Professional Documents
Culture Documents
▲ WARNING
Failure to follow these instructions or
to properly install and maintain this
equipment could result in an explosion,
fire and/or chemical contamination
causing property damage and personal
injury or death.
Fisher™ pressure/vacuum relief
valve must be installed, operated
and maintained in accordance with Figure 2. Enardo 550 Series Pressure/Vacuum Relief Valve -
federal, state and local codes, rules Vent-to-Atmosphere
and regulations and Emerson Process
Management Regulator Technologies
Tulsa, LLC (Emerson) instructions.
Call a qualified service person to service
Introduction
the unit. Installation, operation and
maintenance procedures performed by Scope of the Manual
unqualified person may result in improper
adjustment and unsafe operation. Either This manual provides specifications, installation,
condition may result in equipment operation and maintenance instructions and
damage or personal injury. Only a parts ordering information for the Enardo 450
qualified person shall install or service and Enardo 550 Series pressure/vacuum relief
the Enardo 450 and Enardo 550 Series valve (PVRV).
pressure/vacuum relief valve.
Enardo 450 and Enardo 550 Series
Specifications
The Specifications section on this page provides specifications for the Enardo 450 and Enardo 550 Series
pressure/vacuum relief valve. Specification is stamped on the nameplate attached to the relief valve. Refer to
Product Identification and Marking section for the nameplate details.
1. The pressure limits in this Instruction Manual and any applicable standard or code limitation should not be exceeded.
2. Pressure or vacuum setting has an increment of 0.5 oz./sq. in., 0.5 in. w.c. or 2.2 mbar.
3. Pressure and vacuum settings vary by size. Refer to Table 1 for details.
Enardo 450 — x — / —
Figure 3. Enardo 450 Series Pressure/Vacuum Relief Valve Available Constructions and Model Numbering System
Teflon® and Viton® are marks owned by E. I. du Pont de Nemours and Co.
2
Enardo 450 and Enardo 550 Series
Enardo 550 — — / —
Figure 4. Enardo 550 Series Pressure/Vacuum Relief Valve Available Constructions and Model Numbering System
II 1 G Ex h IIC T6 Ga II 2 G Ex h IIC T6 Gb
Teflon® and Viton® are marks owned by E. I. du Pont de Nemours and Co.
3
Enardo 450 and Enardo 550 Series
4
Enardo 450 and Enardo 550 Series
Table 1. Enardo 450 and Enardo 550 Series Maximum Pressure/Vacuum Setting
5
Enardo 450 and Enardo 550 Series
Table 2. Torque Specifications - Raised Face Flange, Steel only
Notes:
If lubricant is used on bolts, apply Torque Reduction Factor listed in Lubricant Table.
For best results, hardened steel washers should be used on all cast flange bolted connections.
Notes:
Flat faced flanges should never be mated to a raised face flange for installation.
If lubricant is used on bolts, apply Torque Reduction Factor listed in Lubricant Table.
For best results, hardened steel washers should be used on all cast flange bolted connections.
6
Enardo 450 and Enardo 550 Series
7
Enardo 450 and Enardo 550 Series
Table 5. Enardo 450 and Enardo 550 Series Parts Repair
PART REPLACEMENT
Simple replacement. Provided with gasket repair kit along with other gaskets. The pallet seals are fragile, handle the seals
Pallet Seals
carefully to avoid damage. Never fold or crease the pallet seal. Never use abrasive cleaners on a pallet seal.
Pallet Assemblies Drop-in replacement. Requires removal of lid and replacement of gasket. Be careful not to damage the seals.
Body Gaskets Requires disassembly. Provided with gasket repair kit.
Seats Requires gasket to be replaced as well.
Requires removal of lid and replacement of gasket on Enardo 450 Series valves. Ensure that the proper weights are installed
Weights
in the right location.
8. Reinstall valve pallets and weights into their Remove the relief valve from the tank before
proper chambers. attempting any repairs beyond pallet assembly and
weight maintenance as described on the Relief Valve
9. Reinstall weights onto their appropriate Maintenance section.
valve pallets.
Most repairs consist of replacing pallet seals, lid
10. Replace any lid, hood or guide that was removed gaskets and in some cases, the body gaskets. The
and fasten securely. When tightening down lids, seats are also replaceable if necessary. These repairs
make sure the lid gasket has full contact with the
8
Enardo 450 and Enardo 550 Series
Parts Ordering
When corresponding with your local Sales Office about
this equipment, always reference the equipment serial
number stamped on the nameplate.
When ordering replacement parts, specify the
complete 7-character part number of each required
part as found in the following parts list.
Parts List
1 Lid, Pressure
2 Body, Upper
3 Lid, Vacuum
4 Body, Lower
5 Seat, Pressure(1)
9
Enardo 450 and Enardo 550 Series
Enardo 550 Series
Key Description
10
Enardo 450 and Enardo 550 Series
Table 6. Enardo 450 and Enardo 550 Series Pressure Relief Valve Seats Part Number
PART NUMBER
SERIES DESCRIPTION
Aluminum Carbon Steel Stainless Steel
Table 8. Enardo 450 and Enardo 550 Series Pallet Assembly(1) Part Number
VALVE SIZE PART NUMBER
MODEL
In. mm Pressure (Pallet Location) Vacuum (Pallet Location)
2 51 8850401 8850401
3 76 8850402 8850402
4 102 8850403 8850403
Enardo 550 6 152 8850405 8850405
8 203 8850407 8850407
10 254 8850409 8850409
12 305 8850411 8850411
1. Pallet assemblies with 316 Stainless steel with FEP (Teflon®) seals.
11
Enardo 450 and Enardo 550 Series
Table 9. Enardo 450 and Enardo 550 Series Gasket Sets(1) Part Number
VALVE SIZE
MODEL MATERIAL PART NUMBER
In. mm
Compressed Fiber 6105022
2x3 51 x 76
Teflon® 6105024
Compressed Fiber 6105025
3x4 76 x 102
Teflon® 6105027
Compressed Fiber 6105028
4x6 102 x 152
Teflon® 6105030
Webadmin.Regulators@emerson.com Facebook.com/EmersonAutomationSolutions
Enardo.com LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation
D103812X012 © 2015, 2022 Emerson Process Management Regulator
Technologies, Inc. All rights reserved. 01/22.
Emerson Automation Solutions The Emerson logo is a trademark and service mark of Emerson
Electric Co. All other marks are the property of their prospective owners.
Fisher™ is a mark owned by Fisher Controls International LLC, a
Americas Asia Pacific business of Emerson Automation Solutions.
McKinney, Texas 75070 USA Singapore 128461, Singapore The contents of this publication are presented for information purposes
T +1 800 558 5853 T +65 6777 8211 only, and while effort has been made to ensure their accuracy, they are
+1 972 548 3574 not to be construed as warranties or guarantees, express or implied,
regardingthe products or services described herein or their use or
Tulsa, OK 74146 USA
applicability. All sales are governed by our terms and conditions, which
T +1 918 662 6161 are available on request. We reserve the right to modify or improve the
Middle East and Africa designs or specifications of our products at any time without notice.
Europe
Bologna 40013, Italy Dubai, United Arab Emirates Emerson Process Management Regulator Technologies Tulsa, LLC
T +39 051 419 0611 T +971 4 811 8100 does not assume responsibility for the selection, use or maintenance of
any product. Responsibility for proper selection, use and maintenance of
any Emerson Process Management Regulator Technologies Tulsa, LLC
product remains solely with the purchaser.