CABINET FAN

CFC SERIES

Compact Flexible Low Noise


Why KRUGER ?
KRUGER has been a leading innovator and manufacturer of residen al, commercial and industrial fan applica on
solu ons across Asia since 1985. Today with a direct presence in over 18 regions throughout Asia; world class R&D and
manufacturing facili es; KRUGER are able to offer their customers unparalleled service and support at a local level. Our
customers place their trust in KRUGER.

What is a KRUGER Cabinet Fan ?


The CFC Series is a compact cabinet centrifugal fan is designed for supply, exhaust and pressuriza on in general clean air,
grease laden air and smokespill applica on. It is compact, easy to install and service, generates high sta c pressure and
low noise.

Why use a KRUGER CFC Cabinet Fan ?


Compact size ➠ Close to duct size ➠ Lower space requirement
CFC Series compact sized cabinet is comparable to an axial fan but much smaller than a centrifugal fan.
Flexible Instlla on ➠ Suitable for any moun ng orienta on ➠ Free to install anywhere along duct
Cabinet with flexible inlet/outlet direc on that can be changed in the field to suit any installa on.
Low noise ➠ Op mised sound insula on cabinet ➠ installa on near occupant
KRUGER CFC Series offer one of the lowest noise /CMH in the industry allows for very flexible installa on loca on even
above occupants.
Versa le design ➠ Suitable for many ven la on applica ons ➠ Installa on friendly
Suitable for the extract (or supply) of clean, grease laden or high temperature (up to F400) airstreams.

CFC Side Discharge CFC Inline Discharge CFC Side Discharge CFC Side Discharge

1

F

Summary of key standard CFC Series specications:


A- Nominal fan diameter sized from 315-800mm.
B- Airflow and static pressure performance range up to 30,000CMH and 1,000Pa.
C- Airstream operating temperatures

Clean air standard ventilation application -20°C to +55°C. G
Kitchen (grease laden air) application up to +205°C / 400°F.
High temperature smokespill application up to 400°C/2Hrs certified.
D- Extended operating life.
Sealed bearings suitable for L10, >75,000 opera ng hours at maximum
speed. Extended opera ng life construc on of L10, >200,000 opera ng
hours available upon request. Vibra on balanced to G2.5 in accordance
with ISO14694/AMCA 204 standards.
E- Certifications. K
Kruger Ven la on Industries Asia Co.,Ltd cer fies
I
that the CFC Series shown herein is licensed to
bear the AMCA seal. The ra ngs shown are based
on tests and procedures performed in accordance
with AMCA Publica on 211 and AMCA
Publica on 311 and comply with the
requirements of the AMCA Cer fied Ra ngs
Program.
High temperature (up to 400 °C/2Hrs) in accordance with
EN12101-3 cer fica on by TÜV SÜD a third-party globally
renowned tes ng and cer fica on organisa on.
F

Ff250 250 120


F300 300 60
Ff300 300 120
F400 400 120
F- Cabinet
With high gloss surface finished manufactured from ZERO spange galvanized
steel.
G- Kruger's 3rd generation plenum backward curved wheel
Specifically op mized for high efficiency in an inline configura on.
Wheel manufactured in steel finished in zinc rich primer and polyester
D H
powder coa ng with salt spray ra ng up to 1000 hours (ASTM B117). All
wheels are sta cally and dynamically balanced to G2.5 (ISO 21940).
H- High precision shaft
Belt drive sha manufacture from C45 steel with g6 tolerance (ISO286-2),
to minimize eccentricity of sha leading to lower vibra on and longer
bearing life.
I- Service friendly
Motor and drive outside casing and for easier belt adjustment and replacement. Q
J- Built-in inlet and outlet flange for easy duct connection.
K- High Efficiency KRUGER Motors
All CFC Series fans are supplied with a wide variety of both 1PH and 3PH AC,
PM and EC, standard and h igh temperature rated motors.
Please ask local KRUGER Distributor.
M
Options and Accessories
L- "Double skin" cabinet with acoustic and thermal N
insulation.
M- Inlet and outlet safety guard.
N- Flexible duct for normal and high temperature up to M
400˚C.
O- Vibration isolator for ceiling hung or floor mounted
installations.
P- Spark resistance construction per AMCA 99.
Q- Safety electrical switch.
R - Belt cover isolates drive sets from airstream and
protection from rotating pulleys and belts.
2
Nomenclature

