DATE 2/1/2023

SHIFT 1
PERSONIL FITRA

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (Optimized)
CMP #4 Run optimizer (Standby)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/1/2023
SHIFT 2
PERSONIL Junior

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (Optimized)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 1/1/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13066
CMP #3 8897
CMP #4 14248
CMP #5 4407
CMP #6 33148
CMP #7 31352

LOAD HOURS
CMP #5 3308
CMP #6 26068

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 1/1/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual

6442
28782
4.5

Repair Panel VFD terbakar


optimizer (Standby)
optimizer (Baseload)
optimizer (Optimize)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/2/2023
SHIFT 1
PERSONIL FITRA

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Base Load)
CMP #4 Run optimizer (optimaze)
CMP #5 stop Local
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS
pemasangan flexibel join cmp 1
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/2/2023
SHIFT 2
PERSONIL Junior

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Base Load)
optimizer (optimaze)
Local
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/2/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13069
CMP #3 8920
CMP #4 14266
CMP #5 4407
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3308
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/2/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual

5599
27318
4.9

Repair Panel VFD terbakar


optimizer (Optimized)
optimizer (Standby)
optimizer (Baseload)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/3/2023
SHIFT 1
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Optimized)
CMP #3 Run optimizer (Standby)
CMP #4 Run optimizer (Baseload)
CMP #5 Stop Local (Off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/3/2023
SHIFT 2
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Optimized)
optimizer (Standby)
optimizer (Baseload)
Local (Off)
Local (Baseload)
Repair Inverter rusak

Hasil Remark
DATE 2/3/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13088
CMP #3 8923
CMP #4 14290
CMP #5 4407
CMP #6 33197
CMP #7 31352

LOAD HOURS
CMP #5 3308
CMP #6 26116

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/3/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual

5417
27166
5.0

Repair Panel VFD terbakar


optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil Remark
DATE 2/4/2023
SHIFT 1
PERSONIL Junior

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimized)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 stop Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS
Top up N2 liquid
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/4/2023
SHIFT 2
PERSONIL RIZKI

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 stop
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimized)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/4/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13088
CMP #3 8928
CMP #4 14291
CMP #5 4431
CMP #6 33221
CMP #7 31352

LOAD HOURS
CMP #5 3326
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/4/2023
SHIFT 3
PERSONIL RIZKI

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual

6252
28194
4.5

Repair Panel VFD terbakar


optimizer (Baseload)
optimizer (Optimized)
optimizer (Standby)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/5/2023
SHIFT 1
PERSONIL Sandi

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimized)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/5/2023
SHIFT 2
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimized)
optimizer (Standby)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/5/2023

RUNNING HOURS
CMP #1 9968
CMP #2 113111
CMP #3 8939
CMP #4 14294
CMP #5 4431
CMP #6 33245
CMP #7 31352

LOAD HOURS
CMP #5 3326
CMP #6 26164

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/5/2023
SHIFT 3
PERSONIL Fitra

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual

6252
28194
4.5

Repair Panel VFD terbakar


optimizer (Baseload)
optimizer (Optimized)
optimizer (Standby)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/6/2023
SHIFT 1
PERSONIL Junior

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (stand by)
CMP #3 Run optimizer (baseload)
CMP #4 Run optimizer (optimized)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/6/2023
SHIFT 2
PERSONIL Rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (stand by)
optimizer (baseload)
optimizer (optimized)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/6/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13115
CMP #3 8963
CMP #4 14313
CMP #5 4431
CMP #6 33245
CMP #7 31352

LOAD HOURS
CMP #5 3326
CMP #6 26164

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/6/2023
SHIFT 3
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual

5432
27312
5.0

Repair Panel VFD terbakar


optimizer (stand by)
optimizer (baseload)
optimizer (optimized)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/6/2023
SHIFT 1
PERSONIL Junior

