You are on page 1of 37

DOCUMENT / DRAWING

COMMENTS RESOLUTION SHEET (CRS)

Project Name: AP Project No.: Review Code:


NGHP – Green Hydrogen Element (GHE) PM210011

3rd Party/Vendor Transmittal Actual Date Received:


Ref.: N/A 22-Jun-2023 Code 2
3rd Party/Vendor Name: NUI - Nesma United Industries
Unit Code: 900 - Common Buildings

Document / Drawing Title: Document / Drawing Ref. No.: Rev. No.

<Document Title> LV Cable Sizing Calculation - (900-B903) PM210011-NUI900-EC1-00008 0

COMMENTS RESPONSE

Reviewers' REVIEWER'S COMPANY NAME DOCUMENT ORIGINATOR'S COMPANY NAME Reviewers' STATUS
Item Page /
Names Comments
No. Sht. No. Document
/Initials AP's Comments NUI Response Incorporated? Reviewer
Originator

Typical Comments:-
- It is contractor's responsibility to follow the all AP documents and standard
which are listed in document noPM210011-900-MS4-00001- Scope of Work.
Compled Yes Closed Open
- Only deviation & Clarification approved by AP during pre-order stage are
acceptable. IF any deviation considered in the document same shall be
provided to client for approval. If any deviation found during any stage of
project or at site, then it is contractor's responsibility to include the same
01 SHAH Nil without any time cost implication to AP.

1. Vendor to submit the Comment Resolution Sheet (CRS) for the AP


comments.
2. Vendor to provide the revision marking for the changes in the next revision
of this document. Compled Yes Closed Open
3. It is vendor's responsibility to match the data across all the motor
documents.
4. This document will be reviewed in details once load list, panel board
02 SHAH Nil schedule etc. applicble documents will be submitted to AP for their revie

Compled Yes Closed Open


03 SHAH Nil Add AP specification SPEC-ENG-ED003 in reference

Add document number of all reference documents (Load list, SLD, Layout, soil Compled Yes Closed Open
04 SHAH Nil report etc.

Ground fault current shall be considered as per fault current calculation for Compled Yes Closed Open
05 SHAH Nil canteen building.

Compled Yes Closed Open


06 SHAH Nil Add KW instead of HP

Compled Yes Closed Open


07 SHAH Nil Why 103 is considered. Remove the repeat items for full load current

Compled Yes Closed Open


08 SHAH Nil This factor shall be aligned with motor supplier data.

It's a typo error,rectified Yes Closed Open


09 JAIN Nil Iz is 49.84 A, clarify which is correct ?

These cables sizes are based on provided demand load and average power Noted Yes Closed Open
10 JAIN Nil factor 0.8 given in load list. Cable size will change if load rating changes

It is NESMA's responsibility to include all cables in this document according to Complied Yes Closed Open
11 Gaurang Nil the commented canteen building Load list and canteen building DB schedule.

PM210011-NUI900-EC1-00008_00_CRS_(900-B903) - EL Page 1 of 2
DOCUMENT / DRAWING
COMMENTS RESOLUTION SHEET (CRS)

Project Name: AP Project No.: Review Code:


NGHP – Green Hydrogen Element (GHE) PM210011

3rd Party/Vendor Transmittal Actual Date Received:


Ref.: N/A 22-Jun-2023 Code 2
3rd Party/Vendor Name: NUI - Nesma United Industries
Unit Code: 900 - Common Buildings

Document / Drawing Title: Document / Drawing Ref. No.: Rev. No.

<Document Title> LV Cable Sizing Calculation - (900-B903) PM210011-NUI900-EC1-00008 0

COMMENTS RESPONSE

Reviewers' REVIEWER'S COMPANY NAME DOCUMENT ORIGINATOR'S COMPANY NAME Reviewers' STATUS
Item Page /
Names Comments
No. Sht. No. Document
/Initials AP's Comments NUI Response Incorporated? Reviewer
Originator

Complied Yes Closed Open


12 JAIN Nil DB numbering shall be as per AP procedure.

Add 2 line items here for UPS PDBs with following cable sizes provided by AP: Complied Yes Closed Open
13 JAIN Nil 1Rx3Cx35 sq. mm

Complied Yes Closed Open


14 JAIN Nil RIO panel 2 nos. cables from 2nos. UPS DBs shall be considered in cable sizing.

Complied Yes Closed Open


15 JAIN Nil UPS DB shall be fed from UPS only.

Complied Yes Closed Open


16 JAIN Nil DDC UPS shall be fed from 2nos. emergency supply.

NOTE:THIS CRS CONTAINS INTERNAL AP COMMENTS DATED 10.10.2023

PM210011-NUI900-EC1-00008_00_CRS_(900-B903) - EL Page 2 of 2
Release Purpose: IFR

DOCUMENT COVERSHEET

Document Information
Project No: PM210011 Project Name: NEOM Green Hydrogen Elements
Project Doc No: PM210011-NUI900-EC1-00008 Rev: 01
Client Doc No: N/A Rev:
Contractor Doc N/A Issue Date: 19 Oct-
Rev:
No. 2023
Document Title Low Cable Sizing Calculation

VDR Code(s)
Tag No(s):(1):
Note 1 – For multiple Tag No: refer to page 2

Review Status
Sign.
Status Code:
Date:
Status Code Legend
Code 1 Reviewed by Air Products – REJECTED Resubmit for Review
Code 2 Reviewed by Air Products – COMMENTS AS NOTED Resubmit for Review
Code 4 Reviewed by Air Products – NO COMMENTS, No Further Submittal Required Unless Drawing/Document is Revised
Code 5 ACCEPTED FOR INFORMATION ONLY
Vendor is not relieved of responsibility for accuracy of dimensions, performance, design, design of details or any code requirements. Further, review by
Air Products does not relieve Vendor of responsibility or liability, or from furnishing material in conformance with the contract, purchase order, or
other agreement. Air Products’ review shall not be construed as an Approval by Air Products of such documents or an opinion by Air Products that such
documents are true and accurate

Purchase Order Information


Air Products Specifier:
PO Number:
PO Date:
Contractor Name: Nesma United Industries
Contractor Org Code: NUI
Vendor SAP ID:

All the comments provided on R0 document via Aconex are not reflected
in CRS. Update the CRS.
NEOM GREEN HYDROGEN ELEMENT

Contractor : Nesma United Industries Co. Ltd. Project Code: PM210011


Document Number: PM210011-NUI900-EC1-00008
Rev. 01 Date Submitted: 18 Oct-23

LV CABLE SIZING CALCULATION


For

NEOM Green Hydrogen Elements


At

NEOM Industrial City, KSA


Air Products Project No: PM210011

REVISION HISTORY

Rev Pages Date Description

Issued by Checked By Approved


05-31- Issued for Bency Mohan Wael Amari Air Products
00 29
2023 Review QA/QC Manager Project Manager Representative

10-19- Issued for Bency Mohan Wael Amari Air Products


01 31
2023 Review QA/QC Manager Project Manager Representative

==========================
Release Purpose: IFR

DOCUMENT COVERSHEET

Document Information
Project No: PM210011 Project Name: NEOM Green Hydrogen Elements
Project Doc No: PM210011-NUI900-EC1-00008 Rev: 01
Client Doc No: N/A Rev:
Contractor Doc N/A Issue Date: 19 Oct-
Rev:
No. 2023
Document Title Low Cable Sizing Calculation

VDR Code(s)
Tag No(s):(1):
Note 1 – For multiple Tag No: refer to page 2

Review Status
Sign.
Status Code:
Date:
Status Code Legend
Code 1 Reviewed by Air Products – REJECTED Resubmit for Review
Code 2 Reviewed by Air Products – COMMENTS AS NOTED Resubmit for Review
Code 4 Reviewed by Air Products – NO COMMENTS, No Further Submittal Required Unless Drawing/Document is Revised
Code 5 ACCEPTED FOR INFORMATION ONLY
Vendor is not relieved of responsibility for accuracy of dimensions, performance, design, design of details or any code requirements. Further, review by
Air Products does not relieve Vendor of responsibility or liability, or from furnishing material in conformance with the contract, purchase order, or
other agreement. Air Products’ review shall not be construed as an Approval by Air Products of such documents or an opinion by Air Products that such
documents are true and accurate

Purchase Order Information


Air Products Specifier:
PO Number:
PO Date:
Contractor Name: Nesma United Industries
Contractor Org Code: NUI
Vendor SAP ID:
NEOM GREEN HYDROGEN ELEMENT

Contractor : Nesma United Industries Co. Ltd. Project Code: PM210011


Document Number: PM210011-NUI900-EC1-00008
Rev. 01 Date Submitted: 18 Oct-23

LV CABLE SIZING CALCULATION


For

NEOM Green Hydrogen Elements


At

NEOM Industrial City, KSA


Air Products Project No: PM210011

REVISION HISTORY

Rev Pages Date Description

Issued by Checked By Approved


05-31- Issued for Bency Mohan Wael Amari Air Products
00 29
2023 Review QA/QC Manager Project Manager Representative

10-19- Issued for Bency Mohan Wael Amari Air Products


01 31
2023 Review QA/QC Manager Project Manager Representative

==========================
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

LV CABLE SIZING CALCULATION

Doc. No.
PM210011-NUI900-EC1-00008

For

NEOM Green Hydrogen


Elements RC Buildings
(900-B903 Canteen Building)
at

NEOM Industrial City, KSA


Issued for 100% Submittal
October 2023

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 1
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

TABLE OF CONTENTS
1. OBJECTIVE …………………………………………………………………………………………..…….….3
2. REFERENCE CODES AND STANDARDS……………………………………………….…..….…….3
3. CABLE VOLTAGE RATINGS………………………………………………………………..…..….……..3
4. DATA INPUT………………………………………………………………………………….….…….………3
5. DESIGN CONSIDERATION……………………………………………………………….……….………3
6. CRITERIA FOR CABLE SELECTION…………………………………………………..……….……….4
7. DERATING FACTORS………………………………………………………………………………………..5
8. PERMISSIBLE VOLTAGE DROP………………………………………………………………………….5
9. CALCULATIONS………………………………………………………………………………………………..6
10. SAMPLE CALCULATIONS…………………………………………………………………………………..8
11. APPENDIX…………………………………………………………………………………….………………..10

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 2
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

1.0 OBJECTIVE

The purpose of this document is to determine the required size of low voltage power cables for
NEOM green hydrogen project.

2.0 REFERENCE CODES AND STANDARDS

 IEC 60228
 IEC 60287:1982
 IEC60364-4-43
 IEC 60840
 IEC 60364
 Riyadh Cable Catalogue
 HCIS
 Saudi Building Code SBC 401
 AP Specifica on SPEC-ENG-ED003

3.0 CABLE VOLTAGE RATINGS

For 400V System: All LV cable shall be required 1.1kV (E) Grade.

