Parameter list

1x Filter control unit RM300C


1x E/A module RM-V8 with sensor module

Unit No.: 10
Com. No.: 23709
AAT.Pos.: 109 0110001
Customer: Polysius
Filtertype: DSK36/3,5m-IIR

Parameter Brief description Display line 1 Release Unit Min Max Base Settings
no. value value value

P00 Parameter release (111) P00 Relase-param off 000 Nr. 0 250 0 0 off
Test programs
P01 Test programs P01 Testmode on 000 Nr. 0 56 0 0 off
Operations
P02 DP start P02 DP-start on 00.0hpa 1.0 50.0 25.0 12.0 hPa
P03 DP hysteresis P03 DP-hysteresi off 00.0hpa 0.3 4.0 0.3 1.5 hPa
P04 DP min alarm P04 DP-alarm min off 00.0hpa 0.0 20.0 0.0 0.0 hPa
P05 DP max alarm P05 DP-alarm max off 00.0hpa 5.0 50.0 35.0 22.0 hPa
Control times
P06 P06 Downtimecyk. on 000cyk. 0 16 0 4 cyk.
P07 Reserve 1 Reserve 1 off 000 s 0 0 0 0s
P08 Forced cleaning time P08 Forcedclean on Text 0 15 0 Off
P09 Interval 1 P09 Interval 1 on 000 s 3 600 180 20 s
P10 Interval 2 P10 Interval 2 on 000 s 3 252 6 10 s
P11 Fluid valve pulse time P11 Pulse fluit off 0000 ms 200 5000 1000 200 ms
P12 Cleaning valve pulse time P12 Pulse clean off 000 ms 30 900 250 100 ms
Display parameters
P13 Display language P13 Dis.language on Text 0 7 0 001 english
P14 Display selection P14 Disp.select on Text 0 6 0 Differe.pressure Differe.pressure
P15 Display contrast P15 Dis.contrast on 000 Nr. 0 200 120 104
Input functions
P16 Input I2 function P16 Input Mode I2 off Text 0 6 0 000 no funktion
Output functions
P17 Output O2 function P17 Outp.mode Q2 off Text 0 8 1 06 Cleaning on
P18 Output O3 function P18 Outp.mode Q3 off Text 0 8 2 02 Release n.al
P19 Output O4 function P19 Outp.mode Q4 off Text 1 3 1 05 DP-alarm max
System parameters
P20 Controller type P20 Unit type off Text 0 3 0 Unit Type 1 Unit Type 1
P21 DP cleaning mode P21 Clean.mode off Text 0 3 1 001 DP cle.stopp
P22 Sensor type P22 Sensortype off Text 0 2 1 ext.S-Modul=50.0 ext.S-Modul=50.0
P23 Sensor alarm P23 Sensoralarm off Text 0 3 0 000 no aktive
P24 Number of I/O module P24 Dis.RM-VXX off 000Stk. 1 15 1 1 pcs.
P25 Number of valves P25 Dis.Valves off 000Stk. 1 250 1 8 pcs.
P26 Service hours alarm P26 Service Al. off (128) 00000 h 1000 25000 3000 25000

Settings RM-V8
RM-V8-1 Selector switch S1 Setting the I/O module number (selector switch S1) 1
Selector switch S2 Setting the number of valves (selector switch S2) 8
Selector switch S3 Stand-alone mode (ON) / R-IMC-Bus mode (OFF) off
Selector switch S4 without sensor module (ON) / with sensor module (OFF) off
Selector switch S5 without sensor module (ON) / with sensor module (OFF) off