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (optimized)
CMP #4 Run optimizer (stand by)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/7/2023
SHIFT 2
PERSONIL RIZKI

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (optimized)
optimizer (stand by)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/7/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13130
CMP #3 8968
CMP #4 14337
CMP #5 4431
CMP #6 33293
CMP #7 31352

LOAD HOURS
CMP #5 3326
CMP #6 26212

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/7/2023
SHIFT 3
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual

6493
28706
4.4

Repair Panel VFD terbakar


optimizer (baseload)
optimizer (optimized)
optimizer (stand by)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/8/2023
SHIFT 1
PERSONIL efin

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (stand by)
CMP #3 Run optimizer (optimized)
CMP #4 Run optimizer (stand by)
CMP #5 Run Local (baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/8/2023
SHIFT 2
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (stand by)
optimizer (optimized)
optimizer (stand by)
Local (baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/8/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13132
CMP #3 8987
CMP #4 14340
CMP #5 4454
CMP #6 33317
CMP #7 31352

LOAD HOURS
CMP #5 3348
CMP #6 26236

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/8/2023
SHIFT 3
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual

6741
28720
4.3

Repair Panel VFD terbakar


optimizer (stand by)
optimizer (optimized)
optimizer (stand by)
Local (baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/9/2023
SHIFT 1
PERSONIL Sandi

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (OFF)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/9/2023
SHIFT 2
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/9/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13155
CMP #3 9001
CMP #4 14343
CMP #5 4454
CMP #6 33341
CMP #7 31352

LOAD HOURS
CMP #5 3348
CMP #6 26260

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/9/2023
SHIFT 3
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual

6723
27934
4.2

Repair Panel VFD terbakar


optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/10/2023
SHIFT 1
PERSONIL JUNIOR

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (OFF)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/10/2023
SHIFT 2
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/10/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13179
CMP #3 9015
CMP #4 14346
CMP #5 4454
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3348
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/10/2023
SHIFT 3
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual

6760
27960
4.1

Repair Panel VFD terbakar


optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/11/2023
SHIFT 1
PERSONIL riski

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (OFF)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/11/2023
SHIFT 2
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/11/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13184
CMP #3 9039
CMP #4 14362
CMP #5 4454
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3348
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/11/2023
SHIFT 3
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual

6818
28488
4.2

Repair Panel VFD terbakar


optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/12/2023
SHIFT 1
PERSONIL Rizki

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Optimize)
CMP #3 Run optimizer (Standby)
CMP #4 Run optimizer (Baseload)
CMP #5 Stop Local (OFF)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/12/2023
SHIFT 2
PERSONIL JUNIOR

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Optimize)
optimizer (Standby)
optimizer (Baseload)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/12/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13198
CMP #3 9042
CMP #4 14386
CMP #5 4454
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3348
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/12/2023
SHIFT 3
PERSONIL JUNIOR

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual

6539
27824
4.3

Repair Panel VFD terbakar


optimizer (Optimize)
optimizer (Standby)
optimizer (Baseload)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/13/2023
SHIFT 1
PERSONIL Rizki

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/13/2023
SHIFT 2
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/13/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13199
CMP #3 9058
CMP #4 14389
CMP #5 4478
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3371
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/13/2023
SHIFT 3
PERSONIL SANDI

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS
Change CMP hari ke 1
TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual

6937
28734
4.1

Repair Panel VFD terbakar


optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/14/2023
SHIFT 1
PERSONIL Rizki

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/14/2023
SHIFT 2
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/14/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13223
CMP #3 9075
CMP #4 14397
CMP #5 4478
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3371
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/14/2023
SHIFT 3
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS
Change CMP hari ke 2
TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual

6678
27978
4.2

Repair Panel VFD terbakar


optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/15/2023
SHIFT 1
PERSONIL Rizki

