NetCol5000-C Chilled Water In-row Precision Air Conditioner Maintenance Guide (30 kW) http://support.huawei.com
http://enterprise.huawei.com
Issue: 01
Copyright © Huawei Technologies Co., Ltd. 2015. All Rights Reserved.
Date: 2015-03-20
T/H sensor If the temperature error is greater than 1ºC or humidity error is greater than 5%, the T/H
Use a precision T/H sensor to calibrate the T/H sensors inside and outside the
sensor must be calibrated or replaced. For the calibration method, see the Advanced ●
cabinet.
Cooling Controller User Manual.
Export air conditioner logs, alarms, temperature, humidity, and pump
Monitor operating status statistics from the monitoring system. View the historical
N/A ◎
alarms generated in this quarter, select the most common five ones, and
analyze the causes. (If no monitoring system is available, skip this item.)
Evaporator The evaporator fins are not pushed down. Use a fin brush to organize the fins that are pushed down. ●
Electric Check whether the display panel, humidity and temperature sensor or cables
●
Replace the components or cables.
control units is aging on the surface.
Check that the thermal insulation foam is intact, and that there is no
LDU Tightly warp thermal insulation foam around pipes, and check that there is no bare pipe. ●
condensate water on pipes and valves.
Note:
1. For details about parts replacement, see NetCol5000-C Chilled Water In-row Precision Air Conditioner User Manual (30 kW).
2. If you have difficult in troubleshooting, contact Huawei technical support.
Water sensor
If the two terminals of the water sensor are in contact with water or other conductive liquid, the
two terminals are short-circuited, and the main control board generates an alarm after
detecting the signal. During the maintenance, check that the two detection plates are free from
(1) Water sensor detection plats
corrosion, foreign matter, and connection in between.