4.0 DATA INPUT

 PM210011-NUI900-ES6- 00001 - Electrical Single Line Diagram (900-B903)


 PM210011-NUI900-EC1- 00009 - Cable Schedule
 PM210011-NUI900-EL1- 00001 - Electrical Load List
 PM210011-NUI900-EL5 - 00002 - Ground Floor Power Layout
 PM210011-NUI900-EL5 - 00003 - Roof Floor Power Layout
 PM210011-NUI900-EC9 - 00001 - Ground Floor Cable Tray and Conduit Layout
 PM210011-NUI900-EC9 - 00002 - Roof Floor Cable Tray and Conduit Layout
 Riyadh Cables Catalogues for LV Cables

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 3
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

5.0 DESIGN CONSIDERATION

5.1 All cables are XLPE insulated PVC outer sheathed, copper conductor, mul core cables,
armored for direct buried and un-armoured for above ground installa on. NO separate PE
cable will be considered for armoured 3 core cable for Motors/ Welding outlets/
distribu on board. Armour will be used as PE and armour earthing shall be done at both
the ends and for Power cables armouring shall be suitable for ground fault current. Ground
fault current shall be considered as per fault current calcula on for canteen building. The
cable armouring shall be SWA*/AWA** and the outer sheath shall be Flame retardant and
termite resistant PVC suitable for 90°C maximum rated conductor temperature. All cables
shall be UV light resistant and shall be provided.

*Three core cables shall be with Steel Wire Armoured


**Single core cables shall be with Aluminium Wire Armoured

5.2 Motor power factor and efficiency shall be considered as per IEC and same shall be
updated upon receipt of actual data. The motors shall be IE3 type.

5.3 The following installa on condi ons are considered to arrive at overall de-ra ng
factor for cable ampacity;
 Air temperature is considered as per temperature +45 deg.C for electrical cable
laying indoor and outdoor loca ons.

5.4 Cables route length is taken from :


 Cable Schedule PM210011-NUI900- EC1 - 00009
 Electrical Load List PM210011- NUI900- EL1 - 00001
 Ground Floor Power Layout PM210011-NUI900 - EL5 - 00002
 Roof Floor Power Layout PM210011-NUI900 - EL5 - 00003
 Ground Floor Cable Tray and Conduit Layout PM210011-NUI900 - EC9 - 00001
 Roof Floor Cable Tray and Conduit PM210011-NUI900 - EC9 - 00002

5.5 Values of Resistance & Reactance are taken from Riyadh Cable catalogue (Please
refer Appendix-2)
5.6 Cable Ampacity is selected from Riyadh Cable catalogues (Please refer Appendix-2)

5.7 Cable Ampacity shall be based on maximum conductor temperature of 90ºC for XLPE
insula on.

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 4
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

6.0 CRITERIA FOR CABLE SELECTION

The sizing of power cable shall be based on the following considera ons:

A. Cable con nuous current carrying capacity influenced by various de-ra ng factors based on
installa on method and site condi ons.

B. When SCPD is current limi ng type, conductor cross sec on is based on let through energy of
short circuit protec on device (SCPD). Cable k2S2 value should be more than SCPD let through
(I2t) value. Let through values of ABB make, SACE Tmax XT MCCBs are considered for cable sizing
purpose. When SCPD is not current limi ng type, it is checked that short circuit current
withstand by cable for ≤ 1 second is greater than the fault current.

C. Voltage drop during running condi on

D. Voltage drop during motor star ng condi on

Note:
Maximum of the conductor cross-sec on calculated by A to D above is to be selected.
Criteria ‘D’ are applicable only for DOL started motor feeders.

7.0 DERATING FACTORS**

Mul -core cable installa on in cable tray:

Cable laid in cable


S. No Description Remarks
trays- indoor
Considered average
1 Ambient ground temperature(45°C) correction factor ( Ft ) 1.15 factor of 40 & 50
degree celsious
4 No of multy core
cable, single layer on a
2 Cable grouping correction factor ( Fg ) 0.77
horizontal or vertival
cable tray.
3 Total De-rating Factor 0.89

**Note: Dera ng for single core and underground cable is not listed as same is not applicable.

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 5
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

8.0 PERMISSIBLE VOLTAGE DROP

The maximum voltage drops in various sec ons of the electrical system shall be within the limits stated
in the below table:

Maximum Allowable Maximum Allowable


S. No. System Element
Running Voltage Drop Starting Voltage Drop

a) Cables between transformer secondary and switchboards 0.5%

b) Cables between Emergency DG and Emergency switchboards 0.5%

c) LV switchboard to LV motors 5% 15%


Cables between LV switchboard and LV sub distribution (Auxiliary
d) switchboard, MLDB, UPS, battery Charger) located within the same 0.5%
building

Cables between LV switchboard and LV sub distribution (Auxiliary


e) 2%
switchboard,MLDB, UPS, battery Charger) located in other building.

f) Cables between LV switchboard LV heaters/welding sockets 5%

g) Circuit between lighting panels and last lighting point 2.5%*

h) Circuit betweenpower panels and last socket 2.5%*

i) DC distribution board to DC supply current (electrical controls) 5%

j) AC Distribution board to UPS outgoing circuit 5%

Notes:*

1. In case of difficulty in achieving specified voltage drops in cables up to ligh ng panel, 5% drop from
Auxiliary Switchboard / MLDB up to last ligh ng points may be permi ed.

2. In case of LV VFD feeder total voltage drop from LV switchgear to LV motor shall be limited to 5%.
Distribu on between LV switchgear to VFD and from VFD to Motor shall be decided accordingly.

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 6
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

9.0 CALCULATIONS Keep the similarity.

9.1 Full Load Current

 Full Load Current (IL) for Motor


KW*1000 ÷ (√3 * V * CosΦ * η)

 Full load current (I) for non-motor loads Explain the difference in
KW*103 / (√3*V* CosΦ) these 2 items.

 Full load current (I) for non-motor loads


KVA*103 / (√3*V)

 Full load current (I) for motor loads


KW*103 / (√3*V* CosΦ * η)

HP = Horse Power Not required


KW = Kilo wa s
V = Voltage
CosΦ = Power Factor
η = Efficiency
kVA = Kilo Volt Ampere

9.2 Percentage AC Voltage Drop for 3-Phase Motors:

 During Normal Opera ng Condi on


%Vd = [√3 * L * Ib* (R CosΦ + X SinΦ) ÷ (V * N * 1000)] * 100

 For Motor Star ng Condi on


%Vdst = [√3 * L * Ist * (R CosΦ + X SinΦ) ÷ (V * N * 1000)] * 100

L = Cable Length (Meters)


V = Line Voltage (3-phase)
R = Cable Resistance (Ohm/Km)
X = Cable Reactance (Ohm/Km)
CosΦ = Power Factor
SinΦ = √ (1 – Cos2Φ)
Ib = Full Load Current

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 7
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

N = No. of parallel cable Runs

Ist = Star ng Current in Amps = 6*x Full Load Current (Ib) + 20% star ng current
tolerance.
(Note: *Factor shall be aligned as per motor supplier’s data)
%Vd = Percentage Voltage Drop during Normal Opera on
%Vdst = Percentage Voltage Drop during Motor Star ng

(Note: Factor √3 shall be replaced by Factor 2.0 for 1-phase voltage drops.)

9.3 Short Circuit Withstand:

The minimum cross sec on of any cable shall be such as to ensure that no damage occurs to the
cable in case of a short circuit un l fault is cleared by protec ve device such as breaker or fuse.
 For short circuit clearance dura ons of 0.1 sec. ≤ t < 5 sec., the following formula is used
for calcula ng the minimum cable sizes:
K²S² ≥ I²t

i.e. 𝑆 ≥

 For short circuit clearance dura ons (< 0.1 sec.) of current limi ng devices, k²S² must be
greater than the value of the transmi ed energy (I²t) specified by manufacturer of the
protec ve device.

S Cross Sec onal area in sq. mm


I Effec ve short circuit current in amperes
t Dura on of short circuit in seconds
k Cable characteris c constant, based on resis vity, temperature coefficient,
hea ng capacity of conductor material and type of insula on, k = 143 (as per
Table 43A of IEC 60364-4-43) for copper conductors with XLPE insula on, with
90°C ini al conductor temperature and 250°C final conductor temperature.

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 8
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

10.0 SAMPLE CALCULATIONS

(a) System Data

Load Name = 900G03-P730D


Feed from = 900G03-P730A
Length of Feeder = 05 meter
Demand Load = 20.77 kVA
Voltage = 400 V
Frequency = 60 Hz
The opera ng characteris cs of a device protec ng a cable against overload shall sa sfy
the two following condi ons as per SBC_401, clause 43-3.1:

Condi on 1 Ib ≤ In ≤ Iz and
Condi on 2 I2 ≤ 1.45 x Iz

Where
Ib = Full load current for the circuit
Iz = Con nuous current-carrying capacity of the cable (adjusted ampacity)
In = Rated current of the protec ve device

I2 is the current ensuring the effec ve opera on in the conven onal me of protec ve device
(conven onal tripping current I2 = 1.45 In is assumed, The current I2 ensuring the effec ve
opera on of the protec ve device shall be provided by the manufacturer.)

Note- For the adjustable protec ve devices, the rated current In is the current se ng
selected.

(b) (Step-1) Circuit breaker sizing

Full load current (Ib) = KVA*103 / (√3*V)


= 20.77 * 103 / (√3*400)
= 29.99 Amp
Nearest Nominal (In) = 40 A
Breaker Size (In) = 40 AT (100AF)

Since the selected breaker size is more than the Full load current, so the selec on of breaker is
complying the condi on 1.

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 9
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

(c) (Step-2) Continuous current-carrying capacity of the cable

Installa on method Indoor Cable tray


Overall de-ra ng factor 0.89 (Refer to dera ng factor
calcula on)
Demand Load 20.77 kVA
Voltage 400 V

Full load current (Ib) 29.99 Amp

Op on 1
Ampacity of 4C x 10 Cu Cable 56 Amp (Refer the Appendix-2)
Con nuous Ampacity a er de-ra ng, Iz = 56x 0.89 = 49.84 Amp.
Op on 2
Ampacity of 4C x 6 Cu Cable 41 Amp (Refer the Appendix-2)
Con nuous Ampacity a er de-ra ng, Iz = 41x 0.89 = 36.49 Amp.
Op on 3
Ampacity of 4C x 4 Cu Cable 32 Amp (Refer the Appendix-2)
Con nuous Ampacity a er de-ra ng, Iz = 32x 0.89 = 28.48 Amp.

Considering the future load/addi onal requirements we are proposing 10mm2 cables
which can carry a full load current up to 49.84 Amps a er de-ra ng.

Checking for Compliance the condi on 1 and condi on 2

Iz = 49.84 Amp (Refer the sec on 10. c)


In = 40 AT (Refer the sec on 10. b)
Since Iz ≥ In as per above data, so the selected breaker and cable size complying the
condi on 1.

Now, The conven onal tripping current I2 = 1.45 In =1.45 x 40 = 58 Amp.


Condi on 2 is I2 ≤ 1.45 x Iz
58 amp ≤ 1.45 x 49.84 amp
58 ≤ 72.27

So, the compliance of condi on 2 is also verified.

