Professional Documents
Culture Documents
Site Planning Guide – System
Specific requirements for CT project planning
siemens-healthineers.com
Document scope
This document is valid for:
SOMATOM go.Now / go.Up
Document Version
Siemens Healthcare GmbH reserves the right to change its products and services at any time.
In addition, manuals are subject to change without notice. The hardcopy documents correspond to the version
at the time of system delivery and/or printout. Versions to hardcopy documentation are not automatically
distributed.
Please contact your local Siemens Healthineers office to order a current version or refer to our website http://
www.siemens-healthineers.com.
Disclaimer
Siemens Healthcare GmbH provides this documentation “as is” without the assumption of any liability under
any theory of law.
The content described herein shall be used by qualified personnel who are employed by Siemens Healthcare
GmbH or one of its affiliates or who are otherwise authorized by Siemens Healthcare GmbH or its affiliates to
use such documents.
Assemblers and other persons who are not employed by or otherwise directly affiliated with or authorized by
Siemens Healthcare GmbH or one of its affiliates are not entitled to use this documentation without prior
written authority.
Copyright
“© Siemens Healthineers, 2018” refers to the copyright of a Siemens Healthineers entity such as:
1 General information 6
1.1 Preamble 6
1.1.1 CT Basic PG 6
1.1.2 CT Options PG 6
1.2 Safety information 6
1.2.1 Warning notes 6
1.2.2 Regulatory affairs 10
1.3 System configuration 10
1.4 Notes 13
1.4.1 Validity 13
1.4.2 Additional documentation 13
1.4.3 Preliminaries 13
1.4.4 Notes with respect to drawings and figures 14
1.5 Handover to service 14
2 Room planning 15
2.1 General notes 15
2.1.1 Manufacturer and legal notes 15
2.1.2 Flooring 15
2.1.3 Room climate 15
2.2 Room data 15
2.2.1 Area requirements (minimum technical requirement) 16
2.3 Dimensions of components 23
2.3.1 SOMATOM go.Now with PHS Vector 24
2.3.2 SOMATOM go.Now with PHS Vario 1 25
2.3.3 SOMATOM go.Up / go.All / go.Top / go.Fit with PHS Vario 1 / Vario RT 26
2.3.4 SOMATOM go.Up / go.All / go.Top / go.Fit with Vario 2 27
2.3.5 SOMATOM go.Sim / go.Open Pro with Vario RT 28
2.3.6 SOMATOM go.Sim / go.Open Pro with Vario 2 29
2.3.7 PHS Vector 30
2.3.8 PHS Vario 1 / Vario RT on go.Now 31
2.3.9 PHS Vario 1 / Vario RT on go.Up / go.All / go.Top / go.Fit 32
2.3.10 PHS Vario RT on go.Sim / go.Open Pro 33
2.3.11 PHS Vario 2 on go.Up / go.All / go.Top / go.Fit / go.Sim / go.Open Pro 34
2.3.12 Operating console 34
2.3.13 Wireless access point (option) 35
2.3.14 Haloriel (option) 36
2.3.15 Mechanical Docking Station (Option) 37
2.3.16 Injector arm on go.Sim / go.Open Pro 41
2.4 Radiation protection 42
2.4.1 Regulations 42
2.4.2 Visual radiation warning indicators 43
2.4.3 Radiation locking 43
2.4.4 Local dose distribution 44
2.5 Static requirements 51
2.5.1 Floor requirements for gantry and patient table 51
2.5.2 Gantry floor loads 51
2.5.3 Floor and building vibrations 54
3 Installation preparation 57
3.1 General notes and regulations 57
3.2 Installation of components 57
3.2.1 Gantry 57
3.2.2 Patient table 59
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 3 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
Table of contents
4 System connections 88
4.1 General information 88
4.1.1 Line voltage cables 88
4.1.2 Signal- and data cables 88
4.1.3 Fiber-optic cables 88
4.1.4 Wiring sets 88
4.1.5 Fixed points 88
4.2 Wiring schematic with standard components 89
4.3 Cable characteristics 91
5 Technical Data 92
5.1 Dimensions, weights, noise levels, and heat dissipations 92
5.2 Environmental conditions for operation 93
5.2.1 Climatic data for operation 93
5.2.2 Illumination 93
5.2.3 Air intake and air filter 93
5.2.4 Air pollution 93
5.3 Electrical data 93
5.3.1 Loop impedance 93
5.3.2 Line voltage, line frequency, power factor and line impedance 94
5.3.3 Potential difference 95
5.3.4 Power consumption of overall system 95
5.3.5 Transformers 96
5.3.6 UPS for the overall system 97
5.3.7 Connection value 97
5.3.8 Electromagnetic compatibility (EMC) 97
5.3.9 Magnetic field 97
5.3.10 Interference immunity 98
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 5 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
1 General information
1 General information
1.1 Preamble
To simplify handling and editorial effort for the current CT System Planning Guide (CT System PG) a common ...
were developed.
Therefore, the CT Basic PG and the CT Options PG must be used in addition for the planning of a CT system.
1.1.1 CT Basic PG
It includes both common information as well as facts independent of CT model or version that are necessary
for planning CT systems.
The basic requirements for planning CT systems may be identical for some systems independent of the version
model.
1.1.2 CT Options PG
There are CT options available and used by more than one CT system regardless of the CT model or version.
This CT Options PG includes only the required planning information for the CT options that are used by more
than one CT system.
The content of this CT Options PG is limited to the technically required information to plan the on-site
preparation of the corresponding option only.
Please observe the additional safety information provided in the CT Basic PG, print number
CT00-000.891.04.
Observe every warning listed below. The following warnings and cautions always apply for the planning
of SOMATOM go.Now, go.Up, go.All, go.Fit, go.Top, go.Sim and go.Open Pro systems:
CAUTION
[ hz_pgdoc_F02G09U02M03 ] Insufficient spacing between the system and the wall may result in injury
to the user and patient.
Risk of injury!
◆ Minimum distances between the system and the wall have to be observed in accordance with the
planning guide.
hz_pgdoc_F02G09U02M03
CAUTION
[ hz_pgdoc_F02G09U03M03 ] The extension of the scan range may result in injury to the user and the
patient.
Risk of injury!
◆ Minimum distances between the system and the wall have to be observed in accordance with the
planning guide.
hz_pgdoc_F02G09U03M03
CAUTION
[ hz_pgdoc_F02G10U03M04 ] An improperly secured table can cause injury to the user and patient.
Risk of injury!
◆ Securing the patient table to the floor is mandatory as specified in the planning guide and installation
instructions.
hz_pgdoc_F02G10U03M04
CAUTION
[ hz_pgdoc_F04G02U05M04 ] Inadequate room shielding can cause risk of injury to users and
surroundings.
Risk of injury!
CAUTION
[ hz_pgdoc_F12G03U01M04 ] Tripping (e.g. due to cables) can cause injury to the user and the patient.
Risk of injury!
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 7 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
1 General information
WARNING
[ hz_pgdoc_F13G01U12M04 ] Failure to observe the guidelines specified in this document may lead to
serious injury or loss of life.
