Professional Documents
Culture Documents
TDA - L
LONG CASED
Construction
Double flanged casing is produced in mild steel or galvanised
Steel, the impeller having manually adjustable pitch blades is
made of PPG, PAG or Aluminium.
Finish
Painting or galvanised after manufacture is normal finish
on all parts.
Operating Temperature
-20°C to +55°C
Motors
Totally enclosed Class ‘F’ motor, to a min. IP54 protection
are fitted as standard. Standard motor up to 2.2kW are usually
supplied on DOL starting, motor 3.0kW and above are star/
delta starting.
Airflow Direction
Air flow from impeller to motor is fitted as standard. Air
flow from motor to impeller can be supplied upon request.
Option
Spark resistance construction in accordance with AMCA standard
99-0401-86-type C construction can be supplied upon request.
D
N° x Ø
Ø谺B
Ø谻C
Ø谹A
315 315 355 395 355 8 10 8 D71 900 900 945 1000 630 18 12 66 D160M
355 355 395 435 355 8 10 10 D80 1000 1000 1050 1100 630 24 12 73 D160M
400 400 440 480 355 12 10 11 D90S 1120 1120 1185 1250 900 24 12 135 D225M
450 450 490 530 400 12 10 14 D90L 1250 1250 1315 1380 1000 24 12 170 D250M
500 500 540 580 500 12 10 18 D90L 1400 1400 1465 1530 1100 32 14 220 D250M
560 560 605 660 500 12 10 22 D112M 1600 1600 1663 1730 1250 32 14 275 D250M
630 630 675 730 500 12 10 24 D112M 1800 1800 1856 1930 1400 32 14 335 D280M
710 710 755 810 500 18 12 40 D112M 2000 2000 2073 2130 1400 32 14 380 D315M
800 800 845 900 560 18 12 49 D132M 2250 2250 2330 2400 1535 36 18 430 D315M
* Please consult KRUGER if motor frame size is beyond the catalogue range.
• Note: Weight without motor and impeller.
The company is always improving and developing its products, therefore the company reserves the right of making changes to the illustrated products.
Certified dimension can be provided upon request.
Hst (Pa)
1400
1200
1000
800 630
560
600
500
450
400
400
355
200 315
0 1 2 3 4 5 6 7 8
Air Flow (M3/S)
280
240
630
200
560
160
500
120
450
80 400
40 355
315
1000
800
1250
1120
600
1000
400
900
800
200 710
0 3 6 9 12 15 18 21 24 27 30
Air Flow (M3/S)
*** Shaded portion is the recommended operating range based on the duct velocity consideration (friction loss of 1 Pa/m)
QUICK SELECTION GUIDE – 50 Hz
6 POLES - 900 RPM
Hst (Pa)
240
210
180
150
900
120
800
90 710
630
60 6 POLES - 900
560 RPM
500
30 450
0 1 2 3 4 5 6 7 8 9 10
Air Flow (M3/S)
Hst (Pa)
900
800
700
600
500 2000
400 1800
1600
1400
300
1250
200 1120
1000
100
0 10 20 30 40 50 60 70 80 90
Air Flow (M3/S)
0 10 20 30 40 50 60 70
Air Flow (M3/S)
*** Shaded portion is the recommended operating range based on the duct velocity consideration (friction loss of 1 Pa/m)
QUICK SELECTION GUIDE – 60Hz
4 POLES - 1750 RPM
Hst (Pa)
1200
1000
800
600
1000
900
400 800
560 710
630
500
200
450
400
0 2 4 6 8 10 12 14 16 18
Air Flow (M3/S)
300
250
800
200
710
150
630
100 560
500
450
50
0 1 2 3 4 5 6 7 8
Air Flow (M3/S)
1000
800
1600
600 1400
1250
400 1120
1000
200 900
0 10 20 30 40 50 60
*** Shaded portion is the recommended operating range based on the duct velocity consideration (friction loss of 1 Pa/m)