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 10
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

(d) (Step-3) Checking the cable for the Voltage drop

%Voltage Drop = [√3 * L * Ib * (R CosΦ + X SinΦ) ÷ (V * N * 1000)] * 100

L = 05 meter
V = 400 V
R = 2.33 Ohms/Kilometer (Refer the Appendix no-2)
X = 0.094 Ohms/Kilometer (Refer the Appendix no-2)
CosΦ = 0.85 (Assumed)
SinΦ = √ (1 – Cos2Φ) = 0.526
Ib = 29.99 Amp
N = No. of parallel cable Runs

%Voltage Drop = [√3 * L * Ib * (R CosΦ + X SinΦ) ÷ (V * N * 1000)] * 100

= [√3 * 5 * 29.99 * (2.33 x 0.85 + 0.094 x 0.526) ÷ (400 * 1 * 1000)] * 100


= 0.13

Hence for the selected cable (10 mm2 Cu Cable), the voltage drop is within limit.

e) (Step-4) Checking the minimum Cable Cross Section that Withstands the Short
Circuit Current

Refer the Appendix-3. (Data sheet of ABB has been a ached)

11.0 APPENDIX

Appendix-1: LV Cable Sizing Calcula ons

Appendix-2: Riyadh Cable Catalog for LV cables

Appendix-3: Let through energy curve for MCCB

Note :
Soil thermal resis vity data shall be considered 1.5K-m/W for underground rou ng cable.

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

Page | 11
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

APPENDIX - 1

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.
Typical: Last 2 digits shall be always "-LP-01", if there are more
than one cable (i.e. more than 1 run) to the same equipment 900-B903-CANTEEN BUILDING

then it shall be like LP-01/1, LP-01/2, LP-01/3,...


Typical: Last number shall be If there is more than one source of power to the same equipment
2 digits like "-LP-01" like for switchgear panel from normal and emergency
transformers then it shall be LP-01 & LP-02.

This is basically for cable schedule to represent separate tag for


each run of cable to the same equipment. If there is 3 runs, then
NEOM Green Hydrogen Company - Canteen Building Cable Sizing Calculation
3 line items to be created in cable schedule, (Note that: not Correction Factor

applicable for cable sizing document).


Equipment
Full load Current, Ib
(Amp) Breaker
IEC60364‐4‐
convention
Ambient
grouond
Depth of
Laying
Soil
thermal
Cable
Adj. Amp. Iz
(A) = Condition ‐2
Condition ‐3 Cable Cable
%Vd %Vdst
Percentage Percentage
Ib =KVA*10³ / (√3*V) for size al tripping No. of No. of Size Conductor Correction Resistivity Total Derating (IEC60364‐4‐ Cable Resistance Cable Reactance Voltage Voltage
CIRCUIT No. Load Rating Voltage (Volt) Ist = 9.24 Ib 43, Phase Insulation Type of Cable Type of Installation Temparat grouping 1.45 x Iz (IEC60364‐4‐ 43) Impedance Length
non-Motor Load & Ib = In current, Cores Runs mm² Ampacity (A) Factor Correction Derating factor * 43) (R) (X) Drop during Drop during
(In ≥ Ib) ure correction I2 ≤ 1.45 Iz (Z) (meters)
KW*10³ / (√3*V*COSØ*ƞ) (Amp) I2 = 1.45*In (1.0 factor (1.0 factor Conductor Iz ≥ In Normal Motor
Correction factor (Fg)
for Motor Load °C.m/W) °C.m/W) Ampacity Operation Starting
Factor (Ft)
(Fd) (Fth)
From To

900-900G03-P730A-LP-1 900-P413A (900-B902) 900G03-P730A 178.11 KVA 400 257.09 400 Verified 580.00 3φ 3.5C 2 XLPE 150/70

900-900G03-P730B-LP-2 900-P413A (900-B902) 900G03-P730B 266.50 KVA 400 384.67 500 Verified 725.00 3φ 3.5C 2 XLPE 300/150

900-900G03-EP730A-LP-3 900-P413E (900-B902) 900G03-EP730A 246.16 KVA 400 355.31 500 Verified 725.00 3φ 3.5C 2 XLPE 240/120

900-900G03-EP730A-LP-87
900-P521
900G03-PDB1 UP730A KVA 1φ 3C 1 XLPE 35

UP730B
900-900G03-EP730A-LP-88 900G03-PDB2 KVA 1φ 3C 1 XLPE 35

900-900G03-P730C-LP-4 900G03-P730A 900G903-P730C 49.84 KVA 400 71.94 100 Verified 145.00 3φ 4C 1 XLPE 50 Unarmoured 139 Cable Tray 1.15 0.77 0.89 123.08 178.47 Verified Verified 0.495 0.087 0.503 4 0.06

900-900G03-P730D-LP-5 900G03-P730A 900G03-P730D 20.77 KVA 400 29.99 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 5 0.13

900-900G03-P730E-LP-6 900G03-P730A 900G03-P730E 33.16 KVA 400 47.86 80 Verified 116.00 3φ 4C 1 XLPE 25 Unarmoured 99 Cable Tray 1.15 0.77 0.89 87.66 127.11 Verified Verified 0.928 0.090 0.932 5 0.09

900-900G03-K72-LP-7 900G03-P730A 900-B903-K72 (BAIN MARIE) 11.75 KVA 400 16.96 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 Cable Tray 1.15 0.77 0.89 36.31 52.64 Verified Verified 3.930 0.099 3.931 41

900-900G03-K72-LP-8 900G03-P730A 900-B903-K72 (BAIN MARIE) 11.75 KVA 400 16.96 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 Cable Tray 1.15 0.77 0.89 36.31 52.64 Verified Verified 3.930 0.099 3.931 41 1.02

900-900G03-K69-LP-9 900G03-P730A 900-B903-K69 (SALAD CUPBOARD) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.105 5.881 42 0.58

900-900G03-K69-LP-10 900G03-P730A 900-B903-K69 (SALAD CUPBOARD) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.105 5.881 40 0.55

900-900G03-K61-LP-11 900G03-P730A 900-B903-K61 (DISPLAY REFRIGIRATOR) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.105 5.881 40 0.55

900-900G03-K61-LP-12 900G03-P730A 900-B903-K61 (DISPLAY REFRIGIRATOR) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.105 5.881 43 0.59

900-900G03-K55-LP-13 900G03-P730A 900-B903-K55 (CASHIER STAND) 1.25 KVA 230 3.14 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.105 5.881 44 0.61

900-900G03-K78-LP-14 900G03-P730A 900-B903-K78 (SS HEAVY DUTY 4 HOT LATE) 13.00 KVA 400 18.76 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 Cable Tray 1.15 0.77 0.89 36.31 52.64 Verified Verified 3.930 0.099 3.931 37 1.02

900-900G03-K79-LP-15 900G03-P730A 900-B903-K79 (BAIN MARIE) 1.88 KVA 230 4.71 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.105 5.881 37 0.77

900-900G03-K80-LP-16 900G03-P730A 900-B903-K80 (ELECTRIC CONVECTION OVENS) 19.75 KVA 400 28.51 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 37 0.93

900-900G03-K81-LP-17 900G03-P730A 900-B903-K81 (ANALOGIC CONTROL PANEL) 1.75 KVA 230 4.39 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.105 5.881 40 0.77

900-900G03-K82-LP-18 900G03-P730A 900-B903-K82 (OVEN HOOD) 2.50 KVA 400 3.61 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.105 5.881 41 0.32

900-900G03-K54-LP-19 900G03-P730A 900-B903-K54 (AUTO VEG. PREP MACHINE) 1.38 KVA 400 1.98 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.105 5.881 19 0.08

900-900G03-K58-LP-20 900G03-P730A 900-B903-K58 (POTATO & CARROT PEELER) 1.38 KVA 400 1.98 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.105 5.881 18 0.08

900-900G03-K59-LP-21 900G03-P730A 900-B903-K59 (VEGETABLE DRYER) 0.46 KVA 400 0.67 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.105 5.881 20 0.03

900-900G03-K60-LP-22 900G03-P730A 900-B903-K60 (VEGETABLE WASHING MACHINE) 0.59 KVA 400 0.85 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.105 5.881 21 0.04

900-900G03-K47-LP-23 900G03-P730A 900-B903-K47 (COUNTER TOP BONE SAW) 1.00 KVA 400 1.44 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.105 5.881 6 0.02

900-900G03-K34-LP-25 900G03-P730A 900-B903-K34 (FOOD PROCESSOR CUTTER) 0.80 KVA 400 1.15 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.105 5.881 6 0.02

900-900G03-K32-LP-26 900G03-P730A 900-B903-K32 (MEAT MINCER) 2.20 KVA 400 3.18 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.105 5.881 6 0.04

900-900G03-K93-LP-27 900G03-P730B 900-B903-K93 (SS HEAVY DUTY BOILING PAN) 18.00 KVA 400 25.98 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 36 0.82

900-900G03-K93-LP-28 900G03-P730B 900-B903-K93 (SS HEAVY DUTY BOILING PAN) 18.00 KVA 400 25.98 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 36 0.82

900-900G03-K101-LP-29 900G03-P730B 900-B903-K101(SS SOLID TOP) 25.00 KVA 400 36.09 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 34 1.08

900-900G03-K94-LP-30 900G03-P730B 900-B903-K94 (SS HEAVY DUTY TILTING PAN) 15.00 KVA 400 21.65 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 35 0.67

900-900G03-K102-LP-31 900G03-P730B 900-B903-K102 (SS HEAVY DUTY HOT LATE WITH OVEN) 23.75 KVA 400 34.28 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 36 1.08

900-900G03-K107-LP-32 900G03-P730B 900-B903-K107 (PASTA COOKER) 22.50 KVA 400 32.48 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 36 1.03

900-900G03-K95-LP-33 900G03-P730B 900-B903-K95 (SS DEEP FRYER DOUBLE BOWL) 40.00 KVA 400 57.74 63 Verified 91.35 3φ 4C 1 XLPE 25 Unarmoured 99 Cable Tray 1.15 0.77 0.89 87.66 127.11 Verified Verified 0.928 0.090 0.932 36 0.75

900-900G03-K96-LP-34 900G03-P730B 900-B903-K96 (SS LAVA STONE) 25.00 KVA 400 36.09 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 38 1.21

900-900G03-K108-LP35 900G03-P730B 900-B903-K108 (SS HEATED CABINET) 3.75 KVA 400 5.41 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 33 0.39

900-900G03-K100-LP-36 900G03-P730B 900-B903-K100 (SS SHIP DUMP) 1.69 KVA 230 4.23 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 38 0.70

900-900G03-K100-LP-37 900G03-P730B 900-B903-K100 (SS SHIP DUMP) 1.69 KVA 230 4.23 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 39 0.72

900-900G03-K95-LP-38 900G03-P730B 900-B903-K95 (SS DEEP FRYER DOUBLE BOWL) 40.00 KVA 400 57.74 63 Verified 91.35 3φ 4C 1 XLPE 25 Unarmoured 99 Cable Tray 1.15 0.77 0.89 87.66 127.11 Verified Verified 0.928 0.090 0.932 39 0.82