CFC 450 - D - N

Fan Design N = Normal application


S = Smoke application

Drive Type
D = Direct Drive
B = Belt Drive
Nominal Fan Diameter
Fan Model

Dimension
E

G
Weight* Max. Motor**
Model A B C D E F
Direct Belt (kg) Frame Size
Drive Drive
CFC 315 475 475 585 354 715 65 515 845 63 90
CFC 355 525 525 655 388 785 65 565 895 78 90
CFC 400 585 585 735 432 868 65 625 975 90 100
CFC 450 655 655 655 470 887 65 695 1045 144 100
CFC 500 735 735 735 525 865 65 775 1155 154 112

CFC 560 825 825 825 590 955 65 865 1245 181 112
CFC 630 955 955 955 660 1085 65 1005 1440 212 132

CFC 710 1055 1055 1055 750 1185 65 1105 1540 272 132

CFC 800 1175 1175 1175 840 1305 65 1225 1660 320 132

* Weight without motor and drive system. All dimension in mm.


** Please consult KRUGER for details when motor frame size is beyond this range.

3
Example of Selection

CFC 560 (90)


Air Volume Q = 7710 m 3/h FEG 67

Pt [Pa]
η [%] 42 52 59 62 59 48 32
2000
Outlet Velocity V = 6.2 m/s kW

Dynamic Pressure Pd = 23.0 Pa 3


2.5
2.2
1000
Total Pressure Pt = 730 Pa
1.5
N [rpm]
744
Fan Speed N = 1450 rpm 1.1

500
Absorbed Power W = 2.5 kW

400

Total Efciency η = 62 %
300 1750
80
90 1600
Sound Power Level Lw(A) = 83 dB(A)

200 1450

85
1300

83

1150
Lw (A) [dB(A)]

100
.5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]
2.09
Q [m3/h]
2000 3000 5000 10000 20000 30000 50000
7520
V [m/s]
2 3 4 5 6 8 10 20 30 40
6.0
Pd [Pa]
1 5 10 50 100 500 1000
22.0
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

4
CFC 315 (90)
FEG 63

Pt [Pa]
η [%] 35 44 51 53 48 35 22
2000
kW

1.1

1000
0.75

0.55

N [rpm]
0.37

500

400

300

3200
200

90 2850

2600
85

2300
100
80
2000

1750
Lw (A) [dB(A)]

50
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 Q [m3/s]

Q [m3/h]
500 1000 2000 3000 5000 10000 20000

V [m/s]
1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

5
CFC 355 (90)
FEG 63

Pt [Pa]
η [%] 38 48 54 55 51 37 24
2000
kW

1.1
1000

0.75

0.55
N [rpm]

0.37
500

400

300

2850
200
2600
90

2300
85

2000
100
80
1750

75
Lw (A) [dB(A)] 1450

50
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 Q [m3/s]

Q [m3/h]
1000 2000 3000 5000 10000 20000

V [m/s]
1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

6
CFC 400 (90)
FEG 63

Pt [Pa]
η [%] 35 45 53 56 53 40 24
2000
kW

1.5

1000 1.1

0.75

N [rpm]
0.55

500

400

300

2400
90
200
2200

85 2000

1750

100 80

1450

Lw (A) [dB(A)]

50
.2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 Q [m3/s]

Q [m3/h]
1000 2000 3000 5000 10000 20000 30000

V [m/s]
1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
0.5 1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

