5950 AND BSEN 10025 . GRADE S275
ADD ADDITIONAL Ld DEVELOPMENT LENGTH
(PREVIOUSLY GRADE 43) SHALL BE PROVIDED EXCEPT WHERE NOTED.
B/W BOTH WAYS OEF ON EACH FACE

6.4 BOLTED CONNECTIONS: CONT CONTINUOUS, CONTINUED RFT REINFORCEMENT

db NOMINAL DIAMETER OF BAR REBAR REINFORCING BAR


6.4.1 ALL BOLTED CONNECTIONS SHALL BE FORMED USING GRADE 8.8 BOLTS UNLESS OTHERWISE NOTED.
DIR DIRECTION WWF WELDED WIRE FABRIC
6.4.2 MILD STEEL BOLTS AND NUTS SHALL COMPLY WITH THE REQUIREMENTS OF BS 5950 PART 1,BS 4190 AND BS 4320
Ø BAR DIAMETER
RESPECTIVELY.
FY YIELD STRENGTH

6.5 WELDING:
7.4 NOTATION FOR BEAM TYPES:
6.5.1 ALL WELDING SHALL BE TO BS-639
6 6
6.5.2 THE SUPERVISION AND TESTING OF WELDS SHALL BE DONE IN ACCORDANCE WITH BS-709
BEAM TYPE B2 (200 X 800)
6.5.3 ALL FILLET WELDS SHALL BE 6mm CONTINUOUS UNLESS OTHERWISE NOTED. ALL BUTT WELDS SHALL BE PREPARED FOR

FULL STRENGTH FULL PENETRATION WELDS UNLESS OTHERWISE NOTED.

6.5.4 ALL WELDS EXPOSED TO VIEW SHALL BE GROUND SMOOTH.


SERIAL NO. & WIDTH DEPTH
6.5.5 WHERE MOMENT CONNECTIONS ARE CALLED FOR BUT FORCES ARE NOT INDICATED, DESIGN CONNECTIONS FOR FULL
RFT. TYPE
MOMENT CAPACITY OF THE SMALLER MEMBER JOINED.

6.6 ACCURACY:

7.5 NOTATION FOR REINFORCEMENT:


6.6.1 THE CONTRACTOR IS RESPONSIBLE FOR ACCURACY IN FABRICATION AND ERECTION TO THE SPECIFIED TOLERANCES.

6.6.2 IT IS RECOMMENDED THAT THE TRIAL ASSEMBLY OF ALL STEELWORK COMPONENTS SHALL BE UNDERTAKEN PRIOR TO
REV
DISPATCHING TO SITE. DATE REVISIONS BY CHK APP
No.
15 T 20 - 125 - 01- B1
PROJECT:
6.7 DIMENSIONS:
T=TOP RUKAN DEVELOPMENT
NO OF BARS B=BOTTOM
7 6.7.1 THE CONTRACTOR SHALL VERIFY ALL SITE DIMENSIONS PRIOR TO THE START OF FABRICATION. WADI AL SAFA 7 7
NF=NEAR FACE
T - HIGH YIELD PLOT NO: 6654283 (TH-50)
6.8 PROTECTIVE SURFACE TREATMENT: STRENGTH BARS FF=FAR FACE
TYPE OF STEEL OWNER OF TITLE:
R - MILD STEEL EF=EACH FACE
6.8.1 THE STRUCTURAL STEEL PAINTWORK SURFACE TREATMENT SHALL BE AS STATED IN SPECIFICATION.
BAR MARK

6.9 ANCHOR BOLTS: DIA OF BARS IN MM SPACING OF BARS IN MM


DUBAI LAND L.L.C.
6.9.1 ALL ANCHOR BOLT USED SHALL BE OF GRADE 8.8 OTHER WISE UNLESS NOTED.
7.6 WELD SYMBOLS: PURCHASER :

6.9.2 ALL ANCHOR BOLTS SHALL NOT BE PAINTED. THREADED PORTION SHOULD BE OILED.

SUPPLEMENTARY SYMBOLS
Continental Investments
6.10 SPLICE CONNECTIONS:

WELD ALL FIELD MELT CONTOUR


6.10.1 SPLICES SHALL BE DESIGNED TO DEVELOP FULL CAPACITY OF THE MEMBER AT THE POINT OF THE SPLICE. MEMBERS
AROUND WELD THRU FLUSH CONVEX CONCAVE CONSULTANT:
SHALL NOT BE SPLICED AT POINTS OF MAXIMUM STRESS. NO SPLICES SHALL BE MADE UNLESS SHOWN ON THE DRAWINGS

OR REVIEWED AND AGREED BY THE ENGINEER.

8 8
6.10.2 THE CONTRACTOR SHALL SUBMIT, FOR APPROVAL, THE LOCATIONS OF ALL PROPOSED SPLICE CONNECTIONS AND SHALL

BE HELD RESPONSIBLE FOR THEIR DESIGN.


LOCATION OF ELEMENTS OF A WELDING SYMBOL
DRAWING TITLE :

GENERAL NOTES -
2 OF 2 FOR BLOCK 3
REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-002 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

GENERAL DETAILS - 01
1 1

0.33 (L2 OR L3)


0.5 L1 OR 0.25 L2 0.33 L2 OR 1.5 L1 GREATER 0.33 (L2 OR L3) 0.25 L3 0.25 L1 0.25 L1
GREATER GREATER COMPRESSION LAP GREATER COMPRESSION LAP COMPRESSION LAP
D OF SMALLER BAR-50Ø E OF SMALLER BAR-50Ø
OF SMALLER BAR-50Ø E E
D IS GREATER OF C
D C L1 OR L2 C C C
C D IS GREATER OF 0.25 L2 OR 1.0 L1 0.25 (L2 OR L3) 0.25 (L2 OR L3) C 0.20 L3 OR 50 Ø 0.20 L1 OR 50 Ø C 0.20 L1 OR 50 Ø
L1 OR L2 GREATER GREATER GREATER GREATER Ld Ld GREATER GREATER Ld

EFFECTIVE EFFECTIVE EFFECTIVE


D

ANCHORAGE-12Ø ANCHORAGE-12Ø ANCHORAGE-12Ø

B (SEE SCHED)
2 50 50 50 50 50 TENSION LAP 50 50 50 2
A A SPLICE- 50Ø A A
0.08 L1 0.08 L1
TENSION LAP 0.15 L2 0.08 L3
B B B TOP BARS (SEE SCHED.)
SPLICE- 50Ø 0.15 L2 0.15 L3
0.20 L1 0.20 L1 SLAB (WHERE OCCURS)
0.20 L1 0.20 L2 0.20 L2 0.20 L3 0.20 L3
STIRRUPS STIRRUPS STIRRUPS
STIRRUPS STIRRUPS STIRRUPS STIRRUPS STIRRUPS STIRRUPS STIRRUPS STIRRUPS G1+G2 H1+H2 G1+G2
H1+H2 G1+G2 G1+G2 H1+H2 G1+G2 G1+G2 H1+H2 G1+G2
L1 L2 L3 L1
T12 WEB BARS ON

D (SEE SCHED)
CANTILEVER SPAN INTERIOR SPAN END SPAN EF @250 (MAX.) VERT. SPACING IF
D ≥ 750
A-2 TYPICAL SIMPLY SUPPORTED BEAM DETAIL G1/H1
A-1 TYPICAL CONTINUOUS BEAM WITH CANTILEVER DETAIL - SCALE- NTS
G2/H2
- SCALE- NTS
3 NOTE: G1+G2 SPACING TO COMPLY WITH SEC 1-1 OF DWG S-005 3

BOTTOM BARS (SEE SCHED)


SCHEDULE OF BEAMS
STIRRUPS
BEAM SIZE IN MM BOTTOM REINFORCEMENT TOP REINFORCEMENT STIRRUPS T10-200
TYPE EXTRA @ EXTRA @ CONT. EXTRA @ DISCONT. SIDE BARS AT SUPPORT AT MIDSPAN REMARKS
AS PER ROOF LAYOUT
WIDTH DEPTH STRAIGHT MID SPAN SUPPORT SUPPORT O.E.F
A-3 TYPICAL BEAM SECTION
STRAIGHT - SCALE- NTS
(A) (B) (C) (D) (E) (F) OUTER INNER OUTER INNER
FFL

150
(G1) (G2) (H1) (H2)

125
CAMBER NOTES: SSL T10-200 150
1.UNLESS OTHERWISE INDICATED, PROVIDE MINIMUM CAMBER FOR BEAMS WITH SPAN IN EXCESS OF 6.00 M AS FOLLOWS:
CONTINUOUS BEAM - 2.5 MM PER M OF SPAN (i.e. A 10 M SPAN BEAM WILL HAVE 25 MM CAMBER AT MID SPAN)
SIMPLE BEAM - 3.0 MM PER M OF SPAN AT MIDSPAN.
4 2. CANTILEVER BEAM OF ANY SPAN SHALL BE PROVIDED WITH 5.0 MM CAMBER PER METER OF SPAN AT THE FREE END. RF SLAB AS PER 4

3. ANTICIPATED SHORTENING AND SETTLEMENT OF FORM SUPPORTS FOUNDATION WHILE CARRYING WET CONCRETE SHALL BE ADDED TO THESE CAMBERS. LAYOUT
TYPICAL SECTION OF A/C PLINTH

A TYPICAL BEAM ELEVATION AND SCHEDULE


- SCALE- NTS

0.25 L1 0.33 (L1 OR L2) 0.33 (L2 OR L1)


GREATER GREATER
SMALLER BAR
SMALLER BAR SMALLER BAR
.50 Ø E F GREATER OF
.50 Ø .50 Ø
D C L 1.5L OR 0.33 L1
D
D
C
5 5

T
A B 100 (MIN.)
100 (MIN.)
B A

L1 L2 L1

B-2 TYPICAL CANTILEVER SLAB DETAIL


- SCALE- NTS
B-1 TYPICAL CONTINUOUS SLAB DETAIL
- SCALE- NTS

SLAB REINFORCEMENT
6
CONTINUOUS THRU JOINT 1/3 SPAN 6
300 (TYP.)
SSL TOP MESH T10-200 UNO
50 0.25 L 0.25 L
IF t >160 THK.
(SEE SCHED.)