CAUTION
[ hz_pgdoc_F13G01U16M02 ] Transport with the rollers swivelled in is permissible only when narrow
places make it impossible to transport the system with the rollers swivelled out.
Tipping hazard!
◆ As soon as the system has passed through narrow passages, the transport rollers must be swivelled
out again.
hz_pgdoc_F13G01U16M02
WARNING
[ hz_pgdoc_F14G02U01M04 ] In regions prone to earthquakes, the gantry may fall over during an
earthquake.
Risk of injury!
◆ Observe the special instructions in the planning and installation guides regarding regions prone to
earthquake.
hz_pgdoc_F14G02U01M04
In addition, the following hazard information is applicable specifically to the CARE Vision CT options from
ONDAL (effective from 2010) and HSEKE (effective from 2014):
CAUTION
Risk of injury!
◆ The ceiling support and ceiling-mounted monitor have to be installed in accordance with the planning
guide and installation instructions.
hz_pgdoc_F14G05U01M02
CAUTION
Risk of injury!
◆ Observe the minimum distances described in the planning guide.
hz_pgdoc_F14G06U01M03
CAUTION
[ hz_pgdoc_F14G06U02M03 ] Insufficient spacing between the monitor in park position and the gantry
can cause injury to the user.
Risk of injury!
◆ The minimum distances between the monitor in park position and the gantry have to be observed.
hz_pgdoc_F14G06U02M03
CAUTION
[ hz_pgdoc_F21G03U04M02 ] The mounting of the interface plate was not performed correctly.
◆ The mounting of the interface plate and the anchor plate connected to the ceiling may be carried out
only by a company specialized in concrete drilling and sawing.
hz_pgdoc_F21G03U04M02
CAUTION
Risk of injury!
◆ The ceiling support and ceiling-mounted monitor have to be installed in accordance with the planning
guide and installation instructions.
hz_pgdoc_F21G03U05M01
CAUTION
Risk of injury!
◆ The ceiling-support and ceiling-mounted monitor have to be installed according to the planning guide
and installation instructions.
hz_pgdoc_F21G12U01M02
CAUTION
Insufficient spacing between the injector arm and the wall may result in injury to the user and patient.
Risk of injury!
◆ Minimum distances between the injector and the wall have to be observed in accordance with the
planning guide.
hz_pg_F14G06U03M01
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 9 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
1 General information
CAUTION
[hz_pgdoc_F02G31U01M02] Incorrect installation of the camera can cause injury to the user and
patient.
Risk of injury!
◆ The camera needs to be installed according to the Planning Guide and Installation Instructions.
hz_pgdoc_F02G31U01M02
• SOMATOM go.Now
• SOMATOM go.Up
• SOMATOM go.All
• SOMATOM go.Top
• SOMATOM go.Fit
• SOAMTOM go.Sim
System Description
component
go.Now go.Up go.All go.Top go.Fit go.Sim go.Open
Pro
Acquired slices
PDS Integrated in the right gantry stand (consists of PDB and isolation transformer).
System Description
component
go.Now go.Up go.All go.Top go.Fit go.Sim go.Open
Pro
Component Description
Gantry drilling plate Template including footprint information for the gantry only. It can be ordered
in the price book.
(not valid for go.Sim /
go.Open Pro) Order number: 11102305
Installation template Template including footprint information for the gantry and PHS. Order
number:
• 11102041 - go.Now
• 11102042 - go.Up / go.All / go.Top / go.Fit
• 11102043 - go.Sim / go.Open Pro
Haloriel With one lighting integrated inside, the different colors are indicated before,
during and after API playing.
Table footswitch It is to be installed on the floor between gantry and PHS, the load and unload
pedals are located at both left and right side.
System furniture For details, refer to the chapter “System furniture” in the CT option PG, print
number CT00-000.891.03.
Remote control wireless This option provides the same control functions as wired remote control,
however it communicates with the system wirelessly.
• Movement of patient table
• Start / suspend the X-ray scan
• Switch on / off the light markers
Dual Monitors The second monitor is placed next to the main monitor to form one extended
monitor; then the tasks will be shared by two monitors in control room.
• Main monitor: scan and recon
• Dual monitor: viewing, printing and distribution
Additional monitor One or two monitors can be placed in other rooms. They are connected to ICS
via DP splitter, then show the same contents as control room. The Monitor
Ceiling System or Monitor Cart has to be ordered together to support care
vision CT.
For planning details, refer to the chapter “Additional monitors” in the CT
Options PG, print number CT00-000.891.03.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 11 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
1 General information
Component Description
DP splitter The DP splitter replicates the digital video signal from the ICS tower PC into
two digital signals and sends them to two monitors.
The video signal is transmitted from the ICS via the DP splitter and DP cable
straight to the monitor(s).
The DP splitter units are installed in the gantry.
P splitter
Injector arm The accessory is installed at the top of the gantry close to the right side. It
provides the interfaces for both injector and tablet connections. It can be
arranged at the gantry front side or rear side by turning the mechanism.
3D camera This needs to be installed on the ceiling to deliver the required data for the
automatic and reproducible positioning of patients.
For planning details, refer to the chapter “3D camera” in the CT Option PG,
print number CT00-000.891.03.
Component Description
Ethernet switch ICSi-1d only allows a 1GB network connection. A switch is necessary when
the local network does not support 1GB.
It can be sourced from Siemens (#MN 10547105) or procured locally.
1.4 Notes
1.4.1 Validity
This System PG solely addresses technically required planning information for:
• SOMATOM go.Now
• SOMATOM go.Up
• SOMATOM go.All
• SOMATOM go.Top
• SOMATOM go.Fit
• SOMATOM go.Sim
1.4.3 Preliminaries
The project manager has to clarify the following CT components, accessories on-site, information, etc.
Designation Description
System cables Clarify the required cable lengths and include these in the order.
(system connections) • Available cable sets (lengths): 15 m/30 m
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 13 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
1 General information
Designation Description
SRS Connectivity The project manager must ensure that the SRS connection is available
(according to the sales contract) once the system installation is complete.
Without SRS connectivity, service cannot be provided efficiently!
Tab. 4: Preliminaries
All drawings as well as images in this planning guide are not true to scale. For this reason, they are not
suitable for providing actual dimensioning. If not stated otherwise, all dimensions are provided in [mm].
2 Room planning
2.1 General notes
During room planning, please adhere to country-specific guidelines, e.g., national regulations with respect
to safety distances for electrically operated systems.
2.1.2 Flooring
Anti-static flooring is recommended for the examination room (for example, the flooring type specified in IEC
61340-5-1:2007, Part 5-1).
For more details, refer to the “Transport and storage conditions” chapter.
The room environmental conditions must be carefully monitored as soon as the CT system is unpacked.
During room planning, please adhere to country-specific guidelines, e.g., national regulations with respect
to safety distances for electrically operated systems.
Description Height
(mm)
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 15 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
Description Height
(mm)
• Without allowances for safety distances pursuant to the federal guidelines for the country in question.
