CONTRACT NO.

: N-17765

PROJECT TITLE : Unit III Water Transmission Scheme


CLIENTS : Abu Dhabi Transmission & Despatch Company (TRANSCO)

CONTRACTOR : Societie Egyptienne D’etreprises (SEDE)

DOCUMENT – COMMENT SHEET – RESPONSE SHEET

Comment Sheet Ref: N-17765-STANTEC-SEDE-CS-0101 Date of Comment: 14.03.2023

Incoming Submittal Ref: N-17765-SEDE-STC-OT-0124 Date of Receipt: 21.02.2023

Document / Material Number Rev P Document Title QTY

1
1 Wall Thickness Calculations For Miter
N17765-P-11-213-1-02-0 0
Fittings

P: PURPOSE CODES
0: For Distribution 1: Issued for Approval 2: Issued for Construction
3: Issued for Information 4: For further necessary Action

STATUS CODE:

Approved – No comments Not Approved – Re-submit

 Approved Except as Noted Additional Information required


Pr opo s edLin e-1A1 and L i ne-1A2 to existi ng pip el in esweld join ts tes ting tobe doneas per sp eci fic ation
W -P -S -S - 012 (re v .01)c lause 19.1 .1a ndt es t re port sh all besu bmitt edf or revi ew an da ppro v al.
For Information only Please return copy of signed CS for receipt confirmation

Stantec UK Ltd / Home office support

Abu Dhabi Transmission and Despatch Company


(TRANSCO)

Page 1 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET

Comment Sheet Ref: N-1 77 65 - STANTE C- S E DE - CS -0 10 1 Date of Comment: 14.03.2023

Incoming Submittal Ref: N-1 77 65 - SE DE -S TC- OT- 01 24 Date of Receipt: 21.02.2023

Sr. No. Reviewed Stantec / TRANSCO Contractor Response Stantec /


by TRANSCO
Stantec Comments applicable to all mite bend wall thickness calculation (Part A)
A
Stantec As per W-P-SS-002, Section 2, "All materials and workmanship
1. shall comply with the latest editions of applicable standards and
codes."
Modified
For e.g., ASME 31.3, latest edition is 2022, whereas referred
standards are of edition 2012 and 2020.

ASME B36.10M (2018) is superseded with ASME B36.10 2022.


Stantec For DN1200, PN25, wall thickness of 22.5 deg elbow is Modified to 15.88
2. selected as 15.09. Please clarify the reference document from
where this thickness is selected.

As per ASME36.10, standard available wall thickness for


DN1200 pipe next to 14.27 mm is 15.88mm.

Stantec It is noted that, in this calculation, fitting material grade is stated as - We confirm that the fitting material grade is
3. ASTM A516 Gr.70. Please reconfirm the material grade. ASTM A516 Gr.70 as stated.
- Yield stress mentioned value had a typo error
Material Submittal of Carbon Steel Pipes & Fittings (N17765-M-07- and modified to the correct value of 262 Mpa,
109-4-001) indicates material grade as API 5L Gr. B. however it will not affect the calculations as the

Page 2 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET

Comment Sheet Ref: N- 17 76 5 -S TANTE C- SE DE -CS - 01 01 Date of Comment: 14.03.2023

Incoming Submittal Ref: N- 17 76 5 -S E DE - STC- O T-0 12 4 Date of Receipt: 21.02.2023

allowable stress is specified correctly.


Also match the mechanical properties used in this calculation
against the material grade as per ASME B31.3.

For e.g. For ASTM A516, Gr 70; min. yield strength is 262 MPa,
whereas value stated in this calculation is 245 MPa.
Stantec Add snip shot for table/reference with highlighting the values for Added
4. quality factor (E) and weld joint strength reduction factor (W) with
respect to proposed material grade.
Stantec Please check value stated for minimum yield strength (Y) with Added
5. respect to proposed material grade.

Add snip shot for table/reference with highlighting the values for Y.