7
CFC 450 (90)
FEG 63

Pt [Pa]
η [%] 39 48 55 57 53 43 30
2000 kW

2.2

1.5
1000

1.1
N [rpm]

0.75

0.55
500

400

300 2200

2000
90

200
1750
85

1450
80

100
1200

Lw (A) [dB(A)]

50
.3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]

Q [m3/h]
1000 2000 3000 5000 10000 20000 30000

V [m/s]
2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

8
CFC 500 (90)
FEG 63

Pt [Pa]
η [%] 40 49 55 58 54 44 28
2000 kW

2.2

1000
1.5

1.1
N [rpm]

0.75

500

400

300

1900

1750
200
90 1600

1450
85
1300

100
1150

Lw (A) [dB(A)]

50
.4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]

Q [m3/h]
2000 3000 5000 10000 20000 30000

V [m/s]
2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

9
CFC 560 (90)
FEG 67

Pt [Pa]
η [%] 42 52 59 62 59 48 32
2000
kW

2.2
1000

1.5
N [rpm]

1.1

500

400

300 1750
80
90 1600

200 1450

85
1300

1150
Lw (A) [dB(A)]

100
.5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]

Q [m3/h]
2000 3000 5000 10000 20000 30000 50000

V [m/s]
2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

10
CFC 630 (90)
FEG 67

Pt [Pa]
η [%] 34 47 58 63 58 42 24
2000
kW

3
1000
2.2

1.5
N [rpm]

500

400

300

200 1600

1450
90
1300

85 1150
100

80

900
Lw (A) [dB(A)]

50
.4 .5 .6 .8 1 2 3 4 5 6 8 10 20 Q [m3/s]

Q [m3/h]
2000 3000 5000 10000 20000 30000 50000

V [m/s]
1 2 3 4 5 6 8 10 20 30 40 50

Pd [Pa]
0.5 1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

11
CFC 710 (90)
FEG 67

Pt [Pa]
η [%] 44 54 61 63 57 43 29
2000
kW

1000 3

2.2

N [rpm]
1.5

500 1.1

400

300

1300
200
1150
90

1050

85 950

100 875

80

725

Lw (A) [dB(A)]

50
.6 .8 1 2 3 4 5 6 8 10 20 Q [m3/s]

Q [m3/h]
3000 5000 10000 20000 30000 50000 100000

V [m/s]
2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

12
CFC 800 (90)
FEG 67

Pt [Pa]
η [%] 42 51 60 64 58 43 27
2000 kW

5.5

1000 4

N [rpm]
2.2

500

400

300

1250

200 1150
90
1050

950
85
875

100
80
725

Lw (A) [dB(A)]

50
.8 1 2 3 4 5 6 8 10 20 30 Q [m3/s]

Q [m3/h]
3000 5000 10000 20000 30000 50000 100000

V [m/s]
2 3 4 5 6 8 10 20 30 40 50

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

13
CFC 315 (180)
FEG 60

Pt [Pa]
η [%] 33 43 47 50 46 34 21
2000 kW

1.1

1000 0.75

0.55

N [rpm]
0.37

500

400

300
75

3200

200 95
2850

2600
90

2300
85
100
2000

80
1750

Lw (A) [dB(A)]

50
.2 .3 .4 .5 .6 .8 1 2 3 4 5 Q [m3/s]

Q [m3/h]
500 1000 2000 3000 5000 10000

V [m/s]
1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
0.5 1 5 10 50 100 500 1000
- Performance shown is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the effects
of appurtenances in the airstream. Power rating kW does not include drive losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are for
inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet.

