Professional Documents
Culture Documents
IEEE
IEEE
ABSTRACT This paper presents the solution to the security-constrained unit commitment (SCUC) problem
for hybrid voltage source converter (VSC) based multi-terminal DC/AC (VSC-MTDC/AC) power systems
with high penetration of wind generation. The formulated SCUC model presents a detailed representation
of the VSCs with two different VSC control strategies considered, constant DC voltage control (master-
slave control) and DC voltage droop control. In addition, Grid Code for wind farm connection is considered.
Benders decomposition is used to solve the formulated SCUC problem by decomposing it into a master
problem for solving unit commitment (UC) and hourly transmission security check subproblems. The final
SCUC solution provides an economic and secure operation and control strategy for the meshed MTDC/AC
system. Numerical tests illustrated the efficiency of the proposed SCUC model.
INDEX TERMS Wind power, security-constrained unit commitment (SCUC), multi-terminal HVDC
(MTDC), AC/DC system, voltage source converter (VSC), Benders decomposition.
This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see https://creativecommons.org/licenses/by/4.0/
VOLUME 10, 2022 14029
Z. Jiang et al.: Security-Constrained Unit Commitment for Hybrid VSC-MTDC/AC Power Systems
B. CONTROL MODES OF THE MTDC TRANSMISSION IGBT transistor current, Equation (13) is the DC cable current
SYSTEM limit, Equation (14) is the constraint of the DC voltage level.
1) MASTER-SLAVE CONTROL MODE
−Ici max ≤ Ici ≤ Ici max (12)
By using the master-slave control mode, one converter con-
trols the DC bus voltage around a constant value and the other −Idc max ≤ Idcij ≤ Idc max (13)
VSCs operate at constant power control mode. Udci min ≤ Udci ≤ Udci max (14)
where Ici max is the maximum converter current limit, Idcij is
2) DC VOLTAGE DROOP CONTROL
the current flow of the DC
bus, Idc max is the current rating
In this mode, the VSCs work independently to contribute to of the DC cable, Udci min Udci max is the minimum/maximal
the balance of total power together with the slack bus. The ith limit of the DC voltage respectively.
VSC controls the DC voltage around a set value. By adjusting
the DC current with the slope of Ri to balance the DC power E. GRID CODE FOR WIND FARM CONNECTION
at the same time. One possible case for this control mode is Grid|Code for wind farm connection needs to be considered
presented in FIGURE. 3. [19] is a good reference for more in the formation of the UC problem. In this paper, the Grid
details for this control strategy. Code in the UK is applied. Requested by the Grid Code,
a wind farm should control the reactive power at the connect
point. A reactive power capacity of 0.95 power factor lagging
to 0.95 leading should be available at the connection point.
Hence, such requirements can be represented by the follow-
ing constraints:
Qscapi ≥ αPsi (15)
Usi min ≤ Usi ≤ Usi max (16)
q
where Qscapi = Ssi2 − P2si is the reactive capacity ruled by
the Grid Code, α = 0.3287 is the coefficient corresponds to
the power factor 0.95, Ssi is the MVA rating of the ith con-
FIGURE 3. DC voltage droop control characteristic.
verter, Usi is the AC voltage magnitude of the ith converter,
Usi min = 0.94, Usi max = 1.06.