900-900G03-K97LP-39 900G03-P730B 900-B903-K97 (SS GRIDDLE SMOOTH FREE STAND) 17.50 KVA 400 25.26 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 39 0.87

900-900G03-K108-LP-40 900G03-P730B 900-B903-K108 (SS HEATED CABINET) 3.75 KVA 400 5.41 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 33 0.39

900-900G03-K103-LP-41 900G03-P730B 900-B903-K103 (KITCHEN HOOD) 2.50 KVA 400 3.61 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 34 0.27

900-900G03-K104-LP-42 900G03-P730B 900-B903-K104 (BAIN MARIE) 11.75 KVA 400 16.96 30 Verified 43.50 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 38 0.57

900-900G03-K104-LP-43 900G03-P730B 900-B903-K104 (BAIN MARIE) 34.63 KVA 400 49.98 63 Verified 91.35 3φ 4C 1 XLPE 25 Unarmoured 99 Cable Tray 1.15 0.77 0.89 87.66 127.11 Verified Verified 0.928 0.090 0.932 24 0.43

900-900G03-K105-LP-44 900G03-P730B 900-B903-K105 (OVEN HOOD) 1.25 KVA 400 1.80 16 Verified 23.20 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 24 0.09

900-900G03-K-42-LP-44A 900G03-P730B 900-B903-K-42(CONVEYOR DISHWASHER) 27.50 KVA 400 39.69 40 Verified 58.00 3φ 4C 1 XLPE 16 Unarmoured 74 Cable Tray 1.15 0.77 0.89 65.53 95.01 Verified Verified 0.928 0.090 0.932 38 0.55
900-B903-CANTEEN BUILDING

NEOM Green Hydrogen Company - Canteen Building Cable Sizing Calculation


Correction Factor

Full load Current, Ib Depth of Soil Adj. Amp. Iz %Vd %Vdst


Ambient
Equipment (Amp) Breaker convention Laying thermal (A) = Condition ‐2 Percentage Percentage
IEC60364‐4‐ grouond Cable Condition ‐3 Cable Cable
Ib =KVA*10³ / (√3*V) for size al tripping No. of No. of Size Conductor Correction Resistivity Total Derating (IEC60364‐4‐ Cable Resistance Cable Reactance Voltage Voltage
CIRCUIT No. Load Rating Voltage (Volt) Ist = 9.24 Ib 43, Phase Insulation Type of Cable Type of Installation Temparat grouping 1.45 x Iz (IEC60364‐4‐ 43) Impedance Length
non-Motor Load & Ib = In current, Cores Runs mm² Ampacity (A) Factor Correction Derating factor * 43) (R) (X) Drop during Drop during
(In ≥ Ib) ure correction I2 ≤ 1.45 Iz (Z) (meters)
KW*10³ / (√3*V*COSØ*ƞ) (Amp) I2 = 1.45*In (1.0 factor (1.0 factor Conductor Iz ≥ In Normal Motor
Correction factor (Fg)
for Motor Load °C.m/W) °C.m/W) Ampacity Operation Starting
Factor (Ft)
(Fd) (Fth)
From To

900-900G03-FZ-LP-45 900G03-P730C 900-B903-FREEZER 6.25 KVA 400 9.02 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 In Pipe 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 31 0.61

900-900G03-MCS-LP-46 900G03-P730C 900-B903-MEAT COLD STORAGE 5 KVA 400 7.22 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 In Pipe 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 27 0.42

900-900G03-VCS-LP-47 900G03-P730C 900-B903-VEGETABLE COLD STORAGE 5 KVA 400 7.22 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 In Pipe 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 25 0.39

900-900G03-EDH-01-LP-48 900G03-P730D 900-B903-EDH-01 11.25 KVA 400 19.10 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 In Pipe 1.15 0.77 0.89 36.31 52.64 Verified Verified 3.930 0.099 3.931 25 0.70

900-900G03-EDH-02-LP-49 900G03-P730D 900-B903-EDH-02 11.25 KVA 400 19.10 30 Verified 43.50 3φ 4C 1 XLPE 6 Unarmoured 41 In Pipe 1.15 0.77 0.89 36.31 52.64 Verified Verified 3.930 0.099 3.931 20 0.56

900-900G03-EDH-03-LP-50 900G03-P730D 900-B903-EDH-03 5.5 KVA 400 9.34 20 Verified 29.00 3φ 4C 1 XLPE 6 Unarmoured 41 In Pipe 1.15 0.77 0.89 36.31 52.64 Verified Verified 3.930 0.099 3.931 11 0.15

900-900G03-EDH-04-LP-51 900G03-P730D 900-B903-EDH-04 5.5 KVA 400 9.34 20 Verified 29.00 3φ 4C 1 XLPE 6 Unarmoured 41 In Pipe 1.15 0.77 0.89 36.31 52.64 Verified Verified 3.930 0.099 3.931 13 0.18

900-900G03-EF-01-LP-52 900G03-P730E 900-B903-EF-01 0.22 KVA 230 1.13 6.98 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 57 1.73

900-900G03-EF-03-LP-53 900G03-P730E 900-B903-EF-03 0.05 KVA 230 0.26 1.59 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 54 0.37

900-900G03-EF-08-LP-54 900G03-P730E 900-B903-EF-08 0.13 KVA 230 0.66 4.12 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 48 0.86

900-900G03-EF-06-LP-55 900G03-P730E 900-B903-EF-06 2.75 KVA 230 8.12 50.35 20 Verified 29.00 1φ 3C 1 XLPE 6 Unarmoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 36 4.63

900-900G03-EF-07-LP-56 900G03-P730E 900-B903-EF-07 0.5 KVA 400 0.85 5.26 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 23 0.26

900-900G03-EF-04-LP-57 900G03-P730E 900-B903-EF-04 0.56 KVA 230 2.86 17.76 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 24 1.85

900-900G03-EF-02-LP-58 900G03-P730E 900-B903-EF-02 0.06 KVA 230 0.31 1.90 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 21 0.17

900-900G03-EF-09-LP-59 900G03-P730E 900-B903-EF-09 0.37 KVA 230 1.89 11.73 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 19 0.97

900-900G03-EF-05-LP-60 900G03-P730E 900-B903-EF-05 0.05 KVA 230 0.26 1.59 16 Verified 23.20 1φ 3C 1 XLPE 4 Armoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 13 0.09

900-900G03-HWSP-1-LP-62 900G03-P730E HOT WATER RECIRCULATION PUMP SET-1 1.875 KVA 230 9.59 59.46 20 Verified 29.00 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 33 8.54

900-900G03-EWH-1-LP-64 900G03-P730E 900-B903-EWH-1 5.63 KVA 400 8.12 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 29 0.51

900-900G03-EWH-2-LP-65 900G03-P730E 900-B903-EWH-2 5.63 KVA 400 8.12 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 30 0.53

900-900G03-EWH-3-LP-66 900G03-P730E 900-B903-EWH-3 5.63 KVA 400 8.12 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 29 0.51

900-900G03-EWH-4-LP-67 900G03-P730E 900-B903-EWH-4 5.63 KVA 400 8.12 20 Verified 29.00 3φ 4C 1 XLPE 4 Unarmoured 32 Cable Tray 1.15 0.77 0.89 28.34 41.09 Verified Verified 5.880 0.011 5.880 29 0.51

900-900G03-SPU-OU-1A-LP-68 900G03-EP730A 900-B903-SPU-OU-1A 2.81 KVA 230 14.37 89.12 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 15 3.94

900-900G03-SPU-OU-1B-LP-69 900G03-EP730A 900-B903-SPU-OU-1B 2.81 KVA 230 14.37 89.12 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 13 3.42

900-900G03-SPU-OU-2A-LP-70 900G03-EP730A 900-B903-SPU-OU-2A 2.38 KVA 230 12.17 75.48 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 50 11.13

900-900G03-SPU-OU-2B-LP-71 900G03-EP730A 900-B903-SPU-OU-2B 2.38 KVA 230 12.17 75.48 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 55 12.25

900-900G03-SPU-OU-3 -LP-72 900G03-EP730A 900-B903-SPU-OU-3 2.43 KVA 230 12.43 77.06 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 5.880 0.011 5.880 23 7.71

900-900G03-SPU-OU-4-LP-73 900G03-EP730A 900-B903-SPU-OU-4 2.81 KVA 230 14.37 89.12 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 24 6.31

900-900G03-SPU-OU-5-LP-74 900G03-EP730A 900-B903-SPU-OU-5 2.38 KVA 230 12.17 75.48 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 26 5.79

900-900G03-SPU-OU-6-LP-75 900G03-EP730A 900-B903-SPU-OU-6 2.81 KVA 230 14.37 89.12 30 Verified 43.50 1φ 3C 1 XLPE 6 Armoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 28 7.36

900-900G03-UPS-DDC-LP-76 900G03-EP730A 900-DDC-903 2 KVA 230 10.23 30 Verified 43.50 1φ 3C 1 XLPE 6 Unarmoured 39 In Pipe 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 3 0.09

900-900G03-UPS-DDC-LP-86 900G03-EP730A 900-DDC-903 2 KVA 230 10.23 30 Verified 43.50 1φ 3C 1 XLPE 6 Unarmoured 39 In Pipe 1.15 0.77 0.89 34.53 50.08 Verified Verified 3.930 0.099 3.931 3 0.09

900-900G03-PAU-01A-LP-77 900G03-EP730A 900-B903-PAU-01A (DUTY) 68.5 KVA 400 116.32 1074.82 125 Verified 181.25 3φ 3C 1 XLPE 95 Armoured 216 Cable Tray 1.15 0.77 0.89 191.27 277.34 Verified Verified 0.248 0.083 0.262 34 0.44 4.03

900-900G03-PAU-01B-LP-78 900G03-EP730A 900-B903-PAU-01B (STANDBY) 68.5 KVA 400 116.32 1074.82 125 Verified 181.25 3φ 3C 1 XLPE 95 Armoured 216 Cable Tray 1.15 0.77 0.89 191.27 277.34 Verified Verified 0.248 0.083 0.262 33 0.42 3.91

900-900G03-PAU-02A-LP-79 900G03-EP730A 900-B903-PAU-02A (DUTY) 71.12 KVA 400 120.77 1115.93 125 Verified 181.25 3φ 3C 1 XLPE 95 Armoured 216 Cable Tray 1.15 0.77 0.89 191.27 277.34 Verified Verified 0.248 0.083 0.262 22 0.29 2.70

900-900G03-PAU-02B-LP-80 900G03-EP730A 900-B903-PAU-02B (STANDBY) 71.12 KVA 400 120.77 1115.93 125 Verified 181.25 3φ 3C 1 XLPE 95 Armoured 216 Cable Tray 1.15 0.77 0.89 191.27 277.34 Verified Verified 0.248 0.083 0.262 16 0.21 1.97