14
CFC 355 (180)
FEG 60

Pt [Pa]
η [%] 28 38 49 52 50 40 24
2000 kW

1.5
1.1

1000
0.75

0.55 N [rpm]

0.37

500

400

300
2850
90
2600
200
85 2300

80 2000

100 1750
75

1450

Lw (A) [dB(A)]

50
.1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 Q [m3/s]

Q [m3/h]
500 1000 2000 3000 5000 10000 20000

V [m/s]
.6 .8 1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
0.5 1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

15
CFC 400 (180)
FEG 60

Pt [Pa]
η [%] 25 36 48 54 51 38 23
2000
kW

1.5

1.1
1000
0.75

0.55
N [rpm]

500

400

300

2400

200 90
2200

2000

85
1750

100
80
1450

Lw (A) [dB(A)]

50
.1 .2 .3 .4 .5 .6 .8 1 2 3 4 5 6 8 Q [m3/s]

Q [m3/h]
500 1000 2000 3000 5000 10000 20000 30000

V [m/s]
.6 .8 1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
0.5 1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

16
CFC 450 (180)
FEG 60

Pt [Pa]
η [%] 38 47 52 54 51 40 25
2000
kW

2.2

1.5
1000
1.1

N [rpm]
0.75

0.55
500

400

300
2200
90

2000
200
85
1750

80
1450

100

1200

Lw (A) [dB(A)]

50
.3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]

Q [m3/h]
1000 2000 3000 5000 10000 20000 30000

V [m/s]
1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

17
CFC 500 (180)
FEG 60

Pt [Pa]
η [%] 39 48 53 55 51 42 29
2000
kW

2.2

1000 1.5

1.1
N [rpm]

0.75

500

400

300
1900

90 1750

200 1600

85 1450

1300
80

1150
100

Lw (A) [dB(A)]

50
.3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]

Q [m3/h]
1000 2000 3000 5000 10000 20000 30000

V [m/s]
1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

18
CFC 560 (180)
FEG 63

Pt [Pa]
η [%] 35 45 55 59 57 48 33
2000
kW

3
2.2

1000
1.5

1.1 N [rpm]

500

400

1750
300

1600

85
1450
200

1300
80

1150

Lw (A) [dB(A)]

100
.3 .4 .5 .6 .8 1 2 3 4 5 6 8 10 Q [m3/s]

Q [m3/h]
1000 2000 3000 5000 10000 20000 30000 50000

V [m/s]
.8 1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
0.5 1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

19
CFC 630 (180)
FEG 63

Pt [Pa]
η [%] 41 51 57 59 56 46 32
2000
kW

3
1000
2.2

N [rpm]
1.5

500

400

300 1600

1450
90
200 1300

85
1150

80
100
900

Lw (A) [dB(A)]

50
.5 .6 .8 1 2 3 4 5 6 8 10 20 Q [m3/s]

Q [m3/h]
2000 3000 5000 10000 20000 30000 50000

V [m/s]
2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

20
CFC 710 (180)
FEG 63

Pt [Pa]
η [%] 42 51 57 59 56 46 31
2000
kW

1000 3

2.2
N [rpm]
1.5

500 1.1

400

300

1300
90
200 1150

1050
85

950

875
80
100

725

Lw (A) [dB(A)]

50
.6 .8 1 2 3 4 5 6 8 10 20 Q [m3/s]

Q [m3/h]
2000 3000 5000 10000 20000 30000 50000

V [m/s]
1 2 3 4 5 6 8 10 20 30 40

Pd [Pa]
0.5 1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

21
CFC 800 (180)
FEG 63

Pt [Pa]
η [%] 44 52 58 60 56 46 32
2000 kW

5.5

4
1000

3
N [rpm]
2.2

500

400

300 1250

1150
90
1050
200
950
85
875

80
100 725

Lw (A) [dB(A)]

50
.8 1 2 3 4 5 6 8 10 20 30 Q [m3/s]

Q [m3/h]
3000 5000 10000 20000 30000 50000 100000

V [m/s]
2 3 4 5 6 8 10 20 30 40

Pd [Pa]
1 5 10 50 100 500 1000
- Performance certified is for Installation type D - Ducted inlet, Ducted outlet. Performance ratings do not include the
effects of appurtenances (belt cover). Power rating kW does not include transmission losses.
- The A-weighted sound ratings shown have been calculated per AMCA International Standard 301. Values shown are
for inlet Lwi (A) sound power levels for installation type D - Ducted inlet, Ducted outlet. Ratings include the effects of
duct end correction

