SHIFT 1
PERSONIL FITRA
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (Optimized)
CMP #4 Run optimizer (Standby)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/1/2023
SHIFT 2
PERSONIL Junior
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (Optimized)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 1/1/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13066
CMP #3 8897
CMP #4 14248
CMP #5 4407
CMP #6 33148
CMP #7 31352
LOAD HOURS
CMP #5 3308
CMP #6 26068
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 1/1/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual
6442
28782
4.5
Hasil
Remark
DATE 2/2/2023
SHIFT 1
PERSONIL FITRA
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Base Load)
CMP #4 Run optimizer (optimaze)
CMP #5 stop Local
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
pemasangan flexibel join cmp 1
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/2/2023
SHIFT 2
PERSONIL Junior
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Base Load)
optimizer (optimaze)
Local
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/2/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13069
CMP #3 8920
CMP #4 14266
CMP #5 4407
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3308
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/2/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual
5599
27318
4.9
Hasil
Remark
DATE 2/3/2023
SHIFT 1
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Optimized)
CMP #3 Run optimizer (Standby)
CMP #4 Run optimizer (Baseload)
CMP #5 Stop Local (Off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/3/2023
SHIFT 2
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Optimized)
optimizer (Standby)
optimizer (Baseload)
Local (Off)
Local (Baseload)
Repair Inverter rusak
Hasil Remark
DATE 2/3/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13088
CMP #3 8923
CMP #4 14290
CMP #5 4407
CMP #6 33197
CMP #7 31352
LOAD HOURS
CMP #5 3308
CMP #6 26116
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/3/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual
5417
27166
5.0
Hasil Remark
DATE 2/4/2023
SHIFT 1
PERSONIL Junior
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimized)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 stop Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
Top up N2 liquid
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/4/2023
SHIFT 2
PERSONIL RIZKI
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 stop
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimized)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/4/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13088
CMP #3 8928
CMP #4 14291
CMP #5 4431
CMP #6 33221
CMP #7 31352
LOAD HOURS
CMP #5 3326
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/4/2023
SHIFT 3
PERSONIL RIZKI
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #3 Penggantian busbar & flexible joint not avaible
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual
6252
28194
4.5
Hasil
Remark
DATE 2/5/2023
SHIFT 1
PERSONIL Sandi
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimized)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/5/2023
SHIFT 2
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimized)
optimizer (Standby)
Local (off)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/5/2023
RUNNING HOURS
CMP #1 9968
CMP #2 113111
CMP #3 8939
CMP #4 14294
CMP #5 4431
CMP #6 33245
CMP #7 31352
LOAD HOURS
CMP #5 3326
CMP #6 26164
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/5/2023
SHIFT 3
PERSONIL Fitra
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual
6252
28194
4.5
Hasil
Remark
DATE 2/6/2023
SHIFT 1
PERSONIL Junior
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (stand by)
CMP #3 Run optimizer (baseload)
CMP #4 Run optimizer (optimized)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/6/2023
SHIFT 2
PERSONIL Rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (stand by)
optimizer (baseload)
optimizer (optimized)
Local (off)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/6/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13115
CMP #3 8963
CMP #4 14313
CMP #5 4431
CMP #6 33245
CMP #7 31352
LOAD HOURS
CMP #5 3326
CMP #6 26164
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/6/2023
SHIFT 3
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual
5432
27312
5.0
Hasil
Remark
DATE 2/6/2023
SHIFT 1
PERSONIL Junior
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (optimized)
CMP #4 Run optimizer (stand by)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/7/2023
SHIFT 2
PERSONIL RIZKI
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (optimized)
optimizer (stand by)
Local (off)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/7/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13130
CMP #3 8968
CMP #4 14337
CMP #5 4431
CMP #6 33293
CMP #7 31352
LOAD HOURS
CMP #5 3326
CMP #6 26212
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/7/2023
SHIFT 3
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual
6493
28706
4.4
Hasil
Remark
DATE 2/8/2023
SHIFT 1
PERSONIL efin
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (stand by)
CMP #3 Run optimizer (optimized)
CMP #4 Run optimizer (stand by)
CMP #5 Run Local (baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/8/2023
SHIFT 2
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (stand by)