900-900G03-MAU-01-LP-81 900G03-EP730A 900-B903-MAU-01 90.75 KVA 400 154.11 1423.94 200 Verified 290.00 3φ 3C 1 XLPE 120 Armoured 251 Cable Tray 1.15 0.77 0.89 222.26 322.28 Verified Verified 0.198 0.083 0.215 43 0.61 5.62

900-900G03-EP730B-LP-82 900G03-EP730A 900G03-EP730B 11.77 KVA 400 16.99 40 Verified 58.00 3φ 4C 1 XLPE 10 Unarmoured 56 Cable Tray 1.15 0.77 0.89 49.59 71.90 Verified Verified 2.330 0.094 2.332 4 0.06

900-900G03-DAC-01B-LP-83 900G03-P730E 900-B903-DAC-01B 1 KVA 230 1.70 10.53 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 29 1.15

900-900G03-DAC-01A-LP-84 900G03-P730E 900-B903-DAC-01A 1 KVA 230 1.70 10.53 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 23 0.91

900-900G03-DAC-01C-LP-85 900G03-P730E 900-B903-DAC-01C 1 KVA 230 1.70 10.53 16 Verified 23.20 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 19 0.75

900-900G03-ITC-01-LP-61 900G03-EP730B 903-ITC-001 3 KVA 230 15.35 30 Verified 43.50 1φ 3C 1 XLPE 6 Unarmoured 39 Cable Tray 1.15 0.77 0.89 34.53 50.08 Verified Verified 5.880 0.011 5.880 32 2.14

900-900G03-FRIO-121A-LP-89 900G03-PDB1 P00-G903-FRIO-121A 0.7 KVA 230 3.58 20 Verified 29.00 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 5 0.08

900-900G03-FRIO-121A-LP-90 900G03-PDB2 P00-G903-FRIO-121A 0.7 KVA 230 3.58 20 Verified 29.00 1φ 3C 1 XLPE 4 Unarmoured 31 Cable Tray 1.15 0.77 0.89 27.45 39.80 Verified Verified 5.880 0.011 5.880 5 0.08

Update the tag nos.

Add one no. raw power


supply to RIO panel.
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

APPENDIX – 2

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.
Single Core - Copper Conductor, XLPE Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
1- Core CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 1.5 7 1.6 0.7 1.4 6 50
1 x 2.5 7 2.0 0.7 1.4 7 70
1x4 7 2.6 0.7 1.4 7 80
1x6 7 3.1 0.7 1.4 8 110
1 x 10 7 4.0 0.7 1.4 9 150
1 x 16 7 5.0 0.7 1.4 10 210
1 x 25 7 6.3 0.9 1.4 11 310
1 x 35 7 7.4 0.9 1.4 13 410
1 x 50 19 8.8 1.0 1.4 14 530
1 x 70 19 10.6 1.1 1.4 16 740
1 x 95 19 12.4 1.1 1.5 18 1000
1 x 120 37 14.0 1.2 1.5 20 1240
1 x 150 37 15.5 1.4 1.6 22 1520
1 x 185 37 17.4 1.6 1.6 24 1890
1 x 240 61 20.3 1.7 1.7 28 2460
1 x 300 61 22.7 1.8 1.8 30 3060
1 x 400 61 25.4 2.0 1.9 34 3910
1 x 500 61 28.8 2.2 2.0 38 4980
1 x 630 61 30.4 2.4 2.2 40 6260
1 x 800 61 33.7 2.6 2.3 44 7950
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps

1 x 1.5 22 21 21 22 24 21 18 25 19
1 x 2.5 29 27 29 29 31 27 25 34 26
1x4 38 34 37 37 39 35 32 44 33
1x6 47 43 45 47 49 44 42 56 43
1 x 10 62 57 59 61 65 57 58 77 59
1 x 16 80 73 77 79 83 75 76 101 79
1 x 25 102 94 98 100 106 95 100 133 103
1 x 35 122 113 119 120 128 115 127 166 131
1 x 50 144 134 139 142 150 135 153 200 157
1 x 70 176 164 172 173 184 167 195 254 201
1 x 95 211 197 204 206 220 199 241 313 248
1 x 120 240 225 234 234 251 228 282 365 291
1 x 150 268 253 261 262 281 256 325 418 335
1 x 185 302 286 297 295 318 291 375 482 387
1 x 240 351 333 347 341 371 341 455 583 470
1 x 300 392 373 393 381 417 385 517 667 535
1 x 400 443 423 448 430 476 441 605 781 625
1 x 500 496 475 515 481 541 505 697 909 721
1 x 630 547 525 574 530 606 566 777 1025 804
1 x 800 599 576 639 580 676 633 873 1167 903
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Two & Three Cores) - Copper Conductor, XLPE Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
2-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 1.5 7 1.6 0.7 1.8 13 190 22 21 21
2 x 2.5 7 2.0 0.7 1.8 13 240 29 27 29
2x4 7 2.6 0.7 1.8 14 290 38 34 37
2x6 7 3.1 0.7 1.8 16 350 47 43 45
2 x 10 7 4.0 0.7 1.8 17 480 62 57 59
2 x 16 7 5.0 0.7 1.8 19 650 80 73 77
2 x 25 7 6.3 0.9 1.8 23 930 102 94 98
2 x 35 7 7.4 0.9 1.8 25 1190 122 113 119
2 x 50 19 8.8 1.0 1.8 28 1540 144 134 139
2 x 70 19 10.6 1.1 1.8 32 2100 176 164 172
2 x 95 19 12.4 1.1 2.0 37 2830 211 197 204
2 x 120 37 14.0 1.2 2.1 40 3500 240 225 234
2 x 150 37 15.5 1.4 2.2 44 4260 268 253 261
2 x 185 37 17.4 1.6 2.3 50 5340 302 286 297
2 x 240 61 20.3 1.7 2.5 56 6900 351 333 347
2 x 300 61 22.7 1.8 2.7 62 8600 392 373 393
2 x 400 61 25.4 2.0 2.9 69 10830 443 423 448
2 x 500 61 28.8 2.2 3.1 77 13710 496 475 515
*Overall Diameter Tolerence Range: [-2% , +6%]

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
3-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 1.5 7 1.6 0.7 1.8 13 210 21 17 18
3 x 2.5 7 2.0 0.7 1.8 14 260 27 23 24
3x4 7 2.6 0.7 1.8 15 330 35 29 31
3x6 7 3.1 0.7 1.8 16 410 44 37 39
3 x 10 7 4.0 0.7 1.8 18 570 58 49 54
3 x 16 7 5.0 0.7 1.8 20 790 75 63 71
3 x 25 7 6.3 0.9 1.8 24 1160 98 82 96
3 x 35 7 7.4 0.9 1.8 27 1380 115 99 115
3 x 50 19 8.8 1.0 1.8 30 1790 137 118 140
3 x 70 19 10.6 1.1 1.9 35 2510 167 146 176
3 x 95 19 12.4 1.1 2.0 39 3350 200 176 216
3 x 120 37 14.0 1.2 2.1 43 4150 227 201 251
3 x 150 37 15.5 1.4 2.3 48 5120 254 227 285
3 x 185 37 17.4 1.6 2.4 53 6360 286 257 327
3 x 240 61 20.3 1.7 2.6 60 8280 330 299 386
3 x 300 61 22.7 1.8 2.8 67 10270 370 339 441
3 x 400 61 25.4 2.0 3.1 74 13040 414 383 502
3 x 500 61 28.8 2.2 3.3 83 16610 462 431 569
*Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Three and half & Four Cores) - Copper Conductor, XLPE Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
3½ -Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**

mm² No. mm mm mm mm kg/km


3x16+10 7/7 5/4 0.7 / 0.7 1.8 22 900 76 64 73
3x25+16 7/7 6.3 / 5 0.9 / 0.7 1.8 25 1320 98 83 97
3x35+16 7/7 6.6 / 5 0.9 / 0.7 1.8 25 1470 114 97 112
3x50+25 19 / 7 7.5 / 6.3 1.0 / 0.9 1.8 29 1950 135 117 137
3x70+35 19 / 7 9.1 / 7.4 1.1 / 0.9 1.9 33 2740 165 143 172
3x95+50 19 / 19 11 / 8.8 1.1 / 1.0 2.1 37 3670 198 173 211
3x120+70 37 / 19 12.2 / 10.6 1.2 / 1.1 2.2 41 4620 225 197 244
3x150+70 37 / 19 13.8 / 10.6 1.4 / 1.1 2.3 45 5580 251 224 278
3x185+95 37 / 19 15.1 / 12.4 1.6 / 1.1 2.5 50 7000 283 253 318
3x240+120 61 / 37 17.6 / 14 1.7 / 1.2 2.7 55 9040 326 294 373
3x300+150 61 / 37 19.8 / 15.5 1.8 / 1.4 2.9 61 11180 366 333 426
3x400+185 61 / 37 22.2 / 17.4 2.0 / 1.6 3.1 68 14160 412 379 490
3x500+240 61 / 61 26.3 / 20.3 2.2 / 1.7 3.4 76 18070 462 428 558
2
*Sectoral Shape for conductor size > 25 mm
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
4-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 1.5 7 1.6 0.7 1.8 14 240 21 18 18
4 x 2.5 7 2.0 0.7 1.8 15 310 28 23 24
4x4 7 2.6 0.7 1.8 16 390 36 30 32
4x6 7 3.1 0.7 1.8 18 500 45 37 41
4 x 10 7 4.0 0.7 1.8 20 700 59 50 56
4 x 16 7 5.0 0.7 1.8 22 980 77 64 74
4 x 25 7 6.3 0.9 1.8 26 1450 99 84 99
4 x 35 7 6.6 0.9 1.8 26 1650 115 98 114
4 x 50 19 7.5 1.0 1.9 30 2160 136 117 139
4 x 70 19 9.1 1.1 2.0 34 3060 166 144 173
4 x 95 19 11.0 1.1 2.1 38 4100 199 175 213
4 x 120 37 12.2 1.2 2.3 43 5130 225 199 247
4 x 150 37 13.8 1.4 2.4 47 6320 253 225 281
4 x 185 37 15.1 1.6 2.6 52 7830 284 256 322
4 x 240 61 17.6 1.7 2.8 58 10180 328 298 378
4 x 300 61 19.8 1.8 3.0 64 12610 368 337 433
4 x 400 61 22.2 2.0 3.3 73 16120 415 384 497
4 x 500 61 26.3 2.2 3.5 80 20380 465 433 566
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Five Cores) - Copper Conductor, XLPE Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded XLPE Material
Oversheath : Extruded Material (PVC, LSF or PE)
5-Cores CU/XLPE/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 1.5 7 1.6 0.7 1.8 15 280 21 18 19
5 x 2.5 7 2.0 0.7 1.8 16 360 28 23 25
5x4 7 2.6 0.7 1.8 17 460 36 30 33
5x6 7 3.1 0.7 1.8 19 590 45 38 42
5 x 10 7 4.0 0.7 1.8 21 840 60 50 57
5 x 16 7 5.0 0.7 1.8 24 1190 78 66 76
5 x 25 7 6.3 0.9 1.8 28 1770 100 85 102
5 x 35 7 7.4 0.9 1.8 32 2180 120 104 126
5 x 50 19 8.8 1.0 2.0 37 2920 142 124 154
5 x 70 19 10.6 1.1 2.1 42 4050 174 153 194
5 x 95 19 12.4 1.1 2.3 48 5510 208 186 238
5 x 120 37 14.0 1.2 2.4 53 6850 237 212 277
5 x 150 37 15.5 1.4 2.6 58 8380 265 239 315
5 x 185 37 17.4 1.6 2.8 65 10520 299 272 362
5 x 240 61 20.3 1.7 3.0 74 13620 346 318 431
5 x 300 61 22.7 1.8 3.2 82 16990 387 359 491
5 x 400 61 25.4 2.0 3.6 91 21640 434 406 560
5 x 500 61 28.8 2.2 3.8 102 27450 486 459 639
*Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Single Core - Copper Conductor, PVC Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
1-Core CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1
Approx Nominal Nominal Approx. Approx.
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
1 x 1.5 7 1.6 0.8 1.4 6 60
1 x 2.5 7 2.0 0.8 1.4 7 70
1x4 7 2.6 1.0 1.4 8 100
1x6 7 3.1 1.0 1.4 8 120
1 x 10 7 4.0 1.0 1.4 9 170
1 x 16 7 5.0 1.0 1.4 10 230
1 x 25 7 6.3 1.2 1.4 12 340
1 x 35 7 7.4 1.2 1.4 13 440
1 x 50 19 8.8 1.4 1.4 15 580
1 x 70 19 10.6 1.4 1.4 17 790
1 x 95 19 12.4 1.6 1.5 19 1080
1 x 120 37 14.0 1.6 1.5 21 1320
1 x 150 37 15.5 1.8 1.6 23 1610
1 x 185 37 17.4 2.0 1.7 25 2010
1 x 240 61 20.3 2.2 1.8 29 2620
1 x 300 61 22.7 2.4 1.9 32 3260
1 x 400 61 25.4 2.6 2.0 35 4140
1 x 500 61 28.8 2.8 2.1 39 5260
1 x 630 61 30.4 2.8 2.2 41 6470
1 x 800 61 33.7 2.8 2.3 44 8160
*Overall Diameter Tolerence Range: [-2% , +6%]
Continuous Current Rating
Flat Flat Spaced
Nominal Trefoil in One Trefoil in Three Flat Spaced Flat Spaced Flat Touching
Trefoil [Gd] Touching in Three Trefoil [Air]
Area Duct [Gd] Ducts [Gd] [Gd] [Air] [Air]
[Gd] Ducts [Gd]
mm² Amps Amps Amps Amps Amps Amps Amps Amps Amps