SMALLER BAR SMALLER BAR


T

50 Ø E F 50 Ø
D D

FIRST POUR T12@300, EXTRA BAR FOR T > 125

NOTE: BONDING AGENT TO BE ADDED SUBJECT


TO ENGR'S APPROVAL. A B
REV
DATE REVISIONS BY CHK APP
No.
PROJECT:
L
B-3
-
TYPICAL CONSTRUCTION JOINT FOR SUSPENDED SLAB RUKAN DEVELOPMENT
SCALE- NTS
7 B-5 TYPICAL SIMPLY SUPPORTED SLAB DETAIL WADI AL SAFA 7 7
VARIES - SCALE- NTS PLOT NO: 6654283 (TH-50)
OWNER OF TITLE:
HOR. BAR T12@200 CONT.
DOWELS T12@300
DUBAI LAND L.L.C.
VARIES

T.O.S.SLAB
EL.(SEE PLAN)
PURCHASER :

SCHEDULE OF SLABS Continental Investments


BOTTOM STEEL TOP STEEL @ SUPPORT TOP STEEL @ MID SPAN REMARKS
TYPE THICK.
STRUCTURAL SLAB OR
(T) SHORTER SPAN (A) LONGER SPAN (B) SHORTER SPAN (C) LONGER SPAN (D) SHORTER SPAN (E) LONGER SPAN (F) CONSULTANT:
SLAB ON GRADE
NOTES:
* REFER ADDITIONAL BAR ON LAYOUT.
8 8
1. PROVIDE MIN. 2 DOWELS FOR CURB 250 OR MORE WIDE PROVIDE MIN.
2 HOR. BARS FOR CURB 250 OR MORE HIGH
2. SEE ARCH'L., MECH'L., ELECT'L. AND PLUMBING DWGS. FOR CURB SIZES
B TYPICAL SLAB ELEVATION AND SCHEDULE DRAWING TITLE :
- SCALE- NTS
AND LOCATIONS.
GENERAL DETAILS -
B-4 TYPICAL CONCRETE CURB DETAIL 1 OF 5 FOR BLOCK 3
- SCALE- NTS
REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-003 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1
GENERAL DETAILS - 02 1

RC WALL THK (TYP) WALL REINF AS PER DETAIL


(TYP)
U-BAR REINF SAME
U-BAR REINF SAME
AS RC WALL REINF R.C. WALL

LAP 50xØ OF BAR


AS RC WALL REINF COLUMN
R.C. WALL U-BAR REINF SAME RC WALL
AS RC WALL REINF
2 50 R.C. WALL R.C. WALL U-BAR REINF SAME AS SLAB REINF 2
LAP 50xØ OF BAR DIMENSION AS PER SLAB DETAILING

50
R.C. SLAB

50
LAP 50xØ OF BAR REFER TO S-002
50
LAP 50xØ OF BAR

CLEAR COVER
50
LAP 50xØ OF BAR

LAP 50xØ OF BAR

CLEAR COVER
CLEAR COVER

CLEAR COVER CLEAR COVER

LAP 50xØ OF BAR


R.C. WALL
R.C. WALL
U-BAR REINF SAME AS REFER TO S-002
50
RC WALL REINF

CLEAR COVER
3 COLUMN 3
R.C. WALL U-BAR REINF SAME SLAB REINF

CLEAR COVER
COLUMN REINF AS PER DETAIL
AS RC WALL REINF
AS PER DETAIL
RC WALL THK (TYP) CLEAR COVER

50
CLEAR COVER
CLEAR COVER

LAP 50xØ OF BAR


WALL REINF
RC WALL JUNCTION DETAIL RC WALL JUNCTION DETAIL RC WALL -COLUMN JUNCTION DETAIL PLAN AS PER DETAIL
R.C. WALL
PLAN PLAN CORNER DETAIL
RC WALL - COLUMN JUNCTION DETAIL PLAN RC WALL-SLAB JUNCTION SECTION DETAIL

4 4

50 CL.

HOOK ALL BARS


AT TOP LEVEL

5 5
TENSION
SPLICE

FLOOR SLAB

ADDITIONAL BARS AREA = (A)/2 AT ADDITIONAL BARS AREA = (A)/2


STEEL BARS CUT AREA = (A)
DEPTH OF PORTION PLACED TOP & BOTTOM USE 2T16 MIN.
WITH FLOOR & ROOF AT TOP & BOTTOM USE 2T16 MIN. ADDITIONAL BARS AREA = (A)/2 ADDITIONAL BARS AREA = (A)/2
CONCRETE COVER ADDITIONAL BARS AREA = (B)/2
TO MATCH DEEPEST BEAM AT TOP & BOTTOM USE 2T16 MIN.
AS PER NOTES FRAMING INTO WALL AT TOP & BOTTOM USE 2T16 MIN.
AT TOP & BOTTOM USE 2T16 MIN. ADDITIONAL BARS AREA = (B)/2
GROUND SLAB OR GRADE SLAB AT TOP & BOTTOM USE 2T16 MIN.

STEEL BARS CUT AREA = (B) STEEL BARS CUT AREA = (B)

ADDITIONAL DIAGONAL RFT IN CASE


DIA. 400mm SEE NOTE (1,2) ADDITIONAL BARS AREA = (B)/2 STEEL BARS CUT AREA = (B) STEEL BARS CUT AREA = (B)
6 6
STEEL BARS CUT AREA = (A) ADDITIONAL DIAGONAL RFT IN
AT TOP & BOTTOM USE 2T16 MIN. CASE WIDTH 400mm ADDITIONAL BARS AREA = (B)/2
TYPICAL DETAILS OF ADDITIONAL AT TOP & BOTTOM USE 2T16 MIN.

REINFORCEMENT AROUND CIRCULAR STEEL BARS CUT AREA = (A)


SEE NOTE (1,2)
TENSION SPLICE

WATER PROOFING AS PER OPENING IN SLAB AND WALL (UNO)


SPEC (TYP.)
( OPENING SIZE: 900 MM > OPENING DIAMETER > 400 MM ) TYPICAL DETAILS OF ADDITIONAL REINFORCEMENT AROUND
NOTE:
1- ALL TRIMMERS AND DIAGONAL BARS SHALL EXTEND AN ANCHORAGE LENGTH BEYOND RECTANGULAR OPENING IN SLAB AND WALL (UNO)
ROUGHENED CONSTRUCTION THE EDGE OF THE OPENINGS (600 Min.) AND GREATER OF (A)/2 OR (B)/2
JOINT, (TYP.) 2- THE ADDITIONAL DIAGONAL TRIMMERS SHALL BE (THE GREATER OF (A)/2 OR (B)/2) (MAX. SIZE OF OPENING (700X700)
RAFT OF SAME DIAMETER,TYPE AND NUMBER AS TRIMMER BARS.
REV
DATE REVISIONS BY CHK APP
FOUNDATION No.
PROJECT:
DOWELS, SIZE &
SPACING TO MATCH RUKAN DEVELOPMENT
7 WALL VERT BARS WADI AL SAFA 7 7

WATER PROOFING AS PER


PLOT NO: 6654283 (TH-50)
SPEC (TYP.) OWNER OF TITLE:

100 THK. P.C.C. OVER 1000 G


F TYPICAL SHEAR WALL SECTION POLYTHENE SHEET OVER 200 THICK DUBAI LAND L.L.C.
WELL COMPACTED ROAD BASE OVER
-
WELL COMPACTED SOIL UNO
PURCHASER :

Continental Investments

CONSULTANT:

NOTE:
8 8
1. PROVIDE HORIZONTAL AND DIAGONAL REINFORCEMENT AND ASSOCIATED STIRRUPS AS INDICATED FOR ANY 2 OPENINGS
WITH VERTICAL SEPARATION OF 'H' = 2500 OR LESS. FOR OPENINGS WITH H GREATER THAN 2500, OR WITHOUT OPENINGS
DRAWING TITLE :
ABOVE OR BELOW, PROVIDE ADDITIONAL HORIZONTAL AND DIAGONAL RFT. AS TYPICAL CONCRETE SLAB OPENING DETAIL.
2. PROVIDE VERTICAL REINFORCEMENT AND ASSOCIATED TIES INDICATED AT ALL OPENINGS GREATER THAN 300 IN ANY
DIMENSION.
GENERAL DETAILS -
3. FOR ALL BARS SHOWN EXTENDED SPLICE LENGTH BEYOND OPENING, IF EDGE OF CONCRETE OCCURS BEFORE SPLICE 2 OF 5 FOR BLOCK 3
LENGTH OBTAINED, EXTEND BAR FULL AVAILABLE LENGTH AND HOOK.
REV No. DATE SCALE
4. SEE GENERAL STRUCTURAL NOTES. DO NOT PLACE ANY OPENINGS IN SHEAR WALLS GREATER THAN 300 IN EITHER 0 JAN-2022 AT A0
DIMENSION, EXCEPT AS SPECIFICALLY INDICATED ON STRUCTURAL DRAWINGS. PROVIDE MIN. 600 CLEAR VERTICALLY AND
JOB No. DRW.No. STATUS
HORIZONTALLY BETWEEEN OPENINGS NOT INDICATED ON STRUCTURAL DRAWINGS.
----- S-004 FOR APPROVAL
A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

GENERAL DETAILS - 03
1 1

CLEAR COVER CLEAR COVER

CLEAR COVER
AS PER BEAM DETAIL AS PER BEAM DETAIL
2x DEPTH OF BEAM 2x DEPTH OF BEAM COLUMN REINFORCEMENT
COLUMN
AS PER BEAM DETAIL ANCHORED IN BEAM

COVER

COVER
CLEAR
LAP 50xØ OF BAR

SIDE
LAP 50xØ OF BAR 2 COLUMN REINFORCEMENT
2 x DEPTH OF BEAM
LAP 50xØ OF BAR 3 -T10 HORIZONTAL U-BARS

1 1 AS PER BEAM DETAIL

COVER
CLEAR
LAP 50xØ OF BAR
2 2

Ld
BEAM
BEAM REINF. AS PER DETAIL

SIDE COVER
COLUMN (TYP)

Ld
Ld
FOR STIRRUPS SPACING REFER
BEAM

CLEAR COVER
SECTION 1-1.
FOR STIRRUPS SPACING
REFER SECTION 1-1. 50
FOR STIRRUPS SPACING COLUMN REINFORCEMENT
2 x DEPTH OF BEAM

REFER SECTION 1-1. BEAM


FOR STIRRUPS SPACING 50 BEAM REINF. AS PER DETAIL

CLEAR COVER
BEAM
AS PER BEAM DETAIL

3 REFER SECTION 1-1. CLEAR COVER 3


CLEAR COVER
SIDE COVER
NOTE: REFER SECTION 5.2 OF DWG. S-002 FOR Ld DETAILS.
CLEAR COVER
BEAM COLUMN
LAP 50xØ OF BAR

CLEAR COVER FOR LINKS SPACING


REFER SECTION 1-1.