C. POWER EQUATIONS OF THE VSC-MTDC
TRANSMISSION SYSTEM III. SCUC FOR VSC-MTDC/AC SYSTEM WITH WIND
The active power balance equation of the converter can be POWER
formulated as A. FORMULATION OF THE SCUC WITH VARIOUS
CONSTRAINTS
Plossi + Pci + Pdci = 0 (9)
The SCUC is generalized in Equation (17) where f (x) con-
where Pdci and Pci is the active power injected by the con- sists of production cost, starting up and shutting down costs
verter into the DC and AC side, respectively. Pdci can be of individual generation unit for the study horizon [21]:
written as
Min f (x)
Pdci = Udci Idci ∀i ∈ NDC (10) S.t. g1 (x) ≤ b1
where Udci and Idci is the voltage and DC network bus current ge1 (x) = be1 (17)
injection, respectively. The relationship of Udci and Idci can be
where the vector x represents the optimization variables,
expressed by
which are composed of on/off status of generation units,
nDC
X startup and shutdown indicators and AC/DC transmission
Idci = Ydcij Udci − Udcj ∀i ∈ NDC (11) system control variables. The sets of inequality constraints
j=1 g1 (x) ≤ b1 and equality constraints ge1 (x) = be1 repre-
where Ydcij is the element of bus admittance matrix YDC of sents the UC constraints such as:
the DC network. (1) Power balance of the entire VSC-MTDC/AC system.
(2) VSC-MTDC/AC power flow equations with wind
D. OPERATION CONSTRAINTS OF THE VSC-MTDC power being considered.
SYSTEM [14] (3) Ramping up/down limits of the generations in the AC
The following constraints are formulated to ensure the steady grid.
state operating point of the converter to satisfy the corre- (4) Minimum on/off time limits of the generations of the
sponding PQ capacity limit [20], thus to keep the safe opera- AC grid.
tion of the VSC-MTDC. Equation (12) is the constraint of the (5) Capacity limits of the generating units in in the grid.
(6) VSC-MTDC/AC network security constraints includ- where σPD,t is the standard deviation of load forecast errors
ing the AC/DC transmission flow and bus voltage which are normally distributed random variables, σwind,t is
limits, as well as the limits to the IGBT transistors, the standard deviation of wind power forecast errors.
converter current, voltage and power of the VSCs, Normally, σPD,t is considered as a percentage of the
as well as the Grid Code for wind farm connection. expected power load demand [23], taken to be 2% in this
(7) The upper and lower bounds of the MTDC opti- paper. Wind power forecast errors are also considered to be
mization variables composed of linear inequality normally distributed random variables. σwind,t depends heav-
constraints. ily on the forecasting horizon and the expected wind power
(8) Wind power constraints by considering wind power value. For a 24-h forecasting horizon, it can be represented
curtailment: by the following equation [24]:
0 ≤ Pwind,t ≤ Pmean
wind,t (18) Pmean
wind,t
σwind,t = (α · + β)σw,t (23)
where Pwind,t and Pmeanis the expected value and the
wind,t Pinstalled
accommodated wind power, respectively.
(9) Constraints of system reserve requirements (RR) where the standard deviation of normalised wind power fore-
for handling uncertainties in the UC problem. The cast error is expressed as a function of forecast horizon, σw,t ,
method of sizing the RR is described in the following and the coefficients α and β are borrowed from [24].
subsection.
(10) Time limited corrective controls, such as permissible C. SOLUTION OF THE SCUC FOR THE VSC-MTDC/AC
real power adjustments, for handling contingencies. SYSTEM
The Benders decomposition is applied to solve the SCUC
B. SPINNING RESERVE REQUIREMENTS FOR HANDLING for the VSC-MTDC/AC transmission systems as depicted in
UNCERTAINTIES IN THE UC PROBLE FIGURE. 4. The master problem, the UC, is modeled as a
Scenario-based stochastic programming and the RR are two linear mixed integer problem (MIP) in the GAMS environ-
of the most common methods to handle uncertainties in the ment [25], and the CPLEX solver is used to solve the MIP.
