Flange Size Units Units
Fx Fy Fz Mx My Mz
2 INCH Lb 200 500 200 Lb-Ft. 500 1000 500
3 INCH Lb 300 750 300 Lb-Ft. 750 1500 750
4 INCH Lb 400 1000 400 Lb-Ft. 1000 2000 1000
5 INCH Lb 500 1250 500 Lb-Ft. 1250 2500 1250
6 INCH Lb 600 1500 600 Lb-Ft. 1500 3000 1500
8 INCH Lb 800 2000 800 Lb-Ft. 2000 4000 2000
10 INCH Lb 930 2330 930 Lb-Ft. 2500 5000 2500
12 INCH Lb 996 2496 996 Lb-Ft. 3000 6000 3000
Axis Axis
Flange Size Units Units
Fx Fy Fz Mx My Mz
2 INCH N 890 2224 890 N-m 678 1356 678
3 INCH N 1334 3336 1334 N-m 1017 2034 1017
4 INCH N 1779 4448 1779 N-m 1356 2712 1356
5 INCH N 2224 5560 2224 N-m 1695 3390 1695
6 INCH N 2669 6672 2669 N-m 2034 4068 2034
8 INCH N 3559 8896 3559 N-m 2712 5423 2712
10 INCH N 4137 10364 4137 N-m 3390 6779 3390
12 INCH N 4430 11103 4430 N-m 4068 8135 4068
Technical Data
Submittal Document
GPx Series
Full Service
Electric Fire Pump Controller
Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections
MEMBER
2019 -2020 MEMBER
2019 -2020
June 2022
Technical Data
GPx Series Full Service Electric Fire Pump Controller
*
3L2 T2
M
3L2 T2
*
3L1 T1
3L1 T1 CR4
1M 2M T9
M
CR4 CR5 T8
2M
1M T7
3L1
* M
3L2 T2
3L2
* 3L1
T2
T1
M CR4 CR5 2S
3L1 T1
1S 100%
1M
0% ATR
CR5 1M CR5
1M 2S
3L1 65%
1S
2S
3L1
* *
3L2 T2 3L2 T2
3L1 T1
3L1 T1
M
CR4
M
CR4 1M 2M
1M 2M T5 CR5 1S
T5
T4
CR5 1S T4
2M
2M(LB) CR3A T6
2M
T6 3L1 2S
CR5 2M 2S(LB) 2M(LB) CR3A
3L1
1S
1S 1S
1S
3L2
3L2
2S
RES
RES
RES
MEMBER
2019 -2020 MEMBER
2019 -2020
Shortcircuit 200V to 208V 220V to 240V 380V to 415V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating
HP (kw)
Standard 100kA
5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A
Optional 150kA
Standard 50kA 200 (149) 250 (186) 350 - 450 (261 - 335) 450 - 500 (335 - 373)
5 - 500 (3.7- 373)
Optional 100kA N/A N/A 350 - 500 (261 - 373) 450 - 500 (335 - 373)