Stantec Wall thickness calculation subjected to external pressure is missing. According to ASME B31.3 para 304.2.4 and
6. 304.1.3. The detemination of wall thickness for a
Refer ASME B31.3, para 304.2.4 and 304.1.3. miter bend under external pressure can be
specified by the same methodology used for
straight pipes which was already conducted in the
pipes' wall thickness calculation submitted under
document no N-17765.A-P-11-213-1-02-1 . Given
that all fittings have an equal or larger thickness
than the adjacent pipe
Stantec Please demonstrate how wall thickness value (T) is selected. A procedure of iterations was conducted in order
7. to achieve all the following:
i.e., whether the ‘T’ value is randomly selected from ASME36.10 -Minimum wall thickness achieving the required
and cross checked with value of max. allowable pressure (Pm) with pressure rating
different combination of no. of cuts (n). or firstly minimum thickness -Minimum number of cuts
of straight pipe is calculated as per as per ASME 31.4 and then -Used wall thickness equal to or larger than the
selected next standard available thickness in ASME36.10. pipe wall thickness
Page 3 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET

Comment Sheet Ref: N- 17 76 5 -S TANTE C- SE DE -CS - 01 01 Date of Comment: 14.03.2023

Incoming Submittal Ref: N- 17 76 5 -S E DE - STC- O T-0 12 4 Date of Receipt: 21.02.2023

Stantec Demonstrate how value of mechanical allowances (c) is derived. -Corrosion allowance is taken zero according to
8. Clearly indicate each allowance value (mill, corrosion, erosion, etc.) W-P-SS-002 and AWWA M11
separately. - Mill tolerance is taken 5% according to w-p-ss-
002
Add a snapshot of the reference from where values are taken.
Stantec Check the equation for minimum crotch length. It shall be as
9. below.
Modified

Stantec Contractor shall ensure that the miter bend weights are considered To be complied
10. in the pipe stress analysis as per derived total length of miter bend,
selected thickness and material grade.
Comments applicable to all branch connection wall thickness calculation (Part B):
B

Stantec It is noted that, submitted branch connection wall thickness Since W-P-SS-002 under the fittings section
11. calculation is in accordance with ASME B31.3. has stated that " Shop fabricated miter bends
are allowed for sizes larger than DN 600 (24”)
However, as per W-P-SS-002, section 4.1, “The wall in accordance with ASME B31.3 " , the
thickness of water piping components shall be determined by designer has also used ASME B31.3 for the
the Design Engineer considering the applicable design design of branch connection so that all the
conditions, in accordance with ASME B31.4 code and OWNER fittings are following the same specification
design guideline as applicable”.

Also, as per W-P-SS-002, section 4.3, “In general, fittings shall be in


accordance with ASME B31.4 unless otherwise mentioned.”

Please clarify the reason for calculating the branch connection wall
Page 4 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET

Comment Sheet Ref: N- 17 76 5 -S TANTE C- SE DE -CS - 01 01 Date of Comment: 14.03.2023

Incoming Submittal Ref: N- 17 76 5 -S E DE - STC- O T-0 12 4 Date of Receipt: 21.02.2023

thickness in accordance with ASME B31.3.


Stantec It is noted that, in this calculation, fitting material grade is stated as - We confirm that the fitting material grade is
12. ASTM A516 Gr.70. Please reconfirm the material grade. ASTM A516 Gr.70 as stated.

Material Submittal of Carbon Steel Pipes & Fittings (N17765-M-07- - Yield stress mentioned value had a typo error
109-4-001) indicates material grade as API 5L Gr. B. and modified to the correct value of 262 Mpa,
however it will not affect the calculations as the
Also match the mechanical properties used in this calculation with allowable stress is specified correctly.
the stated material grade as per ASME B31.3.

For e.g. For ASTM A516, Gr 70; min. yield strength is 262 MPa,
whereas value stated in the calculation is 245 MPa.
Stantec 2.1 Branch connection Data: The reference for outside diameter is ASME
13. B36.10M, and the allowable stress value is
Indicate reference from where the run tee outside diameter and verified in the proposed calculation sheets
branch tee outside diameter values are derived.

i.e., whether it is refereed from pipe wall thickness calculation or


selected from standard pipe thickness from ASME B36.10 and
verified for allowable stress values.
Stantec 2.2 Material Data: Added
14.
Add snip shots of respective tables (in Appendix) from where values
are referred against the material grade.
Stantec Demonstrate from where run pipe and branch pipe nominal wall The run pipe and branch pipe wall thickness
15. thickness values are derived since these are not matching with the can be equal to or larger than the connection
values stated in the pipe wall thickness calculation submittal. pipes according to proposed stresses and

Page 5 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET

Comment Sheet Ref: N- 17 76 5 -S TANTE C- SE DE -CS - 01 01 Date of Comment: 14.03.2023

