Professional Documents
Culture Documents
Contact with refrigerant can cause frost bite. Keep face and
hands away to help prevent injury.
Personal injury can result from hot coolant. Any contact with hot
coolant or with steam can cause severe burns. Allow cooling
system components to cool before the cooling system is
drained.
If replacement of a component is necessary or repair to a component is necessary, the refrigerant in the system must be recovered. Also, if the
system has lost any charge after a long period of time, the refrigerant in the system must be recovered. It is necessary to perform the evacuating
procedure in order to delete the system of all air and moisture. A complete charge must never be given to a system without first performing the
evacuating procedure. Before evacuating the system, refer to the following manual.
If the system has been left open for more than 1/2 hour, the system has been exposed to air or moisture and a new receiver-dryer, an in-line dryer
or a desiccant accumulator needs to be installed. Moisture will combine with metals in the refrigerant system and this will produce highly corrosive
by-products. The by-products are oxides, iron hydroxide, and aluminum hydroxide. Moisture can freeze the expansion valve and moisture can
freeze the orifice tube. If there is water in the system the water must be removed. Remove the water by pumping the system with a vacuum pump
and boiling the water. Refer to Table 1 that is shown below.
The time for the evacuation process will increase under the following conditions:
https://sis2.cat.com/#/print-preview/service/%257B%2522title%2522%253A%2522Refrigerant%2520System%2520-%2520Evacuate%2520(SENR5664-35)%2522%252C%2522formattedPublicationDate%2522%253… 1/4
19/8/22, 12:32 SIS 2.0
Temperature of Work Area (°C Vacuum That Is Required In Order To Boil Water In An Air Conditioning System (m
(°F)) bar (Hg))
38 °C (100 °F) 95 kPa (28 in Hg)
32 °C (89.6000 °F) 96.5 kPa (28.50 in Hg)
27 °C (81 °F) 97.5 kPa (28.80 in Hg)
21 °C (70 °F) 98.8 kPa (29.20 in Hg)
Table 1
Note: After the leak test is completed, the system must be evacuated for a minimum of 30 minutes. In order to correctly evacuate the system, the
vacuum gauge must be less than three inches away from the system port. If the gauge is more than three inches away from the system port, pull a
vacuum and allow the system to equalize for ten minutes. This will ensure an accurate gauge reading.
NOTICE
All refrigerant must be recovered before the evacuating
procedure is started. Never discharge the refrigerant through
the vacuum pump. Never discharge the refrigerant into the
atmosphere. Always use the Refrigerant Identifier tool in order
to ensure that contamination of the system does not occur.
Illustration 1 g00452649
https://sis2.cat.com/#/print-preview/service/%257B%2522title%2522%253A%2522Refrigerant%2520System%2520-%2520Evacuate%2520(SENR5664-35)%2522%252C%2522formattedPublicationDate%2522%253… 2/4
19/8/22, 12:32 SIS 2.0
1. After the refrigerant is recovered from the system, make sure that the low pressure valve (1) and the high pressure valve (2) are closed.
Disconnect the charging hose (3) of the manifold gauge set from the refrigerant service unit.
2. Check the oil level in the vacuum pump. Refer to the Testing and Adjusting, "Refrigerant Compressor Oil - Check" for the correct procedure.
Add oil if oil is needed. If contamination of the system is indicated, change the oil.
3. Connect the electrical plug from the vacuum pump to an approved electrical outlet.
4. Connect the charging hose (3) to the inlet fitting on the vacuum pump. Refer to Illustration 1.
5. Open low pressure valve (1) and open high pressure valve (2) on the manifold gauge set completely. Turn the valves counterclockwise.
6. In order to start the pump motor, turn the power switch to the ON position.
7. In order to open the vented exhaust valve (8), turn the valve counterclockwise.
Note: The vented exhaust valve (8) must be closed until the vacuum pump has started.
8. Operate the vacuum pump until the low pressure gauge indicates a pressure that is between 95 kPa (28 in hg) and 98 kPa (29 in hg). After
the vacuum in the system reaches a value that is between 95 kPa (28 in hg) and 98 kPa (29 in hg), close the vented exhaust valve (8).
Operate the vacuum pump for a minimum of 90 minutes after the vented exhaust valve is closed. Use a 113 L/min (4 cfm) pump. Make
allowances for pumps that are smaller than 113 L/min (4 cfm) cfm.
Note: 95 kPa (28 in hg) to 98 kPa (29 in hg) is the required specification at sea level. For every 305 m (1000 ft) above sea level, decrease the
required specification by 3 kPa (1 in hg). At high elevations, less vacuum is required.
9. If the specific vacuum cannot be reached, the system may have a leak. Refer to the Testing and Adjusting, Refrigerant Leakage - Test
section. Perform the procedures that are indicated. Repair all leaks and repeat Step 1 of the evacuating procedure.
Note: The evacuating procedure removes air and moisture from the system. Do not use the vacuum pump primarily to indicate a system leak.
10. After 95 kPa (28 in hg) to 98 kPa (29 in hg) vacuum has been reached and held for an additional 90 minutes, close valve (1) and close valve
(2) completely. Turn the power switch on the vacuum pump to the OFFposition. The maximum amount of vacuum loss in five minutes must
not be more than 7 kPa (2 in hg). Excessive vacuum loss is an indication of a possible leak in the system. Refer to the Testing and Adjusting,
Refrigerant Leakage - Test
section. Perform the procedures that are indicated. Repair all leaks and repeat Step 1 of the evacuating
procedure.
11. If the vacuum loss does not exceed 7 kPa (2 in hg) in five minutes, the system is then ready for a complete charge. Refer to the Testing and
Adjusting, Refrigerant System - Charge
section. Perform the procedures that are indicated.
Table 2
(1)
(2) New means never been charged
Rework means the machine has been charged at least once
Note: The times are based on room ambient or machine temperature, whichever is lowest. Refer to table 2 .
Note: If machine has been sitting outside ambient temperatures of 0.0° C (32° F) or lower, run engine to operating temperature prior to starting the
evacuation process. You can also run the heater on output to warm up the machine faster.
PIP-10118791
2022/08/19
15:32:14-03:00
i00816130
https://sis2.cat.com/#/print-preview/service/%257B%2522title%2522%253A%2522Refrigerant%2520System%2520-%2520Evacuate%2520(SENR5664-35)%2522%252C%2522formattedPublicationDate%2522%253… 3/4
19/8/22, 12:32 SIS 2.0
Caterpillar:
Confidential Green
https://sis2.cat.com/#/print-preview/service/%257B%2522title%2522%253A%2522Refrigerant%2520System%2520-%2520Evacuate%2520(SENR5664-35)%2522%252C%2522formattedPublicationDate%2522%253… 4/4