;
5
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 17 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
;
5
Fig. 2: Minimum technical requirements: SOMATOM go.Now with PHS Vario 1 / Vario RT
SOMATOM go.Up, go.All, go.Top and go.Fit with PHS Vario 1 / Vario RT
;
5
Fig. 3: Minimum technical requirements: SOMATOM go.Up / go.All / go.Top / go.Fit gantry and PHS Vario 1 / Vario RT
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 19 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
;
5
Fig. 4: Minimum technical requirement: SOMATOM go.Up, go.All, go.Top and go.Fit with PHS Vario 2
;
5
Fig. 5: Minimum technical requirement: SOMATOM go.Sim / go.Open Pro with PHS Vario RT
No. 3: the range between 1115 and 1700 mm is also acceptable, refer to ( Page 41 Injector arm on
go.Sim / go.Open Pro)
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 21 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
;
5
Fig. 6: Minimum technical requirement: SOMATOM go.Sim / go.Open Pro with PHS Vario 2
No. 3: the range between 1115 and 17000 is also acceptable, refer to ( Page 41 Injector arm on go.Sim /
go.Open Pro)
go.Up
go.Up go.All
go.All go.Top
go.Now
go.Top go.Fit
Adjustable scannable go.Fit go.Sim
range X
go.Open Pro
Range 1c) 1020 (1535) 1175 (1680) 1350 (1680) 1750 (2080)
a) The specified lengths of the head holder and table extension included with delivery are given in the next table
b) The value can be configured as Horizontal Table Range under Service Local >Technical Configuration > Miscellaneous
c) Nominal scannable range of the patient table as delivered.
From July 2019, the delivered PHS Vario RT will be modified with:
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 23 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
2)
422
3
6
7 1)
1
0
9
8
175 603
861 1204
230
761
(D)
(C) 1) 1)
3)
2465 515 1020 100
100
778 2)
422
4)
7
1
7
0
5
6
5 4
5 3 6
7
0 8
1
1
5)
833 118 594
A Side view
B Front view
C Top view
D Dimensions of the fan grille (top view)
1 Slice plane
2 Phantom and phantom holder
3 Scannable range without head holder (250 mm) or table extension (250 mm)
4 Air exhaust for rotation components
5 Air exhaust for stationary components
177
3
6
7
1
0
91)
8
563
(C) (D) 1)
1)
3) 2)
100
2465 505 1175 344
100
778
4) 7
1
7
0
5
6
5 4
5 3 6
0 8 7
1
177 1
5)
118 594
833
A Side view
B Front view
C Top view
D Dimensions of the grille (top view)
1 Slice plane
2 Phantom and phantom holder
3 Scannable range without head holder (250 mm) or table extension (250 mm)
4 Air exhaust for rotation components
5 Air exhaust for stationary components
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 25 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
2.3.3 SOMATOM go.Up / go.All / go.Top / go.Fit with PHS Vario 1 / Vario RT
Fig. 9: Detailed dimensions: SOMATOM go.Up / go.All / go.Top / go.Fit with PHS Vario 1 / Vario RT
A Side view
B Front view
C Top view
D Gantry tilt view
E Dimensions of the fan grille
1 Slice plane
2 Phantom and phantom holder
3 Scannable range without head holder (250 mm) or table extension (250 mm)
4 Air exhaust for rotation components
5 Air exhaust for stationary components
Fig. 10: Detailed dimensions: SOMATOM go.Up / go.All / go.Top with PHS Vario2
A Side view
B Front view
C Top view
D Gantry tilt view
E Dimensions of the fan grille
1 Slice plane
2 Phantom and phantom holder
3 Scannable range without head holder (250 mm) or table extension (200 mm)
4 Air exhaust for rotation components
5 Air exhaust for stationary components
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 27 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
Fig. 11: Detailed dimensions: SOMATOM go.Sim / go.Open Pro with PHS Vario RT
A Side view
B Front view
C Top view
D Gantry tilt view
E Dimensions of the fan grille
1 Slice plane
2 Phantom and phantom holder
3 Scannable range without any accessory
4 Air exhaust for rotation components
5 Air exhaust for stationary components
6 RTP laser units
Fig. 12: Detailed dimensions: SOMATOM go.Sim / go.Open Pro with PHS Vario 2
A Side view
B Front view
C Top view
D Gantry tilt view
E Dimensions of the fan grille
1 Slice plane
2 Phantom and phantom holder
3 Scannable range without any accessory
4 Air exhaust for rotation components
5 Air exhaust for stationary components
6 RTP laser units
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 29 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
(C) (A)
1)
890
829
740
740
610
480 915 1295
1)
422
(B)
X 515 2465
A Side view
B Top view
C Front view of item (A)
1 Slice plane
%
'
&
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 31 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
$
' %
&
Fig. 15: Detailed dimensions: PHS Vario 1 / Vario RT on SOMATOM go.Up / go.All / go.Top / go.Fit
' %
&
Fig. 16: Detailed dimensions: PHS Vario RT on SOMATOM go.Sim / go.Open Pro
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 33 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
2.3.11 PHS Vario 2 on go.Up / go.All / go.Top / go.Fit / go.Sim / go.Open Pro
$
' %
&
Fig. 17: PHS Vario 2 on SOMATOM go.Up / go.All / go.Top / go.Fit / go.Sim / go.Open Pro
Item Description
Monitors • Pre-planning is not necessary due to the small dimensions and the predetermined
locations of the individual components.
• For the dimensions, refer to ( Page 92 Dimensions, weights, noise levels, and
heat dissipations).
Keyboard/mouse No measurements are given; pre-planning is not necessary due to the small dimen‐
sions and the predetermined location of the individual components.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 35 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
4) 3)
5)
1)
2)
6)
mm
5 00
>2
> 2000 mm
7)
1 Access point
2 Wall mounting adapter
3 Power socket outlet (L, N, PE)
4 Power cable (3 m, delivered with access point)
5 Ethernet cable on right side of gantry (15 m or 25 m, starting in Feb. 2019)
6 Distance to isocenter
7 Suggested distance to ground (as high as possible, if room height is less than 2000 mm)
130
100
1) 1)
2)
142
112
58
2)
3) 1) 1)
Ø4
1 Mounting holes
2 Alternative mounting holes
3 Diameter of mounting holes
If one external laser system is planned for the RTP function, the dimensions have to considered to avoid
blocking the laser beam.
4) 510
491
3)
A
2)
0
1) 15
125 125
B
A
C
A Haloriel
B Stand unit of external laser system
C Ceiling unit of external laser system
1 Isocenter
2 Laser beam
3 Distance from Haloriel to isocenter
4 Required min. distance from laser beam to isocenter
The dock must be arranged at least 1.5 m away from the patient table to ensure that it is impossible to
touch the patient and the USB plug contacts at the same time.
1 Dock
2 Mounting plate
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 37 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
1 Slanted frame
2 Base plate
The dock (2.5 kg) must be installed within a 1.5 m radius of a wall outlet.