22
CFC 560 (90)
Fan Energy Indd ex 1.4

1.2
Example of FEI Selection 1.09
1.0

Air Volume Q = 2.14 m3/s 0.8

FEI
Fan Speed N = 1450 rpm 0.6
FEI = 1.09 1450 rpm
0.4

0.2

0.0
0.0 0.5 1.0 1.5 2.0 2.14 2.5 3.0 3.5 4.0 4.5
Flowrate (cms)
Direct Drive models

CFC 315 (90) CFC 355 (90)


1.8 1.8

1.6 1.6

1.4 1.4

1.2 1.2
1450 rpm
1.0 1750 rpm 1.0
FEI

FEI

0.8 0.8
1750
0.6 0.6

0.4 2850 0.4


2850
0.2 0.2

0.0 0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
Flowrate (cms) Flowrate (cms)

CFC400 (90) CFC 450 (90)


1.6 1.4

1.4 1.2

1.2
1.0
1.0
0.8
FEI

FEI

0.8 1450 rpm


1450 rpm
0.6
0.6 1750 1750
0.4
0.4

0.2 0.2

0.0 0.0
0.0 0.4 0.8 1.2 1.6 0.0 0.4 0.8 1.2 1.6 2.0 2.4
Flowrate (cms) Flowrate (cms)

CFC 500 (90) CFC 560 (90)


1.4 1.4

1.2 1.2

1.0 1.0

0.8 1150 rpm 0.8


FEI

FEI

1150 rpm
0.6 0.6
1450
1450
0.4 1750 0.4
1750

0.2 0.2

0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
Flowrate (cms) Flowrate (cms)

Performance certified is for installation type D - Ducted inlet, Ducted outlet. Power rating (kW) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). FEIT values are calculated in accordance with ANSI/AMCA Standard 208 and are based on default motor efficiencies
(Direct Driven type). FEIT values for fans with specific motors will vary slightly from those shown. Fan speed shown in RPM.

23
CFC 630 (90) CFC 710 (90)
1.4 1.6

1.2 1.4

1.2
1.0
1.0
0.8 950 rpm 725 rpm
FEI

FEI
0.8
0.6 1150 875
0.6 950
0.4 1450
0.4 1150

0.2 0.2

0.0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0
Flowrate (cms) Flowrate (cms)

CFC 800 (90) CFC 315 (180)


1.4 1.6

1.2 1.4

1.2
1.0
1.0
0.8 725 rpm
FEI

FEI
0.8 1750 rpm
0.6 875
950 0.6
0.4 1150 0.4
2850
0.2 0.2

0.0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2
Flowrate (cms) Flowrate (cms)

CFC 355 (180) CFC 400 (180)


1.8 1.4

1.6
1.2
1.4
1.0
1.2

1.0 0.8
FEI

FEI

1450 rpm 1450 rpm


0.8 0.6
0.6 1750 1750
0.4
0.4
2850 0.2
0.2

0.0 0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 0.0 0.5 1.0 1.5
Flowrate (cms) Flowrate (cms)

CFC 450 (180) CFC 500 (180)


1.4 1.4

1.2 1.2

1.0 1.0

0.8 0.8
FEI

FEI

1150 rpm
0.6 1450 rpm 0.6
1450
0.4 1750 0.4
1750

0.2 0.2

0.0 0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 0.0 0.5 1.0 1.5 2.0 2.5 3.0
Flowrate (cms) Flowrate (cms)

Performance certified is for installation type D - Ducted inlet, Ducted outlet. Power rating (kW) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). FEIT values are calculated in accordance with ANSI/AMCA Standard 208 and are based on default motor efficiencies
(Direct Driven type). FEIT values for fans with specific motors will vary slightly from those shown. Fan speed shown in RPM.