Optional 200kA 5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A
June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 3
Technical Data
GPx Series Full Service Electric Fire Pump Controller
Locked Rotor • Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds
Protector • Factory set at 600% of motor full load current
DPDT-8A-250V.AC
• Power available
• Phase reversal
• Motor run
• Common pump room alarm (field re-assignable)**
• Overvoltage
• Undervoltage
Remote Alarm • Phase unbalance
Contacts • Low pump room temperature
• High Pump room temperature
• Common motor trouble (field re-assignable)**
• Overcurrent
• Fail to start
• Undercurrent
• Ground fault
• Free (field programmable)**
**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.
June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 5
Technical Data
GPx Series Full Service Electric Fire Pump Controller
June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 7
Technical Data
GPx Series Full Service Electric Fire Pump Controller
D43
Seismic Certification compliant to CBC 2019, L11 Czech
IBC 2018 rigid base/wall mounted only
L12 Portuguese
Special Seismic Certification compliant to
D44
OSHPD rigid base/wall mounted only L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese
Additional Options:
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
Home
2 3
8
5 6 7
June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 9
Electric Fire Pump Controller Model: GPA/GPP/GPY
Dimensions Built to the latest edition of the NFPA 20 standard
33 1/4" [846]
32 3/8" [823]
1/2" [12] 21 3/4" [552] 30" [762]
See Notes
69 1/8" [1756]
68" [1727]
65 7/8" [1673]
62" [1576]
28 3/8" [720]
22 3/4" [576]
27 5/8" [702]
34" [864]
Sensing Line Connection - 1/2 " F.NPT
32" [813]
White
White
White
CR4
Black
Black
Black
17
ST1 1 3L3 64 66 68 2 **
65 67 69
SA1 CR5
18
1S
20
3L2
3L1
2
4 2 3L1 CR5 2
19 21
1S To J2-J3-J4 To J76
1S
2
1
3L2
NO NO +
C J40 J14 AI4
otor Run C
TB1
NC NC -
2
1
NO NO +
C J42 J15 AI3
Power Availa le C
TB2
NC NC -
2
1
NO NO +
C J37 J16 AI2
Phase Reversal C
TB3
NC NC -
2
1
Red
NO NO
J39
+
White
PT1
Pump Room Alarm C C J17 AI1
TB4 Black
NC NC -
1
2
NO
LS1 **
NO LS1-1
C J41 LS1
otor Trou le C
TB5 J54 LS1-2
NC NC
2
1
UP
NO J20
NO
C J55
Field Programma le C
TB6 DOWN
NC NC J8
V B1
Black - +
J46 Red
AB1
AB
Remote anual Start IN1
SV
SV1-1 Brown SV1
Lockout IN2 J43 SV1-2 Blue
IO
Remote Automatic Start J1* IN3
4
Deluge Valve J45
J2* IN4 ST 2
J25
Water Reservoir Low IN5
J44 24V in XTR1
IN6 24V out 3L2
X1 H2
1 24VAC
IN7 J47 24VAC 3 X2 H1
3L1
IN8
NC
J36 CR4-1
CR4
C
CR4-2
CR4
NO
NC
J38 CR5-1
CR5
C
CR5-2
CR5
NO
GF
69
L3 68
J76 67
L2 66 To CT1-CT2-CT3 Legend
65 1 -2 Contactors
1S Contactor
L1 64
AB Alarm Bell
CB Circuit Breaker
CR Control Relay
J3 ST Shunt Trip
L2 3L2 To 3L1-3L2-3L3
SV Solenoid Valve
V B Vi iTouch ain Board
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250)
220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250)
380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)
440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)
600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)
Bending
12 " (305 mm) 16 " (406 mm)
Space
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 2x (1/0 to 500) 2x (2/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 3x (4/0 to 500) -------- -------- -------- -------- -------- --------
220 to 240 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 3x (250 to 500) -------- -------- -------- -------- --------
380 to 416 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (400 to 500) 3x (250 to 500) 3x (300 to 500) --------
440 to 480 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 3x (250 to 500)
600 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)
Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
1x (300) ** or
208 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 1/0) 1x (1/0) 1x (3/0) 1x (4/0 to 250)
1x (250) 90°C *
220 to 240 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (250)
380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (1/0)
440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0)
600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0)
Bending
Space 12 " (305 mm) 16 " (406 mm)
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 2x (2/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 3x (300 to 500) -------- -------- -------- -------- -------- --------
1x (350) **
220 to 240 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (500) 3x (400 to 500) -------- -------- -------- -------- --------
N/A
1x (350) ** 3x (300 to 500)**
380 to 416 1x (3/0) 1x (250 to 350) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (500) 3x (350 to 500) 3x (400 to 500) --------
N/A 2x (500) 90°C *
1x (300 to 350)**
440 to 480 1x (1/0 to 3/0) 1x (3/0) 1x (250) 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (400 to 500) 2x (500) 2x (500) 90°C * 3x (350 to 500)
1x (250) 90°C *
600 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 250) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 2x (500)