The four M4 countersunk screws and expansion tube are included in the delivery.
The dock has sufficient space for the cord inside it, so it can be installed directly on top of a wall outlet,
covering the outlet. The following photo shows the dock mounted on the wall:
Fig. 25: Hollow space to accommodate the cable if the dock is mounted directly on top of the wall outlet
Reserve at least 150 mm on both the left and right sides for handling of installation tools.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 39 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
• Positioning on a desk:
When the dock stand (4.9 Kg) is ordered additionally, it can be placed on a desk.
If required, the dock may be fixed to the desk to keep it from being moved.
$ $
[
r
$$
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 41 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
2.4.1 Regulations
Plan measures involving radiation protection and implement prior to starting up the CT system.
In Germany, DIN 6812 includes the radiation protection required to prevent damage by means of radiation.
Please note the IEC 60601 and CFR 21, as well as the respective country regulations.
• Location:
– if there are no operating panels in the back, a radiation warning indicator is integrated into the rear gantry
cover above the funnel.
It is possible to connect:
• An on-site radiation ready indicator according to IEC 60601-2-44 and CFR 21 in the CT system.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 43 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
• SOMATOM go.Now
Local dose distribution through the system axis in the horizontal and vertical planes. Scanning was
performed using a maximum collimation of 16 x 0.7 mm (11.2 mm) at the maximum tube voltage 130 kV.
A cylindrical PMMA phantom measuring 32 cm in diameter and 15 cm in length was used for the scatter
radiation measurement. The phantom was centered on the tomographic plane.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 45 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
• SOMATOM go.Up
Local dose distribution through the system axis in the horizontal and vertical planes. Scanning was
performed using a maximum collimation of 32 x 0.7 mm (22.4 mm) at the maximum tube voltage of 130
kV. A cylindrical PMMA phantom measuring 32 cm in diameter and 15 cm in length was used for the scatter
radiation measurement. The phantom was centered on the tomographic plane.
• SOMATOM go.All
Local dose distribution through the system axis in the horizontal and vertical planes. Scanning was
performed using a maximum collimation of 32 x 0.7 mm (22.4 mm) at the maximum tube voltage of 140
kV. A cylindrical PMMA phantom measuring 32 cm in diameter and 15 cm in length was used for the scatter
radiation measurement. The phantom was centered on the tomographic plane.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 47 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
• SOMATOM go.Top
Local dose distribution through the system axis in the horizontal and vertical planes. Scanning was
performed using a maximum collimation of 64 x 0.6 mm (38.4 mm) at the maximum tube voltage of 140
kV. A cylindrical PMMA phantom measuring 32 cm in diameter and 15 cm in length was used for the scatter
radiation measurement. The phantom was centered on the tomographic plane.
• SOMATOM go.Sim
Stray radiation is indicated for the horizontal and vertical planes on the basis of the scanner coordinate
system (intersection of scanner axis with scan plane) at the maximum tube voltage and maximum total
collimation width. A cylindrical PMMA phantom with a diameter of 32 cm and a length of 15 cm is centered
in the scan plane for the stray radiation measurement. A 1000 cm3 spherical dose chamber with 140mm
diameter is used for the measurement.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 49 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
Stray radiation is indicated for the horizontal and vertical planes on the basis of the scanner coordinate
system (intersection of scanner axis with scan plane) at the maximum tube voltage and maximum total
collimation width. A cylindrical PMMA phantom with a diameter of 32 cm and a length of 15 cm is centered
in the scan plane for the stray radiation measurement. A 1000 cm3 spherical dose chamber with 140mm
diameter is used for the measurement.
• SOMATOM go.Now
Total static load, resulting in the center of gravity of the gantry: 11.20
Fstat total [kN]
Nominal static load after leveling: Fstat nom [kN] 1.91 3.01 3.31 2.97
During gantry installation and leveling, the maximum possible load on one gantry foot is 6.47 kN (with
the gantry standing on two diagonal feet).
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 51 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
• SOMATOM go.Up
Total static load, resulting in the center of gravity of the gantry: 12.78
Fstat total [kN]
Nominal static load after leveling: Fstat nom [kN] 2.63 3.12 4.37 2.66
During gantry installation and leveling, the maximum possible load on one gantry foot is 7.66 kN (with
the gantry standing on two diagonal feet).
• SOMATOM go.All
Total static load, resulting in the center of gravity of the gantry: 12.86
Fstat total [kN]
Nominal static load after leveling: Fstat nom [kN] 2.65 3.14 4.39 2.68
During gantry installation and leveling, the maximum possible load on one gantry foot is 7.71 kN (with
the gantry standing on two diagonal feet).
Total static load, resulting in the center of gravity of the gantry: 12.95
Fstat total [kN]
Nominal static load after leveling: Fstat nom [kN] 2.66 3/16 4.43 2.70
During gantry installation and leveling, the maximum possible load on one gantry foot is 7.76 kN (with
the gantry standing on two diagonal feet).
• SOMATOM go.Sim
Nominal static load after leveling: Fstat nom [kN] 3.44 4.75 5.10 3.70
During gantry installation and leveling, the maximum possible load on the gantry foot is 9.85 kN (with
the gantry standing on two diagonal feet).
Total static load, resulting in the center of gravity of the gantry: 17.08
Fstat total [kN]
Nominal static load after leveling: Fstat nom [kN] 3.43 4.61 5.26 3.78
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 53 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
During gantry installation and leveling, the maximum possible load on the gantry foot is 9.87 kN (with the
gantry standing on two diagonal feet).
2.5.3.1 General
External vibrations or shocks transmitted by the walls or the floor of the building may affect the gantry and
degrade image quality. Therefore the gantry and the patient table must be installed in an environment free
of vibrations
Sources that produce vibrations include:
• Railroad routes
• Subways
• Roads
• Ferry moorings
The CT system is not sensitive to common vibrations. If the CT is away from vibrational sources, or the CT is
replacing a CT system that to date has not shown image quality problems due to vibrations, it is usually not
necessary to execute vibrational measurements.
If there are any doubts, the following thresholds have to be verified by measurement:
In the 3 spatial directions, acceleration in vibrations at the mounting points of the computed tomography
system (gantry and Patient Handling System PHS) must not exceed the thresholds as described in the following
sections.
NOTES:
• The threshold is defined as acceleration rms value (root mean square) in m/s2 of an FFT spectrum
derived with a frequency resolution of 1 Hz and using a Hanning window.
• The vibrations have to be measured with a sampling rate of 1000 Hz using an anti-aliasing-filter with
a limit frequency of 250 Hz.
• The threshold is valid for vibrations at the installation location with a CT in position.
• Measurements are usually taken at the site before the installation of the CT. Changes in the
eigenfrequency of the slab caused by the additional mass of the CT have to be considered when
comparing the frequency spectrum with the threshold.
