DATA SHEET

Three Phase Induction Motor - Squirrel Cage


Customer :

Product line : W40 High Efficiency

Frame : 444/5TS Locked rotor time : 27 s (hot) 49 s (cold)


Output : 200 HP (150 kW) Temperature rise4 : 80 K
Poles : 2 Duty cycle : Cont.(S1)
Frequency : 60 Hz Ambient temperature : -20 °C to +40 °C
Rated voltage : 200/400 V Altitude : 1000 m.a.s.l
Rated current : 520/260 A Degree of protection : IP23
L. R. Amperes : 3275/1637 A Cooling method : IC01 - ODP
LRC (p.u.) : 6.3 Code G Mounting : F-1
No load current : 134/66.9 A Direct of rotation¹ : Both
Rated speed : 3560 rpm
Slip : 1.11 % Starting method : Direct On Line
Rated torque : 295 ft.lb Approx. weight³ : 1341 lb
Locked rotor torque : 140 % Design : B
Pull up torque : 115 %
Breakdown torque : 210 %
Insulation class : F
Service factor : 1.15
Moment of inertia (J) : 21.8 sq.ft.lb
Output Start 25% 50% 75% 100% Load type: -
Efficiency (%) - 88.7 93.0 94.1 94.5 Load torque: -
Power factor 0.33 0.61 0.82 0.87 0.88 Load inertia (J=GD²/4): -
Drive end Non drive end Foundation loads
Bearing type 6314-C3 6212-Z-C3 Maximum traction : 960 lb
Lubrication interval 14418 h 20000 h Maximum compression : 2300 lb
Lubricant amount 27 g 13 g
Lubricant type MOBIL POLYREX EM
Notes:
Z20036OP3V(BUILD)FP444/5TS-W40
Standards

Specification : MG1 - Part 10 Vibration : MG1 - Part 7


Tests : MG1 - Part 12 Tolerance : MG1 - Part 12
Noise : MG1 - Part 9
This revision replaces and cancels the previous one, which must be eliminated. These are average values based on tests with sinusoidal
(1) When viewed from the drive end. power supply, subject to the tolerances stipulated in NEMA
(2) Measured at 1m and with tolerance of +3dB(A). MG 1-12.
(3) Approximate weight subject to changes after manufacturing process.
(4) At the rated point.

Rev. Summary of changes Performed Checked Date

Performed by lclark 352960/2021


Checked by mparsell Page Revision
Date 17/12/2021 1/1 0
This document is exclusive property of WEG S/A. Reprinting is not allowed without written authorization.
NOZZLE LOADING MAXIMUM FORCES AND MOMENTS*

*The pump suction and discharge piping must be restrained


and supported near the pump to avoid application of forces and
moments to the pump casing.

Axis Axis
Flange Size Units Units
Fx Fy Fz Mx My Mz
2 INCH Lb 200 500 200 Lb-Ft. 500 1000 500
3 INCH Lb 300 750 300 Lb-Ft. 750 1500 750
4 INCH Lb 400 1000 400 Lb-Ft. 1000 2000 1000
5 INCH Lb 500 1250 500 Lb-Ft. 1250 2500 1250
6 INCH Lb 600 1500 600 Lb-Ft. 1500 3000 1500
8 INCH Lb 800 2000 800 Lb-Ft. 2000 4000 2000
10 INCH Lb 930 2330 930 Lb-Ft. 2500 5000 2500
12 INCH Lb 996 2496 996 Lb-Ft. 3000 6000 3000

Axis Axis
Flange Size Units Units
Fx Fy Fz Mx My Mz
2 INCH N 890 2224 890 N-m 678 1356 678
3 INCH N 1334 3336 1334 N-m 1017 2034 1017
4 INCH N 1779 4448 1779 N-m 1356 2712 1356
5 INCH N 2224 5560 2224 N-m 1695 3390 1695
6 INCH N 2669 6672 2669 N-m 2034 4068 2034
8 INCH N 3559 8896 3559 N-m 2712 5423 2712
10 INCH N 4137 10364 4137 N-m 3390 6779 3390
12 INCH N 4430 11103 4430 N-m 4068 8135 4068

Page 153 of 169


Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Document
GPx Series
Full Service
Electric Fire Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

MEMBER
2019 -2020 MEMBER
2019 -2020

Note: The drawings included in this package are for controllers


covered under our standard offering. Actual AS BUILT
drawings may differ from what is shown in this package. MEMBER
2019 -2020
MEMBER
2019 -2020

June 2022
Technical Data
GPx Series Full Service Electric Fire Pump Controller

Select starting method

Model GPA Model GPP


Across the line Partwinding
1M 1M T3
3L3
3L3 T3

*
3L2 T2

M
3L2 T2
*
3L1 T1

3L1 T1 CR4
1M 2M T9
M
CR4 CR5 T8
2M
1M T7
3L1

3L1 3L2 3L2

Model GPS Model GPR


Soft Start Soft Stop Autotransformer
1M 1M
3L3 3L3 T3
T3

* M
3L2 T2
3L2

* 3L1
T2

T1
M CR4 CR5 2S
3L1 T1

1S 100%
1M
0% ATR
CR5 1M CR5
1M 2S

3L1 65%
1S
2S
3L1

3L2 Soft Starter 3L2

Model GPY Model GPW


Wye-Delta Open Wye-Delta Closed
1M 3L3
1M
3L3 T3 T3

* *
3L2 T2 3L2 T2

3L1 T1
3L1 T1

M
CR4

M
CR4 1M 2M
1M 2M T5 CR5 1S
T5

T4
CR5 1S T4
2M

2M(LB) CR3A T6
2M
T6 3L1 2S
CR5 2M 2S(LB) 2M(LB) CR3A
3L1
1S
1S 1S

1S

3L2

3L2
2S
RES
RES
RES

MEMBER
2019 -2020 MEMBER
2019 -2020

*From normal incoming power through Disconnecting Means (IS/CB)


MEMBER MEMBER
2019 -2020 2019 -2020

This is a Marketing document. Please consult factory for more information.