24
CFC 560 (180) CFC 630 (180)
1.4 1.4

1.2 1.2

1.0 1.0

0.8 0.8 950 rpm


FEI

FEI
1150 rpm
0.6 0.6
1150
0.4 1450 0.4 1450
1750
0.2 0.2

0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Flowrate (cms) Flowrate (cms)

CFC 710 (180) CFC 800 (180)


1.6 1.4

1.4 1.2
1.2
1.0
1.0
725 rpm 0.8
725 rpm
FEI

FEI
0.8
0.6
0.6 875 875
950 950
0.4
0.4 1150 1150

0.2 0.2

0.0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Flowrate (cms) Flowrate (cms)

Performance certified is for installation type D - Ducted inlet, Ducted outlet. Power rating (kW) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). FEIT values are calculated in accordance with ANSI/AMCA Standard 208 and are based on default motor efficiencies
(Direct Driven type). FEIT values for fans with specific motors will vary slightly from those shown. Fan speed shown in RPM.

Belt Drive models

CFC 315 (90) CFC 355 (90)


1.6 1.6

1.4 1.4

1.2 1.2

1.0 1.0
1450 rpm
FEI

FEI

0.8 1750 rpm 0.8


1750
0.6 2000 0.6
2300 2000
0.4 2600 0.4 2300
2850 2600
3200 2850
0.2 0.2

0.0 0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8
Flowrate (cms) Flowrate (cms)

Performance certified is for installation type D - Ducted inlet, Ducted outlet. Power rating (kW) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (belt cover). FEIT values are calculated in accordance with ANSI/AMCA Standard 208 and are based on default motor efficiencies
(Belt Driven type). FEIT values for fans with specific motors will vary slightly from those shown. Fan speed shown in RPM.

25
CFC 400 (90) CFC 450 (90)
1.4 1.4

1.2 1.2

1.0 1.0

0.8 0.8 1200 rpm


FEI

FEI
1450 rpm
0.6 0.6
1450
1750
0.4 2000 0.4 1750
2200 2400 2000 2200
0.2 0.2

0.0 0.0
0.0 0.4 0.8 1.2 1.6 2.0 2.4 0.0 0.5 1.0 1.5 2.0 2.5 3.0
Flowrate (cms) Flowrate (cms)

CFC 500 (90) CFC 560 (90)


1.4 1.4

1.2 1.2

1.0 1.0

0.8 0.8
FEI

FEI
1150 rpm
0.6 0.6 1150 rpm
1300
1450 1300
0.4 1600 0.4 1450
1750 1600
1900 1750
0.2 0.2

0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
Flowrate (cms) Flowrate (cms)

CFC 630 (90) CFC 710 (90)


1.4 1.4

1.2 1.2

1.0 1.0

725 rpm
0.8 0.8
FEI

FEI

950 rpm
0.6 0.6 875
1150 950
1300 1050
0.4 1450 0.4 1150
1600 1300

0.2 0.2

0.0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0
Flowrate (cms) Flowrate (cms)

CFC 800 (90) CFC 315 (180)


1.4 1.4

1.2 1.2

1.0 1.0

0.8 0.8
FEI

FEI

725 rpm 1750 rpm


0.6 0.6
875 2000
950 2300
0.4 1050 0.4
1150 1250 2600
2850
0.2 3200
0.2

0.0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4
Flowrate (cms) Flowrate (cms)

Performance certified is for installation type D - Ducted inlet, Ducted outlet. Power rating (kW) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (belt cover). FEIT values are calculated in accordance with ANSI/AMCA Standard 208 and are based on default motor efficiencies
(Belt Driven type). FEIT values for fans with specific motors will vary slightly from those shown. Fan speed shown in RPM.