FOR LINKS SPACING COLUMN


REFER SECTION 1-1.

TYP. BEAM & COLUMN TOP END DETAIL

SECTION 2-2

4
TYP. COLUMN & BEAM JUNCTION DETAIL PLAN (AT TOP) 4

AS PER BEAM DETAIL AS PER BEAM DETAIL


LAP 50xØ OF BAR LAP 50xØ OF BAR
COLUMN

LAP 50 Ø OF BAR
2x DEPTH OF BEAM 2x DEPTH OF BEAM

STIRRUPS SPACING SHALL BE LESSER OF

TENSION LAP SPLICE


1. d/4 OR
STIRRUPS SPACING SHALL BE LESSER OF
2. 8 TIMES OF SMALLER DIA 1. d/4 OR
OF TOP BAR OR 2. 8 TIMES OF SMALLER DIA OF TOP BAR OR
3. 24 TIMES DIA OF STIRRUPS OR 3. 24 TIMES DIA OF STIRRUPS OR
4. 300MM

LAP 50 Ø OF BAR
COVER

4. 300MM
CLEAR

6 @ 100
A
5 A 5

50
1 (MAX.)

GREATER OF 50 Ø OF BAR OR 1000MM


6

50 50
COVER

COVER
50
CLEAR

CLEAR

A
BEAM BEAM B
STIRRUPS AS LAP 50xØ OF BAR STIRRUPS AS
LAP 50xØ OF BAR
PER SCHEDULE PER SCHEDULE

6 @ 100
COLUMN
GREATER OF
1. Lo/6 OR LINKS AS PER DETAIL
6 2. MAXIMUM C/S DIMENSION 6
LINKS SPACING BEAM
OF COLUMNS OR (REINFORCEMENT NOT
SHALL BE LESSER OF CONFINEMENT TIES
3. 450MM. CLEAR SHOWN FOR CLARITY)
1. 8 TIMES DIA. OF SMALLEST LONGITUDINAL BAR OR (SEE COLUMN/SHEAR WALL
COVER
2. 24 TIMES DIA OF LINKS OR SCHED. FOR SIZE & NUMBER
C C 3. SMALLEST C/S DIMENSION OF COLUMN OR PER SET)
4. 300MM.
CLEAR COVER CLEAR COVER LINKS SPACING
SHALL BE LESSER OF
1. 8 TIMES DIA. OF SMALLEST
LONGITUDINAL BAR OR
GREATER OF 2. 24 TIMES DIA OF LINKS OR MAINTAIN ALIGNMENT
1. Lo/6 OR 3. SMALLEST C/S DIMENSION OF BARS AT SPLICE
Lo

2. MAXIMUM C/S DIMENSION OF COLUMN OR


D D OF COLUMNS OR 4. 300MM. REV
DATE REVISIONS BY CHK APP
3. 450MM. No.
PROJECT:

RUKAN DEVELOPMENT
CLEAR
WADI AL SAFA 7
LAP 50 Ø OF BAR

7 7
COVER
PLOT NO: 6654283 (TH-50)
OWNER OF TITLE:

1
LINKS SPACING 8888A101
TYPICAL COLUMN SPLICE DETAILS E COLUMN SPLICE DETAILS DUBAI LAND L.L.C.
SHALL BE LESSER OF
-
1. 8 TIMES DIA. OF SMALLEST LONGITUDINAL BAR OR
GREATER OF 2. 24 TIMES DIA OF LINKS OR PURCHASER :
1. Lo/6 OR 3. SMALLEST C/S DIMENSION OF COLUMN OR
2. MAXIMUM C/S DIMENSION 4. 300MM.
OF COLUMNS OR
3. 450MM. WIDTH WIDTH BREADTH BREADTH Continental Investments
50

A TOP BARS AS PER TOP BARS AS PER


SCHEDULE SCHEDULE

CONSULTANT:

COLUMN MAIN BARS AS COLUMN MAIN BARS AS


DEPTH 'D'

DEPTH 'D'

HEIGHT

HEIGHT
8 8
SIDE BARS WHEREVER SIDE BARS WHEREVER PER SCHEDULE PER SCHEDULE
'd'

'd'

APPLICABLE APPLICABLE
STIRRUPS AS PER DRAWING TITLE :
STIRRUPS AS PER COLUMN LINKS AS PER COLUMN LINKS AS PER
SCHEDULE
SCHEDULE SCHEDULE SCHEDULE
GENERAL DETAILS -
SECTION 1-1 BOTT. BARS AS PER BOTT. BARS AS PER
SCHEDULE SCHEDULE 3 OF 5 FOR BLOCK 3
SECTION A-A SECTION B-B SECTION C-C SECTION D-D REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-005 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

GENERAL DETAILS - 04
1 1

25 25
SCHEDULE OF FOOTINGS L
EQ EQ
COLUMN REINFORCEMENT AS PER
TYPE R.C.COLUMN AS PER SCHE. SCHEDULE
SIZE IN MM REINFORCEMENT DETAILS
REMARKS

LAP 50 Ø
BOTTOM MESH TOP MESH BOTTOM STEEL AS PER SCHEDULE OUTSIDE INSIDE GRADE SLAB AS PER LAYOUT
WIDTH LENGTH DEPTH
(D) (LONG SPAN)
FFL
SHORT BAR LONG BAR SHORT BAR LONG BAR SSL
TT 50

EQ
6

BOTTOM STEEL AS PER SCHEDULE SWL 1 (MAX.)


2 2
* REFER ADDITIONAL BAR ON LAYOUT. (SHORT SPAN)

40
X X
MEMBRANE TUCKED INTO A 20x20 NOTCH IN CONCRETE & 1000 G POLYTHENE SHEET

B
SEALED WITH HOT APPLIED SBS SEALANT
TOP STEEL (IF REQUIRED) AS PER 100 THICK WELL COMPACTED ROAD

TB
BT
FGL (VARIES) SCHEDULE (LONG SPAN) 50 BASE OVER WELL COMPACTED SOIL
RC WALL BB 50 TIE BEAM AS PER SCHEDULE
GRP LINING WATER PROOFING FOOTING AS PER SCHE.
AS PER SPEC (FOR WATER TANK) BITUMEN PROTECTION COAT

EQ
6mm THK PROTECTION BOARD UNO TOP STEEL (IF REQUIRED) AS PER TOP STEEL (IF REQUIRED) AS PER SPEC.
SCHEDULE (SHORT SPAN) SHORT SPAN
SCREED (TYP.) 4MM THK SBS MODIFIED REINFORCED SINGLE LAYER TOP STEEL (IF REQUIRED) LONG
MINIMUM 50mm THK. MEMBRANE TORCH WELDED AND SHALL COMPLY WITH SPAN
SPECIFICATION UNO
3
BASEMENT FFL (VARIES) / 3
SSL SAND/CEMENT ANGLE FILLET

DEPTH (D)
UG WATER TANK
CHAMFER 25MM T12-250 ON FULL PERIMETER (WHEN
CENTROID OF FOOTING & 450
(TYP.) TOP STEEL IS NOT PROVIDED)
COLUMN/PEDESTAL TO MATCH
R.C. COLUMN AS PER SCHE. (UNLESS SHOWN OTHERWISE)
50 THK PROTECTION SCREED COLUMN AS PER LAYOUT (FIRST STAGE OF WORK) FOUNDATION LEVEL -1.0 M
BOTTOM STEEL LONG SPAN

75
4MM THK SBS MODIFIED REINFORCED EQ EQ
SINGLE LAYER MEMBRANE TORCH
4MM THK SBS MODIFIED REINFORCED WELDED AND SHALL COMPLY WITH
TYPICAL DETAIL (PLAN) OF ISOLATED FOOTING 100
BITUMEN PROTECTION
100(TYP.)
100 THK. P.C.C. OVER 1000 G
SINGLE LAYER MEMBRANE TORCH SPECIFICATION UNO BOTTOM STEEL COAT AS PER SPEC. POLYTHENE SHEET OVER 200 THICK
WELDED AND SHALL COMPLY WITH SIZE OF FOOTING L x B ( L > B ) NOTE SHORT SPAN
SPECIFICATION UNO 100 MM THICK RCC PROTECTION COVER WITH A LAYER OF BB- BOTTOM LAYER BOTTOM BAR SECTION X--X WELL COMPACTED ROAD BASE 20 CM
OVER WELL COMPACTED SOIL
BRC MESH A-142 (SECOND STAGE OF WORK)
100 THK. P.C.C. OVER 1000 G
GRP LINING WATER PROOFING
BT- BOTTOM LAYER TOP BAR (TYPICAL EXTERNAL FOOTING)
POLYTHENE SHEET OVER 200 THICK TT- TOP LAYER TOP BAR
WELL COMPACTED ROAD BASE
AS PER SPEC
TB- TOP LAYER BOTTOM BAR
(TOP STEEL SHALL BE PROVIDED ONLY IF REQUIRED)
OVER WELL COMPACTED SOIL UNO
TYP. WATER PROOFING DETAIL FOR CONTRACTOR TO FOLLOW THE SOIL REPORT RECOMMENDATIONS
4 TYP. WATERPROOFING DETAIL FOR U/G R.C. STRUCTURES. COLUMNS INSIDE U/G TANK 4

STONE TILE
BLOCK WALL
AS PER ARCH

PVT FFL BLOCK WALL


BLOCK WALL
B
100

150
100/150
200/250 DPC AS PER DPC AS PER DPC AS PER
SPEC SPEC SPEC BEAM AS PER SCH.