UC problem. Since the former approach needs many scenar- The solution provides the status and the dispatching active
ios to represent the stochastic nature of uncertainties, the RR power of each generation unit, as well as the accommodated
approach is adopted in this paper to handle the randomness wind power. The SCUC sub-problem considers mismatches
of wind generation. of inequality constraints except the power balance constraint
Compared with the deterministic criteria, stochastic cri- formulated in the master problem. The sub-problem is devel-
teria based on the probabilistic confidence level to meet oped from [26] and it is solved based on the Primal-Dural
the forecasted net demand is more flexible and eco- Interior Point (PDIP) algorithm by adding constraints of the
nomic. In order to represent the stochastic constraints, the MTDC system to the available open source Matlab toolbox,
chance-constrained stochastic formulation of the spinning Matpower [27]. The sub-problem generates Benders cuts or
RR is given by Equation (19). The deterministic equivalent updates the power losses of the whole system for the next UC
of Equation (19) can be formulated as Equation (20): iteration if the mismatch exists. The interactive procedure will
N
! not stop until all mismatches are removed.
f
X
Pr o uit Pmax
i ≥ NDt = 1 − αλ (19)
i=1
N
X
uit Pmax
i ≥ NDmean
t + λσND,t (20)
i=1
where Pmax
i is the upper boundary of power output of unit
i, 1 − αλ is the associated confidence level, uit is a binary
variable for the committed status of unit i, NDmean
t is the FIGURE 4. SCUC with VSC-MTDC/AC systems.
f
mean value of net load and NDt is the forecasted net demand,
respectively. Here λ = 3, which means 99.74% of variations D. THE SCUC SUB-PROBLEM
are covered [22]. NDmean
t can be calculated based on the
The objective function of the sub-problem is:
expected hourly wind power Pmean
wind,t and load demand PDt
mean
as follows: NB
X
NDmean = PDmean − Pmean (21) Min w = (MP1b +MP2b + MQ1b +MQ2b ) (24)
t t wind,t
b=1
The standard deviation of the forecast error of net load, σND,t
can be calculated by the following equation: where NB is the number of AC buses, MP1b , MP2b and
q MQ1b , MQ2b are slack variables vectors of mismatched
σND,t = σPD,t 2 + σwind,t
2 (22) active power and reactive power at bus b respectively in the
equality constraint:
A · 1P
P1 P2 dP0
A · 1Q = [J] Xt + Q1 − Q2 = dQ0 (25)
0 0 0 dK0
where 1P and 1Q is the incremental active/reactive vectors,
dP0 and dQ0 the initial AC bus active/reactive mismatch
vectors, dK0 the mismatch vector of other equations of the
DC/AC system, respectively, A is the bus-unit incidence
matrix, J the Jacobian matrix, which is given in Appendix A.
The vector of decision variables at a certain operating point t
for the sub-problem is
t = [θ , U, PG , QG , θ f , θ c , Uf , Uc , Udc , Udc , Ps , Qs ,
XT Ref Ref Ref
URef
s ] (26)
XT
t = [θ , U, PG , QG , θ f , θ c , Uf , Uc , Udc , QRef
s , Us , R]
Ref
(27) FIGURE 5. Modified IEEE 14-bus system with VSC-MTDC connected wind
farms.
where
θ Bus voltage angel state variable vector
U Bus voltage magnitudes state variable vector
PG Active power generation control vector
QG Reactive power generation control vector
Uf Filter bus voltage magnitude state variable vector
Uc Converter bus voltage magnitude state variable
vector
θf Filter bus voltage angle state variable vector
θc Converter bus voltage angle state vector FIGURE 6. Power flow between DC bus 3 and 4.
Udc Bus voltage state variable vector
QRef
s Scheduled reactive power reference control vector current iteration, 1Qmin and 1Qmax are the lower and upper
vector limit vectors for incremental unit reactive power, respectively.
URef
s Scheduled AC bus voltage reference control
vector 1Qmin ≤ 1Q ≤ 1Qmax ψup , ψdn (30)
Note that Equation (26) is for the VSC-MTDC system IV. CASE STUDY
by applying master-slave control mode with URef Ref FIGURE.5 shows the modified IEEE 14-bus power system.
dc and Ps
being the scheduled DC bus voltage control vector and active Two wind farms with a capacity of 70 MW/each are con-
power reference control vector of the converters respectively. nected to bus 3 and bus 7 through a four-terminal HVDC
Equation (27) is for the DC voltage droop control mode with network. Bus 1 is selected as the slack bus for the AC net-
R being the slope control vector. In the sub-problem, all work. Parameters of this hybrid VSC-MTDC/AC system are
generating units except those at the slack bus should satisfy given in Appendix B. Two wind power profiles considered
Equation (28): in this study are provided in Appendix C. Spinning RR are
calculated by using the methods presented in Section III B.