optimizer (optimized)
optimizer (stand by)
Local (baseload)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/8/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13132
CMP #3 8987
CMP #4 14340
CMP #5 4454
CMP #6 33317
CMP #7 31352
LOAD HOURS
CMP #5 3348
CMP #6 26236
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/8/2023
SHIFT 3
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual
6741
28720
4.3
Hasil
Remark
DATE 2/9/2023
SHIFT 1
PERSONIL Sandi
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (OFF)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/9/2023
SHIFT 2
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/9/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13155
CMP #3 9001
CMP #4 14343
CMP #5 4454
CMP #6 33341
CMP #7 31352
LOAD HOURS
CMP #5 3348
CMP #6 26260
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/9/2023
SHIFT 3
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Jalur freeze
Manual
Manual
Manual
Manual
6723
27934
4.2
Hasil
Remark
DATE 2/10/2023
SHIFT 1
PERSONIL JUNIOR
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (OFF)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/10/2023
SHIFT 2
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/10/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13179
CMP #3 9015
CMP #4 14346
CMP #5 4454
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3348
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/10/2023
SHIFT 3
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual
6760
27960
4.1
Hasil
Remark
DATE 2/11/2023
SHIFT 1
PERSONIL riski
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (OFF)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/11/2023
SHIFT 2
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/11/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13184
CMP #3 9039
CMP #4 14362
CMP #5 4454
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3348
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/11/2023
SHIFT 3
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual
6818
28488
4.2
Hasil
Remark
DATE 2/12/2023
SHIFT 1
PERSONIL Rizki
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Optimize)
CMP #3 Run optimizer (Standby)
CMP #4 Run optimizer (Baseload)
CMP #5 Stop Local (OFF)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/12/2023
SHIFT 2
PERSONIL JUNIOR
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Optimize)
optimizer (Standby)
optimizer (Baseload)
Local (OFF)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/12/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13198
CMP #3 9042
CMP #4 14386
CMP #5 4454
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3348
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/12/2023
SHIFT 3
PERSONIL JUNIOR
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual
6539
27824
4.3
Hasil
Remark
DATE 2/13/2023
SHIFT 1
PERSONIL Rizki
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/13/2023
SHIFT 2
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/13/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13199
CMP #3 9058
CMP #4 14389
CMP #5 4478
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3371
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/13/2023
SHIFT 3
PERSONIL SANDI
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
Change CMP hari ke 1
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual
6937
28734
4.1
Hasil
Remark
DATE 2/14/2023
SHIFT 1
PERSONIL Rizki
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/14/2023
SHIFT 2
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
Local (off)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/14/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13223
CMP #3 9075
CMP #4 14397
CMP #5 4478
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3371
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/14/2023
SHIFT 3
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
Change CMP hari ke 2
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual
6678
27978
4.2
Hasil
Remark
DATE 2/15/2023
SHIFT 1
PERSONIL Rizki
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimize)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/15/2023
SHIFT 2
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (standby)
optimizer (Baseload)
optimizer (Optimize)
Local (off)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/15/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13228
CMP #3 9099
CMP #4 14411
CMP #5 4478
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3372
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/15/2023
SHIFT 3
PERSONIL Sandi
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
Change CMP hari ke 3
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
Lakukan pengecekan oil filter compressor no. 2
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Repair Jalur freeze
Manual
Manual
Manual
Manual
7356
29108
4.0
Hasil
Remark
DATE 2/16/2023
SHIFT 1
PERSONIL efin
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimize)
CMP #5 Stop Local (off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/16/2023
SHIFT 2
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (standby)
optimizer (Baseload)
optimizer (Optimize)
Local (off)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/16/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13245
CMP #3 9104
CMP #4 14435
CMP #5 4478
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3372