Bending
5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
Space
* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
** Consult Factory Contact manufacturer for "As Built" drawing.
Notes:
Motor Terminals 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
2M 1M 2M 1M 4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
T7 T8 T9 T1 T2 T3 T6 T4 T5 T1 T2 T3
M M
Model : GPP Models : GPW & GPY
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (2/0 to 3/0) 1x (3/0 to 300) 1x (250 to 300) 2x (1/0 to 300) 2x (3/0 to 350) -------- -------- -------- -------- -------- --------
220 to 240 1x (1/0 to 2/0) 1x (3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (4/0 to 350) -------- -------- -------- -------- --------
380 to 416 1x (4 to 2/0) 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 350) 2x (4/0 to 350) --------
440 to 480 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300) 2x (3/0 to 350) 2x (4/0 to 350)
600 1x (6 to 4) 1x (4) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (250 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300)
208 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (2/0)
220 to 240 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to 2/0) 1x (1/0 to 2/0)
380 to 416 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (3 to 2/0) **
440 to 480 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) **
600 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) **
HP
75 100 125 150 200 250 300 350 400 450 500
Voltage
208 1x (3/0) Consult Factory 1x (300) 90°C * 2x (3/0 to 300) 2x (250 to 350) -------- -------- -------- -------- -------- --------
220 to 240 1x (2/0) 90°C * Consult Factory 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (300 to 350) -------- -------- -------- -------- --------
380 to 416 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (1/0 to 2/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (250 to 300) 2x (300 to 350) 2x (300 to 350) --------
440 to 480 1x (3 to 2/0) ** 1x (2 to 2/0) 1x (2/0) 90°C * 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 350) 2x (300 to 350)
600 1x (4 to 2/0) ** 1x (3 to 2/0) ** 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * Consult Factory 2x (3/0 to 300) 2x (4/0 to 300)
* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.
** Option V659 required. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.
2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Remote Manual Start Close to start pump IN1 J25 Motor Run J40
1
Normally open TB1
NO
Normally closed Closes to alarm C
Opens to alarm NC
2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Lockout Close to block start IN2 J25 Power Available J42
1
Normally open TB2
NO
Normally closed Closes to alarm
C
Opens to alarm NC
2
Normally open NO
Normally closed Closes to alarm
C
Opens to alarm NC
Remote Automatic Start Open to start pump J1* IN3 J25 J37
Phase Reversal Normally open
1
TB3
NO
Normally closed Closes to alarm C
Opens to alarm NC
2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Deluge Valve Open to start pump J2* IN4 J25 Pump Room Alarm ** J3
1
Normally open TB4
NO
Normally closed Closes to alarm
C
Opens to alarm NC
2
Normally open NO
Normally closed Closes to alarm
C
2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Water Reservoir Low Close to signal alarm IN5 J25 (Field Programmable ***) J55
1
Normally open TB6
NO
Normally closed Closes to alarm C
Opens to alarm NC
Project ID
Contact
E-mail
Phone
Date 09.06.2022
Scope of delivery
- Wilo-Helix V high-pressure multistage centrifugal pump
- Installation and operating instructions
- Counter flanges of cast iron with the corresponding screws, nuts
and gaskets for PN16 pump version with oval flanges
Design notes
- Motor protection for 3-phase motor is to be provided on request
or onsite
- Single-phase AC motor equipped with built-in thermal motor
protection and capacitor
- In its standard position, the terminal box is aligned with the
suction flange, but this can be changed if necessary
- The Wilo-Helix V is equipped with a user-friendly mechanical
seal in a cartridge design and standard gasket for easy
maintenance
- The spacer coupling (from = 7.5 kW) allows the mechanical seal
Project ID
Contact
E-mail
Phone
Date 09.06.2022
Product data
Min. fluid temperature: -30 °C
Max. fluid temperature: 120 °C
Max. ambient temperature: 50 °C
Maximum operating pressure: 25 bar
Maximum inlet pressure: 1 MPa