Frequency [Hz] Acceleration rms [m/s2] Frequency [Hz] Acceleration rms [m/s2]
1 0.020 16 0.048
2 0.022 17 0.053
3 0.024 18 0.059
4 0.025 19 0.064
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 55 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
2 Room planning
Frequency [Hz] Acceleration rms [m/s2] Frequency [Hz] Acceleration rms [m/s2]
5 0.026 20 0.070
6 0.027 25 0.079
7 0.027 30 0.086
8 0.028 35 0.093
9 0.029 40 0.100
10 0.029 45 0.122
11 0.030 50 0.146
12 0.030 55 0.172
13 0.034 60 0.200
14 0.039 80 0.300
Tab. 15: Threshold values of admissible acceleration (rms value of 1-Hz resolution FFT)
3 Installation preparation
3.1 General notes and regulations
For details, refer to the chapter “Installation preparation” in the CT Basic PG, print number CT00-000.891.04.
3.2.1 Gantry
Subgrade a) As a rule: concrete and bonded screed For details, refer to the chapter “Installation prepara‐
is to prefer. tion” in the CT Basic PG, print number
CT00-000.891.04.
Evenness of floor The permissible tolerance for the even‐ Gantry leveling tolerance:
ness of the floor is max. 10 mm, refer‐
enced to the area of the adjustable feet • In the Z-direction: ± 0.2 deg.
of the gantry and patient table. • In the X-direction: ± 0.5 deg.
Floor covering Remove the floor covering in the bear‐ The area to be cut out is at least the diameter of the
ing areas. bearing areas of the adjustable feet (∅ 54 mm).
Positioning and level‐ • Stands on 4 adjustable feet. NOTE: The gantry and the patient table have to be on
ing the same (isocenter) plane.
• Leveling with the four adjustable
feet.
Floor mounting Generally not required for system Only as required in accordance with national
operation. regulations currently in force, e.g., in countries
prone to earthquakes.
• The system is leveled by means of the
four adjustable feet ( Page 58, Fig. • The project manager decides how the mounting is
43). performed.
• Five gantry CBC feet ( Page 58, Fig. • Installation materials must be sourced locally. The
44) are delivered with CBC kit relevant California Building Code (CBC)
(option). This provides flexibility and specifications can be found here: ( Page 59, Tab.
allows the use of different screws. 17) .
Cable duct Is attached between gantry base and • No on-site preparations are required.
patient table base.
(between PHS and gan‐ • The cable duct is glued to the floor (double-sided
try) adhesive tape is already attached).
a) An engineer must test the weight capacity of the concrete flooring or other subgrades.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 57 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
1 Long-hole washer
2 Gantry CBC foot
Fig. 46: Preferred screw type and wrench (go.Sim / go.Open Pro)
a) Hexagon-head screws and open-end torque wrench are preferred due to limited space near left gantry stand
Subgrade a) As a rule: concrete and bonded For details, refer to the chapter “Installation prep‐
screed is to prefer. aration” in the CT Basic PG, print number
CT00-000.891.04.
Evenness of floor Permissible tolerance for evenness of Add compensating plates: 1.0 mm X 40 pcs and
floor is max. 10 mm referenced to 0.5 mm x 12 mm included in the delivery vol‐
the area of the adjustable feet of the ume).
gantry and patient table.
Floor covering Remove the floor cover in the entire The drilling template is equal to the footprint of
footprint area of the table base. the patient table base and is used as a help to cut
out the floor covering.
Positioning and leveling • Stands on four adjustable feet. The gantry and the patient table have to be on
the same (isocentric) plane.
• Leveling with the four adjustable
feet.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 59 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Minimum extraction force 4.2 kN at each mounting point bear‐ According to IEC 60601-1, it is mandatory that
ing the greatest load at the max. the 4-fold safety factor be observed.
patient travel path.
Drilling template Metal sheet with the outline of the In delivery volume of the patient table.
patient table base. The positions of
the drill holes are integrated.
Sealing Transition table base/floor. The project manager has to provide silicone dur‐
ing the installation.
Adjustable scannable ranges The scannable range of the PHS Vec‐ The adjustment must be performed during sys‐
tor, PHS Vario 1, Vario RT, and Vario tem start-up.
2 patient tables can be adjusted in a
Refer to ( Page 23, Tab. 6) for the step parame‐
stepwise manner.
ters.
The mechanical end-stop can be
adapted to the on-site room situa‐
tion, e.g. in small examination
rooms.
a) An engineer must test the weight capacity of the concrete flooring or other subgrades.
3.2.2.1 Installation material for floor mounting (included in the delivery volume)
• Drilling template
– Torque: 50 Nm
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 61 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Fig. 47: Anchoring for PHS using Würth anchors (typical example)
a) No screed between the PHS base and the concrete at the four support areas around the anchors.
ᤢ
ᤢ
ᤢ ᤢ
ᤢ ᤢ
ᤢ ᤢ
ᤡ% ᤢ ᤢ
ᤢ ᤢ
ᤢ ᤢ
ᤢ
ᤢ
ᤢ ᤢ
ᤢ ᤢ
ᤢ ᤢ
ᤢ
A Overview of the location of the adjustable feet and the floor mounting holes
B Detailed dimensions of the adjustment feet and the floor mounting holes.
1 Slice plane
2 Adjustable feet of the gantry; bearing area 1600 mm2, inner hole: diameter 17 mm.
3 Floor mounting holes of the PHS; diameter: 25 mm
4 Alternative floor mounting holes; diameter: 25 mm
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 63 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
$
%
Fig. 49: Floor installation: SOMATOM go.Now with PHS Vario 1 / Vario RT (up to July, 2019)
A Overview of the location of the adjustable feet and the floor mounting holes
B Detailed dimensions of the adjustable feet and the floor mounting holes
1 Slice plane
2 Adjustable feet of the gantry; bearing area 1600 mm2, inner hole: diameter 17 mm
3 Floor mounting holes of the PHS; diameter: 25 mm
4 Alternative floor mounting holes; diameter: 25 mm
$
%
Fig. 50: Floor installation: SOMATOM go.Now with PHS Vario RT (from August, 2019)
A Overview of the location of the adjustable feet and the floor mounting holes
B Detailed dimensions of the adjustable feet and the floor mounting holes
1 Slice plane
2 Adjustable feet of the gantry; bearing area 1600 mm2, inner hole: diameter 17 mm
3 Floor mounting holes of the PHS; diameter: 25 mm
4 Alternative floor mounting holes; diameter: 25 mm
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 65 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
$
%
Fig. 51: Floor installation: SOMATOM go.Up / go.All / go.Top / go.Fit with PHS Vario 1 / Vario RT (up to July, 2019)
A Overview of the location of the adjustable feet and the floor mounting holes
B Detailed dimensions of the adjustable feet and the floor mounting holes
1 Slice plane
2 Adjustable feet of the gantry; bearing area: 1600 mm2; inner hole diameter: 17 mm
3 Floor mounting holes of PHS; diameter: 25 mm
4 Alternative floor mounting holes; diameter: 25 mm
$
%
Fig. 52: Floor installation: SOMATOM go.Up / go.All / go.Top / go.Fit with PHS Vario RT (from Aug. 2019) / Vario 2
A Overview of the location of the adjustable feet and the floor mounting holes
B Detailed dimensions of the adjustable feet and the floor mounting holes
1 Slice plane
2 Adjustable feet of the gantry; bearing area: 1600 mm2; inner hole diameter: 17 mm
3 Floor mounting holes of PHS; diameter: 25 mm
4 Alternative floor mounting holes; diameter: 25 mm
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 67 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
%
Fig. 53: Floor installation: SOMATOM go.Sim / go.Open Pro with PHS Vario RT (from Aug. 2019) / Vario 2
A Overview of the location of the adjustable feet and the floor mounting holes
B Detailed dimensions of the adjustable feet and the floor mounting holes
1 Slice plane
2/5 Adjustable feet of the gantry; bearing area: 1600 mm2; inner hole diameter: 17 mm
3 Floor mounting holes of PHS; diameter: 25 mm
4 Alternative floor mounting holes; diameter: 25 mm
5 This feet must touch the floor when the gantry is tiltable
• Special pre-planning is not necessary due to the small dimensions and the predetermined location of the
individual components.