1 x 1.5 18 16 17 18 19 16 11 15 12
1 x 2.5 23 21 23 23 24 22 15 21 16
1x4 30 28 29 30 31 28 21 27 21
1x6 37 34 36 37 39 34 25 34 26
1 x 10 49 45 47 49 51 46 35 47 36
1 x 16 63 58 61 62 66 59 46 62 48
1 x 25 81 75 78 80 85 76 63 83 65
1 x 35 97 90 94 95 101 91 77 101 79
1 x 50 115 107 111 113 120 108 95 123 98
1 x 70 141 132 137 138 147 133 121 156 124
1 x 95 168 158 164 164 175 160 149 191 153
1 x 120 191 180 186 187 200 182 174 224 180
1 x 150 214 202 210 209 224 205 200 256 206
1 x 185 241 228 236 235 253 232 230 294 237
1 x 240 279 265 279 271 295 273 277 354 286
1 x 300 313 298 316 304 333 309 319 408 330
1 x 400 351 336 359 341 378 352 367 472 379
1 x 500 392 376 407 380 428 401 422 548 436
1 x 630 433 416 453 420 480 449 472 621 488
1 x 800 471 453 504 456 533 500 524 703 542
- When cables are arranged in spaced flat formation they are spaced by one cable diameter.

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Two & Three Cores) - Copper Conductor, PVC Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
2-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
2 x 1.5 7 1.6 0.8 1.8 13 210 19 16 13
2 x 2.5 7 2.0 0.8 1.8 14 250 25 21 17
2x4 7 2.6 1.0 1.8 16 340 33 28 23
2x6 7 3.1 1.0 1.8 17 410 41 35 29
2 x 10 7 4.0 1.0 1.8 19 540 55 47 39
2 x 16 7 5.0 1.0 1.8 21 720 71 60 52
2 x 25 7 6.3 1.2 1.8 24 1030 91 78 69
2 x 35 7 7.4 1.2 1.8 26 1300 109 94 84
2 x 50 19 8.8 1.4 1.8 30 1700 130 113 103
2 x 70 19 10.6 1.4 1.9 33 2260 159 139 129
2 x 95 19 12.4 1.6 2.0 39 3080 191 169 160
2 x 120 37 14.0 1.6 2.1 42 3740 217 193 185
2 x 150 37 15.5 1.8 2.2 46 4540 243 217 211
2 x 185 37 17.4 2.0 2.4 51 5690 273 247 241
2 x 240 61 20.3 2.2 2.6 58 7370 316 288 286
2 x 300 61 22.7 2.4 2.7 65 9160 355 326 327
2 x 400 61 25.4 2.6 3.0 71 11510 398 368 373
2 x 500 61 28.8 2.8 3.2 80 14580 445 415 425
*Overall Diameter Tolerence Range: [-2% , +6%]

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
3-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
3 x 1.5 7 1.6 0.8 1.8 13 240 16 14 11
3 x 2.5 7 2.0 0.8 1.8 14 290 21 18 15
3x4 7 2.6 1.0 1.8 16 390 28 24 19
3x6 7 3.1 1.0 1.8 18 480 35 29 25
3 x 10 7 4.0 1.0 1.8 20 650 46 39 34
3 x 16 7 5.0 1.0 1.8 22 880 60 50 45
3 x 25 7 6.3 1.2 1.8 25 1280 77 65 59
3 x 35 7 7.4 1.2 1.8 28 1500 91 78 72
3 x 50 19 8.8 1.4 1.8 32 1950 108 94 87
3 x 70 19 10.6 1.4 2.0 36 2700 132 116 109
3 x 95 19 12.4 1.6 2.1 41 3630 158 139 134
3 x 120 37 14.0 1.6 2.2 45 4440 180 160 156
3 x 150 37 15.5 1.8 2.3 50 5440 201 180 178
3 x 185 37 17.4 2.0 2.5 55 6760 226 205 203
3 x 240 61 20.3 2.2 2.7 63 8800 261 238 240
3 x 300 61 22.7 2.4 2.9 69 10920 291 268 273
3 x 400 61 25.4 2.6 3.1 76 13770 327 304 311
3 x 500 61 28.8 2.8 3.4 86 17520 364 341 353
*Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Three and half & Four Cores) - Copper Conductor, PVC Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
3½ -Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Nominal Outer Approx. Ground Duct [Gd] Free Air
Nominal Number of Strands Approx Conductor Nominal Insulation Approx. Cable
Sheath Overall
Area* [Ph/Ne] Diameter [Ph/Ne] Thickness [Ph/Ne] Weight Amps Amps Amps
Thickness Diameter**

mm² No. mm mm mm mm kg/km


3x16+10 7/7 5/4 1.0 / 1.0 1.8 23 1010 60 51 46
3x25+16 7/7 6.3 / 5 1.2 / 1.0 1.8 27 1460 78 67 61
3x35+16 7/7 6.6 / 5 1.2 / 1.0 1.8 27 1600 90 78 70
3x50+25 19 / 7 7.5 / 6.3 1.4 / 1.2 1.9 31 2150 107 93 86
3x70+35 19 / 7 9.1 / 7.4 1.4 / 1.2 2.0 35 2950 131 115 107
3x95+50 19 / 19 11 / 8.8 1.6 / 1.4 2.2 39 3980 156 138 131
3x120+70 37 / 19 12.2 / 10.6 1.6 / 1.4 2.3 43 4980 177 157 152
3x150+70 37 / 19 13.8 / 10.6 1.8 / 1.4 2.4 47 5950 198 177 173
3x185+95 37 / 19 15.1 / 12.4 2.0 / 1.6 2.6 52 7440 223 202 198
3x240+120 61 / 37 17.6 / 14 2.2 / 1.6 2.8 58 9600 257 234 232
3x300+150 61 / 37 19.8 / 15.5 2.4 / 1.8 3.0 64 11880 288 265 265
3x400+185 61 / 37 22.2 / 17.4 2.6 / 2.0 3.2 72 15060 325 300 304
3x500+240 61 / 61 26.3 / 20.3 2.8 / 2.2 3.5 79 19050 363 337 346
2
*Sectoral Shape for conductor size > 25 mm
**Overall Diameter Tolerence Range: [-2% , +6%]
[Ph]: Phase [Ne]: Neutral

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
4-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area* Strands Amps Amps Amps
Diameter Thickness Sheath Diameter** Weight
mm² No. mm mm mm mm kg/km
4 x 1.5 7 1.6 0.8 1.8 14 270 17 14 11
4 x 2.5 7 2.0 0.8 1.8 15 340 22 18 15
4x4 7 2.6 1.0 1.8 18 470 28 24 20
4x6 7 3.1 1.0 1.8 19 580 35 30 25
4 x 10 7 4.0 1.0 1.8 21 800 47 40 35
4 x 16 7 5.0 1.0 1.8 24 1090 61 52 46
4 x 25 7 6.3 1.2 1.8 28 1600 78 67 62
4 x 35 7 6.6 1.2 1.8 28 1790 91 78 71
4 x 50 19 7.5 1.4 1.9 32 2390 107 94 86
4 x 70 19 9.1 1.4 2.1 36 3280 131 115 108
4 x 95 19 11.0 1.6 2.2 41 4430 157 139 133
4 x 120 37 12.2 1.6 2.4 45 5470 178 159 154
4 x 150 37 13.8 1.8 2.5 49 6720 199 179 175
4 x 185 37 15.1 2.0 2.7 55 8360 224 204 201
4 x 240 61 17.6 2.2 2.9 61 10790 259 237 236
4 x 300 61 19.8 2.4 3.1 67 13370 290 267 269
4 x 400 61 22.2 2.6 3.4 76 17030 327 304 309
4 x 500 61 26.3 2.8 3.6 83 21440 365 342 351
*Sectoral Shape for conductor size > 25 mm2
**Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore (Five Cores) - Copper Conductor, PVC Insulated Cables