1P = 0 π (28)
A. MASTER CONTROL MODE
If the positive w equals to 0, power losses provided by the
sub-problem solution are updated for the master problem. The following cases are studied when the MTDC system
Otherwise, a mismatch Benders cut will be added to the adopts the master control mode:
master problem for the next iterative solution: Case1: Based on the method proposed in [12], the SCUC of
the AC system without the grid-interconnected wind
w+π PG − P̂G + ψup Qmax u − û
generation is carried out. This is the base case for the
+ ψdn Qmax u − û ≤ 0 (29)
comparison with the SCUC proposed in this paper.
Case2: The SCUC for the meshed VSC-MTDC/AC system
where π , ψup , ψdn are the Lagrange multiplier vectors for is carried out by use of the proposed method in this
constraints (28) and (30), u is the binary variable vector of paper without the limits of the DC-side variables i.e.,
the generation status (where 1 indicates the generation unit the lower and upper limits, being imposed. But both
is committed), P̂G and û are the optimization results in the maximum and minimum power flow limits of the DC
lines connecting DC bus 3 and 4 are taken to be 0 and TABLE 2. Results of SCUC for different cases.
the hourly forecasted wind power is assumed to be 0.
This case is used to compare with Case1, to verify
the correctness of the model proposed.
Case3: The SCUC is carried out by the method proposed in TABLE 3. Wind curtailment for Case 3 and Case 4.
this paper. Various control references for the MTDC
are given in Table 1.
Case4: Same to Case3 but both maximum and minimum
power flow limits of the DC lines connecting DC
bus 3 and 4 are taken to be 0. This case is for the
TABLE 4. SCUC results for voltage drop control.
comparison of the meshed MTDC system with the
point-to-point HVDC system.
Case5: Same to Case3 but wind power curtailment is not
allowed. This case is used to study the impacts of
wind power curtailment when using the proposed TABLE 5. SCUC results for voltage drop control.
method.
AC DC
JA JB AC
J =
JC JD DC
where JA is the Jacobian matrix for AC system, which is
provided in [27].
TABLE 11. DC transmission line data.
APPENDIX B
HYBRID VSC-MTDC/AC SYSTEM DATA
See Tables 6–12.
APPENDIX C
WIND DATA (MW)
FIGURE 9. UC cost with different power capacity of DC line.
is, more flexibility the MTDC system can have to control the
power flow to allocate the available wind power between two
connecting locations.
In practice, the selection of connecting locations, the
MTDC network configuration and the DC line capacity is
determined by many factors, rather than just the operational
cost. However, the proposed SCUC model can be used to
examine the aspect of operational cost of whole AC/DC
system.
V. CONCLUSION
APPENDIX D
In this paper, a SCUC approach for the meshed BASE QUANTITIES
VSC-MTDC/AC systems with wind power is presented Grid frequency 50 Hz
which could be utilized by the dispatch center to schedule Power 100 MW
the power generation and wind power economically. The for-
mulated SCUC scheme takes the different control strategies
REFERENCES
of VSCs and the Grid Code of wind farm interconnection into
[1] Y. Liu, L. Xiao, H. Wang, S. Dai, and Z. Qi, ‘‘Analysis on the hourly
full consideration. The tests showed the effectiveness of the spatiotemporal complementarities between China’s solar and wind energy
proposed approach. The proposed scheme can be also used resources spreading in a wide area,’’ Sci. China Technol. Sci., vol. 56, no. 3,
for the selection of connection location of MTDC network of pp. 683–692, Mar. 2013.
