Fire Pumps

Before ordering a fire pump, consult FM Approvals regarding size, type of driver, suction supplies and location. Proposals for fire
pump installations, including plans showing location and piping connections, should be sent to FM Global for review before the order
is placed. Give the manufacturer complete data, including rated capacity, net head and suction head. Contracts for pump installations
or changes should be let subsequent to acceptance of plans and subject to satisfactory field tests by FM Global.
The pump manufacturer or his authorized representative is responsible for furnishing a complete unit consisting of pump, driver and
necessary accessories, all according to FM Global's standards.
Satisfactory performance in an operating test after installation should be guaranteed. A new fire pump installation is not acceptable
until FM Global has witnessed a satisfactory field acceptance test. This will include a test of endurance of the pump and reliability of
the power supply.
Exact horsepower requirements for each pump must be determined by a shop test on the specific pump. Approximate horsepower
requirements at rated pump conditions are as follows:

Rated Rated
Capacity, Net Approximate
gal/min Head, Power
(dm 3 psi Required,
/min) (kPa) hp (kW)
500 100 50-60
(1895) (690) (37-45)

750 100 60-75


(2840) (690) (45-56)

1000 100 75-100


(3785) (690) (56-75)

1500 100 100-125


(5680) (690) (75-93)

2000 100 125-150


(7570) (690) (93-112)

2500 100 150-200


(9465) (690) (112-149)

In the listings on the following page, rated net head represents the amount of pressure boost obtainable from a pump of a given type
and impeller size when operating at rated speed.
The rated net head range indicates that impellers of various diameters are obtainable for the given type of pump.
Although not recommended for installations where suction is normally taken under lift, FM Approved pumps have been tested for
proper operation under negative suction conditions up to 15 ft (5 m) at 150% of rated capacity.

Centrifugal Fire Pumps, Horizontal Split-Case Type


FM Approved horizontal split-case type centrifugal fire pumps are relatively simple to operate and repair. These pumps have a
two-part casing divided in a horizontal plane through the shaft centerline. They are well suited to fire protection service where a water
supply is obtainable under a positive head.

Horizontal Mounted
5AEF11 *

Company Name: Peerless Pump Company


Company Address: 2005 Dr Martin Luther King Jr St, Indianapolis, Indiana 46206, USA
Company Website: http://peerlesspump.com
New/Updated Product Listing: No
Listing Country: United States of America

© 2007-2021 FM Approvals. All rights reserved. Page 1 of 2


Rated Capacity, (gal/min) : 1000
Rated Capacity, (dm³/min): 3785
Rated Net Head at Rated Capacity, psi: 75-135
Rated Net Head at Rated Capacity, kPa: 515-930
Rated Speed, r/min: 3000
Suction Inlet, dia., in.: 6
Discharge Outlet, dia., in.: 5
Stage(s): 1
Certification Type: FM Approved
Class of Work: 1311-Centrifugal Fire Pumps, Horz

* When requested, Peerless can furnish pumps designed for applications where the suction pressures exceed 75 psi (515 kPa).
These pumps are designated by the addition of the letter "H" after the type designation.