June 2022 2
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

Built to NFPA 20 (latest edition)


Underwriters Laboratory
UL218 - Fire Pump Controllers
(UL)
Standard, FM Global Class 1321/1323
Listings,
Approvals and New York City Accepted for use in the City of New York by the Department of Buildings
Certifications CE Mark Various EN, IEC & CEE directives and standards
Built in Canada or U.A.E Built in Europe
CE Mark Option Supplied as Standard
Protection Rating

Built in Canada or U.A.E Built in Europe

Standard: NEMA 2 Standard: IP55


Optional

NEMA 12 NEMA 4X-304 sst painted IP54

Enclosure NEMA 3 NEMA 4X-304 sst brushed finish IP55

NEMA 3R NEMA 4X-316 sst painted IP65

NEMA 4 NEMA 4X-316 sst brushed finish IP66

Accessories Paint Specifications


• Bottom entry gland plate • Red RAL3002
• Lifting Lugs • Powder coating
• Keylock handle • Glossy textured finish

Shortcircuit 200V to 208V 220V to 240V 380V to 415V 440V to 480V 575V to 600V
Withstand 60Hz 60Hz 50 Hz / 60Hz 60Hz 60Hz
Rating
HP (kw)

Standard 100kA
5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A
Optional 150kA

Standard 50kA 200 (149) 250 (186) 350 - 450 (261 - 335) 450 - 500 (335 - 373)
5 - 500 (3.7- 373)
Optional 100kA N/A N/A 350 - 500 (261 - 373) 450 - 500 (335 - 373)

Optional 200kA 5 - 150 (3.7 - 110) 5 - 200 (3.7 - 149) 5 - 300 (3.7 - 223) 5 - 400 (3.7 - 298) N/A

*Please see Disconnecting Means details on page 4

June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 3
Technical Data
GPx Series Full Service Electric Fire Pump Controller

Ambient Standard: Optional:


Temperature 4°C to 40°C / 39°F to 104°F 4°C to 55°C / 39°F to 131°F
Rating
Controllers built in Dubai, UAE (Tornatech FZE) are supplied standard with 55°C rating.
Surge
Surge arrestor rated to suppress surges above line voltage
Suppression
• Isolating switch and circuit breaker assembly:
- Door interlocked in the ON position
- Isolating switch rated not less than 115% of motor full load current
Disconnecting
- Circuit breaker continuous rating not less than 115% of motor full load current
Means
- Overcurrent sensing non-thermal type, magnetic only
- Instantaneous trip setting of not more than 20 times the motor full load current
• Common flange mounted operating handle
Service Entrance
Suitable as service entrance equipment
Rating

Emergency Start • Flange mounted • Integrated limit switch


Handle • Pull and latch activation • Across the line start (direct on line)

Locked Rotor • Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds
Protector • Factory set at 600% of motor full load current

Electrical • Voltage phase to phase (normal power)


Readings • Amperage of each phase when motor is running
Pressure • Continuous system pressure display
Readings • Cut-in and Cut-out pressure settings
• Pressure readings with date stamp
• Event recording with date stamp
Pressure and
• Under regular maintained operation, events are stored in memory for the life of the controller.
Event recorder
• Data viewable on operator interface display screen
• Downloadable by USB port to external memory device
• Pressure transducer and run test solenoid valve assembly for fresh water application
• Pressure sensing line connection 1/2” Female NPT
Pressure Sensing • Drain connection 3/8”
• Rated for 0-500PSI working pressure (standard display at 0-300PSI)
• Externally mounted with protective cover

This is a Marketing document. Please consult factory for more information.


June 2022 4
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

Audible Alarm 6” alarm bell - 85 dB at 10ft. (3m)


• Power available • Deluge valve start • Pump on demand/Automatic start
• Motor run • Remote automatic start • Pump room temperature (ºF or ºC)
Visual Indications
• Periodic test • Remote manual start • Lockout
• Manual start • Emergency start
Visual
• Control voltage not healthy • Overcurrent • Pump on demand
• Invalid cut-in • Overvoltage • Pump room alarm
• Lock rotor current • Phase loss L1 • Service required
• Loss of power • Phase loss L2 • Undercurrent
Visual & Audible • Phase loss L3 • Undervoltage
• Low ambient temperature
Alarms • Phase unbalanced • Check weekly test solenoid
• Low water level
• Motor trouble • Pressure transducer fault detected • Weekly test cut-in reached
• Phase reversal (normal power)
Visual and audible
• Fail to start

DPDT-8A-250V.AC
• Power available
• Phase reversal
• Motor run
• Common pump room alarm (field re-assignable)**
• Overvoltage
• Undervoltage
Remote Alarm • Phase unbalance
Contacts • Low pump room temperature
• High Pump room temperature
• Common motor trouble (field re-assignable)**
• Overcurrent
• Fail to start
• Undercurrent
• Ground fault
• Free (field programmable)**

**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.

June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 5
Technical Data
GPx Series Full Service Electric Fire Pump Controller

• Embedded microcomputer with software PLC logic


ViZiTouch V2 • 7.0” color touch screen (HMI technology)
Operator Interface • Upgradable software
• Multi-language
• Protocol: Modbus
Communication
• Connection type: Shielded female connector RJ45
Protocol
• Frame Format: TCP/IP
Capability
• Addresses: See bulletin MOD-GPx
• Start on pressure drop
Automatic Start • Remote start signal from automatic device
• Deluge valve start
• Start pushbutton
Manual Start • Run test pushbutton
• Remote start from manual device
• Manual with Stop pushbutton
Stopping
Operation • Automatic after expiration of minimum run timer ***
• Minimum run timer ***(off delay)
Field Adjustable &
Timers • Sequential start timer (on delay)
Visual Countdown
• Periodic test timer
• Pressure
Actuation
• Non-pressure
Visual Indication
• Automatic
Mode
• Non-automatic

***Can only be used if approved by the AHJ

This is a Marketing document. Please consult factory for more information.