• Mounting is required only in accordance with currently valid country regulations in countries prone to
earthquakes, for example. Mounting materials must be provided on-site
Gantry to patient table System cables Routed within the cable duct between the
PHS and the gantry.a)
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 69 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
1037
85 1)
115
2)
69
3)
90 160
Fig. 55: Dimensions: Cable inlet - SOMATOM go.Up / go.All / go.Top / go.Fit
A A A-A
X
22
18
70
70
X Length: 603mm for PHS Vector, 427mm for PHS Vario 1 / Vario RT, 575 mm for PHS Vario 2
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 71 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Rectangular • 300 mm x 60 mm (W x H)
• 200 mm x 60 mm (W x H)
For more details, refer to the chapter “Installation preparation” in the CT Basic PG, print number CT00–
000.891.04.
3.4.3 Routing
The cable ducts can be routed on and in the floor.
We recommend routing the cable ducts in the floor for further service feasibility.
Fig. 58: Cable duct routing beside gantry (on the floor)
On SOMATOM go.Sim and go.Open Pro, the 5th gantry foot is designed.
Only when the system has tilt function, the tilt actuator will be equipped, then the fifth gantry foot has to
touch the floor during system installation.
The fifth foot shouldn’t share floor load from the other four feet on static mode. It will share the load from the
tilt actuator when the gantry is tilting.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 73 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Upholding basic CT system requirements with respect to the on-site power supply line is mandatory.
380 VAC to 480 VAC go.Now One fuse block with 3 fuses per phase:
go.Up 63 A to 80 A NH Type gl/gG.
a) When using other fuses, observe the values shown in the “time-current-characteristics diagram, SIEMENS type series 3NA3 0”. For details, refer
to the chapter “Installation preparation” in the CT Basic PG, print number CT00-000.891.04
In Germany, it is a requirement according to the German regulation DIN VDE 0100- 0530 not to install
an RCD Type B after an RCD Type A.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 75 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Regulatory requirements specify that there must be one STOP or EPO switch located within 5000 mm of any
point in the room.
Therefore, if the scan room is so large so that it cannot be completely covered by a circle with a radius of 5000
mm and 1) ( Page 77, Fig. 61) (1) as the center point, then an additional EPO switch ( Page 77, Fig. 61)
(2) must be installed.
00 0
00
R 50
R5
1)
2)
Scan Room
These buttons are preferably installed so that they are easily accessible on a wall in the operating room.
Pushing the "OFF button" will initiate a system shutdown, taking into account the time, e.g. for cooling down
the gantry. When all processes in the system have finished, the system will open the on-site main conductor.
The ON/OFF push buttons must be provided on-site by the customer and usually consist of two separate
push buttons:
1. ON button: “1 x closer”,
Recommendation: Alternatively, both push buttons can be accommodated in one common housing as a
switching combination incl. a power ON indicator.
In conjunction with the customer, the project manager determines the installation location of the ON/OFF
push button(s). We recommend installing the ON/OFF push button on a wall according the customer's room
choice.
Line System Type Size of connecting ter‐ Recommended length of wire strip‐ Remarks
minal ping and wire terminal
mm2 AWG mm
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 77 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Line System Type Size of connecting ter‐ Recommended length of wire strip‐ Remarks
minal ping and wire terminal
mm2 AWG mm
• ON/OFF switch
• EPO switch
• REPO connection
• RCD
In addition, the on-site power distributor has to comply with the local and national regulations in your
country.
All electrical connections in the on-site power distributor have to be performed as permanent connections.
The system needs a high-quality power distributor that ensures reliable system functionality. It is highly
recommended to order such a power distributor from the Accessory Solutions Pricebook, as a complete,
pre-assembled, tested, and regulatory-approved cabinet. Also use the combination matrices to make sure
you are selecting the right power distributor.
Scan the QR code or click the following link to access AS4U https://as4u.hccloud.siemens.com/#!home
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 79 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Fig. 62: Suggestion: electrical installation with on-site power distributor (go.Now / go.Up)
4a Summation current transformer for MRCD-B attached to Siemens circuit breaker 5SV8701-2KP
11 MRCD Type B 24 V connected to circuit breaker, DC, Siemens 5SV8111-4KK Room Group 1 300 mA, Room Group 2 30 mA
GR Gantry
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 81 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Fig. 63: Suggestion: Electrical installation with on-site power distributor (go.All / go.Top / go.Fit / go.Sim / go.Open Pro)
4b Summation current transformer for MRCD-B attached to Siemens circuit breaker 5SV8702-2KP
11 MRCD Type B 24 V connected to circuit breaker, DC, Siemens 5SV8111-4KK Room Group 1 300 mA, Room Group 2 30 mA
GR Gantry
Energy cables that do not belong to the system must be separated prior to installing the unit cables (distance
>100 cm), or they must also be metallically shielded. For USA: PE is equivalent to Protective-GND and PA is
equivalent to Transient-GND.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 83 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Door switch • floating ground switching Ratings of the switch contact according to
contact the power ratings of the relay.
(on-site)
• NO contact (normally open)
Power ratings Switch contact: The supply voltage for the radiation indi‐
cators from the internal 24 VDC power
• 230 VAC/2 A or supply at contact X20_2 (“User 24V”) can
• 24 VDC/2 A be used.
3.6.1 Function
A general overview of the air cooling function is shown in the following self-explanatory schematic:
SOMATOM go.Now
Fig. 64: Location of air intake and air exhaust in the gantry (back view)
1 Air intake
2 Air exhaust
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 85 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
3 Installation preparation
Fig. 65: Location of air intake and air exhaust in the gantry (back view)
1 Air intake
2 Air exhaust
There are no other special room requirements regarding area sizes, dimensions, etc. because the cooling
system is integrated in the gantry.
Item Description
Item Description
Humidity 20-75%
(air intake)
a) This means from “checkup” to “checkup” when switching the CT system ON/OFF
Siemens EPS (Enhanced Productivity Services) and RUH (Remote Update Handling) are part of the Siemens
Med Strategy and require a mandatory broadband VPN connection.