GRADE SLAB WITH A E E E B


A LAYER OF BRC MESH A-193 GRADE SLAB
AS PER LAYOUT
TYPICAL BASE SLAB DETAIL FOR STONE PAVING TILES
(EXTERNAL WORKS)

40

40
5 5
200

200

200
C
40

40
C
INDUCED CRACK

75
75

75
A A A A
T12 - 150 C/C T10 - 150 C/C C
SURFACE GROOVE, 50
50 T10 - 150 C/C
5 TO 10mm WIDE & DEPTH=D/4, E 100 200 600 200 100 100 200 400 200 100
SEALED IF NECESSARY 100 200 300 D

D WALL FOOTING DETAIL- 2


C WALL FOOTING DETAIL- 1 TYPICAL SECTION UNDER 100 / 150THK. BLOCK WORK
D-1 WALL FOOTING DETAIL-3
TYPICAL SECTION UNDER 200 THK. BLOCK WORK WALL ON GRADE SLABS TYPICAL SECTION UNDER BLOCK WORK
WALL ON GRADE SLAB WALL ON GRADE SLABS
MESH AS PER LAYOUT
TIMBER OR PLASTIC
CRACK INDUCER
A WALL FOOTING DETAILS (WF)
6
CRACK CONTROL JOINT 6

AS PER SCHED.
IMPOTANT NOTE:
MAIN BEAM RFT. GROUND WATER TABLE (GWT) SHALL BE CONFIRMED BY MAIN
SECONDARY BEAM RFT. SECONDARY BEAM RFT.
CONTROL JOINT AS PER LAYOUT AS PER SCHEDULE CONTRACTOR DURING CONSTRUCTION BY CONDUCTING ADDITIONAL
AS PER SCHEDULE T.O.B AS PER SCHEDULE
(SAW CUT JOINT) BOREHOLE AS PER SPEC AND FOLLOWING WATER PROOFING TYPE
AS PER SCHEDULE

AS PER SCHEDULE
50 250/200 BLOCK WALL 12THK. FLEXCEL SHALL BE APPLIED SUBJECT TO ENGINEER APPROVAL:
6x20mm GROOVE 50
(WITH SEALANT) E JOINT a) PAD, STRIP, COMBINED, RAFT FOUNDATION AND FIRE ESCAPE
12X8 THICK
APPROVED SEALANT STAIR WALLS:
E
DPC AS PER SPEC i. LIQUID APPLIED WATER PROOFING SHALL BE APPLIED AS PER
SPEC IF G.W.T FOUND 1.50 m BELOW FOUNDATION LEVEL. REV
DATE REVISIONS BY CHK APP
No.
SECONDARY BEAM RFT.
ii. SINGLE LAYER OF 4 mm THICK REINFORCED MEMBRANE AS PER PROJECT:
MESH (900 LONG) MAIN BEAM RFT.
SPEC. SHALL BE APPLIED IF G.W.T FOUND LESS THAN 1.5m
AS PER SCHEDULE AS PER SCHEDULE
BELOW FOUNDATION LEVEL. RUKAN DEVELOPMENT
7
TYPICAL DETAIL OF MAIN AND SECONDARY TIE BEAM b) UNDER GROUND TANK, LIFT PIT, STRUCTURE ELEMENTS SUBJECT WADI AL SAFA 7 7
A
TO PLANTER AND BASEMENT( WALL AND RAFT), TWO LAYERS OF 4 PLOT NO: 6654283 (TH-50)
A
LONGITUDINAL CONSTRUCTION JOINT mm THICK. REINFORCED MEMBRANE AS PER SPEC. SHALL BE OWNER OF TITLE:
APPLIED.

R.C. TIE BEAM
℄ 1000 C/C
c) SWIMMING POOLS, TWO LAYERS OF 4 mm THICK. REINFORCED DUBAI LAND L.L.C.
MEMBRANE AS PER SPEC. SHALL BE APPLIED, SUBJECT TO
20mm EXPANSION JOINT 1000 C/C PLINTH 170 ENGINEER APPROVAL .
WATER PROOFING AS
50 50 DOWEL BARS 20 DIA. x 600 LONG @ 600 C/C PER SPEC.
PLINTH 200X600 WITH PURCHASER :
E 200X600 WITH
(HALF BAR COATED WITH DEBONDING AGENT) 200THK. SOLID BLOCK WALL 2T12 T & B
2T12 T & B 170
C
T8-150 STIRRUP
T8-150 STIRRUP RAFT/BASE SLAB LEGEND Continental Investments
FDN. LEVEL 2T12 SIDE BAR AS PER LAYOUT

600*
2T12 SIDE BAR
128

ON EACH FACE A. 1000 G POLYTHENE SHEET OVER 100 THICK WELL COMPACTED ROAD BASE OVER WELL
A ON EACH FACE COMPACTED SOIL UNO. CONSULTANT:
SSL
600*

DOWEL CAP END FILLED WITH


20mm FLEXCEL B. 12MM THICK FLEXCEL WITH SEALANT
COMPRESSIBLE MATERIAL TYPICAL DETAIL OF ISOLATION JOINT AND SSL
AS PER LAYOUT

8 WITH SEALANT 8
A
C. 75MM THICK BLINDING WITH 75MM PROJECTION ON EACH FACE OF WALL/ BEAM.
SOLID BLOCK WORK @ EXTERNAL WALLS
D

SLAB AS PER DRAWING TITLE :


LAYOUT D. 100MM THICK BLINDING WITH 100MM PROJECTION ON EACH FACE OF WALL/ BEAM.
TRANSVERSE CONTROL (EXPANSION) JOINT GENERAL DETAILS -
'*' TO BE CONFIRMED BY MEP ENGINEER
TYPICAL DETAIL OF GRADE SLAB CONSTRUCTION JOINT / EXP JOINT E. GRADE SLAB AS PER LAYOUT
4 OF 5 FOR BLOCK 3
TYPICAL WATER TANK PLINTH AT ROOF LEVEL '*' TO BE CONFIRMED BY MEP ENGINEER
(GRADE SLAB AREA > 30M²) REV No. DATE SCALE
TYPICAL WATER TANK PLINTH AT RAFT LEVEL
0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-006 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1
GENERAL DETAILS - 05 1

1 FLOOR SLAB/ 4000 FOR EXTERNAL WALLS NOTE:


BEAM 5000 FOR INTERNAL WALLS 1. ALL WALL TIES, HEAD TIES, ETC., FOR EXTERNAL WALLS
4000 FOR EXTERNAL WALLS -- FLOOR SLAB/
5000 FOR INTERNAL WALLS BEAM 1 SHALL BE GALVANISED STAINLESS STEEL INSTEAD OF
-- GALVANISED IRON.
600 W 400
3 MINIMUM MINIMUM
-- 3 1 JAMBS UPTO FLOOR
2Ø16 VERTICAL
-- -- AND ROOF BEAM
STEEL REINFORCEMENT
END/CORNER BLOCK

A RC. COLUMN LINTEL BEAM 2 T 16 (TYP.) RC LINTEL


A

REFER ARCH. DWGS.


-- --
C
-- B
OPEN

2 2

R.C. STIFFENER COLUMN --


CAST AFTER BLOCK WORK

600 MIN.
(RESTRAINT POST)

2
RC. COLUMN
-- CONCRETE JAMBS
WALL THICK.
NOTE:

LINTEL
DEPTH
EXPANDED METAL LATH TOP BARS
OMIT BARS FOR OPENING LESS THAN 200 VER. & 400 HOR.
EVERY SECOND COURSE BOTTOM BARS
25 CL. TYP.
WALL CONNECTIONS
B CONCRETE MASONRY WALL STIRRUPS
ISOMETRIC VIEW
3 B WALL PANEL ELEVATION (SINGLE HEIGHT) SECTION 1-1 3
OPENING WITH LINTEL BEAM
-- T8-200 T8-200

200

200
D
E 4-T12 4-T12
--
-- 2-T16 VERTICAL

200
2-T16 VERTICAL 150 200
10mm COMPRESSIBLE 30mm. x 1.5mm. THK. R.C. COLUMN / WALL STEEL
200 UNO 300 STEEL
FILLER WITH SEALANT GALVANISED HOOP-IRON 150 2-T16 VERTICAL REINFORCEMENT 500
WHERE VISIBLE ANGLE SHOT FIXED TO TYP. 2-T16 VERTICAL STEEL
200 REINFORCEMENT CONCRETE JAMBS REINF TYPICAL REINFORCEMENT PLAN 200
COLUMN AT ALTERNATE STEEL W
R.C. STIFFENER
COURSE (MIN. 2 FIXINGS) REINFORCEMENT
REINFORCEMENT DETAIL OF RC STIFFENER COLUMN
COLUMN CAST AFTER 2T12 END/CORNER BLOCK
BLOCK WORK FLOOR SLAB/

300
(RESTRAINT POST) BEAM
DOVE TAIL SLOT-IN DOVE TAIL ANCHOR DOVE TAIL SLOT-IN DOVE TAIL ANCHOR
BLOCK WORK DOVE TAIL SLOT-IN CONCRETE 25*1.5*250 MM EVERY CONCRETE 25*1.5*250 MM EVERY
DOVE TAIL ANCHOR 3T16
CEMENT MORTAR CONCRETE 25*1.5*250 MM EVERY RC STIFFENER THREE COURSES RC STIFFENER THREE COURSES CABLE CONDUIT
EXPAMET TO COVER ALL
2

200
JOINTS. (TYP.) THREE COURSES REINFT. 6T12 T8-150 CEMENT MORTAR CEMENT MORTAR
RC STIFFENER T8-150 LINKS REINFT. 6T12 T8-150 2T16 VERTICAL
CEMENT MORTAR LINKS
-- FOR INTERNAL WALL
LINKS
FOR EXTERNAL WALL STEEL REINFORCEMENT 400
(MASONRY ANCHORED TO CONCRETE) JUNCTION BOX 200
EXPANDED METAL LATH SECTION- A SECTION- B SECTION- C SECTION- D SECTION- E CONCRETE
EVERY SECOND COURSE

MAX AREA = 14 SQM


4 4
WALL PANEL ELEVATION (DOUBLE HEIGHT)
NOTE: 1-T20 DOWEL BAR 350

200
1. PROVIDE PRECAST OR CAST-IN-PLACE LINTELS USING CONCRETE OF Fcu=35.0 MPA. MM LONG DEBONDED
30 75 IN POST CABLE CONDUIT 400
2. SEE ARCHITECTURAL DRAWINGS OF OPENING WIDTH AND LOCATIONS.

