1 Wall Thickness Calculations For Miter
N17765-P-11-213-1-02-0 0
Fittings
P: PURPOSE CODES
0: For Distribution 1: Issued for Approval 2: Issued for Construction
3: Issued for Information 4: For further necessary Action
STATUS CODE:
Pr opo s edLin e-1A1 and L i ne-1A2 to existi ng pip el in esweld join ts tes ting tobe doneas per sp eci fic ation
W -P -S -S - 012 (re v .01)c lause 19.1 .1a ndt es t re port sh all besu bmitt edf or revi ew an da ppro v al.
For Information only Please return copy of signed CS for receipt confirmation
Page 1 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET
Stantec It is noted that, in this calculation, fitting material grade is stated as - We confirm that the fitting material grade is
3. ASTM A516 Gr.70. Please reconfirm the material grade. ASTM A516 Gr.70 as stated.
- Yield stress mentioned value had a typo error
Material Submittal of Carbon Steel Pipes & Fittings (N17765-M-07- and modified to the correct value of 262 Mpa,
109-4-001) indicates material grade as API 5L Gr. B. however it will not affect the calculations as the
Page 2 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET
For e.g. For ASTM A516, Gr 70; min. yield strength is 262 MPa,
whereas value stated in this calculation is 245 MPa.
Stantec Add snip shot for table/reference with highlighting the values for Added
4. quality factor (E) and weld joint strength reduction factor (W) with
respect to proposed material grade.
Stantec Please check value stated for minimum yield strength (Y) with Added
5. respect to proposed material grade.
Add snip shot for table/reference with highlighting the values for Y.
Stantec Wall thickness calculation subjected to external pressure is missing. According to ASME B31.3 para 304.2.4 and
6. 304.1.3. The detemination of wall thickness for a
Refer ASME B31.3, para 304.2.4 and 304.1.3. miter bend under external pressure can be
specified by the same methodology used for
straight pipes which was already conducted in the
pipes' wall thickness calculation submitted under
document no N-17765.A-P-11-213-1-02-1 . Given
that all fittings have an equal or larger thickness
than the adjacent pipe
Stantec Please demonstrate how wall thickness value (T) is selected. A procedure of iterations was conducted in order
7. to achieve all the following:
i.e., whether the ‘T’ value is randomly selected from ASME36.10 -Minimum wall thickness achieving the required
and cross checked with value of max. allowable pressure (Pm) with pressure rating
different combination of no. of cuts (n). or firstly minimum thickness -Minimum number of cuts
of straight pipe is calculated as per as per ASME 31.4 and then -Used wall thickness equal to or larger than the
selected next standard available thickness in ASME36.10. pipe wall thickness
Page 3 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET
Stantec Demonstrate how value of mechanical allowances (c) is derived. -Corrosion allowance is taken zero according to
8. Clearly indicate each allowance value (mill, corrosion, erosion, etc.) W-P-SS-002 and AWWA M11
separately. - Mill tolerance is taken 5% according to w-p-ss-
002
Add a snapshot of the reference from where values are taken.
Stantec Check the equation for minimum crotch length. It shall be as
9. below.
Modified
Stantec Contractor shall ensure that the miter bend weights are considered To be complied
10. in the pipe stress analysis as per derived total length of miter bend,
selected thickness and material grade.
Comments applicable to all branch connection wall thickness calculation (Part B):
B
Stantec It is noted that, submitted branch connection wall thickness Since W-P-SS-002 under the fittings section
11. calculation is in accordance with ASME B31.3. has stated that " Shop fabricated miter bends
are allowed for sizes larger than DN 600 (24”)
However, as per W-P-SS-002, section 4.1, “The wall in accordance with ASME B31.3 " , the
thickness of water piping components shall be determined by designer has also used ASME B31.3 for the
the Design Engineer considering the applicable design design of branch connection so that all the
conditions, in accordance with ASME B31.4 code and OWNER fittings are following the same specification
design guideline as applicable”.
Please clarify the reason for calculating the branch connection wall
Page 4 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET
Material Submittal of Carbon Steel Pipes & Fittings (N17765-M-07- - Yield stress mentioned value had a typo error
109-4-001) indicates material grade as API 5L Gr. B. and modified to the correct value of 262 Mpa,
however it will not affect the calculations as the
Also match the mechanical properties used in this calculation with allowable stress is specified correctly.
the stated material grade as per ASME B31.3.
For e.g. For ASTM A516, Gr 70; min. yield strength is 262 MPa,
whereas value stated in the calculation is 245 MPa.
Stantec 2.1 Branch connection Data: The reference for outside diameter is ASME
13. B36.10M, and the allowable stress value is
Indicate reference from where the run tee outside diameter and verified in the proposed calculation sheets
branch tee outside diameter values are derived.
Page 5 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET
TRANSCO The collapsing pressure due to the external loads shall be checked -Already added in the pipe wall thickness
21. KY / AAM pursuant to equation # 4.4 & 4.4M vide AWWA M-11. proposed calculations.
-Please note that all fittings have either equal
or larger wall thickness to the pipe of the
same diameter
TRANSCO Buckling shall be checking for the allowable stress for above ground -Already added in the pipe wall thickness
22. KY / AAM pipework (for e.g., pipework inside pump hall, pipework at reservoir proposed calculations.
inlet) where external pressure (collapsing pressure) can apply.
Therefore, please the pipe collapsing pressure due to external loads
-Please note that all fittings have either equal
shall be checked for above ground pipework as per AWWA M11, or larger wall thickness to the pipe of the
Section - EXTERNAL PRESSURE—EXPOSED OR SUBMERGED same diameter
PIPE.
Note: The above comments and/or approvals do not relieve the Contractor from his contractual obligations to ensure conformance to the specifications.
Any deviation(s) found after this approval are to be corrected by the Contractor to the satisfaction of the OWNER/ENGINEER.
Also, it is to be understood that these comments and/or approval shall not be interpreted in anyway as limiting the CONTRACTOR's responsibilities
Page 7 of 8
DOCUMENT – COMMENT SHEET – RESPONSE SHEET
and obligations to provide a safe working place complying with all related regulations. The execution of subject work shall complete with all
necessary requirements to facilitate and ensure trouble free operation, maintenance, and safety of the complete installation.
Page 8 of 8