June 2022 6
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

A4 Flow switch provision C19 Emergency start alarm contact (DPDT)


Foam pump application w/o pressure C20 Manual start alarm contact (DPDT)
A8
transducer and run test solenoid valve.
C21 Deluge valve start alarm contact (DPDT)
A9 Low zone pump control function
C22 Remote automatic start alarm contact (DPDT)
A10 Middle zone pump control function
C23 Remote manual start alarm contact (DPDT)
A11 High zone pump control function
High pump room temperature alarm contact
Non-pressure actuated controller w/o pressure C24
A13 (DPDT)
transducer and run test solenoid valve
Second set of standard alarm contacts (DPDT)
Lockout/interlock circuit from equipment C25
A16 (Typical for city of Los Angeles and Denver)
installed inside the pump room
Additional visual and alarm contact (Specify
Built in alarm panel (120V.AC supervisory Cx
function) (DPDT)
power) providing indication for:
• Audible alarm & silence pushbutton for motor Low suction pressure transducer for fresh
B11 D1 water rated at 0-300PSI with visual indication
run, phase reversal, loss of phase.
• Pilot lights for loss of phase & supervisory and alarm contact
power available Low suction pressure transducer for sea water
Built in alarm panel same as B11 but 220- D1A rated at 0-300PSI with visual indication and
B11B alarm contact
240VAC supervisory power
High motor temperature c/w thermoster relay Pressure transducer and run test solenoid
B19A D5 valve for fresh water rated for 0-500PSI (for
and alarm contacts (DPDT)
factory calibration purposes only)
High motor temperature c/w PT100 relay and
B19B Pressure transducer and run test solenoid
alarm contacts (DPDT) D5D
valve for sea water rated for 0-500PSI
Ground fault alarm detection c/w visual
B21 D10 Omit mounting feet (when applicable)
indication and alarm contact (DPDT)
C1 Extra motor run alarm contact (DPDT) High withstand rating for:
• 200V to 208V @ 150HP max. = 150kA*
C4 Periodic test alarm contact (DPDT) • 200V to 208V @ 200HP = 100kA*
C6 Low discharge pressure alarm contact (DPDT) • 220V to 240V @ 200HP max. = 150kA*
• 220V to 240V @ 250HP = 100kA*
Low pump room temperature alarm contact D13
C7 • 380V to 415V @ 300HP max. = 150kA*
(DPDT) • 380V to 415V @ 350HP to 450HP = 100kA*
Low water reservoir level alarm contact • 440V to 480V @ 400HP max. = 150kA*
C10 • 440V to 480V @ 450HP to 500HP = 100kA*
(DPDT)
• 600V @ 500HP max. = 100kA*
High electric motor temperature alarm contact
C11 High withstand rating for:
(DPDT)
D13A • 380V to 480V = 65kA*
High electric motor vibration c/w visual
C12 • 600V = 25kA*
indication and alarm contact (DPDT)
High withstand rating for:
Pump on demand / automatic start alarm
C14 • 200V to 208V @ 150HP max. = 200kA*
contact (DPDT)
D13B • 220V to 240V @ 200HP max. = 200kA*
C15 Pump fail to start alarm contact (DPDT) • 380V to 415V @ 300HP max. = 200kA*
• 440V to 480V @ 400HP max. = 200kA*
C16 Control voltage healthy alarm contact (DPDT)
D14 Anti-condensation heater & thermostat
Flow meter valve loop open c/w visual
C17 D14A Anti-condensation heater & humidistat
indication and alarm contact (DPDT)
High water reservoir level c/w visual indication Anti-condensation heater & thermostat &
C18 D14B
and alarm contact (DPDT) humidistat

*For fire pump controller section only.


Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 7
Technical Data
GPx Series Full Service Electric Fire Pump Controller

D15 Tropicalization L01 Other language and English (bilingual)


D18 CE Mark with factory certificate L02 French
Modbus with RTU frame format and RS485 L03 Spanish
D26
connection
L04 German
Motor heater connection (external single
D27 phase power source and heater on/off L05 Italian
contact)
L06 Polish
Motor heater connection (internal single
D27A phase power source and heater on/off L07 Romanian
contact)
L08 Hungarian
D28 Customized drawing set
L09 Slovak
Field programmable I/O board -
D34A L10 Croatian
5 Input / 5 output

D43
Seismic Certification compliant to CBC 2019, L11 Czech
IBC 2018 rigid base/wall mounted only
L12 Portuguese
Special Seismic Certification compliant to
D44
OSHPD rigid base/wall mounted only L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese

Additional Options:

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

This is a Marketing document. Please consult factory for more information.


June 2022 8
Manufacturer reserves the right to modify this information without notice
Technical Data
GPx Series Full Service Electric Fire Pump Controller

ViZiTouch V2 Operator Interface

Home

2 3

8
5 6 7

1 - Color touch screen 3 - Screen protector


2 - Onscreen menu 4 - Power LED (3 colors)
• HOME page 5 - START button
• ALARM page 6 - STOP button
• CONFIGURATION page 7 - RUN TEST button
• HISTORY page 8 - USB port
• SERVICE page
• MANUAL page
• LANGUAGES page

June 2022 This is a Marketing document. Please consult factory for more information.
Manufacturer reserves the right to modify this information without notice 9
Electric Fire Pump Controller Model: GPA/GPP/GPY
Dimensions Built to the latest edition of the NFPA 20 standard
33 1/4" [846]
32 3/8" [823]
1/2" [12] 21 3/4" [552] 30" [762]

18" [457] 28 1/2" [724]


Ø7/8" [Ø23] X2 Ø3/8" [Ø10] X4

See Notes

69 1/8" [1756]

68" [1727]
65 7/8" [1673]

62" [1576]

28 3/8" [720]
22 3/4" [576]
27 5/8" [702]

1" [25] Adjustable Feet

34" [864]
Sensing Line Connection - 1/2 " F.NPT
32" [813]

Ø1/2" [Ø13] X4 11" [279] 1" [25]


Drain - 3/8 " M.TUBE

Voltage / Power Table 11 1/8" [284] Normal


11" [279]
Power and
16" [406]
Motor Leads
Voltage Min HP Max HP Entrance

208 75 150 Notes: 3 1/2" [89] 3" [76]