All planning-related information for SRS must be taken from the “SRS Planning Guide”, print number
TDIT-000.891.01., established for this purpose.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 87 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
4 System connections
4 System connections
4.1 General information
System wiring Lengths available for General notes for all cables:
all cables:
• Order the shortest possible cable kit length according to
• 15 m the on-site room situation.
• 30 m • Do not roll up and bundle excess lengths!
• Let the excess cable meander, do not roll it up!
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 89 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
4 System connections
Operating Console GR
3) 4)
1) 6) Gantry
2)
USB MON_1 MON_2 5)
COD_1 GC
PHS
W61
W90
8)
W50
W46
9)
W50
W48
10)
W60
W51
W60
7)
COD_2
L1/L2/L3/N/PE
11)
EPO
12) 17)
MON_1
x-ray "ready"
13)
x-ray "on"
14) 18)
MON_2
door switch
15)
16) + 24 VDC
W46 Power for moni‐ 230 VAC MON_1 GR 12 m/27 m Line voltage cable
tor 1
W46Y Power for monitor 230 VAC MON_1 GR 12 m/27 m Line voltage cable; Y-cable;
1 and monitor 2 and replace W46 when the 2nd
monitor is installed
MON_2
W51 Keyboard/mouse 5 VAC USB GR 12 m/27 m USB splitter; part of the mon‐
control itor
W60 Control device 24 VDC COD_1 GR 12 m/27 m Control cable for control
cable device
W60 Control device 24 VDC COD_2 GR 12 m/27 m Control cable for control
cable device 2; only available if
using a 2nd control device
Tab. 34: Legend for the cable IDs used in the circuit diagram: Line voltage and protective conductor
a) The cables are delivered with 15m/30m, however, Max.3 m is required for internal routing in gantry.
of each of the standard cables as a help to size the on-site cable ducts/cable conduits.
W46 9 30
W48 5 11
W50 7 40
W51 5 16
W60 7 12
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 91 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
5 Technical Data
5 Technical Data
5.1 Dimensions, weights, noise levels, and heat dissipations
The dimensions and weights given in the following table are without packaging.
For transport dimensions and weights, refer to ( Page 102 Transporting CT system components).
Item Value
5.2.2 Illumination
No sunshine directly on gantry, the insulation has to be applied on the window(s), e.g. curtain.
If an RCD has been installed, it is not necessary to measure and maintain the loop impedance.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 93 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
5 Technical Data
System Type Line voltage fuses Nominal line Loop impe‐ Measurement
(on-site) voltage dance a) point from/to
a) These are a maximum of values, including the impedance of the line voltage inlet from the on-site power distributor to the
power input of the CT system from L to PE.
5.3.2 Line voltage, line frequency, power factor and line impedance
System Type Line voltage Line frequency Power factor Maximum line
(cos-phi)a) impedance
System Type Line voltage Line frequency Power factor Maximum line
(cos-phi)a) impedance
a) Average value
30 sec. 37 kVA
50 sec. 31 kVA
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 95 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
5 Technical Data
30 sec. 75 kVA
50 sec. 63 kVA
Tab. 42: Power consumption of the overall system (go.All / go.Top / go.Sim / go.Open Pro)
5.3.5 Transformers
Designation Description
a) 100 kVA is only applicable when LCB or CPIN is ordered and installed.
If a UPS is being used for the overall system, it must have at least a 30% margin based on the power calculation
of the pre-transformer to overcome the dynamic output performance of the UPS.
For more details, refer to the chapter “Technical data” in the CT Basic PG, print number CT00–000.891.04.
Components Distance
Tab. 45: Magnetic field: Distances to the CT system components and line voltage cables
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 97 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
5 Technical Data
Designation Description
Hue designation SOMATOM go.Now SOMATOM go.Up / go.All / go.Top / RAL comparable color
go.Fit number
Signal white Primary color for gantry Primary color for gantry RAL 9003
(texture painting 4)
Silver • Gantry front left cover • Gantry front left bottom cover RAL 9006
(white aluminum) • Gantry stand left cover • Gantry stand left cover
• Haloriel cover plate • Gantry stand right front cover
• Gantry stand right bottom cover
• Gantry frame
• Haloriel cover plate
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 99 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
5 Technical Data
1. The data for transporting and storing the CT system components are applicable only if the system is
shipped free of damage in the transport packaging provided by the manufacturer.
2. All components have to be stored in the respective transport packaging provided by the manufacturer.
3. Use equivalent packaging for intermediate storage if the original packaging provided by the manufacturer
is no longer available.
Designation Range
After moving the CT system from a cold environment into a warm room, make sure that the entire CT system
is dry before switching it on.
If the CT system has been unpacked and installed in a room without climate control, it must be repacked and
sealed against humidity.
Without temperature and humidity control, the high-value components may be damaged during storage.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 101 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
6 Transport and storage conditions
• If doors, corridors, and elevators are suitable for delivery of the CT system components
Designation Description
Other CT system com‐ The dimensions of the monitors, keyboards, and the optional LCB do not present
ponents difficulties.
Item Description
Transport device A special transport device is available and orderable for transporting the gantry.
Refer to the CT Basic PG, print number CT00-000.891.04 for details regarding:
• Order procurement
• Functions
Transport dimensions The following diagrams show the actual overall transport dimensions of the gantry
with the transport device.
(with transport device)
• SOMATOM go.Now - see ( Page 104 SOMATOM go.Now)
• SOMTOM go.Up / go.All / go.Top / go.Fit - see ( Page 105 SOMATOM go.Up /
go.All / go.Top / go.Fit)
• SOMATOM go.Sim / go.Open Pro - see ( Page 107 SOMATOM go.Sim /
go.Open Pro)
NOTE: The transport device with the gantry can be lowered to a ground clearance of
7 mm.
Transport weights • Gantry with transport device (without packaging): See ( Page 92, Tab. 36)
Item Description
Reducing the gantry weight In special cases the gantry weight must be reduced by a few kilograms, e.g. to use a
freight elevator with a limited freight load. This can be done by removing certain parts
of the gantry covers as shown in the following table.
NOTE: A service engineer is required for disassembly and reassembly. Store the
removed covers carefully at a safe location to avoid damage during transport of
the gantry.
The following list shows the weight of the removable covers:
• Front covers: 35 kg
• Rear covers: 33 kg
• Side covers: 14 kg
Floor load during transport The maximum possible floor load (two-point load) per roller may be reached during
gantry transport.
NOTE: If necessary, cover the transport route with metal sheets to distribute the
load.
The gantry can be lowered with the transport device to a ground clearance of 7 mm.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 103 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
6 Transport and storage conditions
Fig. 73: Gantry transport dimensions - SOMATOM go.Up / go.All / go.Top / go.Fit
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 105 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
6 Transport and storage conditions
Transport
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 107 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
6 Transport and storage conditions
On SOMATOM go.Up / go.All / go.Top / go.Sim / go.Open Pro the gantry covers have to be removed as well.