Conductor : Round Stranded Copper


Insulation : Extruded PVC Material
Oversheath : Extruded Material (PVC or PE)
5-Cores CU/PVC/Sheathed 600/1000 V Cables as per IEC 60502-1 Continuous Current Rating
Approx Nominal Nominal Approx. Approx. Ground Duct [Gd] Free Air
Nominal Number of
Conductor Insulation Outer Overall Cable
Area Strands Amps Amps Amps
Diameter Thickness Sheath Diameter* Weight
mm² No. mm mm mm mm kg/km
5 x 1.5 7 1.6 0.8 1.8 15 310 17 14 12
5 x 2.5 7 2.0 0.8 1.8 16 400 22 19 15
5x4 7 2.6 1.0 1.8 19 550 29 24 21
5x6 7 3.1 1.0 1.8 20 690 36 30 26
5 x 10 7 4.0 1.0 1.8 23 960 47 40 36
5 x 16 7 5.0 1.0 1.8 26 1330 61 53 48
5 x 25 7 6.3 1.2 1.8 30 1960 79 68 63
5 x 35 7 7.4 1.2 1.9 33 2390 95 82 78
5 x 50 19 8.8 1.4 2.1 39 3210 112 99 95
5 x 70 19 10.6 1.4 2.2 44 4360 138 122 120
5 x 95 19 12.4 1.6 2.4 51 5980 165 148 148
5 x 120 37 14.0 1.6 2.5 55 7320 187 169 171
5 x 150 37 15.5 1.8 2.7 61 8990 209 191 195
5 x 185 37 17.4 2.0 2.9 68 11180 236 217 224
5 x 240 61 20.3 2.2 3.1 77 14480 273 253 266
5 x 300 61 22.7 2.4 3.3 85 18080 305 284 302
5 x 400 61 25.4 2.6 3.7 95 22910 343 323 345
5 x 500 61 28.8 2.8 4.0 106 29110 382 362 391
*Overall Diameter Tolerence Range: [-2% , +6%]

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Single Core - Copper Conductor, XLPE Insulated Cables [90oC]

Electrical Parameters [TOUCHED Cables in Trefoil & Flat Formation ]


DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance Current
Area [60 Hz] [90 C] 3-φ 1-φ Resistance [20oC]
[20 oC] o
[90 C] [90 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1 x 1.5 12.10 15.43 15.43 0.597 0.225 15.43 21.61 24.96 0.103 1045 0.21
1 x 2.5 7.41 9.45 9.45 0.546 0.206 9.45 13.31 15.37 0.114 840 0.36
1x4 4.61 5.88 5.88 0.514 0.194 5.88 8.35 9.64 0.121 720 0.57
1x6 3.08 3.93 3.93 0.474 0.179 3.93 5.63 6.50 0.131 585 0.86
1 x 10 1.83 2.33 2.33 0.439 0.165 2.34 3.41 3.93 0.140 475 1.43
1 x 16 1.15 1.47 1.47 0.407 0.153 1.48 2.19 2.53 0.149 385 2.29
1 x 25 0.727 0.927 0.927 0.387 0.146 0.939 1.44 1.66 0.147 400 3.58
1 x 35 0.524 0.668 0.668 0.365 0.138 0.683 1.07 1.24 0.153 340 5.01
1 x 50 0.387 0.494 0.494 0.353 0.133 0.511 0.823 0.950 0.155 330 7.15
1 x 70 0.268 0.342 0.342 0.336 0.127 0.365 0.606 0.700 0.157 310 10.02
1 x 95 0.193 0.246 0.247 0.321 0.121 0.275 0.468 0.541 0.162 260 13.59
1 x 120 0.153 0.195 0.197 0.305 0.115 0.228 0.392 0.452 0.163 255 17.17
1 x 150 0.124 0.158 0.160 0.307 0.116 0.198 0.342 0.395 0.161 270 21.46
1 x 185 0.0991 0.126 0.129 0.298 0.112 0.171 0.295 0.340 0.161 275 26.47
1 x 240 0.0754 0.0961 0.0992 0.292 0.110 0.148 0.252 0.291 0.163 255 34.34
1 x 300 0.0601 0.0766 0.0807 0.281 0.106 0.133 0.222 0.256 0.165 240 42.93
1 x 400 0.0470 0.0599 0.0650 0.280 0.105 0.123 0.199 0.230 0.165 235 57.23
1 x 500 0.0366 0.0467 0.0529 0.278 0.105 0.118 0.182 0.211 0.166 230 71.54
1 x 630 0.0283 0.0361 0.0436 0.276 0.104 0.113 0.168 0.195 0.166 235 90.14
1 x 800 0.0221 0.0282 0.0368 0.275 0.104 0.110 0.159 0.184 0.166 230 114.47

Electrical Parameters [SPACED Cables in Trefoil & Flat Formation ]


DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance Current
Area [60 Hz] [90 C] 3-φ 1-φ Resistance [20oC]
[20 oC] [90 oC] [90 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1 x 1.5 12.10 15.43 15.43 0.782 0.295 15.43 21.69 24.96 0.103 1045 0.21
1 x 2.5 7.41 9.45 9.45 0.731 0.276 9.45 13.38 15.37 0.114 840 0.36
1x4 4.61 5.88 5.88 0.699 0.264 5.88 8.42 9.64 0.121 720 0.57
1x6 3.08 3.93 3.93 0.659 0.248 3.94 5.70 6.50 0.131 585 0.86
1 x 10 1.83 2.33 2.33 0.624 0.235 2.35 3.48 3.93 0.140 475 1.43
1 x 16 1.15 1.47 1.47 0.592 0.223 1.48 2.26 2.53 0.149 385 2.29
1 x 25 0.727 0.927 0.927 0.572 0.216 0.952 1.51 1.66 0.147 400 3.58
1 x 35 0.524 0.668 0.668 0.550 0.207 0.700 1.14 1.24 0.153 340 5.01
1 x 50 0.387 0.494 0.494 0.538 0.203 0.534 0.895 0.950 0.155 330 7.15
1 x 70 0.268 0.342 0.342 0.520 0.196 0.394 0.678 0.700 0.157 310 10.02
1 x 95 0.193 0.246 0.247 0.506 0.191 0.312 0.541 0.541 0.162 260 13.59
1 x 120 0.153 0.195 0.196 0.489 0.185 0.269 0.465 0.452 0.163 255 17.17
1 x 150 0.124 0.158 0.159 0.492 0.186 0.245 0.415 0.395 0.161 270 21.46
1 x 185 0.0991 0.126 0.128 0.483 0.182 0.222 0.367 0.340 0.161 275 26.47
1 x 240 0.0754 0.0961 0.0978 0.477 0.180 0.205 0.325 0.291 0.163 255 34.34
1 x 300 0.0601 0.0766 0.0788 0.466 0.176 0.193 0.295 0.256 0.165 240 42.93
1 x 400 0.0470 0.0599 0.0626 0.464 0.175 0.186 0.272 0.230 0.165 235 57.23
1 x 500 0.0366 0.0467 0.0500 0.463 0.174 0.181 0.254 0.211 0.166 230 71.54
1 x 630 0.0283 0.0361 0.0402 0.461 0.174 0.179 0.241 0.195 0.166 235 90.14
1 x 800 0.0221 0.0282 0.0331 0.460 0.173 0.176 0.231 0.184 0.166 230 114.47

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Single Core - Copper Conductor, PVC Insulated Cables [70oC]

Electrical Parameters [TOUCHED Cables in Trefoil & Flat Formation ]


DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance o Current
Area o [60 Hz] [70 C] 3-φ 1-φ Resistance [20 C]
[20 C] [70 oC] [70 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1 x 1.5 12.10 14.48 14.48 0.597 0.225 14.48 20.30 23.43 0.315 15.0 0.17
1 x 2.5 7.41 8.87 8.87 0.546 0.206 8.87 12.50 14.43 0.348 10.0 0.29
1x4 4.61 5.52 5.52 0.514 0.194 5.52 7.85 9.06 0.346 10.0 0.46
1x6 3.08 3.69 3.69 0.489 0.184 3.69 5.30 6.17 0.375 10.0 0.69
1 x 10 1.83 2.19 2.19 0.452 0.171 2.20 3.21 3.71 0.405 10.0 1.15
1 x 16 1.15 1.38 1.38 0.420 0.158 1.39 2.07 2.39 0.434 10.0 1.84
1 x 25 0.727 0.870 0.870 0.387 0.146 0.882 1.36 1.57 0.437 5.1 2.88
1 x 35 0.524 0.627 0.627 0.376 0.142 0.643 1.02 1.17 0.459 5.0 4.03
1 x 50 0.387 0.463 0.463 0.353 0.133 0.482 0.780 0.901 0.458 5.0 5.75
1 x 70 0.268 0.321 0.321 0.336 0.127 0.346 0.577 0.667 0.477 5.0 8.05
1 x 95 0.193 0.231 0.232 0.329 0.124 0.263 0.450 0.52 0.482 5.0 10.93
1 x 120 0.153 0.183 0.186 0.312 0.118 0.219 0.378 0.437 0.494 5.0 13.8
1 x 150 0.124 0.148 0.150 0.307 0.116 0.190 0.329 0.38 0.492 5.0 17.25
1 x 185 0.0991 0.119 0.121 0.305 0.115 0.167 0.287 0.331 0.493 5.0 21.28
1 x 240 0.0754 0.0902 0.0934 0.298 0.112 0.146 0.246 0.284 0.498 5.0 27.6
1 x 300 0.0601 0.0719 0.0759 0.292 0.110 0.134 0.219 0.253 0.502 5.0 34.5
1 x 400 0.047 0.0562 0.0612 0.289 0.109 0.125 0.198 0.229 0.505 5.0 41.12
1 x 500 0.0366 0.0438 0.0501 0.282 0.106 0.117 0.180 0.207 0.510 5.0 51.4
1 x 630 0.0283 0.0339 0.0414 0.280 0.106 0.114 0.168 0.193 0.515 5.0 64.77
1 x 800 0.0221 0.0264 0.0353 0.275 0.104 0.110 0.157 0.181 0.525 5.0 82.24

Electrical Parameters [SPACED Cables in Trefoil & Flat Formation ]


DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance Current
Area [60 Hz] [70 C] 3-φ 1-φ Resistance [20oC]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1 x 1.5 12.10 14.48 14.48 0.782 0.295 14.48 20.37 23.43 0.315 15.0 0.17
1 x 2.5 7.41 8.87 8.87 0.731 0.276 8.87 12.57 14.43 0.348 10.0 0.29
1x4 4.61 5.52 5.52 0.699 0.264 5.52 7.92 9.06 0.346 10.0 0.46
1x6 3.08 3.69 3.69 0.674 0.254 3.69 5.37 6.17 0.375 10.0 0.69
1 x 10 1.83 2.19 2.19 0.637 0.240 2.20 3.28 3.71 0.405 10.0 1.15
1 x 16 1.15 1.38 1.38 0.605 0.228 1.40 2.14 2.39 0.434 10.0 1.84
1 x 25 0.727 0.870 0.870 0.572 0.216 0.900 1.43 1.57 0.437 5.1 2.88
1 x 35 0.524 0.627 0.627 0.561 0.211 0.662 1.09 1.17 0.459 5.0 4.03
1 x 50 0.387 0.463 0.463 0.538 0.203 0.506 0.853 0.901 0.458 5.0 5.75
1 x 70 0.268 0.321 0.321 0.520 0.196 0.376 0.649 0.667 0.477 5.0 8.05
1 x 95 0.193 0.231 0.232 0.514 0.194 0.302 0.523 0.52 0.482 5.0 10.93
1 x 120 0.153 0.183 0.184 0.497 0.187 0.262 0.450 0.437 0.494 5.0 13.8
1 x 150 0.124 0.148 0.149 0.492 0.186 0.239 0.401 0.38 0.492 5.0 17.25
1 x 185 0.0991 0.119 0.120 0.489 0.185 0.220 0.360 0.331 0.493 5.0 21.28
1 x 240 0.0754 0.0902 0.0920 0.483 0.182 0.204 0.319 0.284 0.498 5.0 27.6
1 x 300 0.0601 0.0719 0.0741 0.477 0.180 0.195 0.292 0.253 0.502 5.0 34.5
1 x 400 0.047 0.0562 0.0590 0.474 0.179 0.188 0.271 0.229 0.505 5.0 41.12
1 x 500 0.0366 0.0438 0.0473 0.467 0.176 0.182 0.252 0.207 0.510 5.0 51.4
1 x 630 0.0283 0.0339 0.0381 0.465 0.175 0.179 0.239 0.193 0.515 5.0 64.77
1 x 800 0.0221 0.0264 0.0316 0.460 0.173 0.176 0.229 0.181 0.525 5.0 82.24

