TECHNICAL DATA SHEET


Description Values

Technical Particulars
Manufacturers Name FAST CABLES LIMITED
Type of cable MV
Rated voltage 8.7/15 (17.5) KV
Nominal size of cable 1x240mm² AL/XLPE/PVC
General standard followed WAPDA:P:29:2010,IEC
60228,60502-2
Overall dia of the cable (mm) 38 (Approximate)
Diameter of wire (conductor) mm 17.60~19.20
No. of wires 30 (Min)
Current carrying capacity at ambient temperature 30°C in Air (Amp) 510
Current carrying capacity laid direct at 15°C (Amp) 400
Current carrying capacity Single way ducts (Amp) 395
Conductor operating temperature 90° C
Continuous operation 90° C
Emergency overload 160° C
Short circuit 250° C
Short circuit current Rating Rq
Short circuit for 1 sec (KA) 22.50
Short circuit for 3 sec (KA) 13
Cross sectional area of conductor (mmsq) 240
Cable weight Kg per kilometer 1890 (Approximate)
Thickness of semiconducting over Conductor (mm) 0.70
Thickness of semiconducting over Insulation (mm) 0.70
Thickness of overall PVC sheath (mm) 2.00
Embossing As Required
Electrical Test
Conductor Resistance at 20°C ohm/Km (Max) 0.125
Voltage withstand test 30.5 KV AC for 05 Min.
Screen Resistance at 20°C ohm/Km (Max) 0.727
Resistivity of semiconducting screen over conductor 1000 ohm.m (Max)
Resistivity of semiconducting over insulation 500 ohm.m (Max)
Partial Discharge test 10 pC (Max)
Mechanical Test XLPE Insulation
Tensile strength Rq
Before ageing 12.50 N/mm² (Min)
After ageing at 135°C for 7 days ± 25 % of Unaged value
Elongation at break Rq
Before ageing 200 % (Min)
After ageing at 135°C for 7 days ± 25 % of Unaged value
Water absorption at 85°C for 14 days 1mg/cm² (Max)
Hot set test at 200°C for 15 Minutes 175 % (Max)
Permanent Elongation 15 % (Max) after cooling
Shrinkage test at 130°C for 1 hour 4 % (Max)
Mechanical / Physical Test (PVC Sheath)
Tensile strength Rq
Before ageing 12.50 N/mm² (Min)
After ageing at 100°C for 7 days ± 25 % of Unaged value
Elongation at break Rq
Before ageing 150 % (Min)
After ageing at 100°C for 7 days ± 25 % of Unaged value

This is a system generated document and does not require signature.In case of any variation please contact cr@fast-cables.com
FAST CABLES LTD
www.fast-cables.com UAN:111-000-343

TECHNICAL DATA SHEET


Description Values

Loss of Mass test at 100°C for 7 days 1.50 mg/cm² (Max)


Cold bend test at -15°C for 16 Hours No Cracks
Heat shock test at 150°C for 1 Hour No Cracks
Hot deformation test 50 % (Max)
Bending Radius 760 mm
Cable Length 1000 Mtr.