[2] N. Flourentzou, V. G. Agelidis, and G. D. Demetriades, ‘‘VSC-based
AC grid, the optimization of DC line power capacity, as well HVDC power transmission systems: An overview,’’ IEEE Trans. Power
as the chosen of the DC network structure. Electron., vol. 24, no. 3, pp. 592–602, Mar. 2009.
[3] O. Gomis-Bellmunt, J. Liang, J. Ekanayake, R. King, and N. Jenkins, [22] G. Strbac, A. Shakoor, M. Black, D. Pudjianto, and T. Bopp, ‘‘Impact of
‘‘Topologies of multiterminal HVDC-VSC transmission for large offshore wind generation on the operation and development of the UK electricity
wind farms,’’ Electr. Power Syst. Res., vol. 81, no. 2, pp. 271–281, 2011. systems,’’ Electr. Power Syst. Res., vol. 77, no. 9, pp. 1214–1227, 2007.
[4] T. Samus, B. Lang, and H. Rohn, ‘‘Assessing the natural resource use and [23] Y. V. Makarov, C. Loutan, J. Ma, and P. D. Mello, ‘‘Operational impacts of
the resource efficiency potential of the Desertec concept,’’ Sol. Energy, wind generation on California power systems,’’ IEEE Trans. Power Syst.,
vol. 87, pp. 176–183, Jan. 2013. vol. 24, no. 2, pp. 1039–1050, May 2009.
[5] J. De Decker and A. Woyte, ‘‘Review of the various proposals for the [24] M. Albadi and E. El-Saadany, ‘‘Comparative study on impacts of wind
European offshore grid,’’ Renew. Energy, vol. 49, pp. 58–62, Jan. 2013. profiles on thermal units scheduling costs,’’ IET Renew. Power Gener.,
[6] J. G. Chen, C. B. Yu, T. T. Sun, and K. J. Ou, ‘‘Characteristics analysis and vol. 5, no. 1, pp. 26–35, Nov. 2011.
simulation testing on modular multilevel converter VSC-HVDC based on [25] B. A. McCarl, McCarl GAMS User Guide Version 22.0, GAMS Develop-
RTDS,’’ Appl. Mech. Mater., vols. 397–400, pp. 1794–1799, Sep. 2013. ment Corporation, Fairfax, VA, USA, 2006.
[7] H. Ambriz-Pérez, E. Acha, and C. R. Fuerte-Esquivel, ‘‘High voltage direct [26] J. Cao, W. Du, H. F. Wang, and S. Q. Bu, ‘‘Minimization of transmission
current modelling in optimal power flows,’’ Int. J. Electr. Power Energy loss in meshed AC/DC grids with VSC-MTDC networks,’’ IEEE Trans.
Syst., vol. 30, no. 3, pp. 157–168, Mar. 2008. Power Syst., vol. 28, no. 3, pp. 3047–3055, Aug. 2013.
[8] N. P. Padhy, ‘‘Unit commitment—A bibliographical survey,’’ IEEE Trans. [27] R. D. Zimmerman, C. E. Murillo-Sanchez, and R. J. Thomas,
Power Syst., vol. 19, no. 2, pp. 1196–1205, May 2004. ‘‘MATPOWER: Steady-state operations, planning, and analysis tools for
[9] V. Sarkar and S. A. Khaparde, ‘‘Implementation of LMP-FTR mecha- power systems research and education,’’ IEEE Trans. Power Syst., vol. 26,
nism in an AC-DC system,’’ IEEE Trans. Power Syst., vol. 23, no. 2, no. 1, pp. 12–19, Feb. 2011.
pp. 737–746, May 2008.
[10] J. Wang, M. Shahidehpour, and Z. Li, ‘‘Security-constrained unit com-
mitment with volatile wind power generation,’’ IEEE Trans. Power Syst.,
vol. 23, no. 3, pp. 1319–1327, Aug. 2008.