125
CEMENT MORTAR 150
SHOT FIXING (2 NO.) FOR ALL VERTICAL &
LINTEL SCHEDULE 10mm. WEAK 1T20
RC COLUMN 2-T16
SOCKET BOX HORIZONTAL JOINTS
U/S OF SLAB OR BEAM DOWEL BAR RC SLAB / BEAM
MORTAR PACKING

550
WALL LINTEL SOFFIT
MASONRY BOTTOM TOP STIRRUPS

20 100
RC SLAB
OPENING WIDTH THICKNESS DEPTH BARS BARS COMPRESSIBLE
PREFABRICATED GALVANISED FILLER 10 MM

200
STRAP AT 800 c/c. 2.5mm THICK THICK WITH 400

200
1000 MAXIMUM 200 150 2 T 12 2 T 12 T 8 @ 150 REFER DETAIL -`1a'. (APPLICABLE SEALANT 2-T16 CABLE CONDUIT
TO EXTERNAL WALLS ONLY) 50
25 MM CAP WITH
1500 ---> 2000 200 150 2 T 16 2 T 12 T 8 @ 150 100
15
COMP. FILLER ELECTRICAL INSTALLATIONS IN CONCRETE
2000 ---> 3000 200 250 2 T 16 2 T 12 T 8 @ 150 COLUMN WITH HORIZONTAL STIFFENER CONNECTION
15 (CONNECTION TO RC SLAB (CONNECTION TO RC BLOCK WALL ISOMETRIC VIEW CONCRETE BLOCKS TYPES
50

3000 ---> 4000 200 300 3 T 16 2 T 12 T 8 @ 150


AT BOTTOM OF SLAB AT TOP OF DETAILS STIFFENER BEAM SIZE 200X200/300X200
STIFFENER) STIFFENER)

4000 --->5000 200 400 3 T 16 2 T 12 T 8 @ 150 DETAIL- 1 DETAIL- 1a DETAIL- 2 DETAIL- 3


5 5

TYPICAL MANHOLE DETAILS


RC WALL AS PER LAYOUT
4-T12, T8-150 COVER AND FRAME TO GIVE
COVER AND FRAME TO GIVE AROUND OPENING CLEAR OPENING 600x600
CLEAR OPENING 600x600 (HEAVY DUTY)AS PER MEP
DETAIL 'A' (HEAVY DUTY) AS PER MEP T12-150 165 2000 TO 3000 165
DETAIL 'A' T12-150
FINISHED PAVING LVL 330
FINISHED PAVING LVL
137 1000 TO 2000 137
SSL
165

D Max.1500
330 RAFT/BASE SLAB
110

AS PER MEP 'X2' (REFER WALL


MESH AS PER LAYOUT SECTION DETAILS)

110
1 1
138

AS PER LAYOUT
AROUND OPENING
600

T10-150 (TYP) 50Ø

1000 TO 1500
4-T12, T8-150 T16 @ 150

AS PER MEP
WATER PROOFING
2 2

Max.2000
HEAVY DUTY T12-150 (TYP)
2000 TO 3000

SYSTEM AS PER SPEC. MANHOLE COVER


1000 TO 2000

SUMP PIT
600

AS PER MEP
WATER PROOFING T12 @ 150
6 6
HEAVY DUTY SYSTEM AS PER SPEC.
D

16
MANHOLE COVER T12 @ 150 100
1500 TO 3000

Ø
AS PER MEP AS PER LAYOUT

AS PER LAYOUT
82
T12-150 (TYP) T12-150 (TYP)
BENCHING CONSTRUCTION JOINT
137

X1

D
165
248(TYP.)
T16-150 (TYP) T16-150 (TYP)
165

PLAN 75 THK PCC


100 THK ROAD BASE

55
OVER WELL
PLAN COMPACTED SOIL
WATER STOPPER 137 1000 TO 2000 137
AS PER SPEC
CONSTRUCTION JOINT SECTION 2-2
-SOLID BLOCK MIGHT BE USED AS PER ENGINEER APPROVAL REV
DATE REVISIONS BY CHK APP
TYPICAL DETAIL OF SUMP PIT AT CORNER No.
82

PROJECT:

RUKAN DEVELOPMENT
165

COVER AND FRAME TO GIVE


7 100 THK PCC 1000 CLEAR OPENING 600x600 WADI AL SAFA 7 7
110 110
200 THK ROADBASE (MAX) (HEAVY DUTY)AS PER MEP RAFT/BASE SLAB MESH MANHOLE COVER PLOT NO: 6654283 (TH-50)
OVER WELL 4-T12, T8-150
COMPACTED SOIL AROUND OPENING
T12-150
FINISHED PAVING LVL
SSL AS PER LAYOUT AS PER SPECIFICATION / MEP SSL OWNER OF TITLE:
50Ø Max.1200mm
T16-150ADD
110

T12-150ADD AS PER MEP


165 2000 TO 3000 165
DUBAI LAND L.L.C.

AS PER LAYOUT
3 3
SECTION 1-1
110

(MAX)
1000

MAX 2000MM
AS PER MEP
50Ø 50Ø
T10-150 (TYP) PURCHASER :
(MAX)
600

COVER AND FRAME TO GIVE 4-T12, T8-150


AROUND OPENING
82

4-T12, T8-150 CLEAR OPENING 600x600 D D


FINISHED T10-150

16Ø

16Ø
AROUND OPENING (HEAVY DUTY) T12-150 PAVING LVL
Continental Investments
200

WATER PROOFING
HEAVY DUTY
MANHOLE COVER SYSTEM AS PER SPEC.
AS PER MEP
110

75 THK PCC

D
D
200

100 THK ROAD BASE


CONSULTANT:
OVER WELL
T12-150
X1
RSA 70X70X8 (TYP) COMPACTED SOIL 1000
WATER PROOFING PLAN 110
(MAX)
110
SYSTEM AS PER SPEC.
8 TOP&BOTTOM MESH 8
REINF AS PER DETAIL REINF AS PER DETAIL SECTION 3-3 AS PER LAYOUT
-SOLID BLOCK MIGHT BE USED AS PER ENGINEER APPROVAL NOTE: DRAWING TITLE :
TYPICAL DETAIL OF GREASE TRAP
1- REFER S-004 FOR 'X1' DETAIL
DETAIL 'A'
GENERAL DETAILS -
5 OF 5 FOR BLOCK 3
REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-007 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

2 2

1- REFER DWG.S001 & S002 FOR GENERAL NOTES


,GRADE OF CONCRETE, STEEL GRADE,
CLEAR COVER,..., ETC.
01* 04
01 02 03 05 06 07 08 09 10 2- REFER DWG.S003 TO S007 FOR GENERAL DETAILS
3- COLUMNS REACTIONS ARE SERVICE LOADS(DL+LL)
46800
4- COLUMNS DESIGNED FOR BUILDING G+1+R.
5200 5200 5175 5225 5200 5200 5200 5200 5200

3 3

COLUMN DETAILS

S.NO FROM FOUNDATION TO


700 125 125 125 125 125 125 100 125 100 GROUND
110

100

100

100

100

100

100

100

100

110
A
C2 700

C2
2180

2180

2180

2180

2180

2180

2180
C3 C3 C3 C3 C3 C3 C3 C3 C1

250
1100 1100 1100 1100 1100 1100 1100
22T 20
T10@150C/C
C1 C1 C1 C1
C1 C1 C1
7140

4 4
800
100
CS
C2

220
18T20
2110

T10@150C/C
C2 C2 C2 C2 C2 C2 C2 C2 C2
C4

400

400
400

400

400

400

400

400

400
B
100

NC 300 1100

110 110 110 110 110 110 110 110


110
2340

2340

2340

2340

2340

2340

2340

2340

2340

2340
C3

250
100 100 100 100 100 100 100 100 100 100 22T20
T10@150C/C
NC NC NC NC NC NC NC NC NC NC
6540

500

5 5

C4

300
C3 14T20
C2 C2 C2 C2 C2 C2 C2 C2 C2 T10@150C/C
800

210
C
200
100

100

100

100

100

100

100
125
110 110 110 110 110 110 110 100
200

200
NC 4 T 16
T10@150C/C
UPTO TIE BEAM

300

200
6
CS 4 T 16
6

T10@150C/C
UPTO STAIR LANDING

COLUMN LAYOUT AT FOUNDATION LEVEL


SCALE- 1:100
REV
DATE REVISIONS BY CHK APP
No.
PROJECT:
COLUMN WIDTH RUKAN DEVELOPMENT
7 WADI AL SAFA 7 7

PLOT NO: 6654283 (TH-50)


OWNER OF TITLE:

ABOVE GROUND LEVEL


DUBAI LAND L.L.C.

25 PURCHASER :
25 GROUND
S.S.L.
Continental Investments

COVER 50mm CONSULTANT:


BELOW GROUND LEVEL

8 8

DRAWING TITLE :
(TYP) COLUMN SECTION COLUMN LAYOUT
BELOW GROUND LEVEL AT FOUNDATION LEVEL
FOR BLOCK 3
REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-101 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

2 NOTE: 2

1- REFER DWG.S001 & S002 FOR GENERAL NOTES


,GRADE OF CONCRETE, STEEL GRADE,
CLEAR COVER,..., ETC.
2- REFER DWG.S003 TO S007 FOR GENERAL DETAILS
3- COLUMNS DESIGNED FOR BUILDING G+1+R.

01* 04
3
01 02 03 05 06 07 08 09 10 3

46800

5200 5200 5175 5225 5200 5200 5200 5200 5200

COLUMN DETAILS

S.NO FROM FOUNDATION TO


700 125 125 125 125 125 125 100 125 100 GROUND
110

100

100

100

100

100

100

100

100

110
4 A 4
C2 700

C2
2180

2180

2180

2180

2180

2180

2180
C3 C3 C3 C3 C3 C3 C3 C3 C1

250
1100 1100 1100 1100 1100 1100 1100
22T 20
T10@150C/C
C1 C1 C1 C1
C1 C1 C1
7140

800
100
CS
C2

220
18T20
2110

T10@150C/C
C2 C2 C2 C2 C2 C2 C2 C2 C2
C4

400

400
400

400

400

400

400

400

400
B
100

1100
300
5 110 110 110 5
110 110 110 110 110 110
C3

250
22T20
T10@150C/C
6540

500

C4

300
C3 14T20
C2 C2 C2 C2 C2 C2 C2 C2 C2 T10@150C/C
800

210
C
200
100

100

100

100

100

100

100
125
110 110 110 110 110 110 110 100
300

200
6
CS 4 T 16
6

T10@150C/C NOTE:
UPTO STAIR LANDING 1- REFER DWG.S001 & S002 FOR GENERAL NOTES,GRADE OF CONCRETE,
STEEL GRADE, CLEAR COVER,..., ETC.
2- REFER DWG.S003 TO S007 FOR GENERAL DETAILS

REV
DATE REVISIONS BY CHK APP
COLUMN LAYOUT AT GROUND FLOOR& FIRST FLOOR COLUMN WIDTH No.
PROJECT:

SCALE- 1:100 RUKAN DEVELOPMENT


7 WADI AL SAFA 7 7

PLOT NO: 6654283 (TH-50)


OWNER OF TITLE:
ABOVE GROUND LEVEL
DUBAI LAND L.L.C.
25 25 GROUND
S.S.L.
PURCHASER :

Continental Investments
COVER 50mm
BELOW GROUND LEVEL
CONSULTANT:

8 8

(TYP) COLUMN SECTION


BELOW GROUND LEVEL DRAWING TITLE :
COLUMN LAYOUT AT
GROUND FLOOR
FOR BLOCK 3
REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-102 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

2 NOTE: 2

1- REFER DWG.S001 & S002 FOR GENERAL NOTES


,GRADE OF CONCRETE, STEEL GRADE,
CLEAR COVER,..., ETC.
2- REFER DWG.S003 TO S007 FOR GENERAL DETAILS
3- COLUMNS DESIGNED FOR BUILDING G+1+R.

