Professional Documents
Culture Documents
BATTERY
Specification 6-GFM-2.3
Nominal Voltage 12V
Nominal Capacity(20HR) 2.3AH
Length 178 2mm (7.00 inches)
Width 35 1mm (1.38 inches)
Dimensions
Container Height 60 1mm (2.36 inches)
Total Height (with Terminal) 66 1mm (2.60 inches)
Approx Weight Approx 0.93 kg
Terminal F1
Container Material ABS
2.30 AH/0.115A (20hr ,1.80V/cell,250C/770F)
2.14 AH/0.214A (10hr,1.80V/cell,250C/770F) Applications
Rated Capacity 1.84 AH/0.368A (5hr,1.75V/cell,250C/770F)
1.725 AH/0.575A (3hr,1.75V/cell,250C/770F) All purpose
1.403 AH/1.403A (1hr,1.60V/cell,250C/770F) Uninterruptable Power Supply (UPS)
Max. Discharge Current 34.5A (5s) Electric Power System (EPS)
Internal Resistance Approx 90mÙ Emergency backup power supply
0
Discharge : -15 50 C (5 122 F) 0
Emergency light
Operating Temp.Range Charge : 0 400C (32 1040F) Railway signal
Storage : -15 400C (5 1040F)
Aircraft signal
Nominal Operating Temp. Range 25 30C (77 50F ) Alarm and security system
Initial Charging Current less than 0.69A.Voltage Electronic apparatus and equipment
Cycle Use
14.4V~15.0V at 250 C(770 F)Temp. Coefficient -30mV/0C
Communication power supply
No limit on Initial Charging Current Voltage DC power supply
Standby Use
13.5V~13.8V at 250 C(770 F)Temp. Coefficient -20mV/0C Auto control system
40o C (104o F) 103%
Capacity affected by
25o C ( 77o F) 100%
Temperature
0o C ( 32o F) 86%
Pattern PT series battery may be stored for up to 6 months
Self Discharge at 250 C(770F) and then a freshening charge is required.
For higher temperatures the time interval will be shorter. 9
0 0
Constant Current Discharge (Amperes) at 25 C (77 F )
1
Dimensions
F1 Terminal
Unit: mm [inches]
35 1
4.75(0.187)
60 1
66 1
10.5
3.2(0.126)
178 1
6.35(0.25)
0.8(0.031)
12.0
0.25
120 15.0
110 Charged Volume
Terminal Voltage(V)
11.0
0.20
100
0.093C 0.05C 14.0
0.207C 90 Charge Voltage
10.0 0.4C 80 0.15 (Constant 2.25v/cell)
70 13.0
1C 0.628C
9.0 60
After 50% Discharge
50 0.10
12.0
40 After 100% Discharge
8.0 30
3C 2C 0.05 11.0
20
10 Charging Current
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20
0 0
Min H
0 4 8 12 16 20 24 28 32 36 40
Discharge Time Charging Time(hours)
Temperature Effects in Relation to Battery Capacity Effect of Temperature on Long Term Float Life
10
120 8
6
A
100
0 .0 5 C 5
Charging voltage :
A
0 .1 C 4
2.25V/cell
80
Life expectancy(year)
3
0 .2 C A
Capacity %
60 2
1 .0 C A
40
A 3. 0C A 1
2 .0 C
20
0 0.5
-20 -10 0 10 20 30 40 50 20 30 40 50 0
O
C
68 86 104 122 F
0
Temperature( C) Battery temperature
120 60
B
400C 300C
100 40
80 C
20
Capcity(%)
60
100% 50% 30% 0
DOD DOD DOD 2 4 6 8 10 12
40
Ambient Termperature: Storage Time(Months)
25oC (77oF)
20 No supplementary charge required
A (Carry out supplementary charge before use if 100% capacity is required.)
0 Supplementary charge required before use.Optional charging way as below:
0 200 400 600 800 1000 1200 1.Charged for above 3 days at limted current 0.25CA and constant volatge 2.25V/cell.
B 2.Charged for above 20hours at limted current 0.25CA and constant volatge 2.45V/cell.
Number of Cycles 3.Charged for 8~10hours at limted current 0.05CA .