Minimum efficiency index (MEI):
Motor data
Mains connection: 3~460 V/60 Hz
Voltage tolerance: +-6 %
Rated power: 11 kW
Motor efficiency class: IE3
Rated current: 18,2 A
Rated speed: 3535 1/min
Power factor: 0,91
Motor efficiency:
Motor efficiency:
Motor efficiency:
Insulation class: F
Protection class: IP55
Materials
Pump housing: 1.4301
Impeller: 1.4307
Shaft: 1.4301
Shaft seal: U3BE3GG
Gasket material: EPDM
Installation dimensions
Pipe connection on the suction side: DN 50, PN 25
Pipe connection on the discharge side: DN 50 , PN 25
Ordering information
Brand: Wilo
Product description: Helix V 1609-1/25/E/KS/460-60
Net weight, approx.: 123 kg
Article number: 4192471
Project ID
Contact Installation location
E-mail Customer pos.no
Phone
Date 09.06.2022
Impeller 1.4307
Shaft 1.4301
Shaft seal U3BE3GG
Gasket material EPDM
Information for order placements
Weight approx. 123 kg
Item number 4192471
Technical Data
Submittal Document
Model JP3
Across the Line Start
Jockey Pump Controller
Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections
Technical Data
Model JP3 Jockey Pump Controller
JP3
A4 Elapsed time meter (time totalizer) Seismic Certification compliant to CBC 2019, IBC
D35
A5 Motor run alarm contact 2018 rigid base/wall mounted only
A6 Loss of power alarm contact Special Seismic Certification compliant to OSHPD
D36
rigid base/wall mounted only
A7 Overload or short circuit alarm contact
Pressure transducer 0-600psi with ½” MNPT 316
D11D stainless steel bushing
L01 Other language and English (bilingual)
D14 Export packing for 1 controller L02 French
D13A Externally mounted wetted parts L03 Spanish
D14 Export packing for 1 controller L04 German
D18 Audible alarm L05 Italian
D19 Anti-condensation heater and thermostat L06 Polish
D20 Anti-condensation heater and humidistat L07 Romanian
D21 Tropicalization L08 Hungarian
Phase reversal / failure pilot light and alarm L09 Slovak
D22
contact
L10 Croatian
Controller power healthy pilot light and alarm
D23 L11 Czech
contact
L12 Portuguese
Pump failure via current sensing relay with pilot
D24 L13 Dutch
light and dry alarm contact
D25 Low zone pump control function L14 Russian
D26 Mid zone pump control function L15 Turkish
D27 High zone pump control function L16 Swedish
D28 Selector switch in auto alarm contacts L17 Bulgarian
D29 Selector switch in off alarm contacts L18 Thai
D30 Motor heater circuit L19 Indonesian
Service entrance rated - 100kA short circuit L20 Slovenian
withstand rating: L21 Danish
• 120V/1ph (0.5hp max.) L22 Greek
• 240V/1ph (1hp max.)
D32 L23 Arabic
• 200V-208V - 60hz (2hp max.)
• 220V-240V - 60hz (3hp max.) L24 Hebrew
• 380V-416V - 50hz - 60hz (5hp max.) L25 Chinese
• 440V-480V - 60hz (5hp max.)
Service entrance rated - 65kA short circuit
withstand rating:
• 120V/1ph (0.5hp max.)
• 240V/1ph (1hp max.)
D33
• 200V-208V - 60hz (3hp-15hp max.)
• 220V-240V - 60hz (515hp max.)
• 380V-416V - 50hz - 60hz (7.5hp - 40hp max.)
• 440V-480V - 60hz (7.5hp-40hp max.)
Service entrance rated - 42kA short circuit
D34 withstand rating:
• 600V - 60hz (7.5hp max.)
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
3 2
4 7
HAND AUTO
5
8
FU1 DS
B B
D
XTR1
IPD
F C
C C
Main Disconnect
G
Y
ON
R
OL1
OFF
HAND G G AUTO
C1
G DS
D B E D
PT1
Underwriters
Laboratories Inc.
DANGER
R R
LISTED
ENCLOSED INDUSTRIAL CONTROL PANEL
No. AC-XXX
Rating
E Label E
Standard Internal Layout
3
8 "[ ] x4
Dimensions*
Maximum Motor Horsepower Enclosure Dimensions Door Dimensions Anchor Dimensions
2- " [58]
A
H H
L1 L2 L3 Pressure Sensor
PT1 Type 0.5 - 4.5V
B B
G
DS G
White
Black
Red
R
B W G R 5 S
RESET J5
HA D G G AUT
Ps ut-
PsIn-
Ps ut+
PsIn+
L1
C 34 33 7 C
9 I 1 J9
J21
G
I 2
UTPUT J8
J19
"IPD+"
D D
F5
FU1 J2 J3 J1
TR1
24Vac 24Vac
H2 1 3 A2 A1
3 1 22 8
H1 2
1
E E
A1 A2
C1
F F
G G
H H
L1
C1
I
- Drawing for information only. I
G Manufacturer reserves the right to modify this drawing without notice.
T1 T2 T3
Contact manufacturer for "As Built" drawing.
P1
0 1 2 3 4 5 6 7 8
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller NYC
Dpt of Building
Approved
B B
3 Phase
Incoming Power
Bonding Ground
C C
L1 L2 L3
DS
C1
D T1 T2 T3 D
E E
G G
I I
0 1 2 3 4 5 6 7 8
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not e retransmitted pu lished reproduced copied or used in any manner including as the asis for the manufacture or sale of any products without the e press prior written consent of Tornatech Inc.