1" [25]
1 1/4" [31]
220 - 240 100 200
- Standard NEMA: NEMA 2
- Standard paint : textured red RAL 3002.
380 - 400 - 415 150 300
- All dimensions are in inches [millimeters].
- Center of ViZiTouch screen: 61-5/8" [1564] from Bottom.
440 - 480 200 400 - Bottom conduit entrance through removable gland plate recommended.
- Use watertight conduit and connector only.
600 250 500 - Protect equipment against drilling chips.
- Door swing equal to door width.
Drawing for information only. Projection
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
4. Removed Seismic logo (optional) 18/05/22
Approved
3. HP Table Modified 22/12/20 GPX-DI361 /E
2. New Logo 10/05/18 CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
lectric Fire Pump Controller
Reduced Voltage Wye-Delta Open Transition
odel GPY
Wiring schematic Built to the latest edition of the NFPA 20 standard
IS1 CB1
1L3 3L3 CT3 1 **
1L2 3L2 CT2
1L1 3L1 CT1

White

White

White
CR4

Black

Black

Black
17
ST1 1 3L3 64 66 68 2 **
65 67 69
SA1 CR5
18
1S
20
3L2
3L1
2
4 2 3L1 CR5 2
19 21
1S To J2-J3-J4 To J76
1S
2
1
3L2
NO NO +
C J40 J14 AI4
otor Run C
TB1
NC NC -
2
1

NO NO +
C J42 J15 AI3
Power Availa le C
TB2
NC NC -
2
1

NO NO +
C J37 J16 AI2
Phase Reversal C
TB3
NC NC -
2
1
Red
NO NO
J39
+
White
PT1
Pump Room Alarm C C J17 AI1
TB4 Black
NC NC -

1
2

NO
LS1 **
NO LS1-1
C J41 LS1
otor Trou le C
TB5 J54 LS1-2
NC NC
2
1
UP
NO J20
NO
C J55
Field Programma le C
TB6 DOWN
NC NC J8
V B1
Black - +
J46 Red
AB1
AB
Remote anual Start IN1

SV
SV1-1 Brown SV1
Lockout IN2 J43 SV1-2 Blue

IO
Remote Automatic Start J1* IN3

4
Deluge Valve J45
J2* IN4 ST 2
J25
Water Reservoir Low IN5
J44 24V in XTR1
IN6 24V out 3L2
X1 H2
1 24VAC
IN7 J47 24VAC 3 X2 H1
3L1
IN8
NC
J36 CR4-1
CR4
C
CR4-2
CR4
NO

NC
J38 CR5-1
CR5
C
CR5-2
CR5
NO

GF

69
L3 68
J76 67
L2 66 To CT1-CT2-CT3 Legend

65 1 -2 Contactors
1S Contactor
L1 64
AB Alarm Bell
CB Circuit Breaker
CR Control Relay

J53 CT Current Transformer


B lectric I O Board
IS Isolating Switch
J Jumper
J4 L3 3L3 LS Limit Switch
PT Pressure Transducer
SA Surge Arrester

J3 ST Shunt Trip
L2 3L2 To 3L1-3L2-3L3
SV Solenoid Valve
V B Vi iTouch ain Board

B1 J2 L1 3L1 XTR Transformer

Drawing for information only


* Remove jumper to use this feature anufacturer reserves the right to modify this drawing without notice
** Contact closes when emergency start is in "ON" position Contact manufacturer for "As Built" drawing

REV. DESCRIPTION DD/MM/YY Drawing num er


NYC
Dpt of Building
3 Removed Seismic logo optional 18 05 22
Approved
2 Update Logo 23 04 18 GPY-WS600
1 Removed fail safe te t from Power Availa le relay 20 02 17 CDL
Copyright © 2022 Tornatech Inc. All right reserved This drawing and the information contained or depicted herein are the sole property of Tornatech Inc Copies are communicated to the recipient in strict confidence and may not e retransmitted pu lished reproduced copied or used in any manner including as the asis for the manufacture or sale of any products without the e press prior written consent of Tornatech Inc
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing for Isolating Switch Built to the latest edition of the NFPA 20 standard
Power Terminals
3 Phases Notes:
Bonding Incoming Power 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
Ground 2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
L1 L2 L3
IS1

COPPER CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
Space 5 " (127 mm) 8 " (203 mm)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250)

220 to 240 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (3 to 1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0)

Bending
12 " (305 mm) 16 " (406 mm)
Space

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 2x (1/0 to 500) 2x (2/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 3x (4/0 to 500) -------- -------- -------- -------- -------- --------

220 to 240 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (350 to 500) 3x (250 to 500) -------- -------- -------- -------- --------

380 to 416 1x (1/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (400 to 500) 3x (250 to 500) 3x (300 to 500) --------

440 to 480 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (4/0 to 250) 2x (1/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 3x (250 to 500)

600 1x (3 to 1/0) 1x (1 to 3/0) 1x (2/0 to 3/0) 1x (3/0 to 250) 1x (250) 2x (2/0 to 500) 2x (3/0 to 500) 2x (4/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (350 to 500)

Bending
Space 5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

ALUMINUM CONDUCTORS for Isolating Switch (IS1).


Field Wiring According to Bending Space (AWG or MCM). Terminals L1 - L2 - L3
Bending
Space 5 " (127 mm) 8 " (203 mm) 10 " (254 mm)

HP
5 7.5 10 15 20 25 30 40 50 60
Voltage
1x (300) ** or
208 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (1 to 1/0) 1x (1/0) 1x (3/0) 1x (4/0 to 250)
1x (250) 90°C *
220 to 240 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (3 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (250)

380 to 416 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0) 1x (1/0)

440 to 480 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0) 1x (1 to 1/0)

600 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (10 to 1/0) 1x (8 to 1/0) 1x (6 to 1/0) 1x (6 to 1/0) 1x (4 to 1/0) 1x (4 to 1/0) 1x (2 to 1/0)

Bending
Space 12 " (305 mm) 16 " (406 mm)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 2x (2/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (350 to 500) 3x (300 to 500) -------- -------- -------- -------- -------- --------
1x (350) **
220 to 240 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (500) 3x (400 to 500) -------- -------- -------- -------- --------
N/A
1x (350) ** 3x (300 to 500)**
380 to 416 1x (3/0) 1x (250 to 350) 2x (3/0 to 500) 2x (4/0 to 500) 2x (300 to 500) 2x (500) 3x (350 to 500) 3x (400 to 500) --------
N/A 2x (500) 90°C *
1x (300 to 350)**
440 to 480 1x (1/0 to 3/0) 1x (3/0) 1x (250) 2x (3/0 to 500) 2x (250 to 500) 2x (300 to 500) 2x (400 to 500) 2x (500) 2x (500) 90°C * 3x (350 to 500)
1x (250) 90°C *
600 1x (1 to 1/0) 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (4/0 to 250) 1x (350 to 500) 2x (3/0 to 500) 2x (4/0 to 250) 2x (300 to 500) 2x (350 to 500) 2x (400 to 500) 2x (500)