01* 04
3
01 02 03 05 06 07 08 09 10 3

46800

5200 5200 5175 5225 5200 5200 5200 5200 5200

COLUMN DETAILS

S.NO FROM FOUNDATION TO


700 125 125 125 125 125 125 100 125 100 GROUND
110

100

100

100

100

100

100

100

100

110
4 A 4
C2 700

C3 C3 C3 C3 C3 C3 C2
C3 C3 C1

250
22T 20
T10@150C/C
7140

800

C2

220
18T20
T10@150C/C
C2 C2 C2 C2 C2 C2 C2 C2 C2
C4

400

400
400

400

400

400

400

400

400
B
100

1100
300
5 110 110 110 5
110 110 110 110 110 110
C3

250
22T20
T10@150C/C
6540

500

C4

300
C3 14T20
C2 C2 C2 C2 C2 C2 C2 C2 C2 T10@150C/C
800

210
C
200
100

100

100

100

100

100

100
125
110 110 110 110 110 110 110 100

6 6

NOTE:
1- REFER DWG.S001 & S002 FOR GENERAL NOTES,GRADE OF CONCRETE,
STEEL GRADE, CLEAR COVER,..., ETC.
2- REFER DWG.S003 TO S007 FOR GENERAL DETAILS

REV
DATE REVISIONS BY CHK APP
COLUMN LAYOUT AT FIRST FLOOR COLUMN WIDTH No.
PROJECT:

SCALE- 1:100 RUKAN DEVELOPMENT


7 WADI AL SAFA 7 7

PLOT NO: 6654283 (TH-50)


OWNER OF TITLE:
ABOVE GROUND LEVEL
DUBAI LAND L.L.C.
25 25 GROUND
S.S.L.
PURCHASER :

Continental Investments
COVER 50mm
BELOW GROUND LEVEL
CONSULTANT:

8 8

(TYP) COLUMN SECTION


BELOW GROUND LEVEL DRAWING TITLE :
COLUMN LAYOUT AT
FIRST FLOOR
FOR BLOCK 3
REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-103 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

2
01* NOTE: 2

01 02 03 04 05 06 07 08 09 10 1- FOR FOUNDATION LEVEL& SECTION REFER


TO SHEET NO -S-006
46800

5200 5200 5175 5225 5200 5200 5200 5200 5200

3 3

700 925 975 950 925 975 925 950 925 700
800

800
700

700

700

700
F1 F1

650

650

650
800
F3 600 F5 F5 F3 F5 F3 F5 F3
A
1805

1805

1805

1805

1805

1805

1805
625625 625625
F2 625 625 F2 625 F2 F2 F2 F2 F2
7140

1150 1150 1150 1150 1150 1150 1150 1150


4 4
F2
1500
F4 F4 F4 F4 F4 F4 F4 F4 F4

1460
1450

1450

1450

1450

1450

1450

1450

1450
1200
F4

1150

F0 F0 F0 F0 F0 F0 F0 F0 F0 F0
6540

900
900 950 900 900 900 900 950
800
F3
1850

700
1450

1450
1400

1400

1400

1400

1400
F3 F5 F3 F3 F3 F3 F5
1300

5 F1 5

800
F1
C

6 FOUNDATION LAYOUT 6

SCALE- 1:100

FOUNDATION NOTE:

· ALLOWABLE NET BEARING CAPACITY OF SOIL UP TO WIDTH 3M IS 160 KN/M2.


· ALLOWABLE NET BEARING CAPACITY OF SOIL FOR WIDTH 3-4M IS 140 KN/M2.
· FOUNDATION SURFACE SHALL BE PREPARED (FORMATION LEVEL WHICH IS -1.0 M FROM GL) BY WELL COMPACTED SOIL AND SHALL COMPLY WITH SOIL REV
DATE REVISIONS BY CHK APP
No.
INVESTIGATION REPORT RECOMMENDATION PROJECT:

RUKAN DEVELOPMENT
7
· CHECK SOIL INVESTIGATION REPORT FOR SOIL REPLACEMENT AND THE METHODS FOR IMPROVEMENT THE SOIL (IF NECESSARY) . WADI AL SAFA 7 7
SCHEDULE OF FOOTINGS PLOT NO: 6654283 (TH-50)
· CHECK SOIL INVESTIGATION REPORT FOR ALL RECOMMENDATION REGARDING FOUNDATION WORK BEFORE STARTING IN THE SITE .
R.C.C. SIZE BOTTOM TOP OWNER OF TITLE:
· FOUNDATIONS WORKS SHOULD DONE BY AUTHORIZED AND SUBJECTED TO CONSULTANT ENGINEER AND AUTHORITY APPROVALS . TYPE REMARKS
(MM ) LONG WAYS SHORT WAYS LONG WAYS SHORT WAYS
a. REFER TO SOIL REPORT FOR DEWATERING (IF NECESSARY) . DUBAI LAND L.L.C.
F0 1000x1000x350 T12@200C/C T12@200C/C - -
b. SUITABLE SIDE PROTECTION SHALL BE ENSURED DURING EXCAVATIONS AND FOUNDATION PLACEMENT WORKS.
F1 1600X2000X400 T12@150C/C T12@150C/C - -
PURCHASER :
c. THE REFERENCE LEVEL SHALL BE CONSIDERED FROM ARCH DRAWINGS.
F2 1200X1400X400 T12@150C/C T12@150C/C - -
d. EXCAVATE THE CONSTRUCTION AREA AS MENTIONED ABOVE IN TABULATION (NATURAL) GROUND LEVEL. Continental Investments
F3 2200X1800X400 T12@150C/C T12@150C/C - -
e. BACKFILL THE CONSTRUCTION AREA IN LAYERS NOT EXCEEDING 250MM USING APPROVED FILL MATERIAL UP TO FOUNDATION LEVEL AS
F4 2900X2300X400 T16@200C/C T16@200C/C - -
CONSULTANT:
MENTIONED ABOVE SUCH THAT EACH LAYER HAS TO BE COMPACTED TO NOT LESS THAN 98% OF THE MAXIMUM DRY DENSITY OF FILL MATERIAL F5 2300X1900X400 T12@125C/C T12@125C/C - -
8
USING A 20 TON HEAVY ROLLER 8

f. THE FOUNDATION SHALL BE PLACED ON PLAIN CONCRETE ( GRADE C20 ) LAYER OF 100 mm THICK BLINDING CONCRETE AND EXTENDING 100mm
DRAWING TITLE :
FROM BOTH SIDES.
FOUNDATION LAYOUT
g. CONTINUE THE BACK FILLING AS SPECIFIED IN STEP 'e'. UP TO THE PROPOSED FINAL GR LEVEL
FOR BLOCK 3
h. IN SITU DENSITY TESTS AS WELL AS PLATE LOAD TEST AT THE FINAL FOUNDATION LEVEL MUST BE DONE BY AUTHORIZED LAB TO DETERMINE
REV No. DATE SCALE

DEGREE OF COMPACTION AND ALLOWABLE BEARING CAPACITY PRIOR FOOTING CASTING AND MUST APPROVED BY THE ENGINEER. 0 JAN-2022 AT A0

JOB No. DRW.No. STATUS


i. COMPACTION TEST RESULTS SHOULD BE APPROVED BY THE ENGINEER PRIOR TO PROCEEDING WITH THE NEXT LAYER. ----- S-201 FOR APPROVAL
A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

01* 04
2
01 02 03 05 06 07 08 09 10 2

46800

5200 5200 5175 5225 5200 5200 5200 5200 5200

3 3

TB3 TB3 TB3 TB3 TB3 TB3 TB3 TB3 TB3


A
T16@150 T16@150
STAIR STARTER STAIR STARTER
+0.70 +0.70

TB1
T16@150 +0.70
TB1

TB1

TB1

TB1

TB1

TB1
T16@150 SSL T16@150
+0.70

TB1
STAIR STARTER STAIR STARTER SSL +0.70
STAIR STARTER SSL SSL +0.70 +0.70
TB1 +0.70 100 GRADE SLAB 100 GRADE SLAB TB1 SSL SSL
WITH A252 MESH 100 GRADE SLAB SSL
SSL WITH A252 MESH 100 GRADE SLAB
WITH A252 MESH 100 GRADE SLAB 100 GRADE SLAB
WITH A252 MESH 100 GRADE SLAB

TB2
100 GRADE SLAB WITH A252 MESH WITH A252 MESH
WITH A252 MESH
TB1

TB1

TB1

TB1

TB1

TB2

TB1

TB2

TB1

TB1

TB1

TB2

TB1

TB1

TB1

TB2
7140

100 GRADE SLAB WITH A252 MESH


WITH A252 MESH T16@150
STAIR STARTER WF

WF
+0.70
TB1
TB1

SSL

WF
WF WF WF WF WF WF WF WF WF WF
TB1

WF

WF
4 4

WF
WF WF WF WF WF
TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1
B WF

WF
WF
WF

TB1

TB1

TB1

TB1

TB1

TB1
WF
WF

WF

WF
WF
WF

WF
WF
TB1

TB1

TB1

WF WF WF WF WF WF

WF
WF

WF

WF
WF

WF
TB2 TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB2
WF WF
TB1

TB1

TB1

TB1

TB1

TB1

TB1

TB1
TB1
6540

TB1

TB1
TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1
5
C CTB1
5

6
GROUND FLOOR FRAMING LAYOUT 6

SCALE- 1:100

SCHEDULE OF TIE BEAMS


REV
DATE REVISIONS BY CHK APP
No.
BEAM SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT STIRRUPS PROJECT:
SIDE BARS NO OF
TYPE
STRAIGHT
EXTRA @ STRAIGHT EXTRA @ CONT. EXTRA @
O.E.F (F) AT SUPPORT AT MIDSPAN LEGS
REMARKS RUKAN DEVELOPMENT
MM XMM DISCONT.
7
(A) MID SPAN(B) (C) SUPPORT (D) EACH SIDE OUTER INNER OUTER INNER WADI AL SAFA 7 7

