You are on page 1of 4

Configuration Design

Created with Select and Config tool


KB_GCR_NW_CB - 220606.0

Configuration

1- Characteristics

1.1- General
Characteristic Value
In rated current [4000 A]
Rating code [H1]
Breaking capacity [65 kA 220/415 V IEC]
Poles description [3P]
Trip unit name [Micrologic 6.0 P]
Derating [no]
Type of measurement [power meter]
Neutral position [-]
Anticorrosion treatment [-]
Mounting mode [drawout device with
chassis]
Upstream connections [vertical]
Downstream connections [vertical]
Communication option [no]
Remote ON/OFF [yes]
Okken Partner [no]

1.2- Options

Remote control & accessories

Characteristic Value
MCH gear motor [yes]
Control circuit voltage [400...480 V AC]
XF closing release [yes]
Device short name [XF]
Control circuit voltage [24...30 V DC]
BPFE pushbutton [no]
MX opening release [yes]

Configuration date: 5 Apr, 2023 1/4


Configuration Design
Created with Select and Config tool
KB_GCR_NW_CB - 220606.0

Characteristic Value
Device short name [MX]
Control circuit voltage [24...30 V DC]
MX 2nd opening release [no]
MN undervoltage release [yes]
Control circuit voltage [24...30 V DC]
MN+adjustable delay unit Rr [no]
MN+Non-adjustable delay unit R [no]
Ready to close contact [standard]

Configuration date: 5 Apr, 2023 2/4


Configuration Design
Created with Select and Config tool
KB_GCR_NW_CB - 220606.0

2- Bill of material
Reference Quantit Price
Description
y
48322 Circuit breaker frame, MasterPact 1
NW40H1, 4000A, 65kA/440VAC 50/60Hz
(Icu), 3 poles, drawout, without control
unit

48396 Chassis, MasterPact NW40, drawout, 1


4000A, H type, 3 poles

48140 Vertical rear connection, MasterPact 1


NW40, 3 poles, fixed/drawout, 4000A,
bottom mounting

48364 Control unit MicroLogic 6.0P, MasterPact 1


NW drawout, LSIG protections

48135 Vertical rear connection, MasterPact 1


NW40, 3 poles, fixed/drawout, 4000A, top
mounting

48530 Gear motor MCH, drawout MasterPact 1


NW, 440/480VAC 50/60Hz

48481 Standard closing voltage release XF, 1


MasterPact NW drawout, 24/30VDC,
24VAC

48491 Standard opening voltage release MX, 1


MasterPact NW drawout, 24/30VDC,
24VAC

Configuration date: 5 Apr, 2023 3/4


Configuration Design
Created with Select and Config tool
KB_GCR_NW_CB - 220606.0

Reference Quantit Price


Description
y
48469 Ready to close contact (PF), MasterPact 1
NW drawout, 1 changeover contact,
standard, 5A/240VAC

48501 Standard opening undervoltage release 1


MN, MasterPact NW drawout, 24/30VDC,
24VAC

3- Disclaimer
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its
affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.

Configuration date: 5 Apr, 2023 4/4