26
CFC 355 (180) CFC 400 (180)
1.6 1.4

1.4 1.2
1.2
1.0
1.0
0.8
FEI

FEI
0.8 1450 rpm
1450 rpm
0.6
0.6 1750 1750
2000 0.4
0.4 2300 2000 2200
2600 2400
2850 0.2
0.2

0.0 0.0
0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 0.0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Flowrate (cms) Flowrate (cms)

CFC 450 (180) CFC 500 (180)


1.4 1.4

1.2 1.2

1.0 1.0

0.8 0.8
FEI

FEI
1200 rpm
1150 rpm
0.6 0.6
1450 1300
1450
0.4 1750 0.4 1600
1750
2000 1900
2200
0.2 0.2

0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5
Flowrate (cms) Flowrate (cms)

CFC 560 (180) CFC 630 (180)


1.2 1.4

1.0 1.2

1.0
0.8
0.8
FEI

FEI

0.6 1150 rpm 950 rpm


1300 0.6
1450 1150
0.4 1300
1600 0.4 1450
1750 1600
0.2 0.2

0.0 0.0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 0.0 1.0 2.0 3.0 4.0 5.0 6.0
Flowrate (cms) Flowrate (cms)

CFC 710 (180) CFC 800 (180)


1.4 1.4

1.2 1.2

1.0 1.0

0.8 725 rpm 0.8


FEI

FEI

725 rpm
0.6 875 0.6
950
1050 875
0.4 1150 0.4 950
1300 1050
1150 1250
0.2 0.2

0.0 0.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Flowrate (cms) Flowrate (cms)

Performance certified is for installation type D - Ducted inlet, Ducted outlet. Power rating (kW) does not include transmission losses. Performance ratings do not include
the effects of appurtenances (belt cover). FEIT values are calculated in accordance with ANSI/AMCA Standard 208 and are based on default motor efficiencies
(Belt Driven type). FEIT values for fans with specific motors will vary slightly from those shown. Fan speed shown in RPM.

27
KRUGER GROUP (VENTILATION)

THAILAND (Regional HQ) CHINA (GUANGZHOU)