Incoming Submittal Ref: N- 17 76 5 -S E DE - STC- O T-0 12 4 Date of Receipt: 21.02.2023

wall thickness calculations


Stantec Expand the section for run pipe and branch pipe pressure design Expanded
16. thickness values calculation.
Stantec Add reference of selected value of reinforcement pad wall thickness -Reinforcement pad wall thickness is an
17. (Tr). individual output for each branch calculations,
noting that the thickness is selected based on
Check calculated value of outer diameter of reinforcement pad ASME B36.10M
(ODpad). It is not matching with 2 x d2 - 2d2 is the maximum value of R-Pad
diameter in the reinforcement area,
description was modified
Stantec Add equation for calculation of available reinforcement area in pad Equations are already presented in the
18. (Ar), in branch weld field (Aw1) and pad weld field (Aw2). calculations, and fig.328.5.4D for acceptable
details for branch attachment welds are
presented in the appendix with symbols on
the figure.
TRANSCO The wall thickness shall be verified by the piping stress analysis and - To be complied
19. KY / AAM hydraulic calculations. Contractor shall be responsible for any -Maximum surge pressure is additional 10%
required design changes, if necessary, as per the pipeline stress of the design pressure according to ASME
analysis. B31.4 overpressure criteria presented in
pipes wall thickness calculation sheets
Please also specify the maximum surge pressure that the selected -Maximum surge pressure is added in the
wall thickness can withstand. Surge pressure during the surge
fittings wall thickness sheet
analysis shall not exceed this value. Please confirm.
TRANSCO Add the load case for checking bucking pressure for scenario of -Already added in the pipe wall thickness
20. KY / AAM external loadings of dead load plus compactor loads during proposed calculations.
construction, considering that 2 layers of 300 mm above the pipe
crown would be manually compacted followed by dynamic
-Please note that all fittings have either equal
compaction with a certain roller or plate compactor weight. or larger wall thickness to the pipe of the
same diameter
Page 6 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET

Comment Sheet Ref: N- 17 76 5 -S TANTE C- SE DE -CS - 01 01 Date of Comment: 14.03.2023

Incoming Submittal Ref: N- 17 76 5 -S E DE - STC- O T-0 12 4 Date of Receipt: 21.02.2023

TRANSCO The collapsing pressure due to the external loads shall be checked -Already added in the pipe wall thickness
21. KY / AAM pursuant to equation # 4.4 & 4.4M vide AWWA M-11. proposed calculations.
-Please note that all fittings have either equal
or larger wall thickness to the pipe of the
same diameter
TRANSCO Buckling shall be checking for the allowable stress for above ground -Already added in the pipe wall thickness
22. KY / AAM pipework (for e.g., pipework inside pump hall, pipework at reservoir proposed calculations.
inlet) where external pressure (collapsing pressure) can apply.
Therefore, please the pipe collapsing pressure due to external loads
-Please note that all fittings have either equal
shall be checked for above ground pipework as per AWWA M11, or larger wall thickness to the pipe of the
Section - EXTERNAL PRESSURE—EXPOSED OR SUBMERGED same diameter
PIPE.

Also add a clause in Section 4.2 b stating "Buckling for above


ground pipe" for external load condition.
TRANSCO Contractor shall refer to ASME B31.4 # 403.2.5 “The designer is No other protective measured are needed as
23. KY / AAM cautioned that susceptibility to flattening, ovality, buckling, and pipes and fittings wall thicknesses have been
denting increases with D/t ratio, decreased wall thickness, checked with different internal and external
decreased yield strength, and combinations thereof. Pipe having a cases of loading and construction case in
D/t ratio greater than 100 may require additional protective
addition to that detailed stress analysis of the
measures during construction”.
system to be provided with multiple
combinations of loading cases.
Contractor to verify and confirm if any additional protective
measures are needed during construction.

Note: The above comments and/or approvals do not relieve the Contractor from his contractual obligations to ensure conformance to the specifications.
Any deviation(s) found after this approval are to be corrected by the Contractor to the satisfaction of the OWNER/ENGINEER.

Also, it is to be understood that these comments and/or approval shall not be interpreted in anyway as limiting the CONTRACTOR's responsibilities
Page 7 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET

Comment Sheet Ref: N- 17 76 5 -S TANTE C- SE DE -CS - 01 01 Date of Comment: 14.03.2023

Incoming Submittal Ref: N- 17 76 5 -S E DE - STC- O T-0 12 4 Date of Receipt: 21.02.2023

and obligations to provide a safe working place complying with all related regulations. The execution of subject work shall complete with all
necessary requirements to facilitate and ensure trouble free operation, maintenance, and safety of the complete installation.

STATUS CODE: Approved – Except as Noted

Signed: ______________________________ Signed: HSAJ, AAM / ASA__________


For Stantec UK Ltd / Home office support for TRANSCO

Page 8 of 8