This is a supervising relay provided to ensure correct preparation for the traction
as well as braking side. When ever cab1 MPJ is kept on ‗F‘ or cab2 MPJ is kept on ‗R‘
position, J1 & J2 drums set to upward position. When ever cab1 MPJ is kept on ‗R‘ or
cab2 MPJ is kept on ‗F‘ position, J1 & J2 drums set to downward position. Traction side
supply for relay Q50 goes from CCPT fuse and through BL1, MPJ ‗F‘ or MPJ ‗R‘, J1
‗F‘ & J2 ‗F‘ OR J1 ‗R‘ & J2 ‗R‘, CTF1 (Running), CTF2 (Running), CTF3 (Running),
C145 N/C, DJ N/O (now closed), Q50 N/C, GR ‗0‘, MP ‗0‘ and BL1 interlocks, the
circuit completes for Q50 relay and energizes. When Q50 is energised, it‘s N/C I/L open
and path is maintained to Q50 through RQ50. Q50 N/O I/L closes parallel to GR ‗0‘ and
MP
‗0‘ I/Ls, so the path to Q50 is maintained even after moving MP to ‗N‘ position and GR
is moved away from ‗0‘.
When ever Q50 is energised, the following I/Ls will close or open on different
control circuits that are given below.
i. NC interlock opens on QV64 branch in SIGNALLING lamp circuit. Hence
LSB extinguishes.
ii. NO interlock closes parallel to MP ‗0‘ and GR ‗0‘ interlock on Q50 control
circuit.
iii. NO interlock closes on line contactors control circuit.
iv. NC interlock opens parallel to RQ50 in Q50 control circuit.
v. NC interlock opens on VE2 coil in tap changer control circuit.
vi. NO interlock closes on VE2 coil in tap changer control circuit.
vii. NO interlock closes on VE1 coil in tap changer control circuit.