Bending
5 " (127 mm) 8 " (203 mm) 12 " (305 mm)
Space

* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
** Consult Factory Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


N C
Dpt of Building
Approved Removed Seismic logo (optional)
1 18/05/22 GPX-TD612 1/2 /E
0 First issue 22/12/20 CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing For GPP,GPY & GPW Built to the latest edition of the NFPA 20 standard

Notes:
Motor Terminals 1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.
2 - Controller suitable for service entrance in USA.
3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.
2M 1M 2M 1M 4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.
T7 T8 T9 T1 T2 T3 T6 T4 T5 T1 T2 T3

M M
Model : GPP Models : GPW & GPY

COPPER CONDUCTORS for Motor Connection (1M-2M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4) 1x (6 to 4) 1x (6 to 4) 1x (4 to 2/0) 1x (2 to 2/0) 1x (1 to 2/0)

220 to 240 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4) 1x (6 to 4) 1x (6 to 4) 1x (4) 1x (3 to 2/0) 1x (2 to 2/0)

380 to 416 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4) 1x (6 to 4) 1x (4)

440 to 480 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4) 1x (6 to 4)

600 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (10 to 4) 1x (8 to 4) 1x (8 to 4)

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (2/0 to 3/0) 1x (3/0 to 300) 1x (250 to 300) 2x (1/0 to 300) 2x (3/0 to 350) -------- -------- -------- -------- -------- --------

220 to 240 1x (1/0 to 2/0) 1x (3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (4/0 to 350) -------- -------- -------- -------- --------

380 to 416 1x (4 to 2/0) 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (2/0 to 300) 2x (3/0 to 300) 2x (4/0 to 350) 2x (4/0 to 350) --------

440 to 480 1x (4 to 2/0) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300) 2x (3/0 to 350) 2x (4/0 to 350)

600 1x (6 to 4) 1x (4) 1x (3 to 2/0) 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (2/0 to 3/0) 1x (4/0 to 300) 1x (250 to 300) 1x (300) 2x (1/0 to 300) 2x (2/0 to 300)

ALUMINUM CONDUCTORS for Contactor (1M-2M).


Field Wiring According to Bending Space (AWG or MCM). Terminals T1-T2-T3-T4-T5-T6-T7-T8-T9
HP
5 7.5 10 15 20 25 30 40 50 60
Voltage

208 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (2/0)

220 to 240 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (2 to 2/0) ** 1x (1 to 2/0) 1x (1/0 to 2/0)

380 to 416 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) ** 1x (3 to 2/0) **

440 to 480 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) ** 1x (4 to 2/0) **

600 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (12 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (10 to 2/0) ** 1x (8 to 2/0) ** 1x (8 to 2/0) ** 1x (6 to 2/0) **

HP
75 100 125 150 200 250 300 350 400 450 500
Voltage

208 1x (3/0) Consult Factory 1x (300) 90°C * 2x (3/0 to 300) 2x (250 to 350) -------- -------- -------- -------- -------- --------

220 to 240 1x (2/0) 90°C * Consult Factory 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (300 to 350) -------- -------- -------- -------- --------

380 to 416 1x (2 to 2/0) 1x (1/0 to 2/0) 1x (1/0 to 2/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (4/0 to 300) 2x (250 to 300) 2x (300 to 350) 2x (300 to 350) --------

440 to 480 1x (3 to 2/0) ** 1x (2 to 2/0) 1x (2/0) 90°C * 1x (2/0 to 3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * 2x (3/0 to 300) 2x (4/0 to 300) 2x (250 to 350) 2x (300 to 350)

600 1x (4 to 2/0) ** 1x (3 to 2/0) ** 1x (2 to 2/0) 1x (1/0 to 3/0) 1x (3/0) 1x (3/0) 90°C * 1x (300) 1x (300) 90°C * Consult Factory 2x (3/0 to 300) 2x (4/0 to 300)

* For standard enclosure, use 90°C aluminium wire. Consult Factory for Use of Conductors Rated Lower than 90°C.
** Option V659 required. Drawing for information only.
Manufacturer reserves the right to modify this drawing without notice.
Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


NYC
Dpt of Building
Approved Removed Seismic logo (optional)
1 18/05/22 GPX-TD612 2/2 /E
0 First issue 22/12/20 CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Electric Fire Pump Controller Model: GPX
Terminal Diagram and Sizing Built to the latest edition of the NFPA 20 standard

Control Terminals (EB1) Remote Alarm Terminals (EB1)


Terminals Wire Size: Terminals Wire Size:
24 - 12 AWG 24 - 12 AWG
0.5 Nm 0.5 Nm

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Remote Manual Start Close to start pump IN1 J25 Motor Run J40
1
Normally open TB1
NO
Normally closed Closes to alarm C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Lockout Close to block start IN2 J25 Power Available J42
1
Normally open TB2
NO
Normally closed Closes to alarm
C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm
C
Opens to alarm NC
Remote Automatic Start Open to start pump J1* IN3 J25 J37
Phase Reversal Normally open
1
TB3
NO
Normally closed Closes to alarm C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Deluge Valve Open to start pump J2* IN4 J25 Pump Room Alarm ** J3
1
Normally open TB4
NO
Normally closed Closes to alarm
C
Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm
C

Alarm Inputs (EB1) Motor Trouble **


Opens to alarm
1
NC
J41
Normally open TB5
Terminals Wire Size: NO
24 - 12 AWG Normally closed Closes to alarm C
0.5 Nm Opens to alarm NC

2
Normally open NO
Normally closed Closes to alarm C
Opens to alarm NC
Water Reservoir Low Close to signal alarm IN5 J25 (Field Programmable ***) J55
1
Normally open TB6
NO
Normally closed Closes to alarm C
Opens to alarm NC

Network Connection (VMB1)


Shielded Female Connector RJ45

Modbus TCP/IP I/O

* Remove umper to use this feature Drawing for information only.


