NetCol5000-C Chilled Water In-row Precision Air Conditioner Maintenance Guide (30 kW) http://support.huawei.com
http://enterprise.huawei.com
Issue: 01
Copyright © Huawei Technologies Co., Ltd. 2015. All Rights Reserved.
Date: 2015-03-20

Component Item Troubleshooting Monthly Quarterly Yearly


Check whether the air filter is dust, damaged, and deformed. It is recommended that you replace the filter once every 6 months. ▽
Block 75% of the air return vent with plastic material or baffle plate. If the air
Filters Check whether the pressure tube of the air filter clogging switch is fixed properly. (The
filter blocking alarm is generated, the differential pressure sensor is working
pressure tube is fixed under the air filter, and it is on the right side of the unit.) If the fault ▽
properly. If the air filter blocking alarm is not generated, check whether the
is not rectified, contact Huawei technical support.
differential pressure tube is correctly connected.
Check that screws fastening the condensate pump are securely connected. Secure the screws tightly. ▽
Raise the high float, choose Running > Status on the controller to confirm
Condensate Check the float cable connection. If the cable connection is correct, replace the float. ▽
that the float status is ON (two persons work as a team).
pump
Choose Alarms > Query Hist. Alarms on the controller to check if there are ▽
See NetCol5000-C Chilled Water In-row Precision Air Conditioner User Manual (30 kW).
condensate pump alarms and clear the alarms.
Chilled water Check that the valve does not leak. Replace the chilled water valve. ▽
valve
Check that the condensate water pan in the air conditioner is clean and not
Clean the sundries. ▽
blocked.
Clean the sundries, apply thermal insulation materials to frozen sections, and timely
Check that the outdoor drainage port is clean and not blocked. ▽
Pipeline dredge the pipes.
Check that no water exists under the water pipe or on the thermal insulation Close the water inlet valve and service the leaking sections. If the thermal insulation

foam. foam is damaged or missing, rewrap the thermal insulation foam.
Check that the thermal insulation foam on the chilled water pipe is intact. Wrap the thermal insulation foam. ▽
Check that no foreign matter exists in the fan. Clean the foreign matters. ▽
Indoor fans Check that no abnormal voice is generated during operation. Clean the foreign matters, and make sure that the fan is fixed properly. ▽
Check that the screws are secured and not deformed. Tighten the screws. Replace the screws if necessary. ▽
Check that T/H sensors in the air conditioner and aisles are securely installed. Secure the sensors. ▽

T/H sensor If the temperature error is greater than 1ºC or humidity error is greater than 5%, the T/H
Use a precision T/H sensor to calibrate the T/H sensors inside and outside the
sensor must be calibrated or replaced. For the calibration method, see the Advanced ●
cabinet.
Cooling Controller User Manual.
Export air conditioner logs, alarms, temperature, humidity, and pump
Monitor operating status statistics from the monitoring system. View the historical
N/A ◎
alarms generated in this quarter, select the most common five ones, and
analyze the causes. (If no monitoring system is available, skip this item.)
Evaporator The evaporator fins are not pushed down. Use a fin brush to organize the fins that are pushed down. ●
Electric Check whether the display panel, humidity and temperature sensor or cables

Replace the components or cables.
control units is aging on the surface.
Check that the thermal insulation foam is intact, and that there is no
LDU Tightly warp thermal insulation foam around pipes, and check that there is no bare pipe. ●
condensate water on pipes and valves.

Note:
1. For details about parts replacement, see NetCol5000-C Chilled Water In-row Precision Air Conditioner User Manual (30 kW).
2. If you have difficult in troubleshooting, contact Huawei technical support.

Water sensor

If the two terminals of the water sensor are in contact with water or other conductive liquid, the
two terminals are short-circuited, and the main control board generates an alarm after
detecting the signal. During the maintenance, check that the two detection plates are free from
(1) Water sensor detection plats
corrosion, foreign matter, and connection in between.