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Multicore - Copper Conductor, XLPE Insulated Cables [90oC]
Electrical Parameters
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance o Current
Area o [60 Hz] [90 C] 3-φ 1-φ Resistance [20 C]
[20 C] [90 oC] [90 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1.5 12.10 15.43 15.43 0.319 0.120 15.43 21.50 24.83 0.103 1045 0.21
2.5 7.41 9.45 9.45 0.294 0.111 9.45 13.21 15.25 0.114 840 0.36
4 4.61 5.88 5.88 0.279 0.105 5.88 8.25 9.53 0.121 720 0.57
6 3.08 3.93 3.93 0.262 0.099 3.93 5.55 6.40 0.131 585 0.86
10 1.83 2.33 2.33 0.248 0.094 2.33 3.33 3.85 0.140 475 1.43
16 1.15 1.47 1.47 0.237 0.089 1.47 2.13 2.45 0.149 385 2.29
25 0.727 0.927 0.928 0.239 0.090 0.932 1.38 1.59 0.147 400 3.58
35 0.524 0.668 0.669 0.231 0.087 0.675 1.02 1.18 0.153 340 5.01
50 0.387 0.494 0.495 0.230 0.087 0.502 0.775 0.895 0.155 330 7.15
70 0.268 0.342 0.343 0.227 0.086 0.354 0.565 0.652 0.157 310 10.02
95 0.193 0.246 0.248 0.221 0.083 0.262 0.430 0.497 0.162 260 13.59
120 0.153 0.195 0.198 0.220 0.083 0.214 0.360 0.416 0.163 255 17.17
150 0.124 0.158 0.161 0.222 0.084 0.182 0.311 0.359 0.161 270 21.46
185 0.0991 0.126 0.130 0.223 0.084 0.155 0.268 0.309 0.161 275 26.47
240 0.0754 0.0961 0.101 0.220 0.083 0.131 0.227 0.262 0.163 255 34.34
300 0.0601 0.0766 0.0830 0.218 0.082 0.117 0.200 0.231 0.165 240 42.93
400 0.0470 0.0599 0.0678 0.218 0.082 0.106 0.179 0.207 0.165 235 57.23
500 0.0366 0.0467 0.0562 0.217 0.082 0.099 0.163 0.188 0.166 230 71.54

Multicore - Copper Conductor, PVC Insulated Cables [70oC]


Electrical Parameters
DC DC AC Short Circuit
Nominal Reactance Impedance Voltage Drop Voltage Drop Min. Insulation
Resistance Resistance Resistance Inductance o Capacitance o Current
Area [60 Hz] [70 C] 3-φ 1-φ Resistance [20 C]
[20 oC] [70 oC] [70 oC] [Conductor]
mm² Ω /km Ω /km Ω /km mH/km Ω /km Ω /km V/A/km V/A/km µF/km MΩ
Ω .km kA
1.5 12.10 14.48 14.4777 0.332 0.125 14.478 20.191 23.31 0.315 15.0 0.17
2.5 7.41 8.87 8.8661 0.305 0.115 8.867 12.405 14.32 0.348 10.0 0.29
4 4.61 5.52 5.5159 0.307 0.116 5.517 7.764 8.97 0.346 10.0 0.46
6 3.08 3.69 3.6853 0.287 0.108 3.687 5.219 6.03 0.375 10.0 0.69
10 1.83 2.19 2.1898 0.269 0.101 2.192 3.139 3.63 0.405 10.0 1.15
16 1.15 1.38 1.3763 0.255 0.096 1.38 2.007 2.32 0.434 10.0 1.84
25 0.727 0.870 0.8703 0.253 0.095 0.875 1.305 1.51 0.437 5.1 2.88
35 0.524 0.627 0.6276 0.244 0.092 0.634 0.965 1.12 0.459 5.0 4.03
50 0.387 0.463 0.464 0.244 0.092 0.473 0.739 0.853 0.458 5.0 5.75
70 0.268 0.321 0.3221 0.236 0.089 0.334 0.539 0.622 0.477 5.0 8.05
95 0.193 0.231 0.2329 0.235 0.088 0.249 0.414 0.478 0.482 5.0 10.93
120 0.153 0.183 0.1856 0.23 0.087 0.205 0.348 0.401 0.494 5.0 13.8
150 0.124 0.148 0.1515 0.231 0.087 0.175 0.3 0.347 0.492 5.0 17.25
185 0.0991 0.119 0.1225 0.23 0.087 0.15 0.26 0.300 0.493 5.0 21.28
240 0.0754 0.0902 0.0953 0.228 0.086 0.128 0.221 0.256 0.498 5.0 27.6
300 0.0601 0.0719 0.0782 0.227 0.086 0.116 0.198 0.228 0.502 5.0 34.5
400 0.047 0.0562 0.064 0.226 0.085 0.106 0.177 0.204 0.505 5.0 41.12
500 0.0366 0.0438 0.0532 0.224 0.085 0.1 0.162 0.187 0.510 5.0 51.4

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Typical Cables' Correction Factors for Variation in
Installation Conditions In Ground
Correction Factors For Soil Thermal Resistivity
T.R Single-Core Multi-Core Single-Core Multi-Core
o
[ C.m/W] Cable Cable (in Duct) (in Duct)
1.00 1.36 1.29 1.25 1.17
1.20 1.26 1.21 1.18 1.12
1.50 1.14 1.12 1.10 1.07
2.00 1.00 1.00 1.00 1.00
2.50 0.90 0.91 0.91 0.93
3.00 0.80 0.80 0.80 0.80

Grouping Factors For Number of Circuits

No. of Circuits Trefoil [Gd] Flat Spaced [Gd] Multicore [Gd]

1 1.00 1.00 1.00


2
125mm 0.80 0.78 0.82
250mm 0.84 0.83 0.86
500mm 0.89 0.88 0.89
3
125mm 0.69 0.67 0.71
250mm 0.75 0.73 0.76
500mm 0.82 0.80 0.81
4
125mm 0.63 0.61 0.65
250mm 0.70 0.68 0.72
500mm 0.78 0.77 0.77
5
125mm 0.59 0.56 0.61
250mm 0.66 0.64 0.68
500mm 0.76 0.74 0.74
6
125mm 0.56 0.54 0.58
250mm 0.64 0.62 0.66
500mm 0.74 0.73 0.72

Correction Factors For Ground Correction Factors For Cable


Temperature Depth
o
Temp.[ C] Factor Depth [mm] Factor
20 1.18 500 1.02
30 1.09 700 1.00
35 1.04 1000 0.95
40 1.00 1200 0.94
50 0.89 1500 0.92
55 0.83 2000 0.85

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Typical Cables' Correction Factors for Variation in
Installation Conditions In Air

Grouping Factors
Cables No. of Circuits or Multi-Core Cables
arrangement 1 2 3 4 5 6 7 8 9
Bunched in air, on a
surface, embedded or 1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50
enclosed
Single layer on wall,
floor or unperforated 1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70
cable tray systems
Single layer fixed
directly under a 0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61
wooden ceiling
Single layer on a
perforated horizontal or
1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72
vertical cable tray
systems
Single layer on cable
ladder systems or cleats 1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78
etc.,

Correction Factors For Air


Temperature
o
Temp.[ C] Factor
20 1.49
30 1.36
35 1.29
40 1.22
50 1.08
55 1.00

RIYADH CABLES GROUP LOW VOLTAGE POWER CABLES


Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

APPENDIX - 3

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

Rated short
Min.
time I2t (Refer
Feeder Type of standard
withstand Attachment k2 S 2 Remarks
Cable Protection cable size
current of 3
(Required)
switchboard & 4)
Lighting DB / Criteria of k2S2 >
Small power MCB I2t is satisfied.
DB 16A (curvetype 10kA 28x103 2.5 sq. mm 127.8x103 Minimum cable
outgoingfeeder B/C, ABB size required is
make) 2.5 sq.mm.
Lighting DB / Criteria of k2S2 >
Small power MCB I2t is satisfied.
DB 63A (curvetype 10kA 78x103 2.5 sq. mm 127.8x103 Minimum cable
outgoingfeeder B/C, ABB size required is
make) 2.5 sq.mm.
LV Current Criteria of k2S2 >
motor/non- I2t is satisfied.
limiting
motor feeders 85kA 0.48x106 6 sq. mm 0.74x106 Minimum cable
ratedup to MCCB (ABB, size required is 6
160A SACE sq.mm.
Tmax XT2)
LV
motor/non- Current Criteria of k2S2 >
motor feeders I2t is satisfied.
limiting
ratedgreater 85kA 0.78x106 10 sq. mm 2.04x106 Minimum cable
than 160A and MCCB (ABB, size required is
up SACE 10 sq.mm.
to 320A Tmax T4)
LV
motor/non- Current Criteria of k2S2 >
motor feeders limiting I2t is satisfied.
ratedgreater 85kA 3.6x106 16 sq. mm 5.2x106 Minimum cable
MCCB (ABB,
than size required is
320A and up to SACE 16 sq.mm.
630A Tmax T6)
LV
Current Criteria of k2S2 >
motor/non-
limiting I2t is satisfied.
motor feeders
85kA 14x106 35 sq. mm 25.05x106 Minimum cable
> 630A to MCCB (ABB,
800A size required is
SACE 35 sq.mm.
Tmax T6)
LV Current Criteria of k2S2 >
motor/non- limiting I2t is satisfied.
motor feeders 85kA 19x106 35 sq. mm 25.05x106 Minimum cable
MCCB (ABB,
> size required is
800A SACE 35 sq.mm.
Tmax T6)

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.
Project Document Number: PM210011-NUI900-EC1-00008 Release Purpose: Issued for Client Review Rev: 01

This document contains informa on that is PROPRIETARY to Air Products and Chemicals, Inc. and its subsidiaries or affiliates.
This document or its contents may not be copied or disclosed to others without Air Products ‘wri en permission.

You might also like