[11] Y. Fu, C. Wang, W. Tian, and M. Shahidehpour, ‘‘Integration of large-scale
offshore wind energy via VSC-HVDC in day-ahead scheduling,’’ IEEE
ZHUOYU JIANG is working with Three Gorges Power Corporation Ltd.
Trans. Sustain. Energy, vol. 7, no. 2, pp. 535–545, Apr. 2016. His research interests include the economic analysis and the operation of the
[12] A. Lotfjou, M. Shahidehpour, Y. Fu, and Z. Li, ‘‘Security-constrained micro-grid.
unit commitment with AC/DC transmission systems,’’ IEEE Trans. Power
Syst., vol. 25, no. 1, pp. 531–542, Feb. 2010.
[13] B. Zhou, X. Ai, J. Fang, J. Wen, and J. Yang, ‘‘Mixed-integer second-order
cone programming taking appropriate approximation for the unit commit-
ment in hybrid AC–DC grid,’’ J. Eng., vol. 2017, no. 13, pp. 1462–1467, YI LIU received the B.S. degree from the School of Electrical Engineering,
Jan. 2017. Tianjin University, China, and the Ph.D. degree from the Institution of
[14] M. Baradar, M. R. Hesamzadeh, and M. Ghandhari, ‘‘Second-order cone Electrical Engineering, Chinese Academy of Sciences.
programming for optimal power flow in VSC-type AC-DC grids,’’ IEEE His research interests include the economic and stability analysis of power
Trans. Power Syst., vol. 28, no. 4, pp. 4282–4291, Nov. 2013. systems operation, including renewable power and multi-terminal DC power
[15] L. Jun, J. Tianjun, O. Gomis-Bellmunt, J. Ekanayake, and N. Jenkins, systems.
‘‘Operation and control of multiterminal HVDC transmission for offshore
wind farms,’’ IEEE Trans. Power Del., vol. 26, no. 4, pp. 2596–2604,
Oct. 2011.
[16] T. M. Haileselassie and K. Uhlen, ‘‘Impact of DC line voltage drops on
power flow of MTDC using droop control,’’ IEEE Trans. Power Syst., ZHE KANG is working with Three Gorges Power Corporation Ltd. His
vol. 27, no. 3, pp. 1441–1449, Aug. 2012. research interests include the economic analysis and the operation of PV
[17] J. Beerten, S. Cole, and R. Belmans, ‘‘Generalized steady-state VSC generation and operation of the micro-grid.
MTDC model for sequential AC/DC power flow algorithms,’’ IEEE Trans.
Power Syst., vol. 27, no. 2, pp. 821–829, May 2012.
[18] X.-P. Zhang, ‘‘Multiterminal voltage-sourced converter-based HVDC
models for power flow analysis,’’ IEEE Trans. Power Syst., vol. 19, no. 4,
pp. 1877–1884, Nov. 2004. TAO HAN is working with Three Gorges Power Corporation Ltd. His
[19] L. Xu, L. Yao, and C. Sasse, ‘‘Grid integration of large DFIG-based wind research interests include the economic analysis and the operation of PV
farms using VSC transmission,’’ IEEE Trans. Power Syst., vol. 22, no. 3, generation and operation of the micro-grid.
pp. 976–984, Aug. 2007.
[20] S. Engelhardt, I. Erlich, J. Kretschmann, F. Shewarega, and C. Feltes,
‘‘Reactive power capability of wind turbines based on doubly fed induction
generators,’’ IEEE Trans. Energy Convers., vol. 26, no. 1, pp. 364–372,
Mar. 2011. JING ZHOU is working with Three Gorges Power Corporation Ltd. His
[21] Y. Fu, M. Shahidehpour, and Z. Li, ‘‘Security-constrained unit commit- research interests include the economic analysis and the operation of PV
ment with AC constraints,’’ IEEE Trans. Power Syst., vol. 20, no. 2, generation and operation of the micro-grid.
pp. 1001–1013, May 2005.