** Re-assignable Manufacturer reserves the right to modify this drawing without notice.
*** Not available on GPS models Contact manufacturer for "As Built" drawing.

REV. DESCRIPTION DD/MM/YY Drawing number


N C
Dpt of Building
3 Removed Seismic logo (optional) 18/05/22
Approved Revised logo
2 18/06/18 GPX-TD603 /E
1 General Revision (added AL coverage) 10/07/17 CDL
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
Jockey Pump & Controller data
Tender text
Contact
E-mail
Phone
Fax
Customer Project name Untitled project 2022-06-09 15:52:03.128

Project ID
Contact
E-mail
Phone

Date 09.06.2022

Pos.no Qty. Description PG UP / EUR TP / EUR


Description: High-pressure multistage
centrifugal pump
1 Helix V 1609-1/25/E/KS/460-60 Price on req. Price on req.
Highly efficient high-pressure multistage centrifugal pump in
vertical design with in-line connections.

The non self-priming high-pressure multistage centrifugal pump


has a compact overall design and is particularly efficient and easy
to maintain. The pump shaft and the motor shaft of the IEC
standard motor are connected by means of a clamp coupling.
A separate lantern roller bearing ensures optimum admission of
axial thrusts. Intermediate bearings in the hydraulics and
corrosion-resistant shaft due to stainless steel sleeve ensure a
long service life. Special, permanently attached lifting eyes enable
easy pump installation.
The pump is suitable for water supply and pressure boosting,
industrial recirculation systems, process water and cooling water
circuits. It can also be used in fire extinguishing systems, washing
systems as well as for irrigation.

Special features/product advantages


- Efficiency-optimised, laser-welded 2D/3D hydraulics, flow and
degassing optimised
- Corrosion-resistant impellers, guide vane apparatuses and stage
housings
- Flow and NPSH-optimised pump housing
- Maintenance-friendly design with particularly robust coupling
guard
- Drinking water approval for all parts that come into contact with
the fluid (EPDM version)

Scope of delivery
- Wilo-Helix V high-pressure multistage centrifugal pump
- Installation and operating instructions
- Counter flanges of cast iron with the corresponding screws, nuts
and gaskets for PN16 pump version with oval flanges

Design notes
- Motor protection for 3-phase motor is to be provided on request
or onsite
- Single-phase AC motor equipped with built-in thermal motor
protection and capacitor
- In its standard position, the terminal box is aligned with the
suction flange, but this can be changed if necessary
- The Wilo-Helix V is equipped with a user-friendly mechanical
seal in a cartridge design and standard gasket for easy
maintenance

- The spacer coupling (from = 7.5 kW) allows the mechanical seal

to be replaced without removing the motor


- The flexible lantern design, which is available in two alignments,
enables direct access to the mechanical seal
- Oval and round counter flanges are available as accessories in
stainless steel or cast iron
- Bypass sets are available as accessories

Software version Spaix, Version 4.3.13 - 2021/02/23 (Build 180)


Subject to change Data version 02.05.2022 Pages 1/ 3
Tender text
Contact
E-mail
Phone
Fax
Customer Project name Untitled project 2022-06-09 15:52:03.128

Project ID
Contact
E-mail
Phone

Date 09.06.2022

Pos.no Qty. Description PG UP / EUR TP / EUR


Fluid media: Water 100 %
Fluid temperature: 10,00 °C
Fluid concentration: 100,00 %
Requested flow: 100,00 US g.p.m.
Requested head: 105,00 m

Product data
Min. fluid temperature: -30 °C
Max. fluid temperature: 120 °C
Max. ambient temperature: 50 °C
Maximum operating pressure: 25 bar
Maximum inlet pressure: 1 MPa
Minimum efficiency index (MEI):

Motor data
Mains connection: 3~460 V/60 Hz
Voltage tolerance: +-6 %
Rated power: 11 kW
Motor efficiency class: IE3
Rated current: 18,2 A
Rated speed: 3535 1/min
Power factor: 0,91
Motor efficiency:
Motor efficiency:
Motor efficiency:
Insulation class: F
Protection class: IP55

Materials
Pump housing: 1.4301
Impeller: 1.4307
Shaft: 1.4301
Shaft seal: U3BE3GG
Gasket material: EPDM

Installation dimensions
Pipe connection on the suction side: DN 50, PN 25
Pipe connection on the discharge side: DN 50 , PN 25

Ordering information
Brand: Wilo
Product description: Helix V 1609-1/25/E/KS/460-60
Net weight, approx.: 123 kg
Article number: 4192471

Total Price Price on req.

Software version Spaix, Version 4.3.13 - 2021/02/23 (Build 180)


Subject to change Data version 02.05.2022 Pages 2/3
Technical data
Contact
E-mail High-pressure multistage centrifugal pump
Phone Helix V 1609-1/25/E/KS/460-60
Customer Project name Untitled project 2022-06-09 15:52:03.128

Project ID
Contact Installation location
E-mail Customer pos.no
Phone

Date 09.06.2022

Duty chart Requested data


Head - 1609 Flow 100,00 US g.p.m.
H /m ∆ p / MPa
Head 105,00 m
Media Water 100 %
Eff. 67,6%
1,2 Fluid temperature 10,00 °C
120
115,4 1,131 Density 998,30 kg/m³
Kin. viscosity 1,00 mm²/s
80 A1 0,8
Hydraulic data (Duty point)
Flow 104,85 US g.p.m.
40 0,4 Head 115,44 m
Shaft power P2 11,22 kW
▕◄ Application range ►▏ Hydraulic efficiency 66,80 %
0 0
Shaft power P2
P₂11,22
/ kW NPSH 3,42 m
5 Product data
High-pressure multistage centrifugal pump
0
Hydraulic efficiency Helix V 1609-1/25/E/KS/460-60
η 66,8
/%
Max. operating pressure 2,5 MPa
Inlet pressure max. 10 bar
0 Fluid temperature -30 °C ... + 120 °C
NPSH-values
NPSH / m Max. ambient temperature 50 °C
Minimum efficiency index (MEI)
5
3,42
Motordata per Motor/Pump
0
104,9 120 Motor efficiency level IE3
0 20 40 60 80 100 140 Q / US g.p.m.
Mains connection 3~ 460 V / 60 Hz
ISO 9906: 2012 3B Dimensions mm Permitted voltage tolerance +-6 %
Max. speed 3535 1/min
H 1342 Rated power P2 11,00 kW
H2 942 Rated current 18,20 A
ØM 260 Power factor 0,91
X 191 Efficiency
50% / 75% / 100% //%
Degree of protection IP55
Insulation class F
Motor protection no
Fitting dimensions
Pipe connection on the suction side DN 50, PN 25
Pipe connection on the pressure side DN 50, PN 25
Materials
Pump housing 1.4301