SUPPORT (E) (G1) (G2) (H1) (H2) PLOT NO: 6654283 (TH-50)
TB1 200 x 450 2T16 1T16 2T16 2T16 ------ T10-100 T10-150 2 OWNER OF TITLE:

TB2 200 x 550 2T16 2T16 2T16 2T16 2T16 T10-100 T10-150 2 DUBAI LAND L.L.C.
TB3 200 x 550 2T20 2T20 2T20 2T20 3T20 T10-100 T10-150 2
PURCHASER :

CTB1 200 x 500 2T12 1T12 2T12 1T12 ------ T10-100 T10-150 2
Continental Investments

NOTE: CONSULTANT:

1-WALL FOOTINGS LOCATIONS TO BE COORDINATED


8
WITH ARCHITECTURAL DRAWINGS 8

2-FOR WALLFOOTING DETAIL REFERE TO SHEET


NO. S-006 DRAWING TITLE :
3- REFER DWG.S001 & S002 FOR GENERAL NOTES,GRADE OF CONCRETE, GROUND FLOOR
STEEL GRADE, CLEAR COVER,..., ETC.
4- REFER DWG.S003 TO S007 FOR GENERAL DETAILS
FRAMING LAYOUT
FOR BLOCK 3
REV No. DATE SCALE
5- IN CASE THERE IS NO TIE BEAM EXISTED BELOW BLOCK WORK, WF TO BE PROVIDED
0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-301 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

01* 04
01 02 03 05 06 07 08 09 10
46800

5200 5200 5175 5225 5200 5200 5200 5200 5200

2 NOTE: 2

1- REFER DWG.S001 & S002 FOR GENERAL NOTES,


GRADE OF CONCRETE,STEEL GRADE, CLEAR
A COVER,..., ETC.
2- REFER DWG.S003 TO S007 FOR GENERAL DETAILS
3- REFER DWG.S-401 FOR SECTION DETAILS
6T16(T&B) 6T16(T&B) 6T16(T&B) 6T16(T&B) 6T16(T&B) 6T16(T&B) 6T16(T&B) 6T16(T&B) 6T16(T&B) 4- STAIR AND OPENINGS TO BE RECONFIRMED BY
ARCH PRIOR CASTING.

1200

1200

1200

1200

1200

1200

1200
PS2 STIRRUPS T8@200 STIRRUPS T8@200 PS2
PS2 5- FOR EXACT SLAB EXTENT REFER TO ARCH. DWGS.
PS2 PS2 PS2 PS2

WITH STIRRUPS T10@150


B1
7140

350 THK. 1000 1000


350 THK. 1000
350 THK. 350 THK. 1000 1000
350 THK. 350 THK. 1000 1000
350 THK. 6- FOR ALL ELECTRO-MECHANICAL OPENINGS &

B1

WITH STIRRUPS T10@150


WITH STIRRUPS T10@150

WITH STIRRUPS T10@150


DROP DROP DROP DROP DROP DROP DROP

WITH STIRRUPS T10@150


SLEEVES REFER TOTHE APPROVED BUILDERS

WITH STIRRUPS T10@150

WITH STIRRUPS T10@150


3T16(T&B)

WITH STIRRUPS T10@150


3T12(T&B)

B1

B1
B1

WITH STIRRUPS T10@150


WORK DRAWINGS.

3T16(T&B)

3T16(T&B)
B1

B1

B1
3 3

B1
3T16(T&B)

WITH STIRRUPS T10@150


B1

6T16(T&B)
7- ADDITIONAL TOP REINF. CONCENTRIC WITH

3T16(T&B)
3T16(T&B)
3T16(T&B)
350 THK.
6T16(T&B)
3T12(T&B) 3T16(T&B) DROP 3T12(T&B) 3T12(T&B) 3T12(T&B) COLUMNS CENTER (U.N.O.)
3T12(T&B) WITH STIRRUPS T10@150 3T12(T&B)
T16@150C/C 8- ADDITIONAL BOTTOM REINF. SHOULD BE
L=3m LOCATED AT THE MID PONT BETWEEN COLUMN

3T16(T&B)

2000

2000
T16@150C/C
3000
T12@200C/C

1500
T16@200C/C CENTERS (U.N.O.)
B

L=3m
3T12(T&B) L=3m L=3m 9- REINFORCEMENT TO BE CUT WHERE NECESSARY.
PS1 +3.90
3T12(T&B) SSL +3.90 10-THE INDICATED REINF. LENGTH IS THE
+3.90 +3.90 2500
+3.90 4T16(T&B) +3.90 4T16(T&B) +3.90 +3.90 4T16(T&B)
+3.90 4T16(T&B) SSL SSL PROJECTED LENGTH ON THE PLAN.
SSL SSL 1700
SSL WITH STIRRUPS T10@150 SSL WITH STIRRUPS T12@100 SSL WITH STIRRUPS T12@100
SSL WITH STIRRUPS T12@100 11- ADDITIONAL TOP
3T12(T&B)

200 THK.SLAB 190 THK.SLAB 220 THK.SLAB 220 THK.SLAB 190 THK.SLAB 190 THK.SLAB ADDITIONAL BOTTOM
190 THK.SLAB 200 THK.SLAB

B1
190 THK.SLAB 12-SPAN MORE THAN 5M LENGTH SHOULD BE
T12-150 BOTT MESH T12-150 BOTT MESH T12-150 BOTT MESH T12-150 BOTT MESH T12-150 BOTT MESH T12-150 BOTT MESH T12-150 BOTT MESH
B1

T12-150 BOTT MESH


6540

T10-150 TOP MESH T10-150 TOP MESH T12-150 BOTT MESH PRECAMBERED AS FOLLOWS:
T10-150 TOP MESH

B1

B1

B1
T12-150 TOP MESH T12-150 TOP MESH T10-150 TOP MESH
5700

5700

5700

5700

5700

5700

5700
T10-150 TOP MESH

B1

B1
T10-150 TOP MESH T10-150 TOP MESH

T12@150C/C
450 THK.
DROP 3mm/m SIMPLY SUPPORTED

B1
2.5mm/m CONTINOUS SPANS
T16@200C/C

T16@200C/C

T16@200C/C
450 THK. T16@200C/C

L=3m
L=3m L=3m -WHILE ALL CANTILEVER WITH DIFFERENT
L=3m

L=3m
DROP
2000

2000
4 PS1 4
2000

CB1 2500 LENGTHS SHOULD BE PRECAMBERED 5mm/m

2000
T10@300C/C T10@300C/C T12@150C/C T10@300C/C T10@300C/C T10@300C/C T10@300C/C T10@300C/C

1000
2000 2000
L=3m L=3m L=3m L=3m L=3m L=3m L=3m L=3m
4T16(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B)
C 1400 STIRRUPS T8@200 1400

5 5

FIRST FLOOR FRAMING LAYOUT


SCALE- 1:100

T16@100 T12 LINKS


6 6

T10 LINKS

PS2
TYPICAL DETAIL FOR EXTRA TOP RFT
REV
TO PROVIDE THE BIGGER FROM IT AND THE SHOWN IN PLAN A No.
DATE

PROJECT:
REVISIONS BY CHK APP

PS1 RUKAN DEVELOPMENT


7 WADI AL SAFA 7 7

PLOT NO: 6654283 (TH-50)


OWNER OF TITLE:

SCHEDULE OF BEAMS
DUBAI LAND L.L.C.
BEAM SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT STIRRUPS
SIDE BARS NO OF
TYPE EXTRA @ STRAIGHT EXTRA @ AT SUPPORT AT MIDSPAN REMARKS PURCHASER :
STRAIGHT EXTRA @ CONT. O.E.F (F) LEGS
MM XMM DISCONT.
(A) MID SPAN(B) (C) SUPPORT (D) EACH SIDE OUTER INNER OUTER INNER 4T12 @ 75MM LINKS 3T12 @ 75MM LINKS
SUPPORT (E) (G1) (G2) (H1) (H2) CLOSED CLOSED Continental Investments
B1 200 x 700 2T20 2T20 2T20 3T20 2T16 2T12 T10-100 T10-150 2

2T16 2T12 T10-100 T10-100 2


STIRRUPS T10@150
CB1 200 x 700 2T16 AT ALL SIDES SECTION -A CONSULTANT:

8 TYPICAL DETAIL FOR SHEAR RFT PUNCHING SHEAR REINFORCEMENT 8

PS
FOR OPENINGS FOR ALL COLUMNS WITHOUT BEAMS DRAWING TITLE :

FIRST FLOOR
FRAMING LAYOUT
FOR BLOCK 3
REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-302 FOR APPROVAL


A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

01* 04
1
01 02 03 05 06 07 08 09 10 1

46800

5200 5200 5175 5225 5200 5200 5200 5200 5200

CANOPY TO BE DESIGNED & DETAILED BY SPECIALIST


& IT SHOULD BE SUBMITTED TO CONSULTANT FOR APPROVAL
BEFORE THE WORK COMMENCEMENT.

2 2

A 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B)


WITH STIRRUPS T10@100 WITH STIRRUPS T10@100

2000

2000

2000

2000

2000

2000

2000

2000
PS1
T12@300C/C T12@300C/C T12@300C/C T12@300C/C T12@300C/C T12@300C/C T12@300C/C T12@300C/C
L=3m L=3m L=3m L=3m L=3m L=3m L=3m L=3m
NOTE:

B1
1- REFER DWG.S001 & S002 FOR GENERAL NOTES,
GRADE OF CONCRETE,STEEL GRADE, CLEAR

B1
7140

COVER,..., ETC.

B1
2- REFER DWG.S003 TO S007 FOR GENERAL DETAILS
B1 3T12(T&B)

B1

B1

B1
3- REFER DWG.S-401 FOR SECTION DETAILS

B1

B1
3T12(T&B) 3T12(T&B) 4- STAIR AND OPENINGS TO BE RECONFIRMED BY
3 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3T12(T&B) 3
T16@200C/C
250 THK.
DROP
ARCH PRIOR CASTING.
L=3m 5- FOR EXACT SLAB EXTENT REFER TO ARCH. DWGS.