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimize)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/15/2023
SHIFT 2
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (standby)
optimizer (Baseload)
optimizer (Optimize)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/15/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13228
CMP #3 9099
CMP #4 14411
CMP #5 4478
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3372
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/15/2023
SHIFT 3
PERSONIL Sandi

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS
Change CMP hari ke 3
TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual

7356
29108
4.0

Repair Panel VFD terbakar


optimizer (standby)
optimizer (Baseload)
optimizer (Optimize)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/16/2023
SHIFT 1
PERSONIL efin

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimize)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/16/2023
SHIFT 2
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (standby)
optimizer (Baseload)
optimizer (Optimize)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/16/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13245
CMP #3 9104
CMP #4 14435
CMP #5 4478
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3372
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/16/2023
SHIFT 3
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS
Change CMP hari ke 4
TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

6825
28062
4.1

Repair Panel VFD terbakar


optimizer (standby)
optimizer (Baseload)
optimizer (Optimize)
Local (off)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/17/2023
SHIFT 1
PERSONIL RIZKI

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/17/2023
SHIFT 2
PERSONIL Sandi

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/17/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13248
CMP #3 9124
CMP #4 14440
CMP #5 4501
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3393
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/17/2023
SHIFT 3
PERSONIL Sandi

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS
Change CMP hari ke 1
TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

5876
27850
4.7

Repair Panel VFD terbakar


optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/18/2023
SHIFT 1
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS
top up tangki samator
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark

TWIT
DATE 2/18/2023
SHIFT 2
PERSONIL JUNIOR

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/18/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13272
CMP #3 9141
CMP #4 14445
CMP #5 4502
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3393
CMP #6 26477

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/18/2023
SHIFT 3
PERSONIL JUNIOR

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS
Change CMP hari ke 2

Remark TROUBLE SHIFT


Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

6399
27240
4.3

Repair Panel VFD terbakar


optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/19/2023
SHIFT 1
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimized)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark

TWIT
DATE 2/19/2023
SHIFT 2
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Baseload)
optimizer (Optimized)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/19/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13280
CMP #3 9165
CMP #4 14462
CMP #5 4502
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3393
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/19/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

Remark TROUBLE SHIFT


Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

7038
28814
4.1

Repair Panel VFD terbakar


optimizer (Standby)
optimizer (Baseload)
optimizer (Optimized)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/20/2023
SHIFT 1
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (standby)
CMP #3 Run optimizer (optimizer)
CMP #4 Run optimizer (baseload)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark

TWIT
DATE 2/20/2023
SHIFT 2
PERSONIL Sandi

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS
Top Up Nitrogen
TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Optimize)
optimizer (Standby)
optimizer (baseload)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/20/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13295
CMP #3 9173
CMP #4 14486
CMP #5 4501
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3393
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/20/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

Remark TROUBLE SHIFT


Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

6931
28518
4.1

Repair Panel VFD terbakar


optimizer (Optimize)
optimizer (Standby)
optimizer (baseload)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/21/2023
SHIFT 1
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark

TWIT
DATE 2/21/2023
SHIFT 2
PERSONIL JUNIOR

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS
Top Up Nitrogen
TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/21/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13299
CMP #3 9195
CMP #4 14502
CMP #5 4525
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3416
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/21/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS

Remark TROUBLE SHIFT


Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

6722
28154
4.2

Repair Panel VFD terbakar


optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/22/2023
SHIFT 1
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/22/2023
SHIFT 2
PERSONIL Sandi

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/22/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13324
CMP #3 9211
CMP #4 14507
CMP #5 4525
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3416
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/22/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

Remark TROUBLE SHIFT


Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

6724
27262
4.1

Repair Panel VFD terbakar


optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/23/2023
SHIFT 1
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimized)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/23/2023
SHIFT 2
PERSONIL JUNIOR

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Baseload)
optimizer (Optimized)
local off
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/23/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13333
CMP #3 9235
CMP #4 14524
CMP #5 4525
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3416
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/23/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