Impeller 1.4307
Shaft 1.4301
Shaft seal U3BE3GG
Gasket material EPDM
Information for order placements
Weight approx. 123 kg
Item number 4192471

Software version Spaix, Version 4.3.13 - 2021/02/23 (Build 180)


Subject to change Data version 02.05.2022 Pages 3/ 3
Project:
Customer:
Engineer:
Pump Manufacturer:

Technical Data
Submittal Document
Model JP3
Across the Line Start
Jockey Pump Controller

Contents:
Data Sheets
Dimensional Data
Wiring Schematics
Field Connections

Note: The drawings included in this package are for controllers


covered under our standard offering. Actual AS BUILT
drawings may differ from what is shown in this package.
June 2022
M

Technical Data
Model JP3 Jockey Pump Controller

JP3

Underwriters Laboratory (UL) UL508A - Industrial Pump Controllers


New York City Accepted for use in the City of New York by the Department of Buildings
Listing
Optional
CE Mark Various EN, IEC & CEE directives and standards
Protection Rating
Standard: NEMA 2
Optional
NEMA 12 NEMA 4X-304 sst painted
NEMA 3 NEMA 4X-304 sst brushed finish
Enclosure
NEMA 3R NEMA 4X-316 sst painted
NEMA 4 NEMA 4X-316 sst brushed finish
Accessories Paint Specifications
• Wall mounting lugs ( x4) • Red RAL3002
• Powder coating
• Glossy textured finish

This is a Marketing document. Please consult factory for more information.


June 2022 2
Manufacturer reserves the right to modify this information without notice
Technical Data
Model JP3 Jockey Pump Controller

• Main disconnect – padlockable – rotary type handle – door interlocked


Fuseless Motor
• Thermo-magnetic motor protector
Starter
• Contactor
Control Circuit • 24V.AC
• Solid state controls
iPD+ Operator
• All adjustments on door front
Interface
• Navigation pushbuttons
• Pressure transducer for fresh water application 316 stainless steel construction
Pressure Sensing • Rated for 0-600psi working pressure
• Pressure sensing line connection 1/2” brass Male NPT
• Manual motor start/run LED
• Automatic motor start/run LED
• Motor overload
• Pressure reading
• Start pressure
• Stop pressure
Visual Indications • System pressure
• System pressure diagnostic LED’s
• Green: system pressure at or above stop pressure
• Yellow: system pressure between start and stop pressure
• Red: system pressure at or below start pressure
• AUTO mode
• OFF mode
• Minimum run timer (off delay)
Timers • Delay start timer (on delay)
• Visual countdown
• Pump start counter
Counters
• Elapsed timer meter (hours / non-resettable)
• OFF-AUTO pushbutton
Operators
• Start and Stop pushbutton
Automatic Start Start on pressure drop

Manual Start Start pushbutton


Operation
Stopping Stop pushbutton
Field adjustable & • Minimum run timer (off delay)
Timers
visual countdown • Delay start timer (on delay)

This is a Marketing document. Please consult factory for more information.


June 2022 Manufacturer reserves the right to modify this information without notice 3
Technical Data
Model JP3 Jockey Pump Controller

A4 Elapsed time meter (time totalizer) Seismic Certification compliant to CBC 2019, IBC
D35
A5 Motor run alarm contact 2018 rigid base/wall mounted only
A6 Loss of power alarm contact Special Seismic Certification compliant to OSHPD
D36
rigid base/wall mounted only
A7 Overload or short circuit alarm contact
Pressure transducer 0-600psi with ½” MNPT 316
D11D stainless steel bushing
L01 Other language and English (bilingual)
D14 Export packing for 1 controller L02 French
D13A Externally mounted wetted parts L03 Spanish
D14 Export packing for 1 controller L04 German
D18 Audible alarm L05 Italian
D19 Anti-condensation heater and thermostat L06 Polish
D20 Anti-condensation heater and humidistat L07 Romanian
D21 Tropicalization L08 Hungarian
Phase reversal / failure pilot light and alarm L09 Slovak
D22
contact
L10 Croatian
Controller power healthy pilot light and alarm
D23 L11 Czech
contact
L12 Portuguese
Pump failure via current sensing relay with pilot
D24 L13 Dutch
light and dry alarm contact
D25 Low zone pump control function L14 Russian
D26 Mid zone pump control function L15 Turkish
D27 High zone pump control function L16 Swedish
D28 Selector switch in auto alarm contacts L17 Bulgarian
D29 Selector switch in off alarm contacts L18 Thai
D30 Motor heater circuit L19 Indonesian
Service entrance rated - 100kA short circuit L20 Slovenian
withstand rating: L21 Danish
• 120V/1ph (0.5hp max.) L22 Greek
• 240V/1ph (1hp max.)
D32 L23 Arabic
• 200V-208V - 60hz (2hp max.)
• 220V-240V - 60hz (3hp max.) L24 Hebrew
• 380V-416V - 50hz - 60hz (5hp max.) L25 Chinese
• 440V-480V - 60hz (5hp max.)
Service entrance rated - 65kA short circuit
withstand rating:
• 120V/1ph (0.5hp max.)
• 240V/1ph (1hp max.)
D33
• 200V-208V - 60hz (3hp-15hp max.)
• 220V-240V - 60hz (515hp max.)
• 380V-416V - 50hz - 60hz (7.5hp - 40hp max.)
• 440V-480V - 60hz (7.5hp-40hp max.)
Service entrance rated - 42kA short circuit
D34 withstand rating:
• 600V - 60hz (7.5hp max.)