T16@200C/C
3T12(T&B)

L=3m
3000
T12@300C/C T12@300C/C T12@300C/C T12@300C/C T12@300C/C T12@300C/C T12@300C/C 6- FOR ALL ELECTRO-MECHANICAL OPENINGS &

2000
1500

2000

2000

2000
B

2000
2000

2000
L=3m L=3m L=3m L=3m L=3m L=3m L=3m SLEEVES REFER TOTHE APPROVED BUILDERS
PS1
WORK DRAWINGS.
3000 +7.10 +7.10 +7.10 +7.10 +7.10 7- ADDITIONAL TOP REINF. CONCENTRIC WITH
+7.10 +7.10 +7.10 1700 +7.10 SSL SSL
SSL SSL SSL SSL SSL SSL SSL COLUMNS CENTER (U.N.O.)
8- ADDITIONAL BOTTOM REINF. SHOULD BE
3T12(T&B)

LOCATED AT THE MID PONT BETWEEN COLUMN

B1
190 THK.SLAB 190 THK.SLAB 190 THK.SLAB
B1 220 THK.SLAB 220 THK.SLAB 190 THK.SLAB 190 THK.SLAB 190 THK.SLAB 190 THK.SLAB
T12-150 BOTT MESH T12-150 BOTT MESH T12-150 BOTT MESH T12-150 BOTT MESH
T12-150 BOTT MESH T12-150 BOTT MESH T12-150 BOTT MESH T12-150 BOTT MESH CENTERS (U.N.O.)
6540

B1

B1

B1
T12-150 BOTT MESH

B1

B1
T10-150 TOP MESH T10-150 TOP MESH T10-150 TOP MESH T10-150 TOP MESH T10-150 TOP MESH T10-150 TOP MESH 9- REINFORCEMENT TO BE CUT WHERE NECESSARY.
T12-150 TOP MESH T12-150 TOP MESH T10-150 TOP MESH
350 THK. 10-THE INDICATED REINF. LENGTH IS THE

B1
1400 DROP
PROJECTED LENGTH ON THE PLAN.

T16@200C/C
T16@200C/C

T16@200C/C T16@200C/C
L=3m L=3m 11-

L=3m
L=3m
2000

CB1 SR SR PS1 SR SR
2000

2000

2000

2000

2000

2000

2000

2000

2000

2000
T12@150C/C T12@150C/C T12@150C/C T12@150C/C T12@150C/C T12@150C/C T12@150C/C T12@150C/C 12-SPAN MORE THAN 5M LENGTH SHOULD BE

1000
2000
4 2000 4
4T16(T&B) L=3m 3T12(T&B) L=3m 3T12(T&B) L=3m 3T12(T&B) L=3m 3T12(T&B) L=3m 3T12(T&B) L=3m 3T12(T&B) L=3m 3T12(T&B) L=3m 3T12(T&B)
PRECAMBERED AS FOLLOWS:
C 1400
3mm/m SIMPLY SUPPORTED
2.5mm/m CONTINOUS SPANS
-WHILE ALL CANTILEVER WITH DIFFERENT
LENGTHS SHOULD BE PRECAMBERED 5mm/m
13-WATER PROOFING SYSTEM IS COMBO SYSTEM
( FOAM ).
14-FOR MEP EQUIPMENTS LOCATIONS , REFER TO
MEP & ARCH. DRAWINGS

5 5

ROOF FLOOR FRAMING LAYOUT


SCALE- 1:100

SCHEDULE OF BEAMS

BEAM SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT STIRRUPS


T16@150 TYPE
STRAIGHT
EXTRA @ STRAIGHT EXTRA @ CONT. EXTRA @
SIDE BARS
O.E.F (F)
AT SUPPORT AT MIDSPAN
NO OF LEGS
REMARKS
MM XMM DISCONT.
(A) MID SPAN(B) (C) SUPPORT (D) OUTER INNER OUTER INNER
EACH SIDE (G1) (G2) (H1) (H2)
SUPPORT (E)

B1 200 x 700 2T20 2T20 2T20 2T20 1T20 T10-100 T10-150 2

CB1 200 x 700 2T16 2T16 2T12 T10-100 T10-100 2


6 6

TYPICAL DETAIL FOR EXTRA TOP RFT T10 LINKS


T10 LINKS
TO PROVIDE THE BIGGER FROM IT AND THE SHOWN IN PLAN

A
REV
DATE REVISIONS BY CHK APP
No.
BEAM AS SCHEDULE PROJECT:
T10 LINKS PS RUKAN DEVELOPMENT
A
7 WADI AL SAFA 7 7

PLOT NO: 6654283 (TH-50)


PS OWNER OF TITLE:

B
DUBAI LAND L.L.C.
PURCHASER :

400 400

SR Continental Investments
3T10 @ 75MM LINKS
CLOSED
4T10 @ 75MM LINKS 3T10 @ 75MM LINKS CONSULTANT:

CLOSED CLOSED
8 STIRRUPS T10@150 SECTION -A 8

AT ALL SIDES
TYPICAL DETAIL FOR SHEAR RFT PS
PUNCHING SHEAR REINFORCEMENT DRAWING TITLE :

ROOF FLOOR
SECTION -B FOR OPENINGS FOR ALL COLUMNS WITHOUT BEAMS FRAMING LAYOUT
SR (SHEAR REINFORCEMENT) REV No. DATE
FOR BLOCK 3
SCALE

0 JAN-2022 AT A0
- WATER PROOFING SYSTEM IS COMBO SYSTEM ( FOAM ) JOB No. DRW.No. STATUS

- FOR MEP EQUIPMENTS LOCATIONS , REFER TO MEP & ARCH. DRAWINGS ----- S-303 FOR APPROVAL
A B C D E F G H I J K L
A B C D E F G H I J K L

DWG No. REFERENCE DRAWINGS

1 1

60MM SCREED
BLOCK WALL AS PER ARCH. C35 WITH MESH (A-252)
BLOCK WALL AS PER ARCH.
(IF NECESSARY TYP.)
(IF NECESSARY TYP.) 12mm FLEXCELL BOARD WITH YARD LEVEL
12mm FLEXCELL BOARD WITH 150

60
12mm FLEXCELL BOARD WITH 12mm FLEXCELL BOARD WITH JOINT FILLER (TYP.)
JOINT FILLER (TYP.)
JOINT FILLER (TYP.) JOINT FILLER (TYP.) GRADE SLAB AS PER ARCH.
GRADE SLAB AS PER LAYOUT 1T12 CORNER

150
GRADE SLAB GRADE SLAB AS PER LAYOUT 150 HCS
AS PER LAYOUT AS PER LAYOUT GRADE SLAB T8@200mmC/C
GRADE SLAB AS PER ARCH. CLOSED STIRRUPS

150
GRADE SLAB GRADE SLAB S.S.L.
S.S.L.
S.S.L. S.S.L. BEARING PAD 20mm THK. FIRST

200
2 (NEOPRENE BEARING STRIP) S.S.L. 2

SLAB THICK.
TIE BEAM 2T12
TIE BEAM SCHEDULE
TIE BEAM T12@150 SOLID BLOCK WALL
SCHEDULE
SCHEDULE
±0.00

AS/SPECIFIED
SLAB
BEAM AS PER AS PER LAYOUT
WATER PROOF MEMBRANE SCHEDULE
AS/SPECIFIED AS PER MEP.
& ARCH. BLOCK WORK
FOUNDATION LEVEL

100

100
FOUNDATION LEVEL AS PER ARCH

100

100
FOUNDATION LEVEL (IF NECESSARY TYP.)
100

100

250
100 100 PCC
3
100 100 3
100 100
TYPICAL SECTION
100 TYPICAL SECTION
SECTION -G2 (IF NECESSARY)
SECTION -G1 (IF NECESSARY)
SCALE 1:20
SCALE 1:20 TYPICAL DETAIL FOR PUMP MACHINE & TANK
SCALE 1:20

FIRST LANDING
4 S.S.L. S.S.L. 4

FOR TREAD & RISER DIM. FOR TREAD & RISER DIM.
AND STAIR DIRECTION C/C AND STAIR DIRECTION C/C
50 15
0
REFER TO ARCHI. DWGS. 2@1 REFER TO ARCHI. DWGS. 2@
T1 T1
1T10/STEP T16@150C/C 1T10/STEP T16@150C/C
T12@150C/C T12@150C/C
25

25
(TYP). (TYP).

0
0

BEAM BEAM
SCHEDULE SCHEDULE

T10@200C/C /C T10@200C/C /C
0C 0C
15 15
6@ 6@
T1 T 1

GROUND GROUND
5 S.S.L. S.S.L. 5

TYPICAL SECTION STAIRCASE WITH ONE FLIGHT TYPICAL SECTION STAIRCASE WITH TWO FLIGHT
TIE BEAM TIE BEAM
SCHEDULE SCHEDULE

6 6

NOTE:
1- REFER DWG.S001 & S002 FOR GENERAL NOTES,GRADE OF CONCRETE,
STEEL GRADE, CLEAR COVER,..., ETC.
2- REFER DWG.S003 TO S007 FOR GENERAL DETAILS

REV
DATE REVISIONS BY CHK APP
No.
AS PER ARC.
CANOPY AS PROJECT:
AS PER ARC.
1023

S.S.L
RUKAN DEVELOPMENT
AS PER ARC.

S.S.L PER LAYOUT

7 R.C. SLAB R.C. SLAB WADI AL SAFA 7 7


AS PER LAYOUT AS PER LAYOUT
ROOF ROOF AS PER ARC. 150 mm
PLOT NO: 6654283 (TH-50)
S.S.L
10
23

T10@200C/C S.S.L S.S.L OWNER OF TITLE:

T12@200C/C

T12@200C/C DUBAI LAND L.L.C.


T10@200C/C
SECTION (AT CANOPY) PURCHASER :
SECTION (AT PARAPET) SCALE :-1:20
SCALE :-1:20
R.C. SLAB Continental Investments
AS PER LAYOUT ROOF T8 alternative
S.S.L
CONSULTANT:

8 8

SECTION (AT PARAPET) DRAWING TITLE :


SCALE :-1:20
SECTIONS DETAILS
FOR BLOCK 3
REV No. DATE SCALE

0 JAN-2022 AT A0

JOB No. DRW.No. STATUS

----- S-401 FOR APPROVAL


A B C D E F G H I J K L