Remark TROUBLE SHIFT


Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

7321
28648
3.9

Repair Panel VFD terbakar


optimizer (Standby)
optimizer (Baseload)
optimizer (Optimized)
local off
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/24/2023
SHIFT 1
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (optimized)
CMP #3 Run optimizer (standby)
CMP #4 Run optimizer (baseload)
CMP #5 stop Local (Off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/24/2023
SHIFT 2
PERSONIL Rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (optimized)
optimizer (standby)
optimizer (baseload)
Local (Off)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/24/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13352
CMP #3 9241
CMP #4 14548
CMP #5 4525
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3416
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/24/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

Remark TROUBLE SHIFT


Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

6446
27620
4.3

Repair Panel VFD terbakar


optimizer (optimized)
optimizer (standby)
optimizer (baseload)
Local (Off)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/25/2023
SHIFT 1
PERSONIL SANDI

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS
Pengecekan dew point CMP 4 (2.10)
Pengecekan dew point CMP 5 (1.99)
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/25/2023
SHIFT 2
PERSONIL Rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/25/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13356
CMP #3 9258
CMP #4 14557
CMP #5 4549
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3439
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/25/2023
SHIFT 3
PERSONIL rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop

AKTIVITAS
N2 to jetty 1.5 jam

Remark TROUBLE SHIFT


Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

6855
28220
4.1

Repair Panel VFD terbakar


optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
DATE 2/26/2023
SHIFT 1
PERSONIL JUNIOR

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 off local off
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS
Top Up N2 liquid
OVERSHIFT Action
Sett samator 6 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/26/2023
SHIFT 2
PERSONIL Rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Off
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
local off
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/26/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13380
CMP #3 9269
CMP #4 14561
CMP #5 4549
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3440
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/26/2023
SHIFT 3
PERSONIL Rizki

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Off
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

6737
28662
4.3

Repair
optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
local off
Local (Baseload)
Repair

Hasil
Remark
DATE 2/27/2023
SHIFT 1
PERSONIL SANDI

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimize)
CMP #5 Stop local off
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 6 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/27/2023
SHIFT 2
PERSONIL efin

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS
top up samator
TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Baseload)
optimizer (Optimize)
local off
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/27/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13382
CMP #3 9292
CMP #4 14573
CMP #5 4549
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3439
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/27/2023
SHIFT 3
PERSONIL fitra

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

5784
26930
4.7

Repair Panel VFD terbakar


optimizer (Standby)
optimizer (Baseload)
optimizer (Optimize)
local off
Local (Baseload)
Repair Inverter rusak

Hasil
Remark
c 2/28/2023
SHIFT 1
PERSONIL JUNIOR

STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Optimized)
CMP #3 Run optimizer (stand by)
CMP #4 Run optimizer (baseload)
CMP #5 Stop local off
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair

AKTIVITAS

OVERSHIFT Action
Sett samator 6 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
N2 to jetty u/ keperluan blanketing selama 1 jam

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar

Inverter rusak

Hasil Remark
DATE 2/28/2023
SHIFT 2
PERSONIL RIZKI

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Optimized)
optimizer (stand by)
optimizer (baseload)
local off
Local (Baseload)
Repair Inverter rusak

Hasil
DATE 2/28/2023

RUNNING HOURS
CMP #1 9968
CMP #2 13396
CMP #3 9295
CMP #4 14596
CMP #5 4549
CMP #6
CMP #7 31352

LOAD HOURS
CMP #5 3440
CMP #6

STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop

STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal

CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas

DATE 2/28/2023
SHIFT 3
PERSONIL Subur

STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop

AKTIVITAS

TROUBLE SHIFT
Remark Deskripsi Action

OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%

TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual

5719
26446
4.6

Repair Panel VFD terbakar


optimizer (Optimized)
optimizer (stand by)
optimizer (baseload)
local off
Local (Baseload)
Repair Inverter rusak

Hasil
Remark