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

This is a Marketing document. Please consult factory for more information.


June 2022 4
Manufacturer reserves the right to modify this information without notice
Technical Data
Model JP3 Jockey Pump Controller

iPD+ Operator Interface

3 2

4 7

HAND AUTO

5
8

1 - Power on LED 6 - STOP pushbutton


2 - System status LED 7 - Auto start LED
3 - Digital display 8 - Navigation keypad
4 - Hand start LED 9 - ON - OFF pushbutton
5 - START pushbutton

This is a Marketing document. Please consult factory for more information.


June 2022 Manufacturer reserves the right to modify this information without notice 5
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller NYC
Dpt of Building
Approved

Across the Line / 3 Phase REV. DESCRIPTION DD/MM/YY


A Model:JP3 8 Sensing line connection changed 25/03/20 Drawing No. A
Dimensions 10
UL logo updated CSA logo removed
Removed Seismic logo optional
14/07/20
18/05/22
JP3-DI500/E

FU1 DS
B B
D

XTR1
IPD
F C

C C
Main Disconnect
G

Y
ON
R

OL1

OFF
HAND G G AUTO
C1

G DS

D B E D

PT1
Underwriters
Laboratories Inc.

DANGER
R R

LISTED
ENCLOSED INDUSTRIAL CONTROL PANEL
No. AC-XXX

Rating
E Label E
Standard Internal Layout
3
8 "[ ] x4

Sensing Line Connection 1/2 " M.NPT


F F

Dimensions*
Maximum Motor Horsepower Enclosure Dimensions Door Dimensions Anchor Dimensions

G 4- " [115] 200-208V


10HP
220-240V
10HP
380-416V
15HP
440-480V
20HP
575-600V
25HP
AXBXC
10"X12"X6- "
DXE
10- "X12- "
FXG
8"X12- "
G
20HP 30HP 40HP 60HP 60HP 16"X16"X7- " 16- "X16- " 14"X16- "

2- " [58]
A
H H

Notes: Drawing for information only.


- Standard NEMA: NEMA 2
Manufacturer reserves the right to modify this drawing without notice.
- Standard Paint: Textured Red RAL 3002.
I - All Dimensions are in Inches [Millimeters] Contact manufacturer for "As Built" drawing. I
- Use Watertight Conduit and Connector Only. *Dimensions may change depending on option required. Consult Factory for exact Projection

- Protect Equipment Against Drilling Chips. dimensions.


- Door Swing Equal to Door Width
0 1 2 3 4 5 6 7 8
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted published reproduced copied or used in any manner including as the basis for the manufacture or sale of any products without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller C
Dpt of Building
Approved

Across the Line / 3 Phase REV. DESCRIPTION DD/MM/YY


A Model:JP3 7 Revised logo 18/06/18 Drawing o. A
Wiring schematic 8
9
UL logo updated CSA logo removed
Removed Seismic logo (optional)
14/07/20
18/05/22
JP3-WS500/E

L1 L2 L3 Pressure Sensor
PT1 Type 0.5 - 4.5V
B B
G
DS G

White

Black
Red
R

B W G R 5 S

RESET J5
HA D G G AUT

Ps ut-
PsIn-

Ps ut+
PsIn+
L1
C 34 33 7 C
9 I 1 J9
J21
G
I 2
UTPUT J8

J19
"IPD+"
D D
F5

FU1 J2 J3 J1
TR1
24Vac 24Vac
H2 1 3 A2 A1
3 1 22 8
H1 2
1
E E

A1 A2
C1

F F

G G

H H
L1

C1

I
- Drawing for information only. I
G Manufacturer reserves the right to modify this drawing without notice.
T1 T2 T3
Contact manufacturer for "As Built" drawing.
P1
0 1 2 3 4 5 6 7 8
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not be retransmitted, published, reproduced, copied or used in any manner, including as the basis for the manufacture or sale of any products, without the express prior written consent of Tornatech Inc.
0 1 2 3 4 5 6 7 8
PER QUOTE DRAWING No.
Jockey Pump Controller NYC
Dpt of Building
Approved

Across the Line / 3 Phase REV. DESCRIPTION DD/MM/YY


A Model:JP3 7 evised logo
L logo updated CSA logo removed
18/06/18 Drawing No. A
Line and Motor Terminal Size 8
emoved Seismic logo optional
14/07/20
18/05/22
JP3-TD500/E

B B

Power Connections and Motor Connections

3 Phase
Incoming Power
Bonding Ground

C C

L1 L2 L3
DS

C1

D T1 T2 T3 D

E E

Line Terminals L1 L2 L3 GND


Ma imum Motor Horsepower
Wire Size Copper nly Tor ue Wire Size Ground Copper nly
200-208V 220-240V 380-416V 440-480V 575-600V
10HP 10HP 20HP 20HP 25HP #14 AWG - #6 AWG 2 Nm #14 AWG - #2 AWG
20HP 30HP 40HP 60HP 60HP #12 AWG - #1 AWG 6 Nm #6 AWG - #2 AWG

G G

Motor Terminals T1 T2 T3 GND


Ma imum Motor Horsepower
Wire Size Copper nly Tor ue Wire Size Ground Copper nly
200-208V 220-240V 380-416V 440-480V 575-600V
5HP 7.5HP 10HP 15HP 20HP #14 AWG - #10 AWG 1.8 Nm #14 AWG - #2 AWG
H 10HP 10HP 15HP 20HP 25HP #14 AWG - #6 AWG 2.5 Nm #12 AWG - #2 AWG H
15HP 20HP 30HP 50HP 50HP #10 AWG - #3 AWG 5 Nm #12 AWG - #2 AWG
20HP 30HP 40HP 60HP 60HP #10 AWG - #2 AWG 11.3 Nm #12 AWG - #2 AWG

I I

0 1 2 3 4 5 6 7 8
Copyright © 2022 Tornatech Inc. All right reserved. This drawing and the information contained or depicted herein are the sole property of Tornatech Inc. Copies are communicated to the recipient in strict confidence and may not e retransmitted pu lished reproduced copied or used in any manner including as the asis for the manufacture or sale of any products without the e press prior written consent of Tornatech Inc.