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/16/2023
SHIFT 3
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
Change CMP hari ke 4
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
6825
28062
4.1
Hasil
Remark
DATE 2/17/2023
SHIFT 1
PERSONIL RIZKI
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/17/2023
SHIFT 2
PERSONIL Sandi
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/17/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13248
CMP #3 9124
CMP #4 14440
CMP #5 4501
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3393
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 Run
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/17/2023
SHIFT 3
PERSONIL Sandi
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
Change CMP hari ke 1
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
5876
27850
4.7
Hasil
Remark
DATE 2/18/2023
SHIFT 1
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
top up tangki samator
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
TWIT
DATE 2/18/2023
SHIFT 2
PERSONIL JUNIOR
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/18/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13272
CMP #3 9141
CMP #4 14445
CMP #5 4502
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3393
CMP #6 26477
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/18/2023
SHIFT 3
PERSONIL JUNIOR
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
Change CMP hari ke 2
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
6399
27240
4.3
Hasil
Remark
DATE 2/19/2023
SHIFT 1
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimized)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
TWIT
DATE 2/19/2023
SHIFT 2
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Baseload)
optimizer (Optimized)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/19/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13280
CMP #3 9165
CMP #4 14462
CMP #5 4502
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3393
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/19/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
7038
28814
4.1
Hasil
Remark
DATE 2/20/2023
SHIFT 1
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (standby)
CMP #3 Run optimizer (optimizer)
CMP #4 Run optimizer (baseload)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
TWIT
DATE 2/20/2023
SHIFT 2
PERSONIL Sandi
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
Top Up Nitrogen
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Optimize)
optimizer (Standby)
optimizer (baseload)
Local (OFF)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/20/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13295
CMP #3 9173
CMP #4 14486
CMP #5 4501
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3393
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/20/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
6931
28518
4.1
Hasil
Remark
DATE 2/21/2023
SHIFT 1
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
TWIT
DATE 2/21/2023
SHIFT 2
PERSONIL JUNIOR
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
Top Up Nitrogen
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/21/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13299
CMP #3 9195
CMP #4 14502
CMP #5 4525
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3416
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/21/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
6722
28154
4.2
Hasil
Remark
DATE 2/22/2023
SHIFT 1
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/22/2023
SHIFT 2
PERSONIL Sandi
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Baseload)
optimizer (Optimize)
optimizer (Standby)
Local (OFF)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/22/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13324
CMP #3 9211
CMP #4 14507
CMP #5 4525
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3416
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/22/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
6724
27262
4.1
Hasil
Remark
DATE 2/23/2023
SHIFT 1
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimized)
CMP #5 stop Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/23/2023
SHIFT 2
PERSONIL JUNIOR
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Baseload)
optimizer (Optimized)
local off
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/23/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13333
CMP #3 9235
CMP #4 14524
CMP #5 4525
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3416
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/23/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
7321
28648
3.9
Hasil
Remark
DATE 2/24/2023
SHIFT 1
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (optimized)
CMP #3 Run optimizer (standby)
CMP #4 Run optimizer (baseload)
CMP #5 stop Local (Off)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/24/2023
SHIFT 2
PERSONIL Rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (optimized)
optimizer (standby)
optimizer (baseload)
Local (Off)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/24/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13352
CMP #3 9241
CMP #4 14548
CMP #5 4525
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3416
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/24/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
6446
27620
4.3