The detailed steps are described in Installation Instructions (C2-081.812.01.xx.02) which is included in the
delivered volume.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 109 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
6 Transport and storage conditions
Fig. 80: Gantry transport dimensions (< 1m) - SOMATOM go.Up / go.All / go.Top / go.Fit
Fig. 81: Gantry transport dimensions (< 1m) - SOMATOM go.Sim / go.Open Pro
General information The patient table is fully mounted and delivered on a wooden pallet. A ramp
to move the PHS from the pallet is included in the delivery.
A transport device (transport device with rollers) is preinstalled on the table
base. It must be removed after installation. The transport route must be
smooth and level.
Transport weight
520 kg 580 kg 570 kg 592 kg
(with transport packaging)
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 111 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
6 Transport and storage conditions
Item Description
Monitor, keyboard, and mouse Due to the small dimensions and weights, no special planning-related
information is required.
(A)
1)
325
778
833
278
182
230
(C)
278
(B) 1) 1)
1763
890
804
86
182 175 603
A Top view
B Front view
C Side view (right)
1 Center of gravity
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 113 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
6 Transport and storage conditions
A Top view
B Front view
C Side view (right)
1 Center of gravity
A Top view
B Front view
C Side view
1 Center of gravity
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 115 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
6 Transport and storage conditions
(B) (A)
650
1206
580
1)
1) 240
480
A Side view
B Front view
1 Center of gravity
(C)
(A)
650 893
460
1) 300
239
1)
601
(B)
650 965
885
610
2) 2)
300
601
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 117 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
6 Transport and storage conditions
(A)
(C) 960
696
475
601
1) 1)
235
1030
(B)
696
900
610
2) 2)
601
Designation Description
Application For certain countries or customers that cannot provide the required line voltage con‐
nection between 380 VAC and 480 VAC.
The LCB provides several internal interfaces, e.g. for EPO, REPO, and ON/OFF switches.
Function The LCB adapts the line voltage input from 200 VAC (delta) to 400 VAC (star) via an
isolation transformer).
Additionally the LCB provides several external interfaces, e.g. for EPO, REPO, and
ON/OFF switches, a 100 VAC single-phase power output.
Delivery data The LCB is delivered as a stand-alone cabinet without any accessories. All cables, exter‐
nal components (e.g., EPO, REPO, etc.) and mounting materials must be provided on-
site.
Designation Description
Mounting The LCB must be mounted in accordance with country-specific guidelines in countries prone to
earthquakes.
All electrical work Done in accordance with all local and national electrical codes in your country.
• Standing system
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 119 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
7 Line connection box LCB (option)
Floor and wall mount‐ • Floor mounting: Floor mounting is only as required in
ing accordance with national regulations
– Floor mounting holes are included in the currently in force, e.g., in countries prone to
pedestal. earthquakes.
• Wall mounting: • The project manager decides how the
mounting is performed.
– Must always be mounted to the wall (to
prevent tilting). • Installation materials (anchors, screws,
washers, etc.) must be provided on-site.
– A wall mounting hole is included in the back
wall.
• Examination room
• Operator’s room
Technical data Refer to ( Page 92 Dimensions, weights, noise levels, and heat dissipations).
Note that two LCBs have to be positioned in the room for the dual source Naeotom Alpha.
Designation Description
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 121 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
7 Line connection box LCB (option)
Designation Description
Size of line voltage terminal • On-site line voltage input: Max. 125 mm2
clamps Line voltage output to CT: Max. 95 mm2
(A)
L1 L2 L3 PE
X4 X5 X22
5)
PW_ON 6 1 1
5 1 2 3 4 2 2
4) 4 3 3
PW_OFF X1
3 4 4
3) 2 5 5 6)
Line Connection Box LCB
EPO 1 6 6
7 7
8 8
9 3 7)
2)
4
REPO 10
X20.1
1) X7.11
X5.2
DC24V-
X3 X2 K4
A1 A2
12 8
L N PE L1 L2 L3 PE 9)
8) (B)
A Mains input
B 3-phase power output to gantry
1 EPO/REPO unit
2 Remote emergency power off(REPO); NC “normal closed”(opener); to cut off power output of the UPS
3 Emergency power off (EPO); NC “normal closed” (opener); to cut off the power input of the CT system
4 Remote power off switch (reposition button), one short wire must be installed between X4.3 and X4.4 if no remote power-off switch
5 Remote power on switch (reposition button)
6 Connections on PDB to support system on/off control
7 REPO connection on PDB
8 1-phase 100VAC output for auxiliary facility
9 Relay K4 reserved for field use and it has no electrical connection in LCB.
It can be energized by LCB internal 24Vdc power supply. When the coil connected to X5.2 and X7.11. K4 will be energized when LCB power on
Fig. 89:
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 123 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
8 Cos Phi Inductor CPIN (option)
Designation Description
Function The CPIN is designed to restrict the harmonic current of the input system, improve the
power factor for the whole system, and reduce the apparent power requirement.
It is installed between the gantry and the on-site power distributor.
The CPIN is not needed when the LCB is installed.
Delivery data The CPIN is delivered as a stand-alone cabinet without any accessories. All cables and
installation materials must be provided on site.
Designation Description
Mounting In countries prone to earthquakes, the CPIN must be installed in accordance with all country-
specific guidelines.
All electrical work Done in accordance with all local and national electrical codes in your country.
• Standing system
Floor and wall mount‐ • Floor mounting: • The project manager decides how the
ing mounting is performed according to the
– Floor mounting holes are included in the installation location requirement below.
pedestal.
• Installation materials are included in the
or
delivery volume.
• Wall mounting:
– Wall mounting holes are included in the rear
cover.
Cable inlets See diagrams For details, refer to ( Page 126, Fig. 90).
Technical data Refer to ( Page 92 Dimensions, weights, noise levels, and heat dissipations).
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 125 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
8 Cos Phi Inductor CPIN (option)
A 3D view
B Top view (base plate)
C Front view (rear plate)
D Side view
1 Four holes for floor installation
2 Four holes for wall installation
1 Hole to be drilled
2 Concrete floor or wall
Designation Description
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 127 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
9 Stationary container solution
Designation Description
If the container will be transported, then the CT system needs to be disassembled as specified in the document
Disassembly of the System (C2-081.821.01.xx), then transported separately and reinstalled in the new
location.
CAUTION
[ hz_pgdoc_F02G09U02M04 ]
- Make sure that the escape doors can be opened under all circumstances.
- Keep the area behind the rear side of the gantry accessible at all times.
Pre-fuse Refer to ( Page 74, Tab. 23) A 100 A NH fuse is acceptable with 35 mm2
cable diameter in containers for go.Now,
go.Up, go.All, go.Top and go.Fit systems.
SOMATOM go. | Specific requirements for CT project planning – Restricted – Page 129 of 131
Print No. C2-081.891.01.17.02, Revision date: 09.22
10 Changes to previous version
All All DATAMIG errors cleared. Format errors after CMS migration.
siemens-healthineers.com