KRUGER VENTILATION INDUSTRIES ASIA CO. LTD. GUANGZHOU KRUGER VENTILATION CO. LTD.
30/159 Moo 1, Sinsakorn Industrial Estate, No. 9 Huahui Road, Huashan, Huadu,
Chetsadawithi Road, Khok Kham Mueng, Samuthsakorn 74000, Thailand Guangzhou, P.R. China 510880
Tel: +662 1054298 Fax: +662 0248256-9 Tel: +86 20-66356635 Fax: +86 20-86786001/86786500
Website: www.krugerfan.com Email: gzkruger@krugergz.com
THAILAND CHINA (TIANJIN)
KRUGER VENTILATION IND. (THAILAND) CO. LTD. TIANJIN KRUGER VENTILATION CO. LTD.
30/105 Moo 1, Sinsakorn Industrial Estate, Jingjin Science and Technology Park
Chetsadawithi Road, Khok Kham Mueng, Samuthsakorn 74000, Thailand Wuqing District, Tianjin, China
Tel: +662 1050399 Fax: +662 1050370-2 Tel: +86 22-22143480/3481 Fax: +86 22-22143482
Email: mktg@kruger.co.th Email: krugertj@krugertj.com
INDIA CHINA (SHANGHAI)
KRUGER VENTILATION INDUSTRIES (INDIA) PVT. LTD. SHANGHAI KRUGER VENTILATION CO.,LTD.
Kruger Centre, Mumbai-Nasik Highway, No.500 Yuanguo Road, Anting,Jiading District,
Kalamgaon, Shahapur, Thane 421601, Maharashtra, India Shanghai 201814, P.R. China
Tel: +91 9960558899/9975577211 Tel: +86 21-69573266 Fax: +86 21-69573296
Email: sales@krugerindia.com Email: shkruger@krugerchina.com
INDIA (NORTH) CHINA (WUHAN)
KRUGER VENTILATION INDUSTRIES (NORTH INDIA) PVT LTD WUHAN KRUGER VENTILATION CO. LTD.
Village Rohad, Tehsil Bahadurgarh, Jhajjar, Haryana-124507 No. 805, Huian Ave, Dongxihu District, Wuhan, Hubei, P.R. China 430040
Tel. +91-9958991652/9958991660/8586966303 Tel: +86 27- 83248840/83060522/83097505
Fax +91-1276-278096 Fax: +86 27- 83261886
Email: sales.kni@krugerindia.com , service@krugerindia.com Email: whkruger@krugerwh.com
KOREA HONG KONG
NEOMATE CO. LTD. KRUGER VENTILATION (HONG KONG) LIMITED.
2-1010, Ace High Tech City B/D, 775 Gyeongin-ro, Flat C, 9/F, Yeung Yiu Chung (No.8) Industrial Building,
Yeongdeungpo-gu, Seoul, Korea. Postal Code 07299 20 Wang Hoi Road, Kowloon Bay, Kowloon, Hong Kong
Tel: +82-2-2679-2052 Fax: +82-2-2679-2174 Tel: +852 22469182 Fax: +852 22469187
Email: y7890@neomate.co.kr Email: info@kruger.com.hk
MYANMAR TAIPEI
KRUGER VENTILATION (MYANMAR) CO. LTD. KRUGER VENTILATION (TAIWAN) CO. LTD.
Room No. F21, Thiri Yadanar Whole Sale Market, (Htawunbe) No. 157, Ping-an Rd, Hengfeng Village,
Toe Chae Ward, North Okkalapa Township, Yangon. Dayuan Shiang Taoyuan County 337, Taiwan
Tel: +959 763141081/2/3 Tel: +886 3-3859119 Fax: +886 3-3859118
Email: htoon@krugermm.com Email: sales@krugertwn.com.tw
SINGAPORE MALAYSIA
KRUGER ENGINEERING PTE. LTD. KRUVENT INDUSTRIES (M) SDN. BHD.
No. 10 Buroh Street #06-06, West Connect Building, Lot 850, Jalan Subang 7, Taman Perindustrian Subang,
Singapore 627564 47500, Subang Jaya, Selangor D.E.
Tel: +65 68631191 Fax: +65 68631151 Tel: +603 80743399 Fax: +603 80743388
Email: mktg@krugerasia.com Email: mktg@kruger.com.my
AUSTRALIA PHILIPPINES
S&P KRUGER AUSTRALIA PTY. LTD. KRUGER M & E INDUSTRIES CORPORATION
2 Cunningham St, Moorebank N.S.W. 2170 B3 Welborne Industrial Park
Tel: +61 2-98227747 Bancal Carmona Cavite 4116, Philippines
Fax: +61 2-98227757 Tel: +63-2-7 6223260 * +63-46 4129652
Email: info@sandpkruger.com.au HP: +63 925 8018444
Email: mktg@krugerph.net
DUBAI
KRUGER VENTILATION INDUSTRIES, GULF BRANCH. VIETNAM
Jebel Ali Free Zone Area (JAFZA) P.O. Box No. 262949, Dubai, UAE KRUGER VENTILATION INDUSTRIES (VIETNAM) CO. LTD.
Tel: +971 4 8819188/8832017 Lot A7. 2-4, C2 Road, Thanh Thanh Cong IZ,
Fax: +971 4 8832018 Trang Bang Dist. Tay Ninh Province, Vietnam
Email: johncs@krugerasia.com Tel: +84-276 3585200/01/02 Fax: +84-276 3585199
Email: mktg@krugervn.com
INDONESIA
P.T. KRUGER VENTILATION INDONESIA.
JL. Teuku Umar No.20,
Karawaci - Tangerang 15115, Indonesia
Tel: +62 21-5512288/5513557 Fax: +62 21-5513502
Email: mktg@krugerindo.co.id

Edition 1
Printed in April 2021
Kruger Ventilation Industries Asia Co., Ltd.
30/159 Moo 1, Sinsakorn Industrial Estate
Chetsadawithi Road, Khok Kham Mueng,
Samuthsakorn 74000, Thailand
Tel: +662 1054298 Fax: +662 0248256-9
Website: www.krugerfan.com
CAT041.E0 April 2021