Hasil
Remark
DATE 2/25/2023
SHIFT 1
PERSONIL SANDI
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 Run Local (Baseload)
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
Pengecekan dew point CMP 4 (2.10)
Pengecekan dew point CMP 5 (1.99)
OVERSHIFT Action
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/25/2023
SHIFT 2
PERSONIL Rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Optimize)
optimizer (Standby)
Local (Baseload)
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/25/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13356
CMP #3 9258
CMP #4 14557
CMP #5 4549
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3439
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/25/2023
SHIFT 3
PERSONIL rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Run
CMP #6 Run
CMP #7 Stop
AKTIVITAS
N2 to jetty 1.5 jam
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
6855
28220
4.1
Hasil
Remark
DATE 2/26/2023
SHIFT 1
PERSONIL JUNIOR
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (baseload)
CMP #3 Run optimizer (Optimize)
CMP #4 Run optimizer (Standby)
CMP #5 off local off
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
Top Up N2 liquid
OVERSHIFT Action
Sett samator 6 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/26/2023
SHIFT 2
PERSONIL Rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Off
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
local off
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/26/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13380
CMP #3 9269
CMP #4 14561
CMP #5 4549
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3440
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/26/2023
SHIFT 3
PERSONIL Rizki
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Off
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
6737
28662
4.3
Repair
optimizer (baseload)
optimizer (Optimize)
optimizer (Standby)
local off
Local (Baseload)
Repair
Hasil
Remark
DATE 2/27/2023
SHIFT 1
PERSONIL SANDI
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Standby)
CMP #3 Run optimizer (Baseload)
CMP #4 Run optimizer (Optimize)
CMP #5 Stop local off
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 6 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/27/2023
SHIFT 2
PERSONIL efin
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
top up samator
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Standby)
optimizer (Baseload)
optimizer (Optimize)
local off
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/27/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13382
CMP #3 9292
CMP #4 14573
CMP #5 4549
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3439
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/27/2023
SHIFT 3
PERSONIL fitra
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
CMP supply to jetty 06:00 - 09:00 estimasi 3 Jam
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
5784
26930
4.7
Hasil
Remark
c 2/28/2023
SHIFT 1
PERSONIL JUNIOR
STATUS SYSTEM
CMP #1 Stop Repair
CMP #2 Run optimizer (Optimized)
CMP #3 Run optimizer (stand by)
CMP #4 Run optimizer (baseload)
CMP #5 Stop local off
CMP #6 Run Local (Baseload)
CMP #7 Stop Repair
AKTIVITAS
OVERSHIFT Action
Sett samator 6 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
N2 to jetty u/ keperluan blanketing selama 1 jam
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
UNIT AIR COMPRESSOR
HARI
2 3 4 5 6
1 Baseload Optimized Standby Local Off Baseload
2 Standby Baseload Optimized Local Off Baseload
3 Optimized Standby Baseload Local Off Baseload
4 Standby Optimize Standby Baseload Baseload
Panel VFD terbakar
Inverter rusak
Hasil Remark
DATE 2/28/2023
SHIFT 2
PERSONIL RIZKI
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Progress
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Panel VFD terbakar
optimizer (Optimized)
optimizer (stand by)
optimizer (baseload)
local off
Local (Baseload)
Repair Inverter rusak
Hasil
DATE 2/28/2023
RUNNING HOURS
CMP #1 9968
CMP #2 13396
CMP #3 9295
CMP #4 14596
CMP #5 4549
CMP #6
CMP #7 31352
LOAD HOURS
CMP #5 3440
CMP #6
STATUS DRYER
Dryer #1 Stop
Dryer #2 Run
Dryer #3 Run
Dryer #4 Run
Dryer #5 stop
STATUS ADV
Dryer #1 Normal
Dryer #2 Normal
Dryer #3 Normal
Dryer #4 Normal
Dryer #5 Normal
Filter in Dryer #1 Normal
Filter in Dryer #2 Normal
Filter in Dryer #3 Normal
Filter in Dryer #4 Normal
Filter in Dryer #5 Normal
Receiver #1 Normal
Receiver #2 Normal
Receiver #3 Normal
Receiver #4 Normal
Receiver #5 Normal
Receiver CPC #1 Normal
Receiver CPC #2 Normal
Receiver CPC #3 Normal
Receiver CPC #4 Normal
CAN GAS
Produksi N2 FT-1432
Air Compressed Consumption FT-1355
Ratio Can Gas
DATE 2/28/2023
SHIFT 3
PERSONIL Subur
STATUS SYSTEM
CMP #1 Stop
CMP #2 Run
CMP #3 Run
CMP #4 Run
CMP #5 Stop
CMP #6 Run
CMP #7 Stop
AKTIVITAS
TROUBLE SHIFT
Remark Deskripsi Action
OVERSHIFT
Sett samator 4.5 bar dan QTY EVA #1
VALVE TO JETTY (CMP): 25%
VALVE TO JETTY (N2): 0%
TROUBLE LIST
Deskripsi Deskripsi
CMP #1 Proses perbaikan inverter (inverter terbakar)
CMP #7 VSD Inverter trouble
Dryer #1 Jalur freeze
Dryer #3 Pressure swich rusak
ADV Filter in Dryer #3 Belum ada power
Lampu area compressor 2 titik OFF dan 2 titik DIM
Pintu panel LV CMP tidak bisa di tutup otomatis
Pressure oil compressor no. 2, warning alarm (1.3 bar)
Display AD 3 error
Repair Jalur freeze
Manual
Manual
Manual
Manual